Xc2002 Quick start guide
1
Dirk Schepens 10/01/2012
2915 6626 00 edition 00
1 Hardware
2
1 Hardware Xc 2002 Control module - specs
3
2.1 Control panel buttons
4
2.2 Control panel LED functions
5
3.1 Main views survey
Navigation buttons allow user to scroll through readouts on display
6
3.2 Main views detailed Initial view after power-up of the controller, is the fuel level and hour counter The hour counter starts when the engine speed exceeds 800 min-1 The decimal indicator (.) will blink during counting Fuel level: Fuel level is measured by means of a 0,5…4,5 VDC fuel level sender in the main fuel tank. A negativ fuel level indicates an incorrect signal due to a sensor failure or wiring defect
Icon View
Language view
Vessel pressure: Vessel pressure is measured by means of a 0,5…4,5 VDC sender in the load valve manifold. A negativ pressure indicates an incorrect signal due to a sensor failure or wiring defect
7
3.2 Main views detailed Engine rpm: Engine rpm is measured by the engine electronics (EIC) and transmitted to the Xc2002 over Canbus. The value is only available when the engine is running
Battery voltage: The voltage is measured at the voltage in of the controller A too low value will case a “charge fail” warning
Service timers: The counter countes down to “0” meaning that the maintenance is due If not reset, a “service” warning will be displayed at every start-up
8
3.2 Main views detailed Event logs: Up to 20 events can be logged. shutdowns, service timer resets, software downloads
LOG list Alarms list: Displays all active alarms ( warnings & shutdowns).
Alarm list 2 Alarm(s) Parameter: Opens subview where different parameters can be viewed and modified
Parameter SW version: Shows version of currently loaded firmware
9
3.2 Main views detailed Coolant temperature: Coolant temperature is measured by the engine electronics (EIC) and transmitted to the Xc2002 over Canbus
Engine oil pressure : Engine oil pressure is measured by the engine electronics (EIC) and transmitted to the Xc2002 over Canbus
10
4 Log list details LOG list
Xc2002 EVENT LOG # 01 New software dl Time: 000000h Xc2002 EVENT LOG # 02 Element Temp. 1 Time: 000005h Xc2002 EVENT LOG # 03 Emergency stop Time: 000012h
+
The navigation buttons allow the user to scroll trough the different event logs ( max 20)
Back to display views.
11
5 Alarm list details Alarm list
+
2 Alarm(s)
The navigation buttons allow the user to scroll trough the different active alarms
Back to display views.
12
5 Alarm list details When an alarm is triggered, a pop-up screen will appear on the display and the alarm led wiIl be activated.(continuous for a warning, on-off for a shutdown) When the alarm is acknowledged (only that alarm in the popup screen), the alarm will disappear when the fault is corrected (blinking led will then burn continuously) “Acknowledge is done by pressing the ENTER button. An “Unacknowledged” shutdown will prevent the compressor from starting. Unacknowledged alarm:
Acknowledged alarm:
The alarm pop-up will disappear when pressing the BACK button. Active alarms can be viewed by entering the Alarm list. Remark: “Sensor failure W” -> sensor failure, at compressor side, casing a Warning “Sensor failure S” -> sensor failure, at compressor side, casing a Shut down
13
6.1 Extra views survey Extra Views
+
Navigation buttons allow the user to scroll trough the extra views.
Back to display views.
14
6.2 Extra views detailed Air inlet temperature: Air inlet temperature is measured by the engine electronics (EIC) and transmitted to the Xc2002 over Canbus
Engine Fuel consumption: Engine fuel consumptionis measured by the engine electronics (EIC) and transmitted to the Xc2002 over Canbus
Engine Fuel pressure: Engine fuel pressure measured by the engine electronics (EIC) and transmitted to the Xc2002 over Canbus
15
6.2 Extra views detailed Element temperature: Element temperature is monitored by a PT1000 sensor.
Regulating pressure: Regulating pressure is measured by a 0,5…4,5VDC sensor. The value is used to control the engine speed
RegP 00305.6h
16
0.00bar
7.1 Parameters survey Parameter
+
Language Icons
Unit C/bar
C/bar
F/psi
Auto NoLoad No
No
Yes
ST1 Reset No
No
The navigation buttons allow the user to scroll trough the different parameters
Yes
ST2 Reset No
No
Yes
Unit Type 1
1
10
Production Test No selection
Diagnostics Off
Off
On
Back to display views.
17
7.2 Parameters details Set language:
Language Icons
+
Passw. 1999
Language Icons
Passw. 2003
+
Language English
Language German
Language Acknowledge
Spanish
Language French
Back to parameters.
Language Italian
Language Cyrillic
18
7.2 Parameters details Set units:
Unit C/bar
C/bar
F/psi
+
Passw. 2003
+
Passw. 1999
Unit C/bar
Unit F/psi
Acknowledge
Back to parameters.
19
7.2 Parameters details Activate Auto NoLoad: If active , unit will automatically go to NoLoad when in UnLoad for more then 60 sec.
Auto NoLoad No
No
Yes
+
Passw. 2003
+
Passw. 1999
Auto NoLoad No
Auto NoLoad Yes
Acknowledge
Back to parameters.
20
7.2 Parameters details Service Timer reset: Identical procedure for service timer 1 and service timer 2
ST1 Reset No
No
Yes
+
Passw. 1968
+
Passw. 1999
ST1 Reset No
ST1 Reset Yes
Acknowledge
Back to parameters.
21
7.2 Parameters details Set Unit type: Factory set, when initial unit type is set this list will dissapear from view and can only be reset using the PARUS software. (consult GBP for latest list of unit types)
Unit Type 1
1
10
+
Passw. 1999 Unit Type
default
1
Unit Type
Passw. 2003
+
XAMS287DD
2
Unit Type
XAS850CD
3
Unit Type
XAMS287CD
4
Unit Type
XAMS407CD
5
Unit Type
XATS377CD
6
Acknowledge
Unit Type
XAHS237CD
7
Unit Type
XAHS347CD
8
Back to parameters.
Unit Type 9
Unit Type 10
22
XAVS307CD XAH237DD
7.2 Parameters details Diagnostics: When diagnostics is selected, power to the engine electronics will be interrupted for 30 sec.( engine will shutdown if running at that time) before power comes back on in order to carry out engine diagnostics.
Diagnostics Off
Off
On
+
Passw. 2003
+
Passw. 1999
Diagnostics Off
Diagnostics On
Acknowledge
Back to parameters. Disable Diagnostics : switch diagnostics back to the OFF position, press STOP or start the unit.
23
8 Operation START
If the unit is in Local control it can be started with this button. Xc2002 will power up the EIC and initiate the Canbus communication. This can take a few seconds, showing a “WAIT” pop-up on the display. When Canbus communication is ok, Xc2002 will check if EIC is preheating the engine. The display will show a “Preheat “ pop-up. After preheating or if no preheat was needed, the Xc controller will start the engine. The starter motor is activated till the engine reaches 800rpm After a warm-up to +40°C at 1300 rpm, with a max. of 5 minutes, the compressor is ready for loading: the LOAD led will blink When loaded the first time, the engine speed will be raised to max. rpm for 7 sec. Then the regulation system comes in action to adjust the speed. If the LOAD button is applied during the “warming up” fase, LOAD led will blink fast and unit will automatically load when “warming up is finished. When during Loaded operation the LOAD button is applied, load valve will be deactivated and compressor will run in NoLoad at 1300rpm.
24
8 Operation STOP
Compressor can be stopped with this button. If compressor was running in LOAD the load valve will be deactivated and unit will return to NoLoad (1300rpm). After 5 minutes cooldown, the engine will be stopped. If running in NoLoad when stopping , then cooldown time will be 5 minutes minus the time the unit has been running in NoLoad. If compressor has not been loaded there will be no cooldown time. If ON/OFF button is switched to OFF with the unit running, the same procedure will be followed as when the “stop button” was pushed.
25
8 Operation AUTOMATIC
This compressor can be remotely controlled (start-stop-load-noload) trough digital inputs The automatic button switches between local and remote mode. When the “Automatic” led is lid , the unit is in remote control and start /stop buttons on the controller cannot be used.
26
8.1 Operation: most common Icons
27
8.1 Operation: most common Icons
28
9 PARUS (PAR Utility Software) Enabling “Unit Type” selection
29
1.
Start PARUS
2.
Connect to controller
3.
Select PARAMETERS
4.
Load parameters from controller
5.
Dubbelclick channel 8001
6.
Select the “enable” checkbox
7.
“Write” to the controller and close the window
8.
Disconnect PARUS
9.
“Unit type” selection is available in controller menu
We are committed to your superior productivity through interaction and innovation.