Miconic TX-GC/10-GC

INVENTIO AG

Commissioning

K 604016 E / 06

1-11.220

Authorization: Lead Office: Name: Date: Modification: KA No. KA Date: Restrictions

16.03.2005

COMMISSIONING

Authored PD3 P. Klemm 14.03.2005 01 28.02.2001

02 18.12.2001

Reviewed SC7 M. Saul 14.03.2005 03 28.03.2002

04 160061 17.10.2003

Released EB3 B. Kurmann 14.03.2005 05 160128 18.06.2004

06 160254 18.03.2005

This Manual is the property of INVENTIO AG and shall only be used by SCHINDLER personnel or authorized SCHINDLER agents for purposes which are in the interest of SCHINDLER. This design and information is our intellectual property. Without written consent, it must neither be copied in any manner, nor used for manufacturing, nor communicated to third parties. Application for such consent should be addressed to: INVENTIO AG, Postfach, CH-6052 Hergiswil NW

Page 1 of 75

K604016: Commissioning

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

COMMISSIONING Prereq.

Summary

Preparation

Insp. IMOF

Measuring

Car I/Os

Lift I/Os

Group I/Os

Group Ctrl.

This document contains information on commissioning of the elevator controls Miconic TX-GC and Miconic 10-GC. As the hardware platform is identical for both control types, 'control' as generic term for both will be used throughout this document. If a special feature applies only to Miconic TX-GC or to Miconic 10-GC, this is indicated explicitly. An overview of the overall commissioning procedure together with Variodyn VF...BR/PF1 drives can be found in document K 604010.

-

Contents

No. 1

Chapter Prerequisites

2

Preparation of Control

3

Inspection Travel with IMOF

4

Measuring Travel

5 6

Car I/Os Lift I/Os

7

Group I/Os

8

Group Control

A

Appendix A - References

Z

Appendix Z - Table of Contents

-

Authorization Restrictions K 604016 E

16.03.2005

Authored by:

P. Klemm, R&D-ITS 14.03.2005

Technical Review M. Saul, CTT Chaired by: 14.03.2005

Released by:

H. Künzli, CTT 14.03.2005

INVENTIO AG This design and information is our intellectual property. It must without our written consent neither be copied CH-6052 Hergiswil in any way nor used for manufacturing nor communicated to third parties.

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 2 of 75

K604016 Chapter 1: Prerequisites

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Chapter 1

Prerequisites

Summary

This section points out some general points to remember about commissioning. This commissioning instruction gives you concise directions for commissioning and is designed to assist you in your work. Execute the steps in the predefined sequence, and do not go to the next step until the work detailed in the previous step has been successfully completed. If anything does not work according to the procedure, first find out the reason and solve the problem.

Overall Commissioning

Control commissioning must always be seen in the framework of commissioning the entire elevator system, as the control interacts with many of the systems components. An overview of the overall commissioning procedure for the whole elevator system and document references to other parts of system commissioning, is available in a separate document: K 604010: Overall Commissioning Miconic TX-GC / 10-GC with VF...BR/PF1.

Safety Rules

Be sure not to work on live devices! Only if you switch off JH, JHG, and JHL, you can be sure that there are no live parts in the cabinet or on and in the car. Even then, there is still the voltage from the NSG Battery (12 VDC) which is used as emergency power supply! For your own safety, check always the schematics! To avoid problems with plugs: z Pull always only the connector and not the wiring or cable. z Turn off related power supply before you plug or unplug connectors.

Node Dead Behavior

In case of a LON node breakdown or if LON communication becomes faulty, the elevator system always has to go into a save state. When the control looses connection to a LON node which holds special input signals (e.g. inputs for Fire Emergency, Earthquake, Emergency Power), the corresponding services will be activated automatically. This functionality is available only in software version 1.45 or higher. This 'Node Dead Behavior' can be suppressed using the SMLCD command 'Service Visit -> ON'. Remember this before working on an installation in order to prevent the whole elevator group from becoming unavailable. For a new installation, the factory default setting of 'Service Visit' is ON!

Special Tools

The following special tools are used for commissioning the control: Tool Multimeter with z sensitivity greater than 25 kΩ / V z and measuring range greater than 500 VDC z measurement of true RMS (root mean square) z diode test z continuity test. Test leads must have insulated probe tips.

Used for Measurement of all supply voltages in the control before connecting the appropriate plugs. True RMS required for correct measurement of safety circuit supply (only for version 88 VDCRMS pulsed, min. 64 VDC, max. 120 VDC)

Special Tools for Commissioning

16.03.2005

Page 3 of 75

K604016 Chapter 1: Prerequisites Documents

The following additional documents are required for commissioning the control: Title Schematic circuit diagram of actual installation

Document Comm. Number

Overall Commissioning Miconic TX-GC / 10-GC with VF...BR/PF1

K 604010

Diagnostics Miconic TX-GC / Miconic 10-GC

K 604007

Operation SMLCD Miconic TX-GC / Miconic 10-GC

K 604005

Useful Documents for Commissioning Notation

K 604016 E

16.03.2005

The following notation is valid throughout the commissioning documentation: z P0 always means 24 VDC z VCC always means 5 VDC z Brackets ( ) in the commissioning tables indicate source or destination of the respective connector. Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 4 of 75

K604016 Chapter 2: Preparation of Control

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Chapter 2 Summary Preconditions

Preparation of Control After these praparatory steps the control is ready for "Recall Travel with IMOF". z z z z

Switches

Cabinet was installed according to the Installation document K 604 012 If adapter transformer TAS is installed, make sure it is wired correctly (400 VAC at output) Mains voltage of 3 x 400 VAC (-15%, +10%) is available JH, JTHS, JHG and JHL are installed

No.

200

Switch Position Location Remarks The following switches must be in the correct position: JH

OFF

MR

Switch Main Power

JTHS

OFF

MR

Switch Thermal Control

JHL

OFF

MR

Switch Main Light

JHG

OFF

MR

Switch Main Group

JMOF

IMOF

ASILOG

JRH

RECALL

AS

Switch Recall Control

JFIS

OFF

AS

Ground Fault Circuit Breaker Control

JFIL

OFF

AS

Ground Fault Circuit Breaker Light

JTHB

OFF

AS

Switch Thermal Brake

JFISK

OFF

AS

Ground Fault Circuit Breaker Safety Circuit

Switch Installation Travel

(only for safety circuit 88 VDC pulsed)

Preparation in Machine Room

16.03.2005

No.

JTHSK

OFF

AS

Lift ID

1 ... 8

ASILOG

Number of elevator in the group

JTHTUV

OFF

AS/AS2

Switch Thermal Transformer Voltage Fan Drive

JTHSA

OFF

AS/AS2

Switch Thermal Drive Control

Step

Switch Thermal Safety Circuit Simplex = 1

Remarks

Adjust overcurrent setting on JH 201 according to the installation wiring diagrams

According to diagram

In system with 5 wire mains (TN-S): measure presence of neutral conductor: z voltage from neutral conductor to 202 conductor, for each phase z voltage from neutral conductor to grounding conductor

Danger of overvoltage, if ground is not connected properly

In system with 4 wire mains (TN-C): 203 check for jumper on JFIS from neutral conductor to one conductor.

JFIS is not working, if jumper is missing

Page 5 of 75

K604016 Chapter 2: Preparation of Control

PCBs in AS

No.

204

PCB Plug-in Location The following PCBs must be plugged in: z

GCIO360

ASILOG.X5-2-4

Micro Processor PCB

z

SKE

ASILOG.X5-2-5

Safety Circuit PCB

z

MBB

ASILOG.X5-2-6

Brake Module PCB

z

EBLON

ASILOG.X5-2-3

LON interface PCB

z

EBCOM

ASILOG.X5-2-2

VCOM interface PCB

(if existing)

No.

LONIOS LONDAG

BPL1 .. BPL#

Inputs and Outputs on PCBs

z

BAFL#

BPL#.X4-1-4

Bus terminator for lift bus (on BPL with highest number)

Step The following connectors must be unplugged: z

Drive X15 (from AS.SKE.X5-2-1, AS.SKE.X5-3-1)

205

(only if group or GW)

z

z

Connectors in AS

Remarks

z

z

Remarks

Communication to SKE

AS.X3-4-1

Power supply car / door

(from OKR.X1-1-1, OKR.X1-1-2)

(via traveling cable)

AS.X4-1-1 (from A.X8)

MVE and MGB

The following connectors must be plugged in: z

AS.X3-2-1 (from NGSK.X1-1-1)

z

AS.X3-2-4 (from SKE.X5-7-1)

206

z

AS.X3-4-5 (from ESE)

z

AS.X3-4-2 (from JHL)

z

AS.X3-4-3 (from NGL.X1)

Power supply for safety circuit ESE If ESE will be removed later on, set shortcircuit jumper on AS.X3-4-5 (pins 1+4+5 and pins 6+7)!

Power supply light Power supply lift

Connectors on SKE PCB The following connectors must be unplugged: z

207

z

z

SKE.X5-5-2

Hoistway information

(from ICE.X5-4-2)

(via traveling cable)

SKE.X5-6-2

Safety circuit car

(from ICE.X5-5-1)

(via traveling cable)

SKE.X5-7-2

Safety circuit hoistway (in hoistway cable loom)

The following connectors must be plugged in: z

SKE.X5-1-2 (from VF2.X15)

208

z

SKE.X5-2-3

z

SKE.X5-2-1 (from VF.X15)

z

SKE.X5-3-1

Option: parallel operated converters If not existing, check bridges on pins 1 + 2 and pins 5 + 6

Optional Check bridge on pins 1 + 2

Safety circuit Variodyn

(from VF.X15)

16.03.2005

Page 6 of 75

K604016 Chapter 2: Preparation of Control z

SKE.X5-7-1 (from AS.X3-2-4)

z

z

z

SKE.X5-8-1

Safety circuit hand drive

(from KHA.X4)

If not existing, check bridge on pins 1 + 2

SKE.X5-8-2

RKPH

(from RKPH)

If not existing, check bridge on pins 1 + 2

SKE.X5-8-4 (from NGSK.X2 for safety circuit 100 VDC filtered) (from JFISK for safety circuit 88 VDC pulsed)

Connectors on MBB PCB

ESE

Power supply safety circuit

The following connectors must be unplugged: 209

z

MBB.X1-1-2 (from A.X3)

KB, KB1, THMH Check for correct ground connection of shielding!

The following connectors must be plugged in: z

MBB.X1-1-1 (from RMVE / RMPB, if existing)

z

210

MBB.X1-1-3 (from ZQF, if existing)

z

MBB.X1-1-4 (from A.X8, if existing)

z

MBB.X1-1-5 (from JTHB)

Connectors on ASILOG PCB

Motor fan / hydraulic brakes Trip counter Magnet brakes Power supply brake

The following connectors must be unplugged: z

ASILOG.X2-1-3 (from TDIW)

z

ASILOG.X2-1-4 (from VF)

211 z

ASILOG.X4-1-5

z

ASILOG.X4-2-1

z

ASILOG.THERMISTOR

Position tacho Drive communication Check for correct ground connection of shielding!

Option: GST Check, that no jumper on THERMISTOR (for VM and FM Gearless)

The following connectors must be plugged in: 212

Connectors on NGL

Check for jumper on PT100

z

ASILOG.PT100

z

ASILOG.X3-1-2

Power supply lift

(from BPL1.X2-1-2)

(polarity: pin 1 +, pin 2 -)

(for VM and FM Gearless)

The following connectors must be plugged in: z

213 z

NGL.X1

Power supply (input)

(from AS.X3-4-3)

(230 VAC)

NGL.X2

Power supply lift

(from BPL1.X2-1-1)

(24 VDC)

Connectors on BPL1 PCB The following connectors must be unplugged: z

BPL1.X4-1-2 (from ICE.X5-6-6)

214 z

BPL1.X4-1-3 (if existing, from LONLMDMS.X1 in MR)

16.03.2005

LON bus lift Option: LONLMDMS placed on hitch plate

Page 7 of 75

K604016 Chapter 2: Preparation of Control The following connectors must be plugged in: z

215

BPL1.X2-1-1

Power supply lift

(from NGL.X2) z

BPL1.X2-1-2

Power supply lift

(from ASILOG.X3-1-2)

Connectors on LONIOS and LONDAG PCBs

216 All connectors must be unplugged

Commissioning Procedure

217 Switch JH and JTHS to "ON"

Check that all connectors are unplugged

Check LED: 218

RKPH

ON

yellow

ON

green

Option: phase control relay

(if existing)

Check LED: 219

NGL

Power supply lift is OK

On ASILOG, check LEDs: 220

VCC

ON

green

P0 NGL

ON

green

See appendix A-4

On GCIO360, check LEDs:

221

STATUS

OFF

CPU

Flashing fast

green

WDOG

Blinking

green

ERROR

OFF

If LED ERROR is on, PCT is not available! See appendix A-8

On MBB, check LEDs:

222

+15V

ON

green

-15V

ON

green

+5V

ON

green

WDOG

ON

green

BRAKE ON

OFF

SKE OK

OFF

LOCKED

ON

yellow

ERROR

ON

red

See appendix A-15

223 Check display on SMLCD: "FATL" 224 Switch JTHSK to "ON"

Switch Thermal Safety Circuit

JFISK to "ON" 225 Switch (only for safety circuit 88 VDC pulsed)

Ground Fault Circuit Breaker Safety Circuit

On SKE, check LED: 226

T1

ON

green

Phase control relay

227 Switch JTHS to "OFF" The following connector on the ASILOG PCB must be plugged in: 228 z ASILOG.X3-1-1 NSG Battery, alarm power supply (from BATTERY)

(polarity: pin 1 +, pin 2 -)

229 Switch JTHS to "ON"

16.03.2005

Page 8 of 75

K604016 Chapter 2: Preparation of Control On ASILOG, check LED: 230

P0 NGL

ON

green

See appendix A-4

231 Switch JH to "OFF" Next Steps K 604016 E

16.03.2005

Now continue with 'Recall Travel with IMOF' according to document 'K 604010 Overall Commissioning Miconic TX-GC / 10-GC with VF...BR/PF1'. Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 9 of 75

K604016 Chapter 3: Inspection Travel with IMOF

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Chapter 3 Summary Preconditions

Inspection Travel with IMOF This chapter describes the activities for preparing the first travel on the car. z z

Preparation in Machine Room

Installation of the safety circuit on the car and in the shaft must be ready to be plugged in Recall Travel with IMOF must have been completed successfully (see document 'K 604010 - Overall Commissioning with VF...BR/PF1')

No.

Switch Position Location Remarks The following switches must be in the correct position:

300

No.

JH

OFF

MR

Switch Main Power

JTHS

OFF

MR

Switch Thermal Control

JRH

RECALL

AS

Switch Recall Control

JMOF

IMOF

ASILOG

Step The following connectors must be plugged in: z

BPL1.X4-1-1

z

z

BPL1.X4-1-2

LON bus lift

(from ICE.X5-6-6)

(via traveling cable)

EBLON.X1-1-1

LON bus lift

(from BPL1.X4-1-1) z

z

Preparation on the Car

No.

303

16.03.2005

AS.X3-4-1

Power car / door

(from OKR.X1-1-1, OKR.X1-1-2)

(via traveling cable)

SKE.X5-6-2

Safety circuit car

(from ICE.X5-5-1)

(via traveling cable)

Safety circuit hoistway

z

SKE.X5-7-2

z

Supplementary safety circuit cables

(in hoistway cable loom)

For options according to schematic diagram

Switch Position Location Remarks The following switches must be in the correct position:

302

No.

Remarks

LON bus lift

(from EBLON.X1-1-1)

301

Switch Installation Travel

JNGC

OFF

OKR

Switch Power Supply Car

JREC

INSPECTION

C

Switch Inspection Control

Step Remarks The following connectors must be unplugged in order to reach an predefined initial state for the whole procedure: z

All OKR connectors

z

All connectors on PCB ICE

z

All door drive connectors

Except pre-manufactured connectors / bridges and internal wiring!

Page 10 of 75

K604016 Chapter 3: Inspection Travel with IMOF The following connectors in the OKR must be plugged in: z

OKR.X1-1-1 (from AS.X3-4-1)

z

OKR.X1-2-1 (from T, if 400 VAC door drive installed)

z

Power door (400 VAC)

OKR.X1-4-1 (from T2, if 400 VAC door drive 2 installed)

z

OKR.X1-2-4 (from T, if 230 VAC door drive installed)

z

OKR.X1-1-3

Power door (230 VAC)

(from T2, if 230 VAC door drive 2 installed)

304

z

OKR.X1-1-2 (from AS.X3-4-1)

z

OKR.X1-2-2 (from ICE.X5-1-1)

z

OKR.X1-4-2

Power light (230 VAC)

(from C.PC) z

OKR.X1-4-3 (from C.LC)

z

OKR.X1-2-3 (from C.MVEC, if existing)

z

OKR.X1-3-1

Power supply car (230 VAC)

(from NGC.X1 / JNGC)

The following connectors on the ICE PCB must be plugged in: z

ICE.X5-6-1

Power supply car (24 VDC)

(from NGC.X2) z

ICE.X5-6-6

LON bus lift

(from AS.BPL1.X4-1-2) z

ICE.X5-4-13

Logic I/Os REC

(from C.REC) z

ICE.X5-5-1

Safety circuit car

(from AS.SKE.X5-6-2) z

ICE.X5-5-3

Safety circuit PHUET

(from SI.PHUET) z

ICE.X5-5-4

Safety circuit final limit switch

(from C.KNE)

305

z

ICE.X5-5-7

Safety circuit REC

(from C.REC) z

ICE.X5-5-8

Safety circuit door

(from T.JHCT, if existing) z

ICE.X5-5-9 (from C.KF)

z

Safety circuit safety gear

ICE.X5-5-10 (from C.KF1)

z

z

ICE.X5-1-1

Power supply light

(OKR.X1-2-2)

(car light and optional car ventilator)

ICE.X5-5-2

z

(from KNA) z

ICE.X5-5-5

(from DH) z

(from KSSC) z

ICE.X5-5-6 (from ICE2)

16.03.2005

ICE.X5-5-11 ICE.X5-5-12 (from DH2)

z

ICE.X5-5-13 (from ETSL)

These options (safety circuit) in may be available depending on your installation (if not existing / not yet commissioned, check for bridges)

Page 11 of 75

K604016 Chapter 3: Inspection Travel with IMOF The following door connectors must be plugged in on the ICE PCB: z

ICE.X5-2-5 (standard)

306

z

Schindler doors

ICE.X5-2-6 (optional)

ICE.X5-2-1 Third party doors ICE.X5-2-2 (usage of connectors depending on door type) z ICE.X5-2-4 The following additional safety circuit connectors must be plugged in: z z

307

z

T.X#-#-#

Safety circuit door (JHCT, KTC)

(door type specific connector) z

All additional safety circuit cables

According to schematic diagram

Check LON bus address of ICE PCB

ICE: HIGH = B, LOW = 1 ICE2: HIGH = B, LOW = 2

Check for BAFL on ICE PCB

Bus terminator for lift bus

(on ICE.X5-6-7)

(on ICE or on IC2, if existing)

309

Check that LONBIO16 PCB is plugged in on ICE PCB

Attention: Grounding of LONBIO16 via metal distance bolt to ICE PCB must exist and is fully tightened (EMI)!

310

Close the car door fully and prevent it from opening

308

Execute No. Inspection Travel

311

Switch Position Location The following switch settings must be changed now:

Remarks

JH

ON

MR

Switch Main Power

JTHS

ON

MR

Switch Thermal Control

JHL

ON

MR

Switch Main Light

JFIL

ON

AS

Ground Fault Circuit Breaker Light

JFISK

ON

AS

Ground Fault Circuit Breaker Safety Circuit (only for safety circuit 88 VDC pulsed)

16.03.2005

Page 12 of 75

K604016 Chapter 3: Inspection Travel with IMOF No.

Step

Remarks

312 Switch JNGC to "ON" On the ICE PCB, check the following LEDs:

313

P0

ON

green

VCC

ON

green

APPL

ON, blinking green

SERV

OFF

SERV is temporary ON (red) during download of LON application software

314

Press "DREC-D"

Car travels downwards

Press "DREC-U"

Car travels upwards

Carry out a short travel and check operation of JHC

Check safety circuit REC

Check the operation of all switches 315 and contacts in the safety circuit 316 Switch JREC to "NORMAL"

Next Steps

K 604016 E

16.03.2005

Ensure that the car has free passage! Attention: Make sure that hoistway doors are open!

Now continue with 'Installation and Commissioning of Further Components' according to document 'K 604010 - Overall Commissioning Miconic TX-GC / 10-GC with VF...BR/PF1'. Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 13 of 75

K604016 Chapter 4: Measuring Travel

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Chapter 4 Summary

Preconditions

Measuring Travel This chapter describes the activities for preparing and executing the "Measuring Travel". z

Door drive must have been commissioned Hoistway and car doors must have been set up mechanically

z z

The mechanical installation is complete The following components must have been installed: z Position tacho IGS200 or IGBV200 (installation specific) z

Door overbridging PHUET (PHS, PHNR-D)

z

Hoistway information (installation specific: KSE-U / KSE-D, ETSL)

z

Car operating panel (for Miconic 10-GC only, the HTIC PCB and the Z-Line Car Elements must have been installed)

z z

The operation of all switches and contacts in the safety circuit has been checked The counterweight is still equal to the weight of the car, in the current stage of installation ± 10% Important for balance of car when brake is opened!

Preparation in Machine Room

No.

Switch Position Location Remarks The following switches must be in the correct position:

400

No.

JTHS

OFF

MR

Switch Thermal Control

JRH

RECALL

AS

Switch Recall Control

Step Remarks The following connector on the ASILOG PCB must be plugged in: z

ASILOG.X2-1-3 (from MR.TDIW)

401 z

BPL1.X4-1-3 (if existing, from LONLMDMS.X1 in MR)

Position tacho Check for correct ground connection of shielding!

Option: LONLMDMS placed on hitch plate

402 Switch JTHS to "ON" Set the parameter Load Type to "NO_LM" using the SMLCD command load measurement 403 Parameter -> Drive Settings -> Load Type Disable (SMLCD must be logged in for this command) (SW version 1.43 or older: Parameter -> Drive -> Load Type)

404 Set car in motion with recall control

If an emergency stop occurs, change over signal A with B and N_A with N_B on ASILOG.X2-1-3:

Pin

Preparation on the Car

A

B

N_A

N_B

6

4

5

3

405 Switch JNGC to "OFF" The following connectors on the ICE PCB must be plugged in: z

ICE.X5-2-7 (from T.RPHT)

z

ICE.X5-2-8

Door reversing devices

(from T.REP, if existing)

16.03.2005

Page 14 of 75

K604016 Chapter 4: Measuring Travel z

z

ICE.X5-4-2

Hoistway information

(from AS.SKE.X5-5-2)

(via traveling cable)

ICE.X5-4-1 (from SI.KSE-U)

z

Shaft end contacts

ICE.X5-4-3 (from SI.KSE-D)

z

ICE.X5-4-4 (from SI.PHS)

406

z

ICE.X5-4-5

Door overbridging

(from SI.PHNR-D) z

ICE.X5-4-11 (from SI.PHUET)

z

Option: LONLMDMS

ICE.X5-6-5 (from LONLMDMS, if existing)

z

ICE.X5-4-6

Option: Load contacts

(from C.KL-X, if existing) z

ICE.X5-4-7 (from C.KL-V, if existing)

407 Switch JNGC to "ON" On the ICE PCB, check the following LEDs: 408

P0

ON

green

VCC

ON

green

See appendix A-10

Execute 409 Switch JTHS to "OFF" Measuring Travel The following connector on the SKE PCB must be plugged in: 410 z SKE.X5-5-2 Hoistway information (from OKR.ICE.X5-4-2)

(via traveling cable)

411 Switch JTHS to "ON" Move the car with ESE and check the following signal levels visually using the SMLCD command Status -> Board I/Os -> Local I/O z I/Os N_PHS and N_PHNR-D:

412

z

Hoistway

N_PHS

N_PHNR-D

Out of floor level

1i

1i

In vane, below

1i

0a

On floor level

0a

0a

In vane, above

0a

1i

Values for I/O status: Low

High

Inactive

0i

1i

Active

0a

1a

(see appendix A-19)

I/Os for shaft end contacts: Hoistway

KSE-U

KSE-D

Bottom

1a

0i

Middle

1a

1a

Top

0i

1a

413 Release car doors, if blocked 414 Switch JRH to "NORMAL" 415

Switch JMOF on ASILOG PCB to "NORMAL"

Activate JLF using the SMLCD command Wait until measuring travel is 416 Commands -> Special trips -> JLF finished! (SMLCD must be logged in for this command)

16.03.2005

Page 15 of 75

K604016 Chapter 4: Measuring Travel Check that for every access side one door movement has been done: Send a car to a floor with access side 1 (and if available to access side 2) by Measuring travel of door drive 417 using SMLCD and ensure the door opens and closes. Commands -> Car Call -> Floor -> Entry Side

418

In case of load measurement with load contacts, set the parameter Load Type to Load Type = "KL_LMS" for load the appropriate value using the SMLCD contacts. command Parameter -> Drive Settings -> Load Type (SMLCD must be logged in for this command) (SW version 1.43 or older: Parameter -> Drive -> Load Type)

In case of load measurement with LONLMDMS this parameter will be set during LONLMDMS commissioning. Check Ground Fault Circuit Breakers

419

Switch JRH to "RECALL"

Check all Ground Fault Circuit Breakers for correct operation: 420 z JFIS z DSKEL and DSKIK (only for safety circuit 100 VDC filtered) z

K 604016 E

16.03.2005

LONLMDMS will be setup later

Use the Test Pushbutton. If the test fails, replace the defective device!

JFIL Document version 06, released - last edited on March 14, 2005

Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 16 of 75

K604016 Chapter 5: Car I/Os

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Chapter 5

Car I/Os

Summary

This chapter describes the activities for connecting and commissioning all car I/Os.

Contents

K 604016 E

16.03.2005

No.

Section

5-1

Commissioning in the Machine Room

5-2

Preparation of the Car

5-3

Commissioning the Car

5-4

Checks Document version 06, released - last edited on March 14, 2005

Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 17 of 75

K604016 Section 5-1: Car I/Os - Commissioning in the Machine Room

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 5-1 Switches

Commissioning in the Machine Room No.

Switch Position Location Function The following switches must be in the correct position:

500

JTHS

OFF

MR

Switch Thermal Control

JHG

OFF

MR

Switch Main Group

JHL

ON

MR

Switch Main Light

JH

ON

MR

Switch Main Power

JRH

RECALL

AS

Switch Recall Control

By switching JHG to "OFF", the group functions of all elevators in the group are switched off! Commissioning Procedure

No.

Step Remarks The following connectors on the ASILOG PCB must be plugged in: z

501

ASILOG.X4-1-1

Alarm horn

(from +SZ.SOA) z

ASILOG.X4-1-3

NSG Battery (12 VDC)

(from ICE.X5-3-5)

(to traveling cable)

502 Switch JTHS to "ON" Check LED on ASILOG: 503

K 604016 E

16.03.2005

P0 NGL

ON

Power lift is ok green

(see appendix A-4)

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 18 of 75

K604016 Section 5-2: Car I/Os - Preparation of the Car

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 5-2

Preparation of the Car Please observe that there are live voltages at the following locations: z 230 VAC on OKR.ICE for power supply light z 400 VAC on OKR.X1 for power supply door.

Switches

No.

Switch Position Location Function The following control switches must be in the correct position:

504

No.

JREC

INSPECTION

C

Switch Inspection Control

JNGC

OFF

OKR

Switch Power Supply Car

Switch

Value HIGH

LOW

Location

Function

The following LON bus address switches must be in the correct position: TC11.TIC1

C

1

TC11

TC11.TIC2

C

2

TC11

TC11.TIC3

C

3

TC11

505 TC11.TIC4 TC12.TIC1

C

4

TC11

C

5

TC12

TC12.TIC2

C

6

TC12

TC12.TIC3

C

7

TC12

TC12.TIC4

C

8

TC12

Lift bus car, access side 1, tableau 11 (see appendix A-17)

Lift bus car, access side 1 tableau 12 (see appendix A-17)

Addresses of Miconic 10-GC car elements have been set during their commissioning.

Connectors

No.

Step

Remarks

Attention: Grounding of LONBIO16 via Check that LONBIO16 PCB is plugged in metal distance bolt to TIC PCB 506 on all TIC PCBs must exist and is fully tightened (EMI)! The following connectors on TC11 must be plugged in: z

TC11.TIC1.X4-1-1 (from ICE.X5-6-3)

z

TC11.TIC1.X2-1-4 (from TC11.TIC2.X4-1-1, if existing)

z

TC11.TIC2.X4-1-1 (from TC11.TIC1.X2-1-4, if existing)

507

z

z

TC11.TIC2.X2-1-4

Lift bus and 24 VDC power car

(from TC11.TIC3.X4-1-1, if existing)

(see appendix A-17)

TC11.TIC3.X4-1-1 (from TC11.TIC2.X2-1-4, if existing)

z

TC11.TIC3.X2-1-4 (from TC11.TIC4.X4-1-1, if existing)

z

TC11.TIC4.X4-1-1 (from TC11.TIC3.X2-1-4, if existing)

16.03.2005

Page 19 of 75

K604016 Section 5-2: Car I/Os - Preparation of the Car

508

Miconic 10-GC Connectors

For additional car operating panels (TC12/21/22) proceed according to TC11 in step above.

The following connectors on TC11 must be plugged in: 509

z

TC11.TIC1.X2-1-4 (from TC11.ZRTL.X1 for Terminal) (from TC11.HTIC.X1 for FFU)

Lift bus and 24 VDC power car for Hidden Box with Z-Line Terminal / Firefighting Unit (FFU) (see appendix A-17)

510 K 604016 E

16.03.2005

For additional Z-Line car elements (TC12/21/22) proceed according to TC11 in step above. Document version 06, released - last edited on March 14, 2005

Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 20 of 75

K604016 Section 5-3: Car I/Os - Commissioning the Car

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 5-3 Power Supply Alarm

Commissioning the Car No.

Step Remarks The following connectors on the ICE PCB must be plugged in: z

z

511

Emergency Light Car in COP

(from TC11.LNC)

(see Appendix A-10)

ICE.X5-3-9

Push Button Alarm next to REC

(from C.DA) z

z

TICs and LMS

ICE.X5-3-1

ICE.X5-3-11

Push Button Alarm in COP

(from TC11.DA)

(see Appendix A-10)

ICE.X5-3-5

NSG Battery for Alarm

(from ASILOG.X4-1-3)

(see Appendix A-10)

Power supply car 512 Switch JNGC to "OFF" The following connectors on the ICE PCB must be plugged in: z

513

Plug in connector ICE.X5-6-3 (from TC11.TIC1)

z

Lift bus, power supply car

Plug in connector ICE.X5-6-4 (from TC12.TIC1, if existing)

514 Switch JNGC to "ON"

Power supply car

Check LED on ICE PCB: 515

P0

ON

Power supply car 24 VDC is ok green

(see Appendix A-10)

Check LEDs on TC11.TIC1..4 and TC12.TIC1..4: (if existing)

516

P0

ON

green

APPL

FLASHING green

SERV

OFF1)

Power supply car 24 VDC is ok LON node is running (see Appendix A-17)

1)

SERV is temporary ON during download of LON application software (check on SMLCD)

Miconic 10-GC Specific Devices

517 Switch JNGC to "OFF"

Power supply car

in connector ICE.X5-6-2 518 Plug (from AZRC.X1, if existing)

Destination Indicator(s)

519 Switch JNGC to "ON"

Power supply car

Check LED on ICE: 520

ICE2

P0

Power supply car 24 VDC is ok ON

green

(see Appendix A-10)

If there is an ICE2 PCB, it must be 521 commissioned according to the ICE PCB See schematics (steps 512 to 520)

(OKR2 with ICE2 PCB only required, if there

16.03.2005

Page 21 of 75

K604016 Section 5-3: Car I/Os - Commissioning the Car

522

Commissioning Procedure

If there is an ICE2 PCB, connect lift bus and power supply from ICE PCB

are two access sides, i.e. two door drives)

523 Open car door(s) manually Check type and address of car LON nodes: z LONLMDMS (if existing)

524 Miconic 10-GC only: z Z-Line Terminal in hidden box

In the machine room: Use SMLCD

(if existing) z

HTIC(s) of Z-Line Firefighting Unit (if existing)

z

AZRC (Z-Line Destination Indicators)

Press "DREC-D" until all car doors are 525 completely closed

On the car: Check operation of doors and REC (now with switch JMOF on "NORMAL")

526

Position the car so that work can be done in and on top of it.

Make various car calls: 527 Calls should be acknowledged, and then be cancelled after approx. 1 second

In the car: Press various call buttons on car operating panel

For the next steps, ETSL, LONLMDMS 528 and door reversing devices must be operational

For reference documents see document 'K 604010 - Overall Commissioning Miconic TX-GC / 10-GC with VF...BR/PF1'

529 Close car doors

530 Switch JREC to "NORMAL"

531

K 604016 E

16.03.2005

Leave the car and then close hoistway doors

On the car Attention: Make sure that landing doors are open! The safety circuit must be open when switching JREC to "NORMAL", otherwise the elevator will start a correction travel.

Attention: The elevator will now execute a correction travel to the next floor level! Be sure to leave the car / the car roof, as the elevator will start a correction travel as soon as the hoistway doors are closed.

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 22 of 75

K604016 Section 5-4: Car I/Os - Checks

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 5-4 Car Calls

Car Operating Panel

Checks No.

Step

Remarks

Enter at least 5 car calls using the SMLCD 532 Do this before you drive yourself inside the car!

In machine room (ASILOG) Check if an emergency stop occurs!

Activate the car reservation control using 533 the SMLCD command: Commands » Services » JRV=ON

With JRV active, the car door remains open upon arrival

Travel to all floors z Miconic TX-GC: by making car calls on car operating panel z Miconic 10-GC: by making car calls using Hidden Box with Terminal or Firefighting Unit (if existing)

and check: In the car 534 z that all calls are answered z that doors are operating correctly z that the door reversing devices are operating correctly z that indicators are operating correctly: z Miconic TX-GC: Position indicator (if existing) z

Miconic 10-GC: Destination indicators

Press push-buttons DA in the car and on the car: 535 As long as pushed the Alarm Horn must be heard

In the car (COP), on the car (REC)

Deactivate the car reservation control 536 using the SMLCD command: Commands » Services » JRV=OFF Next Steps

K 604016 E

16.03.2005

Now continue with commissioning of further components according 'Car I/Os' in document 'K 604010 - Overall Commissioning Miconic TX-GC / 10-GC with VF...BR/PF1'. Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 23 of 75

K604016 Chapter 6: Lift I/Os

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Chapter 6

Summary

Lift I/Os This chapter describes the activities for connecting and commissioning all lift I/Os for the elevator functions of the control in a simplex installation, or for an individual elevator in a multiplex installation. No.

Contents

Section

6-1

Preparation

6-2

Commissioning BPL PCBs

6-3 Checks K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 24 of 75

K604016 Section 6-1: Lift I/Os - Preparation

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 6-1 Preconditions

Preparation z z

Switches

Commissioning must have been successfully completed up to and including "Chapter 5 - Car I/Os". All lift specific inputs and outputs must have been completely installed and wired up to the LONIOS16 and LONDAG PCBs according to schematic diagram.

No.

600

PCBs

No.

Switch JTHS

Position OFF

Location MR

JHL

ON

MR

Switch Main Light

JH

ON

MR

Switch Main Power

JREC

NORMAL

C

JRH

RECALL

AS

z

LONIOS11

BPL1.X5-1-1

z

LONIOS12

BPL1.X5-1-2

z

LONIOS13 (if existing)

z

LONIOS14 (if existing)

z

LONDAG1 (if existing)

602

Interconnection of BPL PCBs

No.

Switch Thermal Control

Switch Inspection Control Switch Recall Control

PCB Plug-in Location Function The following PCBs must be plugged in on BPL1 and the LON bus address switches must be in the correct positions (see Appendix A-20):

(if existing)

601

Function

BPL1.X5-1-3

Lift I/O on BPL1

BPL1.X5-1-4 BPL1.X5-1-4

Lift I/O for Direction Arrow, Gong

For additional lift specific BPL PCBs proceed according to BPL1 in step above.

Step Remarks The following connectors on the BPL PCBs must be plugged in: z

603

BPL(#).X4-1-4 (from X2-1-1 of next lift BPL)

z

BPL(#+2).X2-1-1

LON bus lift According to schematic diagram # = 1, 3, 5

(from X4-1-4 of previous lift BPL)

K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 25 of 75

K604016 Section 6-2: Lift/Os - Commissioning BPL PCBs

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 6-2 Commissioning BPL1

Commissioning BPL PCBs No. 604

Step

Remarks

Check for correct wiring of hoistway cables

LONIOS11..14, LONDAG1

605 Switch JTHS to "ON" Check LEDs on LONIOS11..14 and LONDAG1: (if existing)

606

P0

ON

green

APPL

FLASHING

green

SERV

OFF1)

Power lift 24 VDC is ok LON node is running See appendices A-12, A-13

1) SERV is temporary ON during download of LON application software (check on SMLCD)

Check LON nodes for types and addresses using SMLCD: 607 z LONIOS11 ... LONIOS14 z LONDAG1

See appendix A-20 for LON node addresses

608 Switch JTHS to "OFF" Plug in connectors to z LONIOS11.X1-1-1 z LONIOS11.X1-2-1 z LONIOS12.X1-1-1 z LONIOS12.X1-2-1 z LONIOS13.X1-1-1 609 z LONIOS13.X1-2-1 z LONIOS14.X1-1-1 z LONIOS14.X1-2-1 z LONDAG1.X1-1-1 z LONDAG1.X1-2-1 z LONDAG1.X1-2-2

Lift I/Os from hoistway cable loom See appendices A-5, A-12, A-13

(if existing)

610 Switch JTHS to "ON" Check LEDs on LONIOS11..14 and LONDAG1: (if existing)

611

P0

ON

green

APPL

FLASHING

green

SERV

OFF1)

Power lift 24 VDC is ok LON node is running See appendices A-12, A-13

1)

SERV is temporary ON during download of LON application software (check on SMLCD)

16.03.2005

Page 26 of 75

K604016 Section 6-2: Lift/Os - Commissioning BPL PCBs Commissioning 612 Switch JTHS to "OFF" BPL1 for Miconic 10-GC (Simplex) Plug in connectors to z LREP2 on BPL1.X5-1-1 613 z LREP2 on BPL1.X5-1-2 z LREP2 on BPL1.X5-1-3 z LREP2 on BPL1.X5-1-4

ZRTL I/Os from hoistway cable loom Attention:

Before plugging in the connectors, make sure that no Z-Line Terminal (ZRTL) at all is connected to the respective hoistway cables. The Z-Line Terminals must first be connected and commissioned (see K 604027) after commissioning of the control is finished.

(if existing)

614 Switch JTHS to "ON" Check LED on ASILOG: 615

P0 NGL

ON

Power lift 24 VDC is ok green

See appendix A-4

If you do not have any further BPL PCBs with lift I/Os, proceed with Section 6-3, 'Checks'. Commissioning Further BPLs

K 604016 E

16.03.2005

For additional BPL PCBs with lift I/Os 616 proceed according to BPL1 in the steps above.

See schematic diagram for the BPL specific designations of the respective I/O PCBs and I/Os

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 27 of 75

K604016 Section 6-3: Lift I/Os - Checks

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 6-3 Check I/Os

Checks No.

Step

617 Switch JRH to "NORMAL"

Remarks Be careful! The car may move!

If this elevator is intended for SIMPLEX operation, you should now check all I/Os connected: Miconic TX-GC: z press landing call buttons: calls are acknowledged and this elevator answers the calls z the further travel indicator is lighted and the gong is activated when the car arrives to serve the call 618 z check all other I/Os Miconic 10-GC: z enter destination on terminal: calls are acknowledged by indicating the elevator designation of this elevator, and it answers the calls z check all other I/Os If this elevator is intended for MULTIPLEX operation, this I/O check will be carried out at a later stage. Final Steps

Execute this step only for SIMPLEX elevator: If this elevator is intended for SIMPLEX operation, commission all control options and check operation for every 619 option. Activate LON Node Dead Behavior using SMLCD Command Commands -> Service Visit = OFF

Next Step K 604016 E

16.03.2005

See installation specific schematic diagrams Monitors failure of nodes with critical signals (e.g. JBF)

Now continue with 'Completion Work Drive' according to document 'K 604010 Overall Commissioning Miconic TX-GC / 10-GC with VF...BR/PF1'. Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 28 of 75

K604016 Chapter 7: Group I/Os

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Chapter 7

Group I/Os

Summary

This chapter describes the activities for connecting and commissioning all group I/Os for the group functions of all elevators with group specific I/Os. There are cabinets in a multiplex installation without group specific I/Os. For these cabinets, only steps 703 and 704 in section '7-1 Preparation' must be executed, the rest of this chapter can then be skipped!

Contents

K 604016 E

16.03.2005

No.

Section

7-1

Preparation

7-2

Commissioning NGG

7-3

Commissioning BPL PCBs

7-4

Checks Document version 06, released - last edited on March 14, 2005

Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 29 of 75

K604016 Section 7-1: Group I/Os - Preparation

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 7-1

Preconditions

Preparation z z

Commissioning must have been successfully completed up to and including "Chapter 6 - Lift I/Os". 'Completion Work Drive' must have been successfully completed (see document 'K 604010 - Overall Commissioning Miconic TX-GC / 10-GC with VF...BR/PF1')

z

All group specific inputs and outputs must have been completely installed and wired up to the LONIOS16 PCBs according to schematic diagram

Switches No.

700

Switch JTHS

Position ON

Location MR

Function

JHG

OFF

MR

Switch Main Group

JHL

ON

MR

Switch Main Light

JH

ON

MR

Switch Main Power

JREC

NORMAL

C

JRH

RECALL

AS

Switch Thermal Control

Switch Inspection Control Switch Recall Control

By switching JHG to "OFF", the group functions of all elevators in the group are switched off! PCBs PCB Plug-in Location Function The following PCBs must be plugged in on BPL2 and the LON bus address switches must be in the correct positions (see Appendix A-20):

701

z

LONIOS21

BPL2.X5-1-1

z

LONIOS22

BPL2.X5-1-2

(if existing) z

LONIOS23 (if existing)

z

LONIOS24 (if existing)

702

Connection to Control

No. 703

BPL2.X5-1-3

Group I/O on BPL2

BPL2.X5-1-4

For additional group specific BPL PCBs proceed according to BPL2 in step above.

Step Remarks The following connector on the BPL2 PCB must be plugged in: z

BPL2.X4-1-1 (from EBLON.X1-1-2)

LON bus group

The following connectors on the EBLON PCB must be plugged in: 704

z

EBLON.X1-1-2 (from BPL2.X4-1-1)

16.03.2005

LON bus group

Page 30 of 75

K604016 Section 7-1: Group I/Os - Preparation Interconnection of BPL PCBs

The following connectors on the BPL PCBs must be plugged in: z

705

BPL(#).X4-1-4 (from X2-1-1 of next group BPL)

z

BPL(#+2).X2-1-1

LON bus group According to schematic diagram # = 2, 4, 6

(from X4-1-4 of previous group BPL)

K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 31 of 75

K604016 Section 7-2: Group I/Os - Commissioning NGG

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 7-2 Commissioning Procedure

Commissioning NGG No.

Step Remarks The following connectors in the AS must be plugged in: z

706

AS.X8-2-1 (from JHG)

z

Power group 230 VAC

AS.X8-4-2 (from NGG.X1)

The following connectors on NGG must be plugged in: z

707

NGG.X1

Power group 230 VAC

(from AS.X8-4-2) z

NGG.X2

Power group 24 VDC

(from BPL2.X2-1-1)

The following connectors on the BPL2 PCB must be plugged in: z

BPL2.X2-1-1 (from NGG.X2) (polarity: pin 2 +, pin 3 -)

708 z

Power group 24 VDC

BPL2.X2-1-2 (from ASILOG.X3-1-3)

The following connector on the ASILOG PCB must be plugged in: 709

z

ASILOG.X3-1-3

Power group 24 VDC

(from BPL2.X2-1-2) (polarity: pin 1 +, pin 2 -)

710 Switch JHG to "ON" Check LED on NGG: 711

---

ON

green

See appendix A-18

Check LED on ASILOG: 712

K 604016 E

16.03.2005

P0 NGG

ON

green

See appendix A-4

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 32 of 75

K604016 Section 7-3: Group I/Os - Commissioning BPL PCBs

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 7-3 Commissioning BPL2

Commissioning BPL PCBs No. 713

Step

Remarks

Check for correct wiring of hoistway cables

LONIOS21..24

Check LEDs on LONIOS21..24 (if existing)

714

P0

ON

green

APPL

FLASHING green

SERV

OFF1)

Power group 24 VDC is OK, LON node is running See appendix A-13

1)

SERV is temporary ON during download of LON application software (check on SMLCD)

Check LON nodes for type and address 715 using SMLCD: z LONIOS21 ... LONIOS24

See appendix A-20 for LON node addresses

716 Switch JHG to "OFF" Plug in connectors on z LONIOS21.X1-1-1 z LONIOS21.X1-2-1 z LONIOS22.X1-1-1 717 z LONIOS22.X1-2-1 z LONIOS23.X1-1-1 z LONIOS23.X1-2-1 z LONIOS24.X1-1-1 z LONIOS24.X1-2-1

Group I/Os from hoistway cable loom See appendices A-5, A-13

(if existing)

718 Switch JHG to "ON" Check LEDs on LONIOS21..24 (if existing)

719

P0

ON

green

APPL

FLASHING green

SERV

OFF1)

Power group 24 VDC is OK, LON node is running See appendix A-13

1)

SERV is temporary ON during download of LON application software (check on SMLCD)

Commissioning 720 Switch JHG to "OFF" BPL2 for Miconic 10-GC (Multiplex) Plug in connectors to z LREP2 on BPL2.X5-1-1 721 z LREP2 on BPL2.X5-1-2 z LREP2 on BPL2.X5-1-3 z LREP2 on BPL2.X5-1-4

ZRTL I/Os from hoistway cable loom Attention:

Before plugging in the connectors, make sure that no Z-Line Terminal (ZRTL) at all is connected to the respective hoistway cables. The Z-Line Terminals can first be connected and commissioned (see K 604027) after commissioning of the control is finished.

(if existing)

722 Switch JHG to "ON" Check LED on ASILOG: 723

16.03.2005

P0 NGG

ON

Power group 24 VDC is OK green

See appendix A-4

Page 33 of 75

K604016 Section 7-3: Group I/Os - Commissioning BPL PCBs z z

Commissioning Further BPLs

K 604016 E

16.03.2005

By switching JHG to "OFF", the group functions of all elevators in the group are switched off! If you do not have any further BPL PCBs with group I/Os, proceed with Section 7-4, 'Checks'.

For additional BPL PCBs with group I/Os 724 proceed according to BPL2 in the steps above.

See schematic diagram for the BPL specific designations of the respective I/O PCBs and I/Os

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 34 of 75

K604016 Section 7-4: Group I/Os - Checks

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 7-4 Check I/Os

Checks No.

Step

725 Switch JRH to "NORMAL"

Remarks Be careful! The car may move!

Check the correct operation of the I/Os connected to the Group Bus: z Miconic TX-GC: press landing call buttons: calls are acknowledged and this 726 elevator answers the calls z Miconic 10-GC: enter destination on terminal: calls are acknowledged by indicating the elevator designation of this elevator, and it answers the calls Check the correct operation of the I/Os connected to the Lift Bus: z Miconic TX-GC: the further travel indicator is lighted 727 and the gong is activated when the car arrives to serve the call z Miconic 10-GC: check all other I/Os Control Options

K 604016 E

16.03.2005

Commission all control options (lift and See installation specific 728 group) and check operation of every schematic diagrams option. Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 35 of 75

K604016 Chapter 8: Group Control

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Chapter 8

Group Control

Summary

This chapter describes the activities for commissioning the multiplex functions of the control.

Contents

K 604016 E

16.03.2005

No.

Section

8-1

Duplex / Multiplex Elevators 1 and 2

8-2

Further Multiplex Elevators

8-3

Checks Document version 06, released - last edited on March 14, 2005

Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 36 of 75

K604016 Section 8-1: Group Control - Duplex / Multiplex Elevators 1 and 2

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 8-1

Duplex / Multiplex Elevators 1 and 2

Summary

This section contains information on connecting the elevators in a duplex system. The same procedure must be executed for connecting the first two elevators in a multiplex system.

Preconditions

z z

Switches

For all elevators in the group, commissioning must have been successfully completed up to and including "Chapter 7 - Group I/Os". If you have a GW PCB installed, check wiring of EBCOM according to schematic diagrams.

The following switches must be in the correct position for elevators 1 and 2: No.

800

Elevator 1

No.

Position OFF

Location MR

JHG

OFF

MR

Switch Main Group

JHL

OFF

MR

Switch Main Light

JH

ON

MR

Switch Main Power

Step

Switch Thermal Control

Remarks Bus termination for group bus

in connector =L1+BPL2.X4-1-3 802 Plug (from L2)

Group bus LON

in connector =L1+EBCOM.X1-1-1 803 Plug (from L2)

Group bus VCOM

z z

Switch =L1+EBCOM.A to "OFF" Switch =L1+EBCOM.B to "ON"

Enable bus termination for group bus VCOM

in connector =L2+BPL2.X4-1-2 805 Plug (from L1)

Group bus LON

Only for elevator 2 of duplex installation: 806 Plug in BAFG to BPL2.X4-1-3

Bus termination group bus LON

in connector =L2+EBCOM.X1-1-2 807 Plug (from L1)

Group bus VCOM

For elevator 2 of duplex installation: z Switch =L2+EBCOM.A to "ON" z Switch =L2+EBCOM.B to "OFF"

Enable bus termination for group bus VCOM

808 For elevator 2 of larger multiplex installation: z Switch =L2+EBCOM.A to "OFF" z Switch =L2+EBCOM.B to "OFF"

Disable bus termination for group bus VCOM

809

z z z

810

z z

Switch =L1.JRH to "RECALL" Switch =L2.JRH to "NORMAL"

Disable elevator 1

Switch JTHS to "ON" Switch JHG to "ON" Switch JHL to "ON"

811 Issue several floor calls

16.03.2005

Function

Plug in BAFG at connector 801 =L1+BPL2.X4-1-2

804

Elevator 2

Switch JTHS

Landing call button of elevator 1

Page 37 of 75

K604016 Section 8-1: Group Control - Duplex / Multiplex Elevators 1 and 2

812

Check if elevator L2 answers the calls correctly

If you have a duplex installation, proceed with Section 8-3, 'Checks'. For a multiplex installation, proceed with the next section 8-2 'Further Multiplex Elevators'. K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 38 of 75

K604016 Section 8-2: Group Control - Further Multiplex Elevators

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 8-2

Further Multiplex Elevators

Summary

This section contains information on adding further elevators to the elevators 1 and 2 which were previously connected as a group.

Elevator 3

No.

Step z

813

z z

Remarks

Switch JTHS to "OFF" Switch JHG to "OFF" Switch JHL to "OFF"

Plug in connector =L2+EBCOM.X1-1-1 814

(from L3)

Plug in connector =L3+EBCOM.X1-1-2

Interconnection of group bus VCOM

(from L2)

Plug in connector =L2+BPL2.X4-1-3 815

(from L3)

Plug in connector =L3+BPL2.X4-1-2

Interconnection of group bus LON

(from L2)

816

z z z

817

z z z

818

z z

Switch =L3+EBCOM.A to "OFF" Switch =L3+EBCOM.B to "OFF"

Disable bus termination for group bus VCOM

Switch =L1.JRH to "RECALL" Switch =L2.JRH to "RECALL" Switch =L3.JRH to "NORMAL"

Disable previous elevators

Switch JTHS to "ON" Switch JHG to "ON" Switch JHL to "ON"

819 Issue several floor calls 820

Check if elevator L3 answers the calls correctly

821

Commission all other elevators in this group

Elevators 4 to 8

Last Elevator

No. 822

K 604016 E

16.03.2005

According to elevator 3, steps 813 .. 820

Terminator Plug-in Location The following connector must be plugged in: z

No. 823

Landing call button of various elevators

BAFG

BPL2.X4-1-3 Step

z z

Switch EBCOM.A to "ON" Switch EBCOM.B to "OFF"

Function

Bus termination group bus LON Remarks Enable bus termination for group bus VCOM

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 39 of 75

K604016 Section 8-3: Group Control - Checks

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Section 8-3 Check Group I/Os

Checks No. 824

Step For all elevators: z switch JRH to "NORMAL"

Remarks Enable all elevators

Issue z Miconic TX-GC: several floor calls on landing call 825 buttons of various fixtures z Miconic 10-GC: several destination calls from various terminals Check correct operation of z Miconic TX-GC: the further travel indicators of all 826 elevators z Miconic 10-GC: the destination indicators in the arrived cars 827

Group Options

Check if all elevators answer the calls in accordance to their traffic mode

Check again operation of all group specific control options, now 828 considering multiplex operation (e.g. fireman's control or emergency power).

See installation specific schematic diagrams

Activate LON Node Dead Behavior using 829 SMLCD Command Commands -> Service Visit = OFF

Monitors failure of nodes with critical signals (e.g. JBF)

Commissioning is finished now. K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 40 of 75

K604016 Appendix A: References

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A

Summary Contents

References This chapter contains information on the references used in commissioning. No.

Section

A-1

Overview of Control Cabinet

A-2

Overview of OKR

A-3

Bus Termination BAFG/BAFL

A-4

PCB ASILOG3

A-5

PCB BPL

A-6

A-7

Picture

PCB EBCOM68

PCB EBLON1/2

A-8

PCB GCIOB360 (since Release 2.0)

A-9

PCB GCIO360 (up to Release 1.47)

A-10 PCB HTIC (Miconic 10-GC only)

A-11 PCB ICE

16.03.2005

Page 41 of 75

K604016 Appendix A: References

A-12 PCB LONBIO16

A-13 PCB LONDAG

A-14 PCB LONIOS16

A-15 PCB LREP2

A-16 PCB MBB

A-17 PCB SKE

A-18 PCB TIC

A-19 Power Supply Units A-20 Hoistway Information A-21 LON Addresses and Lift ID K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 42 of 75

K604016 Appendix A-1: References - Overview of Control Cabinet

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-1

Overview of Control Cabinet

Overview Picture This is an overview of the control cabinet AS for the control together with the associated parts list.

Overview Picture

16.03.2005

Page 43 of 75

K604016 Appendix A-1: References - Overview of Control Cabinet Component List Pos.

The following table identifies the individual components shown in the overview picture:

Name

Component

Techn. Data

Mat. No. -

AS

Control cabinet AS 1810

180 cm × 100 cm × 40 cm (HWD)

LONIOS

PCB LONIOS16.Q (LON interface to I/O for hoistway wiring)

-

590863

LONDAG

PCB LONDAG1.Q (LON interface to I/O for direction arrows, gong, and position indicators)

-

590873

LREP2

PCB LREP2.Q (LON bus repeater)

-

591353

3

BPL

PCB BPL1.Q (backplane for I/O PCBs Pos. 2)

-

590870

4

Battery

NSG Battery

3.5 Ah 12 VDC

419214

5

GW

PCB GW2.M (gateway to building bus, see K 603204) -

1

2

590861

6

Area for Variodyn drive up to VF120BR (one-cabinet solution)

-

-

7

Installation-specific documentation

-

-

TA4L1

Adapter transformer 4 wire for supply of NGL

680 VA

419626

TA4L2

Adapter transformer 4 wire for supply of NGC

940 VA

419272

TAB

Adapter transformer brake

730 VA

419627

With ventilator RV140

419782

With ventilator DV200

434362

With ventilator DV250

434375

(for control releases up to 1.47 only) (for control releases up to 1.47 only)

8 TAMVE/1 Adapter transformer motor ventilator 230 VA

9

NGAE2/3 Additional switching power supply units for indicators

10

NGAE

Switching power supply unit for indicators

11

NGG

Switching power supply unit group

12

NGL

Switching power supply unit lift

431609

(rel. 1.47 and higher)

150 W 24 VDC

419210 (up to rel. 1.46)

For positions 9 to 12, make sure to order the spare part, which fits your control version! (Attention: In a spare part order for releases up to 1.46, the power supply unit for release 1.47 and higher will be delivered on a mounting plate, which fits the installation conditions of the old power supply unit)

13

AS.X3

Terminal block AS.X3 including filter module

-

14

FENS

Mains filter FENS

400V 4x6A

419550

15

FEL

Mains filter light

460V 2x6A

417253

16

FENG

Mains filter group

460V 2x6A

417253

NGSK

Power supply unit safety circuit (transformer)

JTHSK

Thermal switch safety circuit

NGSK

Power supply unit safety circuit (transformer)

JTHSK

Thermal switch safety circuit

JFISK

Ground fault circuit breaker for safety circuit

JTHB

Thermal switch brake

17

16.03.2005

-

Only for safety circuit 100 VDC filtered 100 VDC filtered! JFISK not required! (release 1.45/1.46 and 230V 0.5A higher)

Only for safety circuit 88 VDC pulsed! (up to Release 1.43)

59400410 434380

88 VDC pulsed

258127

230V 0.2A

419577

FIKP2 110/30 2 pole (110 VAC pulsed)

434328

230V 3A

180013

Page 44 of 75

K604016 Appendix A-1: References - Overview of Control Cabinet JFIL

Ground fault circuit breaker for light supply

FIKP 240/30-T

217811

JFIS

Ground fault circuit breaker for control

FIK 440/30-T 4 pole

419605

Up to 0.4 A for geared

419783

0.6 A and higher for gearless

419784

THMVE

Thermal motor ventilator

RMVE

Relay motor ventilator

-

840718

18

-

Area for control options

-

-

19

ESE

Recall control

-

432485

20

SKE

PCB SKE1.M (safety circuit)

-

590871

21

MBB

PCB MBB3.M (brake module)

-

591442

PCB GCIO360.Q (CPU) 22

GC

590862

(for control releases up to 1.47 only)

-

PCB GCIOB360.Q (CPU)

591640

(for control release 2.0 only)

PCB EBLON1.Q (LON bus I/O from / to CPU for simplex elevator)

-

590888

PCB EBLON2.Q (LON bus I/O from / to CPU for multiplex elevator)

-

590865

EBCOM

PCB EBCOM68.Q (VCOM group connection - RS485)

-

590866

ASILOG

PCB ASILOG3.Q (application-specific interface logics and backplane for extension boards, includes SMLCD)

590867

-

BAFL

LON bus termination

105 Ω

434334

-

JTHS

Main switch control, delivered with AS

-

419594

23

24 25

EBLON

Component List K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 45 of 75

K604016 Appendix A-2: References - Overview of OKR

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-2

Overview of OKR

Overview Picture This is an overview of the car interface box OKR for the control together with the associated parts list.

Overview Picture

16.03.2005

Page 46 of 75

K604016 Appendix A-2: References - Overview of OKR Component List Pos.

The following table identifies the individual components shown in the overview picture:

Name

Component

1

OKR

OKR with individual parts: z 1a: cover z 1b: pull-out extension z 1c: base part z 1d: installation socket

2

REC

Inspection control panel

Techn. Data 39 cm × 35 cm × 26 cm (HWD) -

3

NGC

431609

(rel. 1.47 and higher)

150 W 24 VDC

(Attention: In a spare part order for releases up to 1.46, the power supply unit for release 1.47 and higher will be delivered on a mounting plate, which fits the installation conditions of the old power supply unit)

4

TAT

Adapter transformer

-

419999

Switching Power Supply Car Make sure to order the spare part, which fits your control version!

Mat. No.

419210 (up to rel. 1.46)

For QKS11, QKS9/10-1, Wittur AC

419994

For Fermator, Wittur DC

419945

5

JNGC

Switch for NGC

-

419980

6

OKR.X1

Terminal block OKR.X1

-

-

7

ICE

PCB ICE1.Q (car interface PCB)

-

590869

8

LONBIO

PCB LONBIO16.Q

-

590864

-

BAFL

LON bus termination

105 Ω

434334

-

HTIC

PCB HTIC (Miconic 10-GC only: interface to Z-Line Firefighting Unit)

-

180993

-

LONLMDMS Load measurement system

-

419995

-

LREP2

PCB LREP2.Q (optional LON repeater on ICE PCB)

-

591353

-

TIC

PCB TIC (interface to car operating panel)

-

590868

Component List K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 47 of 75

K604016 Appendix A-3: References - Bus Termination BAFL/BAFG/BAF

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-3

Bus Termination BAFL/BAFG/BAF

Introduction

This section contains an overview of the bus termination BAFL/BAFG/BAF.

Bus Termination BAFL/BAFG/BAF K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 48 of 75

K604016 Appendix A-4: References - PCB ASILOG3

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-4

PCB ASILOG3

Introduction

This section contains an overview of the ASILOG3 PCB.

PCB ASILOG3 K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 49 of 75

k604016 Appendix A-5: References - PCB BPL

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-5

PCB BPL

Introduction

This section contains an overview of the BPL PCB.

PCB BPL K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 50 of 75

K604016 Appendix A-6: References - PCB EBCOM68 Miconic TX-GC / 10-GC

INVENTIO AG

CO MMISSIONING © 01/2001

Appendix A-6

PCB EBCOM68

Introduction

This section contains an overview of the EBCOM68 PCB.

Versions QC and Higher

16.03.2005

Page 51 of 75

K604016 Appendix A-6: References - PCB EBCOM68

Versions QA and QB (with Different Switches A/B) K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 52 of 75

K604016 Appendix A-7: References - PCB EBLON1/2

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-7

PCB EBLON1/2

Introduction

This section contains an overview of the EBLON1 and EBLON2 PCBs (EBLON1 is a mounting variant with only one channel: X1-1-1).

PCB EBLON1/2 K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 53 of 75

K604016 Appendix A-8: References - PCB GCIOB360

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-8 Introduction

PCB GCIOB360 This section contains an overview of the GCIOB360 PCB.

PCB GCIOB360 K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 54 of 75

K604016 Appendix A-9: References - PCB GCIO360

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-9 Introduction

PCB GCIO360 This section contains an overview of the GCIO360 PCB.

PCB GCIO360 K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 55 of 75

K604016 Appendix A-10: References - PCB HTIC

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-10 Introduction

PCB HTIC This section contains an overview of the HTIC PCB (used for Miconic 10-GC only).

PCB HTIC (Front / Back) K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 56 of 75

K604016 Appendix A-11: References - PCB ICE

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-11 Introduction

PCB ICE This section contains an overview of the ICE PCB.

PCB ICE K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 57 of 75

K604016 Appendix A-12: References - PCB LONBIO16

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-12 Introduction

PCB LONBIO16 This section contains an overview of the LONBIO16 PCB.

PCB LONBIO16 K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 58 of 75

K604016 Appendix A-13: References - PCB LONDAG

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-13 Introduction

PCB LONDAG This section contains an overview of the LONDAG PCB.

PCB LONDAG K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 59 of 75

K604016 Appendix A-14: References - PCB LONIOS16

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-14 Introduction

PCB LONIOS16 This section contains an overview of the LONIOS16 PCB.

PCB LONIOS16 K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 60 of 75

K604016 Appendix A-15: References - PCB LREP2

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-15 Introduction

PCB LREP2 This section contains an overview of the LREP2 PCB.

PCB LREP2 K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 61 of 75

K604016 Appendix A-16: References - PCB MBB

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-16 Introduction

PCB MBB This section contains an overview of the MBB PCB.

PCB MBB K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 62 of 75

K604016 Appendix A-17: References - PCB SKE

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-17 Introduction

PCB SKE This section contains an overview of the SKE PCB.

PCB SKE K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 63 of 75

K604016 Appendix A-18: References - PCB TIC

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-18 Introduction

PCB TIC This section contains an overview of the TIC PCB.

PCB TIC K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 64 of 75

K604016 Appendix A-19: References - Power Supply Units

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-19

Power Supply Units

Introduction

This section contains information on the power supply units in AS and OKR used for the control.

NGL, NGG, NGC, NGAE (Release 1.47 and Higher)

For supply of lift and group functions (NGL and NGG), for car supply (NGC), as well as for supply of additional landing indicators (NGAE), the same power supply unit is used: Detail

Description Switching power supply, short circuit protected

Execution

Location

AS (NGL, NGG, NGAE), OKR (NGC)

Primary voltage 85 VAC to 132 VAC or 176 VAC to 550 VAC Secondary voltage

24 VDC ± 1%

Power rating

150 W NGL, NGG, NGC, NGAE (Mat. No. 431609)

16.03.2005

Page 65 of 75

K604016 Appendix A-19: References - Power Supply Units For supply of lift and group functions (NGL and NGG), for car supply (NGC), as well NGL, NGG, NGC, NGAE (up as for supply of additional landing indicators (NGAE), the same power supply unit is to Release 1.46 ) used: Detail

Description Switching power supply, short circuit protected

Execution

Location

AS (NGL, NGG, NGAE), OKR (NGC)

Primary voltage 88 VAC to 132 VAC or 170 VAC to 264 VAC Secondary voltage

24 VDC ± 1.25%

Power rating

150 W NGL, NGG, NGC, NGAE (Mat. No. 419210)

In a spare part order for releases up to 1.46 (mat. no. 419210), the power supply unit for release 1.47 and higher will be delivered on a mounting plate, which fits the installation conditions of the old power supply unit.

16.03.2005

Page 66 of 75

K604016 Appendix A-19: References - Power Supply Units NGSK 100 VDC For the elevator program S500 and for Full Scope, the safety circuit is operated with a nominal supply voltage of 100 VDC filtered. This specific supply voltage requires a (Release specific power supply unit: 1.45/1.46 and Higher) Detail Description Power supply unit safety circuit (transformer plus JTHSK), short circuit and overcurrent protected

Execution

DSKEL DSKIK

Test button ground fault (triggers JTHSK)

Test button overcurrent (triggers JTHSK)

JTHSK

Thermal switch safety circuit (specific for 100 VDC filtered)

Location

AS

Primary voltage 323 VAC (380 VAC - 15%) to 457 VAC (415 VAC + 10%) Secondary voltage

Nominal 100 VDC filtered (70 VDC to 133 VDC depending on input voltage and load)

Power rating

25 VA Power Supply Unit Safety Circuit 100 VDC Filtered

In a safety circuit 100 VDC filtered, only these specific versions of NGSK / JTHSK must be used for replacement! For these safety components, only original parts and no locally sourced replacements must be used (mat. no. can be found in chapter 'Spare Parts' of K 604013)!

16.03.2005

Page 67 of 75

K604016 Appendix A-19: References - Power Supply Units NGSK 88 VDC Pulsed (up to Release 1.43)

For the elevator program S300P only, the safety circuit was operated with a nominal supply voltage of 88 VDCRMS pulsed. This specific supply voltage requires a specific power supply unit: Detail

Description Power supply unit safety circuit (transformer plus JTHSK plus JFISK), short circuit protected

Execution

JTHSK

Thermal switch safety circuit (specific for 88 VDC pulsed)

JFISK

Ground fault circuit breaker for safety circuit (110 VDC / 30mA pulsed version)

Location

AS

Primary voltage 323 VAC (380 VAC - 15%) to 457 VAC (415 VAC + 10%) Secondary voltage

Nominal 88 VDCRMS pulsed (64 VDC to 120 VDC)

Power rating

16 VA Power Supply Unit Safety Circuit 88 VDC Pulsed

In a safety circuit 88 VDC pulsed, only these specific versions of NGSK / JTHSK / JFISK must be used for replacement! For these safety components, only original parts and no locally sourced replacements must be used (mat. no. can be found in chapter 'Spare Parts' of K 604013)! NSG K 604016 E

16.03.2005

The NSG function is realized with an external battery, combined with the ASILOG battery charger circuit. Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 68 of 75

K604016 Appendix A-20: References - Hoistway Information

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-20

Hoistway Information

The following picture shows the status of the various hoistway signals for the Overview of Hoistway Signals different car positions in the hoistway:

Pos. A

Description Top floor

B

Bottom floor

C

Zone not relevant for contacts

KSE-D Contact shaft end down KSE-U Contact shaft end up PHNR-D Photo cell releveling down

(Inverted signal N_PHNR-D is displayed by SMLCD)

PHS

16.03.2005

Photo cell floor (Inverted signal N_PHS is displayed by SMLCD)

Page 69 of 75

K604016 Appendix A-20: References - Hoistway Information PHUET Photo cell door overbridging

(enable is active / logic high, otherwise signal is not operational)

Signals

Low

High

Inactive

0i

1i

Active

0a

1a

Hoistway Signals Device SI-V

The following picture gives an overview of the contact arrangement on an SI-V hoistway information device:

Device SI-V K 604016 E

16.03.2005

Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 70 of 75

K604016 Appendix A-21: References - LON Addresses and Lift ID

INVENTIO AG

Miconic TX-GC / 10-GC CO MMISSIONING

© 01/2001

Appendix A-21

LON Addresses and Lift ID

Introduction

This section contains an overview of the LON bus addresses for the LON nodes in the elevator network which must correspond to the settings in the PCT.

LON Addresses

The following table lists the LON bus addresses for the individual devices which may be used in Miconic TX-GC / Miconic 10-GC installations. The addresses are set using one or two hexadecimal rotary switches each. Be sure to set both HIGH and LOW where available: Device / PCB

16.03.2005

Switch

Location

LONIOS11

HIGH 0

LOW 1

LONIOS12

0

2

BPL1

LONIOS13

0

3

BPL1

LONIOS14

0

4

BPL1

LONIOS31

0

5

BPL3

LONIOS32

0

6

BPL3

LONIOS33

0

7

BPL3

LONIOS34

0

8

BPL3

LONIOS51

0

9

BPL5

LONIOS52

0

A

BPL5

LONIOS53

0

B

BPL5

LONIOS54

0

C

BPL5

LONIOS71

0

D

BPL7

LONIOS72

0

E

BPL7

LONIOS73

0

F

BPL7

LONIOS74

D

0

BPL7

LONIOS91

D

1

BPL9

LONIOS92

D

2

BPL9

LONIOS93

D

3

BPL9

LONIOS94

D

4

BPL9

LONIOS111

D

5

BPL11

LONIOS112

D

6

BPL11

LONIOS113

D

7

BPL11

LONIOS114

D

8

BPL11

LONDAG1

0

1

BPL1

LONDAG2

0

2

BPL3

LONDAG3

0

3

BPL5

LONDAG4

0

4

BPL7

LONIOS21

Lift no.1)

1

BPL2

LONIOS22

Lift no.1)

2

BPL2

Function

BPL1

Generic lift I/O

Lift I/O for direction arrows, gong and position indicators

Page 71 of 75

K604016 Appendix A-21: References - LON Addresses and Lift ID

16.03.2005

LONIOS23

Lift no.1)

3

BPL2

LONIOS24

Lift no.1)

4

BPL2

LONIOS41

Lift no.1)

5

BPL4

LONIOS42

Lift no.1)

6

BPL4

LONIOS43

Lift no.1)

7

BPL4

LONIOS44

Lift

no.1)

8

BPL4

LONIOS61

Lift no.1)

9

BPL6

LONIOS62

Lift no.1)

A

BPL6

LONIOS63

Lift no.1)

B

BPL6

LONIOS64

Lift no.1)

C

BPL6

LONIOS81

Lift no.1)

D

BPL8

LONIOS82

Lift no.1)

E

BPL8

LONIOS83

Lift no.1)

F

BPL8

LONIOS84

no.1)

0

BPL8

ZRTL

2)

2)

Floor

Z-Line Terminal as landing control station

ICE

B

1

OKR

Lift I/O car and door, access side 1

ICE2

B

2

OKR2

Lift I/O car and door, access side 2

TC11.TIC1

C

1

TC11

TC11.TIC2

C

2

TC11

TC11.TIC3

C

3

TC11

TC11.TIC4

C

4

TC11

TC12.TIC1

C

5

TC12

TC12.TIC2

C

6

TC12

TC12.TIC3

C

7

TC12

TC12.TIC4

C

8

TC12

TC21.TIC1

C

9

TC21

TC21.TIC2

C

A

TC21

TC21.TIC3

C

B

TC21

TC21.TIC4

C

C

TC21

TC22.TIC1

C

D

TC22

TC22.TIC2

C

E

TC22

TC22.TIC3

C

F

TC22

TC22.TIC4

C

0

TC22

TC11.HTIC1

C

#+1

TC11

TC11.HTIC2

C

#+2

TC11

TC12.HTIC1

C

#+1

TC12

TC12.HTIC2

C

#+2

TC12

TC21.HTIC1

C

#+1

TC21

TC21.HTIC2

C

#+2

TC21

TC22.HTIC1

C

#+1

TC22

TC22.HTIC2

C

#+2

TC22

(0)3)

1

TC11

(0)3)

2

TC12

Lift

Generic group I/O

Lift I/O car operating panel, access side 1

Lift I/O car operating panel, access side 2

Miconic 10-GC only: Hidden Box with Firefighting Unit #: Number of last TIC on respective TC

Miconic 10-GC only: Destination Indicators in door jambs for location SZ1

Page 72 of 75

K604016 Appendix A-21: References - LON Addresses and Lift ID

AZRC

LONLMDMS

(0)3)

3

TC21

(0)3)

4

TC22

(0)3)

5

TC11

(0)3)

6

TC12

(0)3)

7

TC21

(0)3)

8

TC22

(0)3)

14)

C, MR

Load measurement

(0)3)

24)

C

Load measurement

Miconic 10-GC only: Destination Indicators in door jambs for location SZ2 Miconic 10-GC only: Destination Indicators in door jambs for location SZ1 + SZ2

1)

Lift no.: value for Lift ID for the respective elevator (1..8)

2)

Values are set manually on Z-Line Terminal, see K 604027

3)

These values are hardwired and cannot be changed (information only)

4)

Auto-set by software, no way provided for address setting

LON Bus Address Switches Lift ID

K 604016 E

16.03.2005

The lift ID for group I/O is the number of the respective elevator in the group (lift no. in the table above). It is set on the ASILOG PCB of the respective elevator. The lift ID must be 1 for simplex elevators. Document version 06, released - last edited on March 14, 2005 Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 73 of 75

K604016 Appendix Z: Table of Contents Miconic TX-GC / 10-GC

INVENTIO AG

CO MMISSIONING © 01/2001

Appendix Z

Table of Contents 0

Chapter 0 Chapter 1

1

Commissioning Prerequisites

Chapter 2

2

Preparation of Control

Chapter 3

3

Inspection Travel with IMOF

Chapter 4

4

Measuring Travel

Chapter 5

5

Car I/Os 5-1 Commissioning in the Machine Room 5-2 Preparation of the Car 5-3 Commissioning the Car 5-4 Checks 6

Chapter 6

Lift I/Os 6-1 Preparation 6-2 Commissioning BPL PCBs 6-3 Checks

Chapter 7

7

Group I/Os 7-1 Preparation 7-2 Commissioning NGG 7-3 Commissioning BPL PCBs 7-4 Checks

Chapter 8

8

Group Control 8-1 Duplex / Multiplex Elevators 1 and 2 8-2 Further Multiplex Elevators 8-3 Checks

Appendices

16.03.2005

A

References A-1 Overview of Control Cabinet A-2 Overview of OKR A-3 Bus Termination BAFG/BAFL A-4 PCB ASILOG3 A-5 PCB BPL A-6 PCB EBCOM68 A-7 PCB EBLON1/2 A-8 PCB GCIOB360 (since Release 2.0) A-8 PCB GCIO360 (up to Release 1.47) A-10 PCB HTIC (Miconic 10-GC only) A-11 PCB ICE A-12 PCB LONBIO16 A-13 PCB LONDAG A-14 PCB LONIOS16 A-15 PCB LREP2

Page 74 of 75

K604016 Appendix Z: Table of Contents A-16 A-17 A-18 A-19 A-20 A-21 K 604016 E

16.03.2005

PCB MBB PCB SKE PCB TIC Power Supply Units Hoistway Information LON Addresses and Lift ID Document version 06, released - last edited on March 14, 2005

Use, reproduction, transmittal or disclosure of information in this document is subject to the restrictions on the first / title page.

Page 75 of 75