SIGMA Standard
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Rev. Date
Rev. No. Page
2011.02.25 0 33/N
Control box 3.2.1
Daily inspection items and standards - - - - - - - - - - - - - - - - - - - - - - - - - - -
3.2.2
Control box MCCB
---------------------------------------
38
3.2.3
Determine voltage and fuse - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
38
3.2.4
Insulation measuring and earthing- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
39
3.2.5
Electronic contactor
---------------------------------------
40
3.2.6
PCB base board
---------------------------------------
41
1) 2) 3) 4) 5) 6) 7) 8)
--------------------------------------Synchromotor PG card - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - SM.02/1 PCB(TOC Controller Board) - - - - - - - - - - - - - - - - - - - - - - - - - - - SM.02/G PCB --------------------------------------SM-03 PCB(Car Call Board) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - SM.04V 12/A(Call & Display Control Board) - - - - - - - - - - - - - - - - - - - - - SM.04V 12/A --------------------------------------BST Door Controller - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Main PCB
34
41 46 47 49 50 51 52 53
3.2.7
Transformer
---------------------------------------
54
3.2.8
Regeneration resistance- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
54
2005.12.27. Approval
SIGMA Standard 3.2
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Rev. Date
Rev. No. Page
2011.02.25 0 34/N
Control box
The manual mainly introduces content about IRIS NV elevator maintenance work only. Therefore, the manual does not include detailed technology details, please refer to STEP control box manual.
Notice
When check the control box, cut off the power supply; after performing Lock Out /Tag Out, conduct work.
Please determine whether plastic cap is covered on the terminal. If cap is not covered on its top, please make cap cover the top.
If power supply is 200V or 400V, please affix marking label to make others take care.
If PCB is applied, it should be avoided that PCB is scratched by protruded pin at back.
If INV elevator type is applied, after cutting off power supply, smoothing condenser is still in charging state; therefore, please determine whether DC voltage on capacitor two ends conduct working after discharging completely.
3.2.1 Daily inspection items and standards Inspection Part
Inspection item
Tool
State/standard circle Ambient temperature:
Operating environment
Ambient temperature, moisture, vibration, dust, corrosive gas, oil, dust, dribbles etc.
Naked eyes,
lower than 40℃,
thermometer,
accord with moisture
hygrometer
etc. environment
1 month
requirements
LCD indicating
Whether danger exists around the assembly
Naked eyes
No dangerous item
1 month
Whether LCD indicating is normal
Naked eyes
Indicating is normal
1 month
Bolts relaxation is not allowed.
Naked eyes,
No abnormal condition
terminal
Connector relaxation is not allowed.
screwdriver
Assemble is stable
Bolts and tail
Determine whether protective layer cracks
Naked eyes
No abnormal condition
cord
or discolors
Connector
2005.12.27. Approval
1 month 1 month
SIGMA Standard
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Rev. Date
Rev. No. Page
2011.02.25 0 35/N
Determine whether earthing panel deforms. Electromagne
Whether there is vibration noise in working
Naked eyes,
None
acoustic Contact attraction state of contact point
Noise occurs at
sensation
contacting point
Determine liquid leakage, discolor, crack,
Naked eyes
No abnormal condition
tic contactor, relay
Electrolytic capacitor
case expansion conditions
1 month
1 month
Determine whether safety liquid flows out, and whether case expanses
Capacitor
Determine whether there is dust
cooling fan
Naked eyes,
No abnormal condition
1 month
Normal rotation
1 month
No abnormal condition
1 month
hands Determine whether the fan conduct air
Naked eyes
exchanging and determine its fixing state Control box,
Whether there is abnormal noise
Acoustic
cooling fan
(after cutting off the power supply, conduct
sensation,
determination by rotating fan vane
naked eyes,
manually)
hands
Whether there is abnormal vibration
Naked eyes
Whether discoloring condition occurs for
Naked eyes,
over-high temperature.
smell
Determine connecting state between control
Naked eyes
No abnormal condition
1 month
PCB discoloring and abnormal odor
Naked eyes,
No abnormal condition
1 month
PCB crack, damage, deformation
smell
Connector
box and connector, and state of dust & foreign adhesive matter PCB
(1)
Num of electric wire connected on a terminal is 2 strands, and num of both sides is less than 4 strands. And it is not allowed that the current is higher than maximum permissible current of the terminal.
(2)
Slightly draw the electric wire to determine fastening state and connecting state of jack.
(3)
Leave electric wire long enough for conditions of contact moving, or cover opening for fault handle or inspecting etc..
(4)
Figure 2-1 is outline drawing of control box (for function description, please refer to STEP control box manual).
2005.12.27. Approval
Name Code
SIGMA Standard
Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Rev. Date
Rev. No. Page
2011.02.25 0 36/N
Figure 2-1. Outline drawing of control box
Function of each Part
No.
Section
1
Part1
2 3 4
Part2
Part3
Part Name
Function
RR resistance
Consume regenerated electric power
DZ1
Brake resistance
SMPS ERO
Main board & Hall communication wire power supply [input 220V, output 24V] Buttons used for low-speed operation [Up, Com, Down, NOR/INS, E.STOP]
5
FU1
Fuse [110V safety chain, capacity:2A]
6
FU2
Fuse [Brake voltage, capacity:4A]
7
FU3
Fuse [Door & car door power supply, capacity:2A]
8
FSK2
Break [hoistway lighting switch]
9
CP1
Break [SMPS power supply input terminal]
10
Part4
KAD
11
FR
13
FIRE2
2005.12.27. Approval
Safety chain[landing door, KAD contactor will be “on” when landing door is closed] Fire Return contactor [contactor will be “on” when hall switch is on] The 2nd fire-fighting operation contactor [the contactor will be on when the 2nd fire-fighting switch is on]
SIGMA Standard 14 15
Part5
16 17
Part6
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Rev. Date
Rev. No. Page
ERO
ERO switch
DZL
Door Zone Lamp[used for rescue operation]
BY
Brake relay [it will be “on” when starts]
KMZ
2011.02.25 0 37/N
Similar with relay C1ST, it could be started in opening state only]
18
UCM1
Door-opening car-departure [in normal: on, when start: off]
19
UCM2
Door-opening car-departure [in normal: on, when start: off]
20
FIRE1
Relay for the 1st fire-fighting operation
21
GOV
22
Part7
Field panel
23
Part8
TB
Speed governor relay [it is on when speed governor safety chain is enabled] Terminals used for wire connecting of external apparatus of control box Terminal block[used for wire connecting of control box] Transformer [used for supply power for control box (single
24
Part9
Trans
phase), input power supply is 380V, output power supply is 110V Supply for [FU1], 123V[FU2], 220V[FU3]
25
OCB
26
SW Part10
Break of main power supply [380V] Contactor [similar with C1SW, could be started under the state of being enabled only]
27
FSK1
Break used for lighting power supply
28
APD
EMI filter
29
TB
Terminal block
30
Main board
Drive board
PG Card
Rotary Encoder
31
Part11
Integrated
32
(5)
driver
IPM
When connect 2 strands of electric wire end terminal to another, keep maximum contact face between terminals. Please not make wire connecting angle become higher than 60˚.
2005.12.27. Approval
SIGMA Standard
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Rev. Date
Rev. No. Page
60˚
Figure 2-2. Connecting method of connecting terminal
.
2005.12.27. Approval
2011.02.25 0 38/N
SIGMA Standard 3.2.2
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Name Code Application
Rev. Date
Rev. No. Page
2011.02.25 0 39/N
Control box MCCB (OCB) Inspection
Part
Inspection item
Tool
State/standard circle
Voltage regulation [V]
Voltmeter
Unparallel voltage [V] Control box MCCB
(1)
-15 ~+10%
1 month
±10%
1 month
Apparatus surface heats up
Surface thermometer
1 month
Terminal is screw up and conduct wiring
Screwdriver
1 month
If fault is related to input power supply, please inspect following content. 1) The 1st side: ⓐ R-S,
ⓑ R-T,
ⓒ S-T
nd
2) The 2 side: ⓓ R1-S1, ⓔ R1-T1, ⓕ S1-T1 If measured voltage (ⓐ) of the 1st side and measured voltage (ⓓ) of the 2nd side are higher than 2% of service voltage, cut off MCCB of building distributor box, and measure resistance between R-R1 after opening control box MCCB, measuring result should be 0[Ω] or near to 0[Ω]. (2)
Measure rest S, T phase with method same with the one for R mentioned above. If there is abnormal condition, please conduct accurate inspection and takes measures (replacing) according to inspection results.
(3)
Measure peak (p.m. 3~4 o’clock, 8~9 o’clock) voltage in each summer and ordinary (a.m.) voltage, and record measuring results on the daily inspection record.
(4)
After cutting off the power supply and implementing Lock Out / Tag Out, inspect whether MCCB surface discolors; and determine whether its temperature is normal after measuring the temperature.
(5) 3.2.3
Please determine whether there is abnormal noise or vibration inside MCCB. Determine voltage and fuse Inspection
Part
Inspection item
Tool
State/standard circle
Measure voltage and confirm fuse
Each control/signal wire
Voltmeter
Refer to field drawing
1 month
Rated capacity and contact state
Naked eyes
Refer to field drawing
1 month
(1) Confirm voltage and fuse capacity of each control/signal wire. (2)
Confirm fuse connecting state and fastening state of terminals with hands.
2005.12.27. Approval
Name Code
SIGMA Standard 3.2.4
Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
2011.02.25 0 40/N
Rev. Date
Rev. No. Page
Insulation measuring and earthing Inspection
Part
Inspection item
Tool
State/standard circle
nd
The 2 side face of control box Insulation
Each control/signal wire Fastening state of terminals on specified position
Earthing
(1)
Insulation resistance meter
1㏁
Screwdriver
Fastening
0.5 ㏁
12 months
1 month
Working overview Resistance property of insulator is insulation. Measure property of this insulation to prevent electric shock accident and defective insulation to protect apparatus and avoid safety accident coursed by abnormal action of elevator.
(2)
Electric shock preventing 1) DC voltage straightly through main circuit of frequency converter, even though the MCCB is turned off, voltage charged by the capacitor can not be discharged completely at once. Thus, please pay much attention to safety issue. And capacitor (AL electrolytic capacitor) connects with main circuit, even though the MCCB is turned off, voltage charged by the capacitor can not be discharged completely and immediately. Therefore, please adopt tester to determine whether DC voltage is 0~10VDC before working. 2) Please must implement insulation test before measuring the insulation to prevent PCB from being damaged. There are semiconductor elements used in the circuit, therefore, elements will be damaged if integrated circuit is earthed. Thus, please adopt insulation resistance tester (generation voltage 15V) or digital integrated electricity meter to conduct insulation test on all connector terminal in the control box.
(3) Please determine connecting control box earthing. (4)
For detailed insulation measuring methods, please refer to “Sigma Elevator Test-Run Adjust Manual”.
(5)
Regulated value of insulation resistance Circuit name
Measured part
Regulated value
Main circuit
Power supply terminal (TERM1) Frame
2005.12.27. Approval
between
~ Higher than1.0[㏁]
SIGMA Standard
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
2011.02.25 0 41/N
Rev. Date
Rev. No. Page
Motor circuit
Motor terminal (TERM2) between
Control circuit
The 2nd contact point of MCCB used for lighting Higher between
~ Frame
~ Frame
than
0.5[㏁]
The 2nd main contact point of main contactor between (6)
~ Frame
Connect earthing wire on one side of building to specific position. If connect the earthing wire to other position, control part may be can not be protected for interference from external reasons.
3.2.5
Electronic contactor Inspection
Part
Inspection item
Tool
State/standard circle
Contactor
Excess space for fixing and wiring, fasten the terminal
Naked eyes, screwdriver
1 month
Abnormal abrasion, dusting, electric arc, changeable tension force of contact point
Naked eyes, multimeter
1 month
(1)
Please determine whether electric wire used for wiring has excess part.
(2)
Please determine whether changeable tension device could be started smoothly.
(3)
Please determine whether there is serious arc trace occurs for abnormal abrasion (irregular abrasion) of contact point.
(4)
Please determine ON / OFF action of electronic contactor.
2005.12.27. Approval
SIGMA Standard 3.2.6
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Rev. Date
Rev. No. Page
2011.02.25 0 42/N
PCB base board Inspection
Part
Inspection item
Tool
State/standard circle
PCB Board
(1)
Fixing state, jack connecting state
Naked eyes, hands
1 month
Precautions for treatment and cleaning 1) Please pack PCB to prevent it from being impacted in moving. Please do not keep it in humid place for a long term. 2) After cutting of power supply and implementing Lock Out / Tag Out, please pay attention to static electricity, and conduct cleaning.
(2)
Main PCB 1) Outline.
도면 3.18 제어电路端子
2005.12.27. Approval
Name Code
SIGMA Standard
Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Rev. Date
Rev. No. Page
2011.02.25 0 43/N
Figure 3.18 Terminal of control circuit
No
Mic name
Function
Remark
1
JP1-JP5
Low-voltage optical coupling input
2
JP6
Power supply input interface
3
JP7-JP9
CAN communication interface
4
JP10
Used for emergency condition
5
JP11
Modem supervising interface
6
JP12
Portable governor interface
7
JP13-JP16
Relay output interface
8
JP17
High-voltage optical coupling input Drawing 3.18 Terminal of control circuit
2) Switch function Switch name
No. 1
Function
Remark
On
ARM Program start ARM Normal working state DSP Program start
Setup state: OFF Note: when start program, start CPLD firstly → and set SW1 to be ON→ DSP program start→ ARM program start (start window is different) SW2 assembly state: OFF SW3/SW4 assembly state: ON
Off On
SW1 2
SW2
State
Off
DSP Normal working state
On
CAN Terminal resistance setup
Off
CAN Terminal resistance invalid
On
RS485 Terminal resistance setup
Off
RS485 Terminal resistance invalid
SW3 SW4
SW5
2005.12.27. Approval
assembly state: ON
SIGMA Standard
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Rev. Date
Rev. No. Page
2011.02.25 0 44/N
3) MIC name and function description.
Mic
Connected
name
Wire num
JP1
JP2
JP3
JP4
2005.12.27. Approval
Name
1
X0
2
Function
Default default
X1
Auto/Inspection input signal X0 and X1 all input→automatic
3
X2
Up signal
default
4
X3
DN signal,
default
1
X4
2LS(SDS1U)
close
2
X5
1LS(SDS1D)
close
3
X6
4LS(SDS2U)
close
4
X7
3LS(SDS2D)
close
5
X8
GOV CTT contact point input signal
open
6
X9
7
X10
8
X11
1
X12
UL(up limit switch)
close
2
X13
DL(down limit switch)
close
3
X14
2LV(level switch signal)
open
4
X15
1LV(level switch signal)
open
5
X16
close
6
X17
open
1
x18
Fireman(fire-hazard reset switch)
open
2
x19
Fireman Service fireman switch
open
3
x20
open
4
x21
SW CTT contact point input signal
5
x22
BY CTT input signal
open
6
x23
BS1 switch signal (left)
open
7
x24
BS2 switch signal (right)
open
8
x25
MTH signal input
open
KMZ CTT contact point input signal FR CTT contact point input signal
default
open open open
open
SIGMA Standard
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Rev. Date
Rev. No. Page
9
x26
Earthquake signal input (EQS)
open
10
x27
ARD signal(emergency level for power failure)input
open
Name
Function
Default
1
x28
UCM1,2 CTT contact point input
open
2
x29
KAD CTT contact point input
open
3
x30
FIRE1 CTT contact point input (the 1st fire-fighting)
open
4
x31
5
COM
1
GND
2
24V
24VDC power input terminal (used for CTT input circuit)
3
GND
0VDC power input (used for CTT output circuit)
4
24V
24VDC power input (used for CTT output circuit)
Mic Connected name Wire num
JP5
JP6
FIRE2
CTT
input(the 2
nd
contact
point
fire-fighting)
X0~X31 input signal common terminal 0VDC power input terminal (used for CTT input circuit)
1 2 JP7
3 4
JP8
2005.12.27. Approval
CAN1H Tandem communication signal (TXA1+)/(TXA1-) CAN1L (Car & Hall CAN communication)
1
+24V
2
0V
3 4
JP9
2011.02.25 0 45/N
CAN2H Parallel or group-control tandem signal (TXA2+) (TXA2-) CAN2L
1
+24V
2
0V
3
CAN3H
open
SIGMA Standard
Name Code Application
4 JP10
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
JP12
Rev. No. Page
2011.02.25 0 46/N
CAN3L
1 MODEM
JP11
Rev. Date
1
telemonitoring
interface; ARM tandem guiding window Could be connected with RS232 interface portable governor; DSP
1
tandem guiding window
Mic name
JP13
JP14
JP15
2005.12.27. Approval
Connected Wire num
Name
1
Y14B
Output
2
Y14A
Output
3
COM6
Output
4
Y15B
Fire-fighting reset indicating
Output
5
Y15A
Fire-fighting reset indicating
Output
6
COM7
Fire-fighting reset output relay Y15 common terminals
Output
1
Y8
FIRE1 CTT output terminal
Output
2
Y9
FIRE2 CTT output terminal
Output
3
Y10
UCM1,2 CTT output terminal
Output
4
Y11
DZI Lamp output terminal
Output
5
COM4
6
Y12
Output
7
Y13
Output
8
COM5
1
Y4
2
Y5
3
COM2
4
Y6
Output
5
Y7
Output
Function
Default
Output relay Y8-Y11 common terminals
FR CTT output terminal
Output Output
Output relay Y4-Y5 common terminals
SIGMA Standard
Name Code Application
JP16
JP17
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept. COM3
1
Y0
BY CTT output
Output
2
Y1
KMZ CTT output
Output
3
Y2
4
Y3
5
COM1
Output relay Y0-Y3 common terminals
1
X32
Used for inspecting abnormal conditions of safety circuit
2
X33
Used for inspecting abnormal In-put conditions of landing door circuit
3
X34
Used for inspecting abnormal conditions of CAR door circuit
4
X35
5
COM
Synchromotor PG card Input function of processing encoder 1) Outline
Control box interface
PG card frequency resolution output interface
UVW encoder signal input interface
2005.12.27. Approval
Rev. No. Page
2011.02.25 0 47/N
6
JP25
(3)
Rev. Date
Output SW CTT output
Output
In-put
In-put In-put
X32-X35 input signal common terminal 0V CPLD program JTAG guiding window
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Name Code
SIGMA Standard
Application
Rev. Date
Rev. No. Page
2011.02.25 0 48/N
2) Terminal function description
Name
Terminal No.
Terminal function description
Frequency
Frequency resolution signal start
Resolution
Collecting electrode output A,B
signal Collecting electrode output of transistor opencircuit (max. output frequency 50kHz)
Specification
Name
Terminal No.
Terminal function description
Specification
A phase signal B phase signal
Encoder differential signal input
Encoder
Z phase signal
interface, maximum frequency
input signal
U phase signal
50kHz
V phase signal W phase signal Shield earthing
Encoder power supply
(4)
+5V or+5.3V Encoder GND
Shielding field Maximum 200mA output Select S1 bridging
SM.02/1 PCB(TOC Controller Board)
Assembled on tool box, signal for output door driving and input CLS/OLS,PTM.Chime, Safety Shoe etc. signals 1) Outline
2005.12.27. Approval
SIGMA Standard JP3
JP 2
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
JP4
JP1
JP 5
JP6
SW1,2
Rev. Date
Rev. No. Page
JP7
JP9
JP8
2) Switch function and description MIC name
Function
Remark
Used for CAN resistance setup SW1
communication
terminal
(1,2 simultaneously)
2P
(ON: terminal resistance setup, OFF: release terminal resistance)
SW2
Used for program simultaneously)
start
setup
(1,2
(On: program start, OFF: normal operation state)
2P
3) Terminal function and description MIC name JP1
Function CAN communication and power supply
Remark 4P
(1:24V,2:GND,3:CANH,4:CANL) JP2
For adding Board connecting(connecting for ex
14P
pansion) JP3
2005.12.27. Approval
Ring for floor arrival
5P
2011.02.25 0 49/N
SIGMA Standard
(5)
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Rev. Date
Rev. No. Page
JP4
For door drive signal output
8P
JP5
For Safety Shoe signal input
3P
JP6
For 20%, 80%, 110% Micro S/W signal input
4P
JP7
For parallel interface communication
10P
JP8
For relay output of Light/Fan driving
2P
JP9
Used for inspect load(PTM)
4P
DB1
Used for program start
9P
2011.02.25 0 50/N
SM.02/G PCB Assembled on operation panel, through main board input communication, open/close button and input ATT part signal. 1) Outline
JP1
JP5
SW1 SW3
JP3
JP2
JP7 DB1
JP6
SW2
JP4
2) Switch function and description
2005.12.27. Approval
MIC name
SW1
SW2
SW3
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Name Code
SIGMA Standard
Application
Rev. Date
Rev. No. Page
Function Used for CAN communication terminal resistance setup (1,2 simultaneously) (ON: terminal resistance setup, OFF: release terminal resistance) Used for program start setup (1,2 simultaneously) (On: program start, OFF: normal operation state) 1
2
3
4
Operation panel type
On
Off
Off
Off
Main operation panel
Off
On
Off
Off
Back operation panel
Off
Off
On
Off
Operation panel for the
Off
Off
On
Server operation panel
3) Terminal function and description
MIC name JP1
JP2
JP3
Function CAN communication and power supply (1:24V, 2:GND, 3:CANH, 4:CANL) For adding Board connecting(connecting for command) For adding Board connecting(connecting for expansion)
Remark 4P
14P
14P
JP4 JP5
For ATT part switch signal input
5P
JP6
For connecting Open Button
4P
JP7
Used for Close Button
4P
DB1
For connecting program start
9P
2005.12.27. Approval
2P
2P 4P
disable Off
Remark
2011.02.25 0 51/N
Name Code
SIGMA Standard (6)
Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Rev. Date
Rev. No. Page
2011.02.25 0 52/N
SM-03 PCB(Car Call Board) Assembled on COP and connected to SM-02/G PCB, floor button input and Lamp output. 1) Outline -connecting method of floor button and lamp
The 1st and 2nd pins are connected to lamp power supply [-] and [+] terminals respectively. The 3rd and 4th pins are connected command button terminals
2) MIC name and description
Remark Used for button connecting of F 1 car floor
Used for button connecting of F 9 car floor
Used for button connecting of F 57 car floor
Used for button connecting of F 2 car floor
Used for button connecting of F 10 car floor
Used for button connecting of F 58 car floor
Used for button connecting of F 3 car floor
Used for button connecting of F 11 car floor
Used for button connecting of F 59 car floor
Used for button connecting of F 4 car floor
Used for button connecting of F 12 car floor
Used for button connecting of F 60 car floor
Used for button connecting of F 5 car floor
Used for button connecting of F 13 car floor
Used for button connecting of F 61 car floor
Used for button connecting of F 6 car floor
Used for button connecting of F 14 car floor
Used for button connecting of F 62 car floor
Used for button connecting of F 7car floor
Used for button connecting of F 15 car floor
Used for button connecting of F 63 car floor
Used for button connecting of F 16 car floor
Used for button connecting of F 64car floor
Used for button connecting of F 8 car floor
Connector used for expansion
(7)
SM.04V 12/A (Call & Display Control Board) Assembled at hoistway of each floor, landing door calling logging and output IND signal 1) Outline
2005.12.27. Approval
SIGMA Standard
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
2) MIC name and signal
MIC name JP1
Function Power
Remark and
CAN
4P
communication JP2
1: Output
4P
JP3
2: 24V
4P
JP4
3:GND
4P
4: Input JP5 JP6 S1
4P Used for SPI communication Used for PCB fix position
4P 2P
selecting SW1
Used for CAN communication terminal resistance setup
2005.12.27. Approval
2P
Rev. Date
Rev. No. Page
2011.02.25 0 53/N
SIGMA Standard
(8)
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
SM.04V 12/A (Call & Display Control Board) 1) Outline
2) MIC name and description
MIC name
Function
Remark
JP1
Power and CAN communication
4P
JP2
Used for SPI communication
4P
SW1
Used for CAN communication te rminal resistance setup
2P
2005.12.27. Approval
Rev. Date
Rev. No. Page
2011.02.25 0 54/N
SIGMA Standard
(9)
Name Code Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
Rev. Date
Rev. No. Page
2011.02.25 0 55/N
BST Door Controller Assembled on upper part of car and connected to operation panel SM.02/I PCB, implement door opening/closing. 1) Outline
2) MIC name and description Function
Function
Function
Input power Earthing Signal output Signal output
Function Signal output Signal
Drive power Earthing
3) Switch function and description Switch name
Function
Open Speed
- Door Open Speed for adjust
Close
- Door Close Speed for adjust
HOLD
- HOLD Torque for adjust
OBSTruction
- OBSTruction Torque for adjust
Torque
2005.12.27. Approval
Switch name 1 2 3 4
Function ON RIGHT OFF LEFT TEST MODE ENABLE AUTO TUNE Mode Communication Choice
Name Code
SIGMA Standard
Application
IRIS NV Elevator Maintenance OEMS-P1-111-000 Service Business Dept.
2011.02.25 0 56/N
Rev. Date
Rev. No. Page
4) Function description of Push Button and LED Push Button
Function
LED
Function
TEST
Used for confirming door action
OPENED
Used
confirming
Open
finish(OLS)
state CLOSED
(Push to Check The Door) AUTO
(Push
ADJUSTMENT
Door/Auto Tune Motor)
to
Calibrate
Used for confirming Close finish, not used(CLS)
The OBSTRUCTION READ/ERROR
3.2.7
for
Two-side Shoe,used for CUT
Transformer Inspection
Part
Inspection item
Tool
State/standard circle
Transformer
Terminal/terminal relaxation, noise, he ating
Naked eye s
6 months
Wire connecting of earthing wire, cap
Naked eye s
6 months
One side of the 1st and 2nd transformer is electrified, therefore, please conduct inspe ction after cutting off power supply and implementing Lock Out /Tag Out. (1)
Please determine whether abnormal odor or over-heating state occurs.
(2)
Please determine whether there is abnormal noise.
(3)
Please determine whether Transformer bears over-load.
(4)
Please determine whether there is dust or carbon powder between terminals, adopt cleaning cloth or brush to clean up.
3.2.8
Regeneration resistance Inspection
Part
Inspection item
Tool
State/standard circle
Regeneration resistance
Fixing state of connecting part
Naked eyes
No relaxation is allowed
6 months
Heating and assembly state of cap (partition)
Naked eyes
No relaxation is allowed
3 months
(1)
Please determine whether electric wire connected on regeneration resistance is relax.
(2)
Please determine whether over-heat condition occurs on regeneration resistance.
2005.12.27. Approval