Data sheet Project: Editor: Date :
ADK Hospital - Operation Theatre Roshan Indika 09.05.2017
Unit Unit type: Cooling capacity (total): Cooling capacity (sensible): Net total cooling capacity: Net sensible cooling capacity: Condensing temperature: EER: AER: Sound power level: LpA (2m freefield): Number of refrigerant circuits: Number of compressors:
ASU 622 A 58.6 40.0 57.0 38.4 45 4.19 0.17 75.8 56.3 2 2
Fan (Data per unit) Fan type:
kW kW kW kW °C kW/kW W/(m³/h) dB(A) dB(A)
R3G595
Number: Max. revolutions: Nominal power: Revolutions:
2 1,408 U/min 5.8 kW 906 rpm
Compressor (Data per compressor)
Condenser
Unit type: Ambient temperature: Sound pressure group: Required condenser capacity: Available condenser capacity: Difference: Number of fans: Number of condensers:
KSV057A31pC 35 Standard 35.5 41.4 16.6 3 2
°C kW kW %
Airflow: Air velocity: Return air temperature: Return air humidity: Supply air temperature: Altitude above sea level: Height: Width: Depth: Weight: Refrigerant: Power supply:
9,670 1.4 24 55 12 0 1,980 2,200 890 669 R407C 380-415/3/50
m³/h m/s °C rel.% °C m mm mm mm kg
Power consumption:
1.6 kW
ESP external static pressure: Total pressure drop: Control voltage: Motor-efficiency:
250 351 6.1 87
Pa Pa V %
Electrical power consumption: Heat rejection: COP: Number: Evaporating temperature:
6.2 35.5 4.75 2 8.9
kW kW kW/kW
Weight: Current consumption (per fan): Power consumption (per fan): Height: Width: Depth: Airflow: LpA (5m freefield):
The above mentioned data are subject to the measuring tolerances of Eurovent. Unless otherwise stated, all data refer to a product in basic version. StulzSelect Vers. 3.0.0 - New Project: 1 x ASU 622 A
°C
168 kg 3.10 A 0.71 kW 947 mm 2,360 mm 770 mm 16,800 m³/h 60.3 dB(A)