TECHNICAL SPECIFICATION SHEET APW-100 100KVA RICARDO DIESEL GENERATOR SET Genset Model

APW-100

Prime Power (kw/kva) Voltage (v) Frequency (Hz) Connection: Engine Model: Net Weight (kgs)-Open Dimensions (mm)-Open

80/100 220 60 3 phase 4 wire R6105AZLDS2 1370 2300*760*1550

Standby Power(kw/kva) Rated Speed (rpm) Rated Current (A) Power Factor: Alternator Model: Net Weight (kgs)-Silent Dimensions (mm)-Silent

88/110 1800 262.4 0.8 UC274C 1960 2850*1150*1650

Voltage Available: 50Hz: 380-400-415V/220-230-240V; 60Hz: 220-380-416-440-480V/110-208-220-240V Any special voltage is also available as client’s request Prime Power: comply with GB/T2820-97(eqv.ISO8528). Genset can run unlimitedly under certain power range. One hour 10% over load in every 12 running hours is allowed; Standby Power: standby power is the limit value of maximum output for emergency use. It is off-oil power, overloading is prohibited

Standard Configuration: 

Engine: RICARDO R6105AZLDS2



Cooling Fan with fan guard and front guard



Alternator: Single bearing, IP23, H class



24V Charger



Shock Absorber



Dry Air Filter. Dual Fuel Filter. Engine Oil Filter. Coolant Filter.



MCCB Circuit Breaker



Standard Control Panel; ATS for optional



2x12V Start Battery with connecting cable



Storage Battery and battery line, Exhaust pipe, Corrugated pipe for anti-vibration, Cone Tube, Flange, Muffler



Soundproof Enclosure/Canopy for optional



Documents

Quality Assurance: 

Factory Inspection, the test items before delivery are mainly as follows: 

Each genset shall be put into commission more than 4 hours totally. They are tested on idle load, fully load and 10% overload;



The noise level is tested



All of the meters on the control panel shall be tested



The appearance of the genset and all of the label and nameplate shall be checked

TECHNICAL SPECIFICATION SHEET APW-100 

Warranty 12 months or 1000 running hours from shipment date. If the quality problem arise during the warranty period, and verified the problem is caused by our genset-body instead of external or natural reasons. (Refer to all kinds of natural disaster, shipping, loading, unloading, wrong-operation, etc), we will supply the relevant spare parts free of charge for maintenance; after the warranty period, we can supply the required spare parts for you under cost prices.

Engine Parameter: Manufacturer/Model: Aspiration: Fuel System: Cylinder numbers Displacement: Bore x Stroke Compression Ratio: Max. Power: Governing System:

RICARDO R6105AZLDS2, 4 stroke Turbocharged after cooled Direct Injection 6 cylinders 6.75 L 105 x 130 mm 17:1 143KW Mechanical Exhaust System

Exhaust Volume: Exhaust temperature: Max. Allowed Back Pressure:

15.6m³/min 600 ℃ 10 KPa Intake System

Max. Allowed Pressure: Gas Volume: Air Flow:

6.25 kPa 6.9 m³/min 152 m³/min Fuel System

100% Load (Prime): 75% Load(Prime): 50% Load (Prime):

218g/kW.h 163.5g/kW.h 109g/kW.h Lube System

Oil Capacity: Oil Consumption: Max oil Temperature (℃) Oil Pressure at rated speed:

17L ≦2.04g/kw.h 105 350 kPa Cooling system

Coolant Capacity: Thermostat: Max. Water Temperature:

23 L 82-95℃ 104℃

TECHNICAL SPECIFICATION SHEET APW-100 Alternator Parameter:

Basic Information

The alternators meet the standards of: GB755, BS5000, VDE00530, NEMAMG1-22,IED34-1,CSA22.2 and AS1350 Technical Data: Manufacturer: Phases: Connection: Bearing numbers: Power Factor: Protection Class: Altitude Condition: Excitation: Insulation class/Temp. rise class: Tel. Influence Factor TIF: Tel. Harmonic Factor THF: Steady State Voltage Regulation: Alternator Capacity: Efficiency: Cooling Air Flow:

ACEPOW UC274F 3 3 phase 4 wire, Y type 1 0.8 IP23 ≦1000M Brushless, self-excitation H/H ﹤50 ﹤2% ≦±1% 100KVA 92.4% 0.305m³/s

Genset Technical Data: Voltage Setting Range: Steady State Voltage Regulation: Transient Voltage Deviation: --100% sudden power cut: --Sudden power on Voltage Stabilization Time: --100% sudden power cut: --Sudden power on Steady State Frequency Regulation: Frequency Fluctuation Rate: Transient Frequency Deviation: --100% sudden power cut: --Sudden power on Frequency Recovery Time: --100% sudden power cut: --Sudden power on

≧±5% ≦±1% ≦+25% ≦-20% ≦ 6s ≦ 6s ≦5% ≦0.5% ≦+12% ≦-10% ≦ 5s ≦ 5s

TECHNICAL SPECIFICATION SHEET APW-100 Control System:

Standard Control Panel—HP1.0

DSE3110 4-protection panel

Model:

HP1.0

Voltage Meter



Frequency Meter



Current Meter



Water Temp. Meter



AMP Meter



Voltage Phase Switch



Hour Meter

Optional

Current Phase Switch



Oil Pressure Meter



Fuel Meter



Gen. Operating Indicator



AVR



Trans. Indicator



Key Start



Emergency Stop Switch



4 protection function-GTR17

Optional

ATS (Automatic Transfer Switch) Control Panel – HP2.0

Smartgen 6120 ATS Control Panel

Switch Box

Panel Wiring Diagram

Main Features

Deepsea 7510

Display

LED

Language

Chinese / English

Hours



Plug-pull terminal



Com port

Link

Fix Input

1

Config Input

2

Fix output

2

Config output

4

Analog Input

3

Generator Data



Engine Data



Fuel Level



Over speed



High engine temp.



Low oil pressure



Fail to start



Over voltage



Under voltage



Over current



Short circuit



Idle control