SMU02C V500R003C10 Site Monitoring Unit
User Manual
Issue
01
Date
2020-05-30
HUAWEI TECHNOLOGIES CO., LTD.
Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd. All other trademarks and trade names mentioned in this document are the property of their respective holders.
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied. The information in this document is subject to change without notice. Every effort has been made in the preparation of this document to ensure accuracy of the contents, but all statements, information, and recommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Technologies Co., Ltd. Address:
Huawei Industrial Base Bantian, Longgang Shenzhen 518129 People's Republic of China
Website:
https://e.huawei.com
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
i
SMU02C V500R003C10 Site Monitoring Unit User Manual
Preface
Preface Purpose This document describes the site monitoring unit SMU in terms of its hardware, liquid crystal display (LCD), web user interface (WebUI), common operations, remote management, and replacement. This document describes all the functions of the SMU. Some functions are implemented by hardware (such as the DC meter and battery cell detector). If the corresponding hardware is not connected to the SMU, the function is not available. Figures in this manual are for reference only.
Intended Audience This document is intended for:
Sales engineers
Technical support personnel
Maintenance personnel
Symbol Conventions The symbols that may be found in this document are defined as follows. Symbol
Description Indicates a hazard with a high level of risk which, if not avoided, will result in death or serious injury. Indicates a hazard with a medium level of risk which, if not avoided, could result in death or serious injury. Indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury. Indicates a potentially hazardous situation which, if not avoided, could result in equipment damage, data loss, performance deterioration, or unanticipated results. NOTICE is used to address practices not related to personal injury.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
ii
SMU02C V500R003C10 Site Monitoring Unit User Manual
Symbol
Preface
Description Supplements the important information in the main text. NOTE is used to address information not related to personal injury, equipment damage, and environment deterioration.
Change History Changes between document issues are cumulative. The latest document issue contains all the changes made in earlier issues.
Issue 01 (2020-05-30) This is the first official release.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
iii
SMU02C V500R003C10 Site Monitoring Unit User Manual
Contents
Contents Preface.......................................................................................................................................... ii 1 Product Overview..................................................................................................................... 1 2 Component Description .......................................................................................................... 3 2.1 SMU02C ............................................................................................................................................................... 3 2.2 WIM01C1 ............................................................................................................................................................. 7 2.3 UIM02C ................................................................................................................................................................ 9 2.4 UIM02D...............................................................................................................................................................12 2.5 UIM03D...............................................................................................................................................................16 2.6 UIM05B1 .............................................................................................................................................................20 2.7 NIM02D...............................................................................................................................................................24 2.8 NIM01C3 .............................................................................................................................................................25 2.9 CIM02C ...............................................................................................................................................................28 2.10 GIM01C .............................................................................................................................................................31
3 User Interfaces ........................................................................................................................ 33 3.1 LCD .....................................................................................................................................................................33 3.1.1 Setup Wizard .....................................................................................................................................................33 3.1.2 Modifying the display language .........................................................................................................................34 3.1.3 Restart Button....................................................................................................................................................35 3.1.4 Password ...........................................................................................................................................................35 3.1.5 Standby Screen ..................................................................................................................................................35 3.2 WebUI ..................................................................................................................................................................36 3.2.1 Connecting a Communications Cable .................................................................................................................36 3.2.2 Setting Parameters .............................................................................................................................................36 3.2.3 Logging In to the WebUI ...................................................................................................................................37
4 NMS Management ................................................................................................................. 39 4.1 U2000-SPM Management.....................................................................................................................................39 4.1.1 Connecting a Communications Cable .................................................................................................................39 4.1.2 Setting Parameters .............................................................................................................................................40 4.2 NetEco Management ............................................................................................................................................40 4.2.1 IP Networking ...................................................................................................................................................40 4.2.2 Wireless Networking..........................................................................................................................................41
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
iv
SMU02C V500R003C10 Site Monitoring Unit User Manual
Contents
4.2.3 BBU In-band Networking ..................................................................................................................................44 4.2.4 Logging In to the NetEco ...................................................................................................................................45 4.3 NMS Management over SNMP.............................................................................................................................46 4.3.1 Site Configuration .............................................................................................................................................46 4.3.1.1 Connecting a Communications Cable ..............................................................................................................46 4.3.1.2 Setting Parameters ..........................................................................................................................................47 4.3.2 Setting SNMP Parameters ..................................................................................................................................47 4.3.3 NMS Commissioning ........................................................................................................................................52 4.4 NMS Management over YDN1363 Protocol .........................................................................................................52 4.4.1 Connecting a Communications Cable .................................................................................................................52 4.4.2 Setting Parameters .............................................................................................................................................53 4.5 NMS Management over Modbus ..........................................................................................................................54 4.5.1 Connecting a Communications Cable .................................................................................................................54 4.5.2 Setting Parameters .............................................................................................................................................54 4.6 NMS Management over TCP-Modbus ..................................................................................................................55 4.6.1 Connecting a Communications Cable .................................................................................................................55 4.6.2 Setting Parameters .............................................................................................................................................55
5 Common Tasks ....................................................................................................................... 57 5.1 Common Installation Tasks ...................................................................................................................................57 5.1.1 Using a USB Flash Drive for Site Deployment ...................................................................................................57 5.1.2 Setting the Time Zone and Time.........................................................................................................................58 5.1.3 Setting Basic Battery Parameters........................................................................................................................58 5.1.4 Setting the Alarm Enable Option, Alarm Severity, and Associated Relays ...........................................................60 5.1.5 Setting Alarm Parameters for Dry Contacts ........................................................................................................61 5.1.6 Setting Rectifier Addresses ................................................................................................................................62 5.1.7 Setting Basic DG Parameters .............................................................................................................................63 5.1.8 Starting a Genset Self-Check..............................................................................................................................65 5.1.9 Setting WiFi Parameters.....................................................................................................................................67 5.2 Common Maintenance Tasks ................................................................................................................................68 5.2.1 Backing Up the Current Settings ........................................................................................................................68 5.2.2 Importing a Configuration File ...........................................................................................................................68 5.2.3 Restoring Factory Defaults.................................................................................................................................69 5.2.4 Upgrading Software ...........................................................................................................................................70 5.2.5 Changing a User Password .................................................................................................................................70 5.2.6 Viewing Dry Contact Association Information ....................................................................................................72 5.2.7 Viewing Active Alarms ......................................................................................................................................73 5.2.8 Viewing Historical Alarms .................................................................................................................................74 5.2.9 Viewing Version Information .............................................................................................................................75 5.2.10 Exporting Maintenance Information .................................................................................................................75
6 Hardware Replacement ......................................................................................................... 78 6.1 Replacing an SMU02C .........................................................................................................................................78
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
v
SMU02C V500R003C10 Site Monitoring Unit User Manual
Contents
6.2 Replacing a WIM01C1 .........................................................................................................................................79 6.3 Replacing a UIM02C Board..................................................................................................................................81 6.4 Replacing a UIM02D Board .................................................................................................................................83 6.5 Replacing an UIM03D Board ...............................................................................................................................85 6.6 Replacing an UIM05B1 ........................................................................................................................................87 6.7 Replacing an NIM02D Board ...............................................................................................................................88 6.8 Replacing an NIM01C3 ........................................................................................................................................89 6.9 Replacing a CIM02C ............................................................................................................................................91 6.10 Replacing a GIM01C ..........................................................................................................................................92
A Parameter Lists ...................................................................................................................... 93 A.1 LCD Menu Hierarchy ..........................................................................................................................................93 A.2 Running Information ...........................................................................................................................................94 A.3 Setting Wizard ................................................................................................................................................... 108 A.4 Parameters Settings............................................................................................................................................ 111 A.5 Running Control ................................................................................................................................................ 177 A.6 Site Maintain ..................................................................................................................................................... 182 A.7 User Management .............................................................................................................................................. 183
B Technical Specifications ..................................................................................................... 184 C FAQ ....................................................................................................................................... 185 C.1 How Do I Prepare the WebUI Operating Environment? ...................................................................................... 185 C.2 What Should I Do If I Forgot the Password? ....................................................................................................... 189
D Acronyms and Abbreviations............................................................................................ 190
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
vi
SMU02C V500R003C10 Site Monitoring Unit User Manual
1 Product Overview
1
Product Overview
Figure 1-1 Monitoring unit panel
(1) Slots for the communications expansion module and DG expansion module
(2) SMU02C
(3) The user interface module (compatible with the NIM02D)
The NIM01C3 can be installed only in the upper slot. The CIM02C can be installed either in the upper or lower slot. Table 1-1 Monitoring unit configure Monitoring Unit
Function Introduction
SMU02C
The SMU02C (SMU for short) is a compact high-end monitoring module that monitors and manages Huawei's box-type and cabinet-type power systems. The SMU can manage a site power system through the liquid crystal display (LCD), web user interface (WebUI) and Huawei NetEco.
UIM02C, UIM02D, UIM03D, and UIM05B1
It provides sensor ports, RS485 ports, and dry contact input and output ports to manage the interior environment of the power system and to report alarms.
NIM02D
It provides sensor ports, and FE ports to connect the NMS or smart device such as an IP camera.
NIM01C3
It is mainly used for 4G communication. It can also extend the
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
1
SMU02C V500R003C10 Site Monitoring Unit User Manual
Monitoring Unit
1 Product Overview
Function Introduction RS485/CAN port of the main control board or extend the southbound communication equipment.
CIM02C
Issue 01 (2020-05-30)
It is used to extend the RS485/CAN port of the main control board and provides 12 V power supply for the southbound equipment.
Copyright © Huawei Technologies Co., Ltd.
2
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
2
Component Description
2.1 SMU02C Figure 2-1 SMU02C appearance
(1) SD card slot
(2) Run indicator
(3) Minor alarm indicator
(4) Major alarm indicator
(5) Buttons
(6) USB ports (protected by a security mechanism)
(7) RS485/RS232 port
(8) Fast Ethernet (FE) port
(9) CAN communications port
(10) LCD
Indicators Table 2-1 Indicator description Name
Color
Status
Description
Run indicator
Green
Off
The SMU is faulty or has no DC input.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
3
SMU02C V500R003C10 Site Monitoring Unit User Manual
Name
2 Component Description
Color
Minor alarm indicator
Yellow
Major alarm indicator
Red
Status
Description
Blinking slowly (0.5 Hz)
The SMU is running properly and communicating with the host properly.
Blinking fast (4 Hz)
The SMU is running properly but fails to communicate with the host properly.
Off
No minor or warning alarm is generated.
Steady on
A minor or warning alarm is generated.
Off
No critical or major alarm is generated.
Steady on
A critical or major alarm is generated.
Buttons Table 2-2 Button description Button
Name
Description
Up Down
Press and to scroll through the menus or to change the value of a parameter.
Cancel
Returns to the previous menu without saving the settings.
Enter
Enters the main menu from the standby screen.
Enters a submenu from the main menu.
Saves menu settings on a submenu.
NOTE The LCD screen becomes dark if no button is pressed within 30 seconds.
You need to log in again if no button is pressed within 1 minute.
To increase or decrease a parameter value quickly, hold down
To restart the SMU, hold down
To increase (or decrease) the LCD backlight, hold down seconds.
and
or
.
for 10 seconds. and
(or
) for 2
SD Card Slot SD card is used for storing the camera capture images, maximum support 32 G capacity.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
4
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
USB Ports You can quickly deploy a site, import and export configuration files, export running logs, and upgrade software by inserting the USB flash drive that is specially used for site deployment into the USB port. After installing the specific WiFi module using the USB port, you can access the WebUI locally, which facilitates operations.
Using WiFi modules provided by another vendor may cause data loss or function exception. Consequences arising from this will not be borne by Huawei.
Communications Ports Table 2-3 Communications port description Communications Port
Communications Parameter
Communications Protocol
FE
10/100M autonegotiation
HTTPS, NetEco protocol, SNMP, and TCP-Modbus protocol
RS485/RS232
Baud rate: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 14400 bit/s, 19200 bit/s, 115200 bit/s
Master/slave protocol, YDN protocol, and Modbus protocol
CAN
Baud rate: 125 kbit/s
CAN protocol
NOTE All these ports are protected by a security mechanism.
Figure 2-2 Communication port pins
Table 2-4 Pin definitions for the FE port Pin
Issue 01 (2020-05-30)
Signal
Description
Copyright © Huawei Technologies Co., Ltd.
5
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Pin
Signal
Description
1
TX+
Transmits data over FE
2
TX-
3
RX+
6
RX-
4/5/7/8
NA
Receives data over FE
-
Table 2-5 Pin definitions for the RS485/RS232 port Pin
Signal
Description
1
TX+
Transmits data over RS485
2
TX-
4
RX+
5
RX-
3
RX232
Receives data over RS232
7
TX232
Transmits data over RS232
6
PGND
Connects to the ground
8
NA
–
Receives data over RS485
Table 2-6 Description for the CAN port pins Pin
Signal
Description
1
RX+
Receives data over RS485
2
RX-
3
NA
-
4
TX+
Sends data over RS485
5
TX-
6
NA
-
7
CANH
CAN high level signal
8
CANL
CAN low level signal
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
6
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
2.2 WIM01C1 The wireless interface module 01C1 (WIM01C1) is used to transfer signals and supports WiFi access. Figure 2-3 WIM01C1 panel
(1) WiFi indicator
(2) RF indicator
(3) Button
(4) GE cascading port
(5) WiFi antenna port
(6) RF_B antenna port
(7) RF_A antenna port
(8) GE ports
(9) Power port
Indicators and Buttons Table 2-7 RF indicator description Status
Description
Off
There is no power input or the module is faulty.
Steady on
The module does not properly communicate with the host or is not networked.
Blinking at intervals of 2s (on for 1s and then off for 1s)
The module properly communicates with the host.
Blinking at intervals of 0.25s (on for 0.125s and then off for 0.125s)
Networking is in progress.
Blinking at intervals of 0.125s (on for 0.0625s and then off for 0.0625s)
Network parameters are being cleared.
On for 0.25s and off for 0.25s
The module is blinking.
Table 2-8 Button description Action
Function
Description
Hold down
Allow or
When the WIM01C1 is in Disallow Node Networking
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
7
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Action
Function
Description
for 3s
disallow node networking
state, if you hold down the button for 3s, the WIM01C1 switches to the Allow Node Networking state and the indicator blinks at short intervals. When the WIM01C1 is in Allow Node Networking state, if you hold down the button for 3s, the WIM01C1 switches to the Disallow Node Networking state. You can determine the current status of the WIM01C1 according to the indicator description.
Hold down for 8s
Erase the network
After you press the button, the indicator blinks for several seconds (blinks for 1s each time). After the indicator blinks for eight times, it will blink at super short intervals for 3s, indicating that network erasing is successful.
Ports Table 2-9 Pin definitions for the GE_CASCADE/GE1/GE2 ports Pin
Signal
Description
1
TRX0+
2
TRX0-
Communications port, 100M/1000M autonegotiation
3
TRX1+
4
TRX2+
5
TRX2-
6
TRX1-
7
TRX3+
8
TRX3-
Table 2-10 48 V power input port description Port Type
Silk Screen
No.
Description
48 V power input port
48V
+
48 V power input, positive
-
48 V power input, negative
WiFi Function You can locally access the WebUI using WiFi.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
8
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
You are advised to periodically change the WiFi password to improve account security and prevent unauthorized network attacks, such as data tampering.
Huawei will not be liable for any loss caused by your failure to change the password in time or to keep the new password properly.
The WiFi function is disabled by default. Enable the WiFi function before using it and disable it after using it to ensure network security.
Enable or disable the WiFi function: choose System Settings > Network Config > WIFI. Change the WiFi account password: choose System Settings > Network Config > WIFI.
2.3 UIM02C Panel Figure 2-4 Panel
(1) Communications port
(2) Dry contact output ports
(3) Dry contact input ports
(4) Sensor ports
Port Description Table 2-11 Port description Port Type
Silk Screen
Remarks
Sensor ports
TEM-HUM
Ambient temperature and humidity sensor
WATER
Water sensor
TEMP1
Temperature sensor 1
TEMP2
Temperature sensor 2
GATE
Door status sensor
SMOKE
Smoke sensor
BTEMP
Battery temperature sensor
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
9
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Port Type
Silk Screen
Remarks
Dry contact input ports
DIN1
Dry contact input 1
DIN2
Dry contact input 2
DIN3
Dry contact input 3
DIN4
Dry contact input 4
DIN5
Dry contact input 5
DIN6
Dry contact input 6
ALM1
Dry contact output 1
ALM2
Dry contact output 2
ALM3
Dry contact output 3
ALM4
Dry contact output 4
ALM5
Dry contact output 5
ALM6
Dry contact output 6
ALM7
Dry contact output 7
ALM8
Dry contact output 8
COM
RS485
Dry contact output ports
Communications port
Communications Port Table 2-12 COM port description Communications Port
Communications Parameter
Communications Protocol
Purpose
COM
Baud rate: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 14400 bit/s, 19200 bit/s, 115200 bit/s
Master/slave, Modbus and YDN1363 protocols
Connects to a downstream device, such as the intelligent battery detector or intelligent air conditioner.
NOTE The COM port is protected by a security mechanism.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
10
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Figure 2-5 Pins in the COM port
Table 2-13 COM port pin definitions Pin
Signal
Remarks
1
RX+
Receives data over RS485.
2
RX-
4
TX+
5
TX-
6
PGND
Protective ground
3, 7, 8
NA
-
Transmits data over RS485.
Sensor Ports Figure 2-6 Pins in sensor ports
Table 2-14 UIM02C pin definitions Silk Screen
No.
Pins
TEM-HUM
1
12 V
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
11
SMU02C V500R003C10 Site Monitoring Unit User Manual
Silk Screen
WATER
TEMP1
TEMP2
GATE
SMOKE
BTEMP
2 Component Description
No.
Pins
2
ENV_TEMP
3
12 V
4
ENV_HUM
1
12 V
2
WATER
3
GND
4
-
1
GND
2
TEMP1
1
GND
2
TEMP2
1
GATE+
2
GATE-
1
SMOKE
2
12 V
1
GND
2
BTEMP
2.4 UIM02D Panel Figure 2-7 shows a UIM02D panel, and Table 2-15 lists the ports on it. Figure 2-7 UIM02D panel
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
12
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Ports Table 2-15 UIM02D port description Port Type
Silk Screen
Description
Sensor port
TEM-HUM
Ambient temperature and humidity sensor
WATER
Water sensor
TEMP1
Temperature sensor 1
TEMP2
Temperature sensor 2
GATE
Door sensor
SMOKE
Smoke sensor
BTEMP
Battery temperature sensor
Dry contact input
DIN1
Dry contact input 1
NOTE For details about the alarms associated with dry contact inputs, see the power system user manual.
DIN2
Dry contact input 2
DIN3
Dry contact input 3
DIN4
Dry contact input 4
DIN5
Dry contact input 5
DIN6
Dry contact input 6
Dry contact output
ALM1
Dry contact output 1
NOTE For details about the alarms associated with dry contact outputs, see the power system user manual.
ALM2
Dry contact output 2
ALM3
Dry contact output 3
ALM4
Dry contact output 4
ALM5
Dry contact output 5
ALM6
Dry contact output 6
ALM7
Dry contact output 7
ALM8
Dry contact output 8
ALM9
Dry contact output 9
ALM10
Dry contact output 10
ALM11
Dry contact output 11
ALM12
Dry contact output 12
COM
RS485 port
Communications port
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
13
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Communication Port Table 2-16 COM communication port description Communication Port
Communications Parameter
Communications Protocol
Function
COM port
Baud rate: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 14400 bit/s, 19200 bit/s, 115200 bit/s
M/S and Modbus protocol
Connects to lower-level devices such as the battery inspection unit, DC air conditioner
NOTE The COM port supports the security mechanism.
Figure 2-8 Pins in the COM port
Table 2-17 Pin definitions for the COM port Pin
Signal
Description
1
RX+
Receives data over RS485.
2
RX-
4
TX+
5
TX-
6
PGND
Connects to the ground.
3, 7, 8
NA
-
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
Sends data over RS485.
14
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Pins Figure 2-9 shows the numbers of pins in sensor ports. Table 2-18 describes the pin definitions. Figure 2-9 UIM02D pin numbers
Table 2-18 UIM02D pin definitions Silk Screen
No.
Pin Definition
TEM-HUM
1
12 V
2
ENV_TEMP
3
12 V
4
ENV_HUM
1
12 V
2
WATER
3
GND
4
-
1
GND
2
TEMP1
1
GND
2
TEMP2
1
GATE+
2
GATE-
1
SMOKE
2
12V
1
GND
2
BTEMP
WATER
TEMP1
TEMP2
GATE
SMOKE
BTEMP
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
15
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
2.5 UIM03D Panel Figure 2-10 UIM03D panel
(1) Communications ports
(2) Dry contact outputs
(3) Dry contact inputs
(4) Sensor ports
Ports Table 2-19 UIM03D port description Port Type
Silk Screen
Description
Sensor ports
TEM-HUM
Ambient T/H sensor
WATER
Water sensor, normally open (NO) Supports 12 V power supply.
TEMP1
Ambient temperature sensor 1
TEMP2
Ambient temperature sensor 2
GATE
Door status sensor, normally closed (NC)
SMOKE
Smoke sensor, normally open (NO)
BTEMP
Battery temperature sensor
Dry contact input ports
DIN1
Dry contact input 1
(Default setting: normally closed for DIN1, normally open for DIN2–6)
DIN2
Dry contact input 2
DIN3
Dry contact input 3
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
16
SMU02C V500R003C10 Site Monitoring Unit User Manual
Port Type
2 Component Description
Silk Screen
Description
DIN4
Dry contact input 4
DIN5
Dry contact input 5
DIN6
Dry contact input 6
Dry contact output ports
ALM1
The default setting (closed: alarm; open: normal) can be modified.
Dry contact output 1 (normally open by default)
ALM2
Dry contact output 2 (normally open by default)
ALM3
Dry contact output 3 (normally open by default)
ALM4
Reserved
ALM5
Reserved
ALM6
Reserved
ALM8
Dry contact output 8 (normally closed by default)
COM
4-wire RS485
ALM7
2-wire RS485
Communications ports
Communications Ports Table 2-20 Communications port description Communications Port
Communications Parameter
Function
COM
Baud rate:
Connects to a downstream device, such as a third-party power supply.
Default value: 9600 bit/s Options: 300 bit/s, 600 bit/s, 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 14400 bit/s, 19200 bit/s, 38400 bit/s, 56000 bit/s, 57600 bit/s, 115200 bit/s ALM7
Baud rate: Default value: 9600 bit/s Options: 9600 bit/s, 19200 bit/s, 115200 bit/s
Connects to a downstream device, such as a smart device.
NOTE The COM port is protected by a security mechanism.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
17
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Figure 2-11 Pins in the COM port
Table 2-21 COM port pin definitions Pin
Signal
Description
1
RX+
Receives data over RS485.
2
RX-
3
12V
Supplies power.
4
TX+
Transmits data over RS485.
5
TX-
6, 8
PGND
Protective ground
7
Reserved
-
Table 2-22 ALM7 port pin definitions Pin
Signal
Description
+
RS485+
RS485 data +
-
RS485-
RS485 data –
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
18
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Pin Definitions Figure 2-12 UIM03D pin numbers
Table 2-23 Pin definitions for UIM03D sensor ports Silk Screen
No.
Pin Definition
TEM-HUM
1
12V
2
ENV_TEMP
3
12V
4
ENV_HUM
1
12V
2
WATER
3
GND
4
-
1
TEMP1
2
GND
3
TEMP2
4
GND
1
GATE+
2
GATE-
3
12V
4
SMOKE
WATER
TEMP1
TEMP2
GATE
SMOKE
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
19
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Silk Screen
No.
Pin Definition
BTEMP
1
BTEMP
2
GND
2.6 UIM05B1 Figure 2-13 Mian Panel
(1) Dry contact ports and sensor ports
(2) COM communications port
(3) Battery temperature sensor port
(4) Door status sensor port
(5) Battery switch
(6) Cable hole
(7) Handle
The battery switch is used only when the mains supply is unavailable.
Ports Figure 2-14 Dry contacts and sensor ports
Table 2-24 Port description Port Type
Silk Screen
Description
Sensor port
TEMP
Temperature sensor
WATER
Water sensor
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
20
SMU02C V500R003C10 Site Monitoring Unit User Manual
Port Type
Dry contact input
Dry contact output
Communications port
2 Component Description
Silk Screen
Description
SMOKE
Smoke sensor
BTEMP
Battery temperature sensor
GATE
Door status sensor
DIN1 (Multiplexed with dry contact output 1)
Dry contact input 1
DIN2 (Multiplexed with dry contact output 2)
Dry contact input 2
DIN3 (Multiplexed with dry contact output 3)
Dry contact input 3
DIN4
Dry contact input 4
ALM1 (Multiplexed with dry contact input 1)
Dry contact output 1
ALM2 (Multiplexed with dry contact input 2)
Dry contact output 2
ALM3 (Multiplexed with dry contact input 3)
Dry contact output 3
ALM4
Dry contact output 4
ALM5
Dry contact output 5
ALM6
Dry contact output 6
ALM7
Dry contact output 7
ALM8
Dry contact output 8
COM
RS485
Communications Port Figure 2-15 Pins in the COM port
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
21
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Table 2-25 COM port pin definitions Pin
Signal
Description
1
RX+
Receives data over RS485
2
RX-
3
12V
Power supply
4
TX+
Transmits data over RS485
5
TX-
6
GND
Ground
7
Reserved
–
8
GND
Ground
Table 2-26 RS485/CAN port pin definitions Pin
Signal
Description
1
CANH
CAN high level signal
2
CANL
CAN low level signal
3
RS485+
RS485 data +
4
RS485-
RS485 data -
Table 2-27 CAN port pin definitions Pin
Signal
Description
1
CANH
CAN high level signal
2
CANL
CAN low level signal
3
NA
-
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
22
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Sensor Ports Figure 2-16 Pins in sensor ports
Table 2-28 UIM05B1 pin definitions Sensor Port
No.
Pin Definition
TEMP
1
TEMP1+
2
TEMP1-
1
WATER
2
GND
1
12V
2
SMOKE
1
BTEMP1+
2
BTEMP1-
1
GATE+
2
GATE-
WATER
SMOKE
BTEMP
GATE
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
23
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
2.7 NIM02D Panel Figure 2-17 Panel
(1) FE cascade port
(2) Signal Input ports/12 V power port
(3) FE ports
Ports Table 2-29 Port Description Port
Function
Communications Parameter
FE_CASCADE
Connects to the FE port on the SMU.
10/100M autonegotiation
FE1/2
Connects to an NMS or a smart device such as an IP camera.
CH1/2/3/4/5/6
Signal Input ports.
-
12 V
12 V power output.
-
Remarks:
The FE ports are protected by a security mechanism.
CH1/2/3/4 supports AI (4–20 mA), AI (0–10 V DC), or DI detection. The function can be used by hardware jumper or software parameter configuration.
CH5/6 supports only AI (4–20 mA) detection by default.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
24
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Figure 2-18 Pins in an FE communications port
Table 2-30 Pin definitions for FE communications ports Pin
Signal
Description
1
TX+
Transmits data over FE.
2
TX-
3
RX+
6
RX-
4, 5, 7 and 8
NA
Receives data over FE.
-
2.8 NIM01C3 Panel Figure 2-19 NIM01C3 panel
(1) SIM card slots (2 PCS)
Issue 01 (2020-05-30)
(2) 4G indicator
Copyright © Huawei Technologies Co., Ltd.
(3) Alarm indicator
25
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
(4) Run indicator
(5) ANT communications port
(6) COM1 port
(7) COM2 port
(8) COM3/CAN port
(9) COM4 port
(10) Handle
Indicators Table 2-31 Indicator description Indicator
Color
Status
Description
4G indicator
Green
Steady on
The dial-up connection is in the data service state.
Blinking at a period of 2s (on for 0.1s and then off for 1.9s)
The network has been registered.
Blinking at a period of 2s (on for 0.1s, off for 0.1s, on for 0.1s and then off for 1.7s)
A network is in search, or no network is connected.
Off
No alarm is generated.
Steady on
An alarm is generated.
Off
The NIM01C3 is not running because it is faulty or has no DC input.
Blinking at a period of 2s (on for 2s and then off for 1s)
The NIM01C3 is running and communicating with the host properly.
Blinking at a period of 0.25s (on for 0.125s and then off for 0.125s)
The NIM01C3 is running properly, but fails to communicate with the host.
Alarm indicator
Run indicator
Red
Green
Communications Ports Table 2-32 Communications port description Communications Port
Issue 01 (2020-05-30)
Communications Parameter
Copyright © Huawei Technologies Co., Ltd.
Description
26
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Communications Port
Communications Parameter
Description
COM1 port
Baud rate: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 14400 bit/s, 19200 bit/s, 115200 bit/s
Supports master/slave protocols and Modbus protocols. Supplies 12 V power.
COM2 port
Baud rate: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 14400 bit/s, 19200 bit/s, 115200 bit/s
Supports master/slave protocols and Modbus protocols. Supplies 12 V power.
COM3/CAN port
Baud rate: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 14400 bit/s, 19200 bit/s, 115200 bit/s
COM3: Supports master/slave protocols and Modbus protocols. CAN: Supports CAN protocol.
COM4 port
Baud rate: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 14400 bit/s, 19200 bit/s, 115200 bit/s
Supports Modbus protocols.
Figure 2-20 Pins in the COM1, COM2, and COM3 ports
Table 2-33 Description for the pins in the COM1 and COM2 ports Pin
Signal
Description
1
RS485+
RS485 data +
2
RS485-
RS485 data -
3
12 V
Supply power
4
RS485+
RS485 data +
5
RS485-
RS485 data -
6
NA
-
7
NA
-
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
27
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Pin
Signal
Description
8
GND
Ground
Table 2-34 Description for the COM3/CAN port pins Pin
Signal
Description
1
RX+
Receives data over RS485.
2
RX-
3
NA
-
4
TX+
Transmits data over RS485.
5
TX-
6
GND
Grounded.
7
CANH
CAN high level signal.
8
CANL
CAN low level signal.
Table 2-35 Description for the COM4 port pins Silk Screen
Signal
Description
R+
RS485+
RS485 data +
R-
RS485-
RS485 data -
2.9 CIM02C Panel Figure 2-21 CIM02C panel
(1) COM1 port
Issue 01 (2020-05-30)
(2) COM2 port
Copyright © Huawei Technologies Co., Ltd.
(3) COM3/COM4 port
28
SMU02C V500R003C10 Site Monitoring Unit User Manual
(4) 12 V power port
2 Component Description
(5) COM5 port
(6) Handle
Communications Ports Table 2-36 Communications port description Communications Port
Description
Communications Parameter
COM1 port
Supports RS485.
Baud rate
12 V power supply, maximum output 1.5 A.
Default value: 9600 bit/s
Connects to a smart device. COM2 port
Supports RS485.
Options: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 14400 bit/s, 19200 bit/s, 115200 bit/s
12 V power supply, maximum output 1.5 A. Connects to a smart device. COM3/COM4 port
COM3 supports RS485. COM4 supports RS232 and CAN. RS232 is used by default, which can be changed to CAN by using a jumper. Connects to a third-party power supply.
COM5 port
Supports RS232 and RS485. RS485 is used by default, which can be changed to RS232 by using a jumper. Connects to an air conditioner.
Figure 2-22 Pins in the COM1, COM2, or COM3/COM4 port
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
29
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
Table 2-37 Pin definitions for the COM1 and COM2 ports Pin
Single
Description
1
RS485+
RS485 data +
2
RS485-
RS485 data -
3
12 V
Power supply
4
RS485+
RS485 data +
5
RS485-
RS485 data -
6
NA
–
7
NA
–
8
GND
Ground
Table 2-38 Pin definitions for the COM3/4 port Pin
Single
Description
1
RS485_RX+
Receives data over RS485.
2
RS485_RX-
3
RS232_RXD
Receives data over RS232.
4
RS485_TX+
Transmits data over RS485.
5
RS485_TX-
6
GND
Ground.
7
CANH/RS232_TXD
CAN high level signal/Transmits data over RS232.
8
CANL
CAN low level signal.
Table 2-39 Pin definitions for the COM5 port Silk Screen
Signal
Description
R+/TX
RS485+/RS232_TXD
RS485 data + or transmits data over RS232.
R-/RX
RS485-/RS232_RXD
RS485 data - or receives data over RS232.
GND
GND
Ground.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
30
SMU02C V500R003C10 Site Monitoring Unit User Manual
2 Component Description
2.10 GIM01C Panel Figure 2-23 GIM01C panel
(1) Run indicator
(2) DG 1 control ports
(3) DG 2 control ports
(4) DG 1 reset ports
(5) DG 2 reset ports
(6) Fuel level 1 detection ports
(7) Fuel level 2 detection ports
(8) COM communications ports
(9) CAN communications port
(10) Alarm indicator
Indicators Table 2-40 Indicator description Name
Color
Status
Remarks
RUN indicator
Green
Off
The module is faulty or has no DC input.
Blinking slowly (0.5 Hz)
The module is running and communicating with the host properly.
Blinking fast (4 Hz)
The module is running properly but does not communicate with the host properly.
ALM indicator
Red
Reserve
Ports Table 2-41 Port description Port Type
Silk Screen
DG control port
DG1_CTL
Issue 01 (2020-05-30)
Description
Remarks
NC
DO normally closed port
M
Common port
Controls DG startup and
Copyright © Huawei Technologies Co., Ltd.
31
SMU02C V500R003C10 Site Monitoring Unit User Manual
Port Type
Silk Screen
DG2_CTL
DG reset port
RST1
RST2
Fuel level detection port
AI1
AI2
Communications port
COM
CAN
Issue 01 (2020-05-30)
2 Component Description
Description
Remarks
NO
DO normally open port
shutdown.
NC
DO normally closed port
M
Common port
NO
DO normally open port
M
Common port
NO
DO normally open port
M
Common port
NO
DO normally open port
+
+12 V power supply
-
Analog signal
+
+12 V power supply
-
Analog signal
R+
RS485 data +
R-
RS485 data –
+
CAN data +
-
CAN data –
Copyright © Huawei Technologies Co., Ltd.
The DG resets if the port is closed.
Detect the fuel level.
Used for RS485 communication. Used for CAN communication.
32
SMU02C V500R003C10 Site Monitoring Unit User Manual
3 User Interfaces
3
User Interfaces
3.1 LCD 3.1.1 Setup Wizard After the SMU is powered on for the first time, the Setup Wizard page is displayed, as shown in the following figure.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
33
SMU02C V500R003C10 Site Monitoring Unit User Manual
3 User Interfaces
Figure 3-1 Setup wizard
3.1.2 Modifying the display language The monitoring unit supports English, Chinese, French, Spanish, Portuguese, Russian, Italian, German, Turkish, and Japanese. When the monitoring unit is running properly, choose the following menus to select a language. Table 3-1 Modifying the display language Main Menu
Second-Level Menu
Third-Level Menu
Setting
Parameters Settings
Local Parameters
Language
Select a desired language.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
34
SMU02C V500R003C10 Site Monitoring Unit User Manual
3 User Interfaces
3.1.3 Restart Button To restart the monitoring unit, hold down
and
for 10s.
3.1.4 Password Two-level password management supported by the LCD, two user levels are available. Table 3-2 Two-level password management Level
Operation Permission
Password
engineer
All permissions except for changing the administrator password and resetting the web password.
000001
admin
Has all operation permissions.
012589 NOTE The admin password can only be used by the administrator. It must not be provided for third-party maintenance personnel.
3.1.5 Standby Screen The following figure shows the monitoring unit standby screen, which displays basic power system information, including the DC output voltage, total load current, and total battery current.
The parameter values in the figures are for reference only.
Figure 3-2 Standby screen
The standby screen is displayed if no button is pressed within 1 minute on any screen. On the standby screen, you can press , , and to enter the version information screen, basic information screen, and main menu screen respectively, as shown in the following figure.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
35
SMU02C V500R003C10 Site Monitoring Unit User Manual
3 User Interfaces
Figure 3-3 Standby screen operations
Main menu include active alarm, running information, setting wizard, parameters settings, running control, site maintain and user management.
3.2 WebUI 3.2.1 Connecting a Communications Cable Procedure Step 1 Preparing the Operating Environment. Step 2 Connect the FE port on the SMU by using a network cable. Figure 3-4 Connecting a communications cable
----End
3.2.2 Setting Parameters Procedure Step 1 Apply to the site or equipment room network administrator for a fixed IP address. Step 2 Set the IP type, IP address, subnet mask, and gateway address on the LCD.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
36
SMU02C V500R003C10 Site Monitoring Unit User Manual
3 User Interfaces
Table 3-3 IP parameters Main Menu
Second-Level Menu
Third-Level Menu
Default Value
Setting Value
Setting Wizard
Network Parameters
IP Type
IPv4
Set as required.
IP Address
192.168.0.10
Set this parameter according to the address provided by the network administrator.
Subnet Mask
255.255.255.0
Set this parameter according to the subnet mask provided by the network administrator.
Default Gateway
192.168.0.1
Set this parameter according to the gateway address provided by the network administrator.
----End
3.2.3 Logging In to the WebUI Procedure Step 1 Set the PC IP address in the same network segment as the SMU IP address. For example, if the SMU has an IP address of 192.168.0.10, a subnet mask of 255.255.255.0, and a default gateway of 192.168.0.1, set the IP address to 192.168.0.11, subnet mask to 255.255.255.0, and default gateway to 192.168.0.1 on the PC. Step 2 Enter https://monitoring unit local IP address (for example, https://192.168.0.10) in the address box of the browser, and then press Enter to access the WebUI login page. Figure 3-5 WebUI login page
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
37
SMU02C V500R003C10 Site Monitoring Unit User Manual
3 User Interfaces
The preset user names include admin, engineer, and operator, and the preset password is Changeme. The user names are intended for administrators, engineers, and operators respectively. Change the preset password when you first log in to ensure system security. The method about how to change the password, see 5.2.5 Changing a User Password.
----End
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
38
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
4
NMS Management
4.1 U2000-SPM Management 4.1.1 Connecting a Communications Cable Procedure Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU. Step 2 Connect the other end to the MON0 or MON1 port on the BBU. Figure 4-1 Connecting a communications cable
(1) RS485/RS232 port
(2) MON1 port
----End
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
39
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
4.1.2 Setting Parameters Step 1 On the LCD, set the port mode, communications protocol type, baud rate, and communications address on the LCD, as shown in the following table. Table 4-1 Communications parameters Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Setting Value
Parameters Settings
Comm. Parameters
Serial Port
Northbound
Port Mode
Manual
Protocol Type
M/S Protocol
Baud Rate
-
9600
Comm. Address
-
3
M/S Protocol
----End
4.2 NetEco Management 4.2.1 IP Networking Step 1 Connect a network cable to the FE port on the SMU. Figure 4-2 Connecting a communications cable
(1) FE Port
Step 2 Apply to the site or equipment room network administrator for a fixed IP address. Step 3 Set the IP type, IP address, subnet mask, and gateway address on the LCD. Table 4-2 IP parameters Main Menu
Second-Level Menu
Third-Level Menu
Default Value
Setting
Setting
Network
IP Type
IPv4
Set as required.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
40
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
Main Menu
Second-Level Menu
Third-Level Menu
Default Value
Setting
Wizard
Parameters
IP Address
192.168.0.10
Set this parameter based on the address assigned by the network administrator.
Subnet Mask
255.255.255.0
Set this parameter based on the address assigned by the network administrator.
Default Gateway
192.168.0.1
Set this parameter based on the address assigned by the network administrator.
Step 4 Set IP addresses and port numbers for the active and standby NetEco servers and backup NetEco servers on the LCD. Table 4-3 NetEco parameters Main Menu
Second-Level Menu
Third-Leve l Menu
Fourth-Level Menu
Default Value
Setting
Parameters Settings
Comm. Parameters
Network Parameters
NetEco Primary IP
192.168.0.10
Set this parameter to the IP address of the active NetEco server.
NetEco Backup IP
192.168.0.10
Set this parameter to the IP address of the standby NetEco server.
NetEco Port Number
31220
31220 NOTE Please contact Huawei technical support if you need change the port number.
----End
4.2.2 Wireless Networking Installing a Wireless Antenna Step 1 Insert the SIM card into the SIM card slot in the communications expansion board. The SIM card inserted into the communications expansion module (NIM01C3) should support GSM, WCDMA, TD-SCDMA, TDD, and FDD standards, and have the SMS and data service functions enabled. Step 2 Connect the GPRS antenna to the ANT port on the NIM01C3.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
41
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
Figure 4-3 Connection between a GPRS antenna and an NIM01C3
----End
Setting Communications Parameters Step 1 Check whether the default wireless communications parameters on the LCD are consistent with the communication configurations of the carrier network that the SIM card belongs to. If they are inconsistent, modify the parameters according to the actual configurations of the carrier network. Table 4-4 Checking wireless communication parameters Main Menu
Second-Leve l Menu
Third-Level Menu
Fourth-Level Menu
Default Value
Value Range
Parameters Settings
Comm. Parameters
Mobile Data
Carrier Operator
Automatic
Automatic, Others
SIMn Acc Point Name
-
A maximum of 28 characters, including lowercase English letters (a-z), uppercase English letters (A-Z), digits (0-9), and special characters (@_#*-.).
NOTE This parameter is displayed only when Carrier Operator is set to Others.
SIMn Access Point No
-
NOTE This parameter is displayed only when Carrier Operator is set to Others.
SIMn User Name
-
NOTE This parameter is displayed only when Carrier Operator is set to
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
42
SMU02C V500R003C10 Site Monitoring Unit User Manual
Main Menu
Second-Leve l Menu
Third-Level Menu
4 NMS Management
Fourth-Level Menu
Default Value
Value Range
-
A maximum of 27 characters, including lowercase English letters (a-z), uppercase English letters (A-Z), digits (0-9), and special characters (@_#-.).
Others.
SIMn User Password NOTE This parameter is displayed only when Carrier Operator is set to Others.
It is recommended that the password contain at least two types of characters and the length exceed six characters.
Step 2 Set IP addresses and port numbers for the active and standby NetEco servers and backup NetEco servers on the LCD. Table 4-5 Setting NetEco parameters Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Default Value
Setting
Parameters Settings
Comm. Parameters
Network Parameters
NetEco Primary IP
192.168.0.10
Set this parameter to the IP address of the active NetEco server.
NetEco Backup IP
192.168.0.10
Set this parameter to the IP address of the standby NetEco server.
NetEco Port Number
31220
31220
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
NOTE Please contact Huawei technical support if you need change the port number.
43
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
----End
Verifying Network Connection Status After the SIM card and wireless antenna are installed, the SIM card automatically accesses the wireless network in dial-up mode. You can view the network connection status on the LCD. Table 4-6 Verifying the network connection status Main Menu
Second-Level Menu
Third-Level Menu
Remarks
Running Information
Mobile Data Info
Connection Status
Connected indicates successful dial-up and normal network connection.
The following table shows general requirements of GPRS Network performance. If the network performance is worse than the requirements, communication interruption may happen.
Table 4-7 GPRS main performance index Index
Description
Reference
Received signal strength indicator (RSSI)
If the probability of received signal code power (RSCP) greater than –89 dBm is less than 95%, the cell coverage of wireless signals is poor.
P (RSCP > –89 dBm) 95%
Packet Data Protocol (PDP) activation success rate
PDP activation success rate = Successful number of PDP activation/Total number of PDP activation
95%
Attach attachment success rate
Attach attachment success rate = Successful number of PDP attachment/Total number of PDP attachment
95%
Handover success rate
Handover success rate = Successful number of GPRS handover/Total number of GPRS handover
98%
4.2.3 BBU In-band Networking Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU. Step 2 Connect the other end to the MON0 or MON1 port on the BBU.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
44
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
Figure 4-4 Connecting a communications cable
(1) RS485/RS232 Port
(2) MON1 Port
Step 3 Set the port mode, communications protocol type, baud rate, and communications address on the LCD. Table 4-8 Setting communications parameters Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Setting
Parameters Settings
Comm. Parameters
Serial Port
Northbound
Port Mode
Manual
Protocol Type
M/S Protocol
Baud Rate
-
9600
Comm. Address
-
3
M/S Protocol
----End
4.2.4 Logging In to the NetEco Procedure Step 1 Enter https://NetEco IP address: port number for NetEco login (for example, https://10.10.10.1:31943) in the address box of the browser and press Enter. The NetEco login page is displayed.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
45
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
Figure 4-5 NetEco login page
Step 2 Enter the correct user name and password and click Log In.
To obtain the NetEco user name and password, contact the site or equipment room network administrator. ----End
4.3 NMS Management over SNMP 4.3.1 Site Configuration 4.3.1.1 Connecting a Communications Cable Procedure Step 1 Connect the FE port on the SMU by using a network cable, as shown in Figure 4-6. Figure 4-6 Connecting a communications cable
(1) FE port
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
46
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
----End
4.3.1.2 Setting Parameters Procedure Step 1 Apply to the site or equipment room network administrator for a fixed IP address. Step 2 Set the
IP type, IP address, subnet mask, and gateway on the LCD, as shown in Table 4-9
Table 4-9 IP parameters Main Menu
Second-Level Menu
Third-Level Menu
Default Value
Setting Value
Setting Wizard
Network Parameters
IP Type
IPv4
Set as required.
IP Address
192.168.0.10
Set this parameter according to the address provided by the network administrator.
Subnet Mask
255.255.255.0
Set this parameter according to the subnet mask provided by the network administrator.
Default Gateway
192.168.0.1
Set this parameter according to the gateway address provided by the network administrator.
----End
4.3.2 Setting SNMP Parameters Prerequisites You can set SNMP parameters remotely or locally on the WebUI.
Before setting SNMP parameters, obtain the information listed in Table 4-10 from the SNMP NMS.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
47
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
Table 4-10 Information obtained from the NMS Item
Description
SNMP version
SNMP version and port number used for communication between the SMU and NMS. The SNMP version can be SNMPv1, SNMPv2c, SNMPv3.
SNMP Port Number
Read Community Name
If you use SNMPv1 or SNMPv2c, enter the read and write community names that comply with the NMS. Otherwise, the SMU will not connect to the NMS.
Write Community Name
The read community name must be different from the write community name. User Name
To enhance the security, you need a user name and password for authentication if you use SNMPv3. After the authentication succeeds, the SMU can communicate with the NMS.
MD5/SHA Password DES/AES Password Trap Target Address
IP address and port number used for reporting alarm trap packets.
Trap Port Trap Community
If you use SNMPv1 or SNMPv2c, community name used for reporting alarm trap packets.
Procedure Step 1 Log in to the WebUI.
The preset user name is admin, and the preset password is Changeme.
Step 2 Access the System Settings page and set SNMP.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
48
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
Figure 4-7 SNMP Page
There are two or more NMSs and the SNMP versions have both SNMPv1 or SNMPv2c and SNMPv3: Set SNMP Version to ALL in SNMP, and set SNMP Port Number, Read Community Name, and Write Community Name. Then click Add in SNMPv3, and set User Name, MD5/SHA Password, and DES/AES Password. Then click Confirm. Figure 4-8 Choosing SNMP Version to ALL
Issue 01 (2020-05-30)
SNMPv1 or SNMPv2c: Set SNMP Version to SNMPv1&SNMPv2c in SNMP,and set SNMP Port Number, Read Community Name, and Write Community Name. Then click Confirm.
Copyright © Huawei Technologies Co., Ltd.
49
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
Figure 4-9 Choosing SNMP Version to SNMPv1 or SNMPv2c
SNMPv3: Set SNMP Version to SNMPv3 in SNMP, click Add in SNMPv3, and set User Name, MD5/SHA Password, and DES/AES Password. Then click Confirm. Figure 4-10 SNMP Version to SNMPv3
Step 3 In SNMP Trap, click Add.
Issue 01 (2020-05-30)
If the SNMP Version is SNMPv1 or SNMPv2c, set Trap Target Address and Trap Port and set Trap community.
Copyright © Huawei Technologies Co., Ltd.
50
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
Figure 4-11 Adding Trap address
If the SNMP Version is SNMPv3, set Trap Target Address and Trap Port and SNMPv3 User Name. Figure 4-12 Adding Trap address
SNMP Version in this place can be different from the version in Step 2.
Step 4 In Mib files, click Export to export the Mib file and then import it into the NMS.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
51
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
Figure 4-13 Exporting Mib files
If there is only one NMS, perform 4.3.2 Setting SNMP Parameters once only.
----End
4.3.3 NMS Commissioning You can query the power system operating status, active alarms, and the names of user-defined dry contact inputs, and configure dry contact outputs on the network management system (NMS) that is connected over the Simple Network Management Protocol (SNMP).
4.4 NMS Management over YDN1363 Protocol 4.4.1 Connecting a Communications Cable Procedure Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU. Step 2 Connect the other end to the corresponding port on the power and environment monitoring device, as shown in Figure 4-14.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
52
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
Figure 4-14 Connecting a communications cable
(1) Power and environment network management system (NMS)
(2) Power and environment monitoring device
(3) RS485/RS232 port on the SMU
----End
4.4.2 Setting Parameters Step 1 On the LCD, set the port mode, communications protocol type, baud rate, and communications address on the LCD, as shown in Table 4-11. Table 4-11 Communications parameters Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Default Value
Parameters Settings
Comm. Parameters
Serial Port
Northbound
Port Mode
Manual
Protocol Type
YDN1363 Protocol
Baud Rate
-
9600
Comm. Address
-
1
YDN1363 Protocol
----End
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
53
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
4.5 NMS Management over Modbus 4.5.1 Connecting a Communications Cable Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU. Step 2 Connect the other end to the corresponding port on the third-party device, as shown in Figure 4-15. Figure 4-15 Connecting a communications cable
(1) Network management device
(2) Third-party device
(3) RS485/RS232 port on the SMU
----End
4.5.2 Setting Parameters Step 1 On the LCD, set the port mode, communications protocol type, baud rate, and communications address on the LCD, as shown in Table 4-12. Table 4-12 Communications parameters Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Default Value
Parameters Settings
Comm. Parameters
Serial Port
Northbound
Port Mode
Manual
Protocol Type
Modbus Protocol
Baud Rate
-
9600
Comm. Address
-
33
Modbus Protocol
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
54
SMU02C V500R003C10 Site Monitoring Unit User Manual
4 NMS Management
----End
4.6 NMS Management over TCP-Modbus 4.6.1 Connecting a Communications Cable Procedure Step 1 Connect the FE port on the SMU by using a network cable, as shown in Figure 4-16. Figure 4-16 Connecting a communications cable
(1) FE port
----End
4.6.2 Setting Parameters Procedure Step 1 Log in to the WebUI.
The preset user name is admin, and the preset password is Changeme.
Step 2 Choose System Settings > TCP-Modbus Config and set parameters. For details, see Table 4-13. Table 4-13 Communications parameters Parameter
Value
Setting Method
TCP-Modbus link Mode
Sever, Client, Sever+Client
Server: The SMU works as the server and can connect to one client for communication.
Client: The SMU works as a client and can connect to the remote server for communication.
Server+Client: The SMU works as the server and can connect to one client for communication. At the same time, the SMU works as a client and can connect to the remote
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
55
SMU02C V500R003C10 Site Monitoring Unit User Manual
Parameter
Value
4 NMS Management
Setting Method server for communication.
TCP-Modbus SSL server enable
Enable, Disable
TCP-Modbus SSL client enable
Enable, Disable
TCP-Modbus client IP address
-
The default value is Enable. NOTE This parameter is displayed only when TCP-Modbus link Mode is set to Server and Server+Client.
The default value is Enable. NOTE This parameter is displayed only when TCP-Modbus link Mode is set to Client and Server+Client.
The default value is 192.168.0.10. Set the NMS IP address based on the actual situation. NOTE This parameter is displayed only when TCP-Modbus link Mode is set to Client and Server+Client.
TCP-Modbus client IP port
-
The default value is 16100. It is recommended that you not change the value. If necessary, set this parameter based on the actual situation. NOTE This parameter is displayed only when TCP-Modbus link Mode is set to Client and Server+Client.
Step 3 Upload CA certificate file, local certificate file and key file. ----End
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
56
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
5
Common Tasks
5.1 Common Installation Tasks 5.1.1 Using a USB Flash Drive for Site Deployment Prerequisites
The USB flash drive stores the upgrade and configuration files required for site deployment.
The upgrade and configuration files must be stored in the root directory of the USB flash drive. Otherwise, the SMU cannot read the configuration file.
The configuration file name starts with Config and ends with .tar.gz or .zip.
The file name should have less than 80 characters, cannot start with fault, and cannot contain single or double quotation marks, spaces, or the following special characters:< \ > | ; $ & ` ( ) %
The USB flash drive and file have been scanned to ensure that they are not infected with viruses.
Context You can copy site configuration parameters from the LCD or WebUI to a USB flash drive to rapidly set up other sites.
Export configuration parameters from the LCD to a USB flash drive: On the LCD, choose Site Maintain > Export File to USB to export the configurations of the current operating system into a configuration file and save the file in a USB flash drive.
For details about how to export configuration parameters from the WebUI to a USB flash drive, see 5.2.1 Backing Up the Current Settings.
Procedure Step 1 Insert the USB flash drive into the SMU USB port. The LCD displays the Site Maintain screen.
When visiting Site Maintain on the LCD, enter the preset password 000001.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
57
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
Step 2 Choose Site Maintain > U Disk Upgrade/Cfg. Step 3 Select the upgrade or configuration file stored in the root directory of the USB flash drive, and tap
. Back up first. Go on? is displayed.
Step 4 Select YES and tap , Package Classifying is displayed and Config Processing is displayed, indicating that upgrade or data configuration is in progress.
The configuration or upgrade process will take about 5 minutes.
Step 5 After the upgrade or configuration is complete, Config Successful Rebooting in 15s. The SMU will restart 15 seconds later. Step 6 After the restart is complete, remove the USB flash drive. ----End
5.1.2 Setting the Time Zone and Time Set the date and time based on the local time and time zone. Table 5-1 Setting the time zone and time Main Menu
Second-Level Menu
Third-Level Menu
Setting
Setting Wizard
Date and Time
Time Zone
Set to the local time zone.
Date and Time
Set to the local date and time.
5.1.3 Setting Basic Battery Parameters Context Basic battery parameters are fundamental for the monitoring unit to manage batteries and should be set based on the number and capacity of battery strings connected. The monitoring menus are related to the type of connected batteries and the number of battery strings.
Incorrectly setting basic battery parameters affects the battery charge and discharge management and reduces the battery lifespan.
Procedure Step 1 Set the battery type.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
58
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
Table 5-2 Setting the battery type Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Setting
Parameters Settings
Setup Parameter
Basic Parameters
Battery Vendor
Set based on site requirements.
Battery Model
NOTE If lithium batteries and lead-acid batteries are used together, set Battery Vendor and Battery Model based on the lead-acid battery parameters.
Step 2 Set lead-acid battery parameters. Table 5-3 Setting lead-acid battery parameters Main Menu
Second-Level Menu
Third-Level Menu
Setting
Setting Wizard
Batt Parameters
Battery N Connected
Yes/No NOTE
Set the corresponding Battery N Connected to Yes and the other parameters to No based on the circuit breaker or fuse to which lead-acid batteries are connected. Single-String Cap.
Rated capacity of the batteries in a battery string. NOTE The batteries controlled by one circuit breaker or fuse are called a battery string.
For example:
If battery routes 1 and 2 are respectively connected to a battery string (each battery string consists of four 12 V, 150 Ah batteries in series), set Battery 1 Connected and Battery 2 Connected to Yes and others to No, and set Single-String Cap. to 150 Ah.
If battery route 1 is connected to two battery strings in parallel (each battery string consists of four 12 V, 150 Ah batteries in series), set Battery 1 Connected to Yes and others to No, and set Single-String Cap. to 300 Ah.
Step 3 Set lithium battery parameters. Table 5-4 Setting lithium battery parameters Main Menu
Second-Level Menu
Third-Level Menu
Third-Level Menu
Setting
Parameter s Settings
Li Battery
Basic Parameters
Battery 1 Connected
Yes/No
Battery 2 Connected
NOTE Set the corresponding Battery
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
59
SMU02C V500R003C10 Site Monitoring Unit User Manual
Main Menu
Second-Level Menu
5 Common Tasks
Third-Level Menu
Third-Level Menu
Setting N Connected to Yes and the other parameters to No based on the circuit breaker or fuse to which lithium batteries are connected.
Step 4 Set small-capacity lithium battery parameters. Table 5-5 Setting small-capacity lithium battery parameters Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Setting
Parameters Settings
Low Cap Li-ion Batt
Basic Parameters
Battery 1 Connected
Yes/No
Battery 2 Connected
NOTE Set the corresponding Battery N Connected to Yes and the other parameters to No based on the circuit breaker or fuse to which small-capacity lithium batteries are connected.
Rated Capacity
Rated capacity of the batteries in a battery string. NOTE The batteries controlled by one circuit breaker or fuse are called a battery string.
For example, if lithium batteries are connected to battery circuit breaker 1 and lead-acid batteries are connected to battery circuit breaker 2, set lead-acid battery parameters according to 5.1.3 Setting Basic Battery Parameters (set Battery 1 Connected to No and Battery 2 Connected to Yes) and set lithium battery parameters according to 5.1.3 Setting Basic Battery Parameters (set Battery 1 Connected to Yes and Battery 2 Connected to No).
----End
5.1.4 Setting the Alarm Enable Option, Alarm Severity, and Associated Relays
You can enable or disable each alarm based on site requirements. If an alarm is enabled, the monitoring unit generates the alarm when the alarm condition is met. If an alarm is disabled, the monitoring unit does not generate the alarm.
You can set the severity of an alarm to critical, major, minor, or warning.
You can associate an alarm with a specific dry contact output relay.
The following describes how to set alarm parameters for an AC Loop Fault.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
60
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
Table 5-6 Setting the alarm enable option, alarm severity, and associated relays Main Menu
Second-Lev el Menu
Third-Level Menu
Fourth-Lev el Menu
Fifth-Level Menu
Sixth-Level Menu
Setting
Parameters Settings
Alarm Parameters
Alarm Config
Site Unit
AC Loop Fault
Alarm Enable
Enable
Alarm Severity
Major
Output Relay
ALM1 No
Associated camera
Camera 1 No
5.1.5 Setting Alarm Parameters for Dry Contacts Context
You can set associations between dry contact output status and alarm status.
You can clear the associations between all alarms and the selected dry contact inputs or outputs in one click.
You can set associations between dry contact input status and alarm status. Use DIN1 as an example. If you set DIN1 Alarm Condition to Close, the SMU generates a DIN1 Alarm when the DIN1 is closed.
Procedure Step 1 Set alarm actions for dry contact outputs. Use ALM1 as an example. Table 5-7 Setting alarm actions for dry contact outputs Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Setting
Parameters Settings
Alarm Parameters
DO Dry Contact Para.
ALM1 Alarm Action
Close
Step 2 Clear associations between alarms and dry contact outputs. Use ALM1 as an example. Table 5-8 Clearing associations between alarms and dry contact outputs Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Setting
Parameters Settings
Alarm Parameters
Clear ALM Asso.
Clear ALM1 Asso.
Yes
Step 3 Set alarm conditions for dry contact inputs. Use DIN1 as an example.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
61
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
Table 5-9 Setting alarm conditions for dry contact inputs Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Setting
Parameters Settings
Alarm Parameters
DI Dry Contact Para.
DIN1 Alm. Cond.
Close
Step 4 Clear associations between alarms and dry contact inputs. Use DIN1 as an example. Table 5-10 Clearing associations between alarms and dry contact inputs Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Setting
Parameters Settings
Alarm Parameters
Clear DI Asso.
Clear DIN1 Asso.
Yes
----End
5.1.6 Setting Rectifier Addresses Context You can set rectifier addresses only on the LCD and only to the power system that does not have a hardware address. Figure 5-1 Rectifier addresses (twenty 100 A rectifiers are used in the example)
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
62
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
Parameters Table 5-11 Rectifier address parameter description Parameter
Description
Default Value
Value Range
Rect. Address Settings
Select Yes when you need to manually set rectifier addresses.
No
Set each rectifier address manually.
–
N. Rectifier Address
Yes No
1~60
LCD Operations Step 1 Set Rect. Address Settings to Yes. Path: Main Menu > Setting Wizard > Rect. Address Settings Step 2 Press
to choose 1. Rectifier Address.
Step 3 Observe the indicators on rectifiers. If the power indicator (green) on a rectifier blinks at 0.5 Hz, the rectifier is selected. Set the rectifier address to the value shown in Figure 5-1 based on the rectifier position. Step 4 Set the addresses for all rectifiers in the cabinet one by one. Step 5 Press
to choose Save Settings. Press
to save the settings.
----End
5.1.7 Setting Basic DG Parameters Procedure Step 1 Set Genset and fuel tank number. Table 5-12 Setting Genset and fuel tank number Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Default Value
Value Range
Parameters Settings
Setup Parameters
Basic Parameters
Genset Qty
0
0-2
Tank Qty
1
0-4
Step 2 Set basic Genset parameters.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
63
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
Table 5-13 Setting basic Genset parameters Main Menu
Second-Le vel Menu
Third-Level Menu
Fourth-Level Menu
Default Value
Value Range
Parameters Settings
Genset
Genset n
Rated Power
12.5 kW
1 to 5000 NOTE Rated output power of a single DG.
Other Device Config
Fuel Tank n
Run Hour for Maint
9999h
0 to 10000
Days for Maint
500h
0 to 30000
Tank Type
Cuboid
Horizontal Cylinder, Vertical Cylinder, Irregular, Cuboid
Tank Length
1.50 m
0.50 to 20.00 NOTE This parameter is displayed only when Tank Type is set to Horizontal Cylinder.
Cyl Tank Diameter
1.13 m
0.00 to 4.00 NOTE This parameter is displayed only when Tank Type is set to Vertical Cylinder or Horizontal Cylinder.
Cuboid Tank Length
1.00 m
Cuboid Tank Width
1.00 m
Tank Height
1.50 m
0.00 to 10.00 NOTE This parameter is displayed only when Tank Type is set to Cuboid.
0.00 to 10.00 NOTE This parameter is displayed only when Tank Type is set to Cuboid.
0.0 to 10.0 NOTE This parameter is displayed only when Tank Type is set to Vertical Cylinder or Cuboid.
Rated Capacity
1500.00 L
0.00 to 6000.00 NOTE
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
64
SMU02C V500R003C10 Site Monitoring Unit User Manual
Main Menu
Second-Le vel Menu
Third-Level Menu
5 Common Tasks
Fourth-Level Menu
Default Value
Value Range This parameter is displayed only when Tank Type is set to Irregular.
Under Fuel Level
15.0%
0.0 to 50.0
Refuel Level
20.0%
0.0 to 50.0
Abnor Change Thres
3.0 cm
1.0 to 1000.0
Abnor Change Dur
10.0 Min
1.0 to 60.0
Level Filter Time
30 Min
1 to 1440
Calibration Num
10
1 to 100 NOTE This parameter is displayed only when Tank Type is set to Irregular.
Height H n
0.00 cm
0.00 to 200.00
NOTE Set this parameter to H0. Set other parameters based on site requirements.
NOTE This parameter is displayed only when Tank Type is set to Irregular.
0.00 L
0.00 to 6000.00
NOTE Set this parameter to H0. Set other parameters based on site requirements.
NOTE This parameter is displayed only when Tank Type is set to Irregular.
Level Filter Thres
3.00 cm
0.00 to 10.00
Refuel Calc Enb
Yes
Yes, No
Volum V n
----End
5.1.8 Starting a Genset Self-Check Context
Issue 01 (2020-05-30)
There is no battery alarm on the monitoring unit, and battery power supply is normal.
Copyright © Huawei Technologies Co., Ltd.
65
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
If the mains power is used, ensure that the mains AC input circuit breaker on the ATS is OFF.
Procedure Step 1 Check and confirm the control mode is Automatic. If it is Manual, set control mode to Automatic in diesel generator. Table 5-14 Checking the DG control mode Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Setting
Running Control
Genset
Genset Group
Control Mode
Automatic
Step 2 Start a Genset self-check. Table 5-15 Starting a Genset self-check Main Menu
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Setting
Running Control
Genset
Genset Self Check
Confirm Self Check
Yes
A maximum of two DGs can be connected. The auto check process is as follows: 1. About 2 minutes after starting DG 1, the monitoring unit checks the DG running status to determine whether the DG has started. 2. About 2 minutes after shutting down DG 1, the monitoring unit checks the DG running status to determine whether the DG has shut down. 3. About 2 minutes after starting DG 2, the monitoring unit checks the DG running status to determine whether the DG has started. 4. About 2 minutes after shutting down DG 2, the monitoring unit checks the DG running status to determine whether the DG has shut down. After the auto check is complete, the SMU displays the results on the screen:
Control DG Number (0/1/2)
DG 1 Start Result (Success/Fail)
DG 1 Stop Result (Success/Fail)
DG 2 Start Result (Success/Fail)
DG 2 Stop Result (Success/Fail)
A single-DG self-check takes about 4 minutes, and a dual-DG self-check takes more than 8 minutes.
Step 3 Verify that the self-check result is consistent with the actual number of DGs and the DGs work properly. If the DG self-check fails, refer to the DG manual for troubleshooting and DG cable connection checking. ----End
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
66
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
5.1.9 Setting WiFi Parameters You can locally access the WebUI over WiFi. Table 5-16 Setting WIFI parameters Main Menu
Second-Level Menu
Third-Level Menu
Default Value
Value Range
Parameters Settings
WiFi Settings
WIFI Enable
Enable
Enable, Disable
Wifi SSID
HUAWEI_SIT E
A maximum of 31 characters, including lowercase English letters (a to z), uppercase English letters (A to Z), digits (0 to 9), and special characters (@_#-.).
Password
Changeme
A maximum of 31 characters, including lowercase English letters (a to z), uppercase English letters (A to Z), digits (0 to 9), and special characters (@_#-.). It is recommended that the password contain at least two types of characters and the length exceed eight characters.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
67
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
5.2 Common Maintenance Tasks 5.2.1 Backing Up the Current Settings The configuration file contains all user configuration information (such as parameter values and alarm configurations) about the current system. You can back up the configuration file to a local computer or a USB flash drive over the WebUI, and use the configuration file to rapidly configure parameters for other sites.
When importing the backup configuration file, ensure that the system types of the exported and imported configuration files are consistent. Figure 5-2 Backing up the current configuration
5.2.2 Importing a Configuration File You can quickly configure site parameters by importing a configuration file.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
68
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
Figure 5-3 Importing a configuration file
If an encryption password is set during the export of a configuration file, the decryption password entered during the import of the configuration file must be the same as the encryption password of the exported configuration file.
5.2.3 Restoring Factory Defaults
After factory defaults are restored, the monitoring unit restarts. After factory defaults are restored, all parameter values change to their default factory values. You are advised to back up the current settings before restoring factory defaults. Figure 5-4 Restoring factory defaults
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
69
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
5.2.4 Upgrading Software You can use the WebUI and LCD to upgrade software for the SMU BSP, SMU, intelligent device SO library package, and southbound devices.
To retain pre-upgrade parameters, back up the data before upgrading software.
The SMU will restart automatically after the software for the BSP, SMU, and intelligent device SO library package is upgraded.
Exercise caution to choose the version rollback function during software upgrade. After version rollback, the user accounts created are deleted, and the initial user name and password are required for login.
Figure 5-5 Upgrading software
5.2.5 Changing a User Password Context For security purposes, change your password periodically. Only the system administrator can change user passwords.
Changing a User Password Step 1 Log in to the WebUI and choose Maintenance > User Management. The user management page is displayed.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
70
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
Figure 5-6 User management page
Step 2 Select the user whose password needs to be changed and click Modify. The dialog box for modifying user information is displayed. Figure 5-7 Changing the password
Step 3 Select Change Password, set New Password and Confirm Password, and click Confirm. The Recertification dialog box is displayed.
The administrator needs to set Old Password only when changing the administrator's own password.
Change the password in compliance with the following rules:
The password must contain 6 to 20 characters.
The password must consist of at least two of the following types: digits, uppercase letters, lowercase letters, and special characters (! @ * - _ ? { } = /).
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
71
SMU02C V500R003C10 Site Monitoring Unit User Manual
The password must be different from the previous two passwords.
The password must be different from the user name or its reverse.
5 Common Tasks
Step 4 Set New Password of Current Login User and click Submit. ----End
Changing WiFi Password
You are advised to periodically change the WiFi password to improve account security and prevent unauthorized network attacks, such as data tampering.
Huawei will not be liable for any loss caused by your failure to change the password in time or to keep the new password properly.
The WiFi function is disabled by default. Enable the WiFi function before using it and disable it after using it to ensure network security.
Enable or disable the WiFi function: choose System Settings > Network Config > WIFI. Change the WiFi account password: choose System Settings > Network Config > WIFI.
5.2.6 Viewing Dry Contact Association Information Context
You can view the information about association between dry contact outputs and alarms.
You can also view the information about association between dry contact inputs and devices.
Procedure Step 1 View the information about association between dry contact outputs and alarms.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
72
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
Figure 5-8 Viewing the information about association between dry contact outputs and alarms
Step 2 View the information about association between dry contact inputs and devices. Figure 5-9 View the information about association between dry contact inputs and devices
----End
5.2.7 Viewing Active Alarms Active alarms are the alarms that are not cleared.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
73
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
Figure 5-10 Viewing active alarms
5.2.8 Viewing Historical Alarms Prerequisites Historical alarms refer to alarms that have generated and then been cleared manually or automatically.
Procedure Step 1 To filter out historical alarms. Figure 5-11 Filtering out historical alarms
Step 2 View historical alarms.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
74
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
Figure 5-12 Viewing historical alarms
----End
5.2.9 Viewing Version Information View the monitoring version number to facilitate fault diagnosis and check whether the upgrade is successful. Figure 5-13 Viewing Version Information
5.2.10 Exporting Maintenance Information Context
You can export historical alarms, active alarms, performance data, operation logs, and battery test records on the WebUI.
You can view and export e-label information about the power subrack, monitoring unit, and rectifiers on the WebUI.
You can export version information and system operating information in one-click mode on the WebUI to quickly collect information and identify system faults.
It takes about 5 minutes to collect fault information for each rectifier.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
75
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
Procedure Step 1 To export historical data. Figure 5-14 Exporting historical data
Step 2 To export e-label information. Figure 5-15 Exporting e-label information
Step 3 To collect rectifiers fault information. Figure 5-16 Collecting fault information
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
76
SMU02C V500R003C10 Site Monitoring Unit User Manual
5 Common Tasks
Step 4 Collect lithium battery fault information. Figure 5-17 Collect lithium battery fault information
Step 5 To export fault information. Figure 5-18 Exporting fault information
The exported fault information includes the black box information about rectifiers and lithium batteries. If information export fails due to a browser error, wait for a certain period (30 minutes at most), log in, and try again.
----End
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
77
SMU02C V500R003C10 Site Monitoring Unit User Manual
6
6 Hardware Replacement
Hardware Replacement
6.1 Replacing an SMU02C Prerequisites
An ESD wrist strap, ESD gloves, ESD box or bag, and cabinet door key are available.
The new SMU02C is intact.
Procedure Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD gloves.
Record the software version of the old SMU. If the old SMU is damaged and cannot be viewed, send the barcodes of the old SMU and the cabinet to Huawei service personnel for query.
Step 2 Disconnect the communications cable from the SMU02C panel. Step 3 Push the locking latch leftwards. Step 4 Pull the handle outwards and remove the SMU02C. Figure 6-1 Removing the SMU02C
Step 5 Remove the SD card from the side of the SMU02C.
If no SD is installed, go to Step 7.
Step 6 Insert the SD card into the new SMU02C.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
78
SMU02C V500R003C10 Site Monitoring Unit User Manual
6 Hardware Replacement
Figure 6-2 Installing the SD card
Step 7 Place the new SMU02C in the slot, push the locking latch leftwards, and pull out the handle. Step 8 Gently push the SMU02C along guide rails until it is engaged. Close the handle, and push the locking latch rightwards. Figure 6-3 Installing the SMU02C
Step 9 Reconnect the communications cable to the SMU02C panel.
After replacing the old SMU with a new spare part, power on the new SMU and check its software version. If the software version of the new SMU is earlier than that of the old SMU, upgrade the new SMU software.
Step 10 Reset SMU02C parameters. ----End
Follow-up Procedure Pack the removed component and have it sent to the local Huawei warehouse.
6.2 Replacing a WIM01C1 Prerequisites
An ESD wrist strap, ESD gloves, ESD box or bag, door key, and required tools are available.
The new WIM01C1 is intact.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
79
SMU02C V500R003C10 Site Monitoring Unit User Manual
6 Hardware Replacement
Procedure Step 1 Log in to the WebUI and record the WIM01C1 networking diagram. Step 2 Connect the ground cable of the ESD wrist strap, and wear the ESD wrist strap and ESD gloves. Step 3 Record the connection positions of cables on the WIM01C1 panel and disconnect the cables. Step 4 Loosen the screws on both sides of the WIM01C1 panel and take out the WIM01C1. Figure 6-4 Removing the WIM01C1
Step 5 Disconnect the power cables between the WIM01C1 and the UIM. Step 6 Loosen the screws that secure the WIM01C1 to the UIM and take out the WIM01C1. Step 7 Push the new WIM01C1 in place and secure it with holes aligned. Step 8 Reconnect the cables between the WIM01C1 and the UIM. Step 9 Push the UIM into the subrack. Step 10 Reconnect the cables to the new WIM01C1 panel based on the recorded information. Step 11 Disconnect the ground cable of the ESD wrist strap, and remove the ESD wrist strap and ESD gloves. Step 12 Log in to the WebUI and check that there is no alarm about the WIM01C1 and that its networking diagram is consistent with the recorded diagram. ----End
Follow-up Procedure Pack the removed component and send it to the local Huawei warehouse.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
80
SMU02C V500R003C10 Site Monitoring Unit User Manual
6 Hardware Replacement
6.3 Replacing a UIM02C Board Prerequisites
An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and required tools are available.
The new UIM02C board is intact.
Procedure Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD gloves. Step 2 Record the position of signal cables connected to the UIM02C panel, and then disconnect the signal cables. Step 3 Unscrew and take out the UIM02C. Figure 6-5 Taking out the UIM02C
Step 4 Disconnect the –48 V power cable from the UIM02C board.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
81
SMU02C V500R003C10 Site Monitoring Unit User Manual
6 Hardware Replacement
Figure 6-6 Disconnecting the –48 V power cable
(1) -48 V power port
Step 5 Record the connection positions of all cables including cables for internal and external circulation fans and flat cables on the UIM02C board, and then disconnect the cables. Step 6 Remove the UIM02C board. Figure 6-7 Removing the UIM02C board
Step 7 Take out and install the new UIM02C board. Step 8 Connect all the cables on the UIM02C board to the new UIM02C based on the recorded information. Step 9 Reconnect the –48 V power cable to the UIM02C board. Step 10 Push the UIM02C in place and tighten the screws. Step 11 Reconnect signal cables to the new UIM02C panel based on the recorded information. Step 12 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist strap and ESD gloves. ----End
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
82
SMU02C V500R003C10 Site Monitoring Unit User Manual
6 Hardware Replacement
Follow-up Procedure Pack the removed component and have it sent to the local Huawei warehouse.
6.4 Replacing a UIM02D Board The UIM02D consists of two user interface boards. This topic describes how to replace the boards.
Procedure Step 1 Record the positions where signal cables connect to the UIM02D panel, and then disconnect the signal cables. Step 2 Loosen the screws on the UIM02D panel and remove the UIM02D, as shown in Figure 6-8. Figure 6-8 Removing the UIM02D
Step 3 Disconnect the –48 V power cable from the UIM02D backplane. Figure 6-9 Disconnecting the –48 V power cable
Step 4 Disconnect the flat cable from the UIM02D backplane.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
83
SMU02C V500R003C10 Site Monitoring Unit User Manual
6 Hardware Replacement
Step 5 Remove the upper board from the UIM02D. 1.
Unscrew and remove the upper board from the UIM02D, as shown in the following figure. Figure 6-10 Removing the upper board from the UIM02D
2.
Disconnect the cables between upper and lower boards in the UIM02D.
Step 6 Remove the lower board from the UIM02D. 1.
Record the positions of signal cables and communications cables connected to the lower board, and disconnect the cables.
2.
Unscrew and remove the lower board from the UIM02D, as shown in the following figure.
Figure 6-11 Removing the lower board from the UIM02D
Step 7 Install a new lower board in the UIM02D. 1.
Issue 01 (2020-05-30)
Place a new lower board in the UIM02D, and tighten screws.
Copyright © Huawei Technologies Co., Ltd.
84
SMU02C V500R003C10 Site Monitoring Unit User Manual
2.
6 Hardware Replacement
Reconnect the removed signal cables and communications cables to the lower board based on the recorded information.
Step 8 Install a new upper board in the UIM02D. 1.
Reconnect the removed cables between upper and lower boards in the UIM02D.
2.
Place a new upper board in the UIM02D, and tighten screws.
Step 9 Reconnect the –48 V power cable and signal cables to the UIM02D panel based on the recorded information. Step 10 Push the UIM02D into the slot until its front panel aligns with the front panel of the monitoring unit, and tighten the screws. Step 11 Connect the signal cables to the original positions on the UIM02D panel. ----End
Follow-up Procedure Pack the removed component and have it sent to the local Huawei warehouse.
6.5 Replacing an UIM03D Board Prerequisites
An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and required tools are available.
The new user interface board is intact.
Procedure Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD gloves. Step 2 Note where signal cables are connected to the UIM03D panel. Record these positions and disconnect the cables. Step 3 Unscrew and remove the UIM03D. Step 4 Note where all cables are connected to the NIM02D. Record these positions and remove and the cables and NIM02D.
If no NIM02D is deployed, skip this step.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
85
SMU02C V500R003C10 Site Monitoring Unit User Manual
6 Hardware Replacement
Figure 6-12 Removing the NIM02D
Step 5 Record all cable connection positions on the user interface board and disconnect the cables. Step 6 Remove the user interface board, as shown in the following figure. Figure 6-13 Removing the UIM03D
Step 7 Take out and install the new user interface board. Step 8 Connect all the cables to the new user interface board based on the information you recorded. Step 9 Install the NIM02D and connect cables according to the information you recorded.
If no NIM02D is deployed, skip this step.
Step 10 Push the UIM03D in position and tighten the screws. Step 11 Reconnect the signal cables to the UIM03D panel based on the information you recorded.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
86
SMU02C V500R003C10 Site Monitoring Unit User Manual
6 Hardware Replacement
Step 12 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist strap and ESD gloves. ----End
Follow-up Procedure Pack the removed component and have it sent to the local Huawei warehouse.
6.6 Replacing an UIM05B1 Prerequisites
The ESD wrist strap, ESD gloves, ESD box or bag, and toolbox are available.
The new UIM05B1 is intact.
Procedure Step 1 Connect the ESD wrist strap ground cable, and wear the ESD wrist strap and ESD gloves. Step 2 Record the connection positions of cables on the UIM05B1 panel and remove the cables. Step 3 Loosen the screws on the UIM05B1 panel, pull the handle until it is engaged, and take out the UIM05B1. Figure 6-14 Removing the UIM05B1
Step 4 Install the new UIM05B1. Step 5 Install the cables based on the recorded information. ----End
Follow-up Procedure Pack the removed component and have it sent to the local Huawei warehouse.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
87
SMU02C V500R003C10 Site Monitoring Unit User Manual
6 Hardware Replacement
6.7 Replacing an NIM02D Board Prerequisites
An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and required tools are available.
The new NIM02D board is intact.
Procedure Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD gloves. Step 2 Record the connection positions of cables on the NIM02D panel and disconnect the cables. Step 3 Loosen the screws on both sides of the UIM02C panel and pull out the UIM02C. Step 4 Disconnect the power cables between the NIM02D board and the J1 port on the UIM02C. Step 5 Unscrew the NIM02D from the UIM02C board and take out the NIM02D board. Figure 6-15 Removing the NIM02D board
Step 6 Push the new NIM02D board in place and secure it with holes aligned. Step 7 Connect power cables between the power port on the NIM02D board and the J1 port on the UIM02C.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
88
SMU02C V500R003C10 Site Monitoring Unit User Manual
6 Hardware Replacement
Figure 6-16 Connecting power cables
(1) Power port on the NIM02D board
(2) J1 port on the UIM02C board
Step 8 Push the UIM02C into the subrack until its front panel is flush with that of the monitoring unit subrack and then tighten the screws. Step 9 Reconnect the cables to the new NIM02D panel based on the recorded information. Step 10 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist strap and ESD gloves. ----End
Follow-up Procedure Pack the removed component and have it sent to the local Huawei warehouse.
6.8 Replacing an NIM01C3 Prerequisites
An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and required tools are available.
The new NIM01C3 is intact.
Procedure Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD gloves.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
89
SMU02C V500R003C10 Site Monitoring Unit User Manual
6 Hardware Replacement
Step 2 Record the positions where signal cables connect to the NIM01C3 panel, and then disconnect the signal cables. Step 3 Loosen the screws on both sides of the NIM01C3 panel. Step 4 Pull the handle rightwards to remove the NIM01C3. Figure 6-17 Removing an NIM01C3
Step 5 Remove the SIM card from the SIM card slot of the NIM01C3, and insert it into the SIM card slot of the new NIM01C3. Skip this step if no SIM card is installed. Step 6 Place the new NIM01C3 at the entry to the appropriate slot in the monitoring unit subrack, and push the NIM01C3 until its front panel is flush with the front panel of the monitoring unit subrack. Step 7 Push the handle inwards until it is engaged, and then tighten the screws. Figure 6-18 Installing an NIM01C3
Step 8 Connect the signal cables to the original positions on the NIM01C3 panel. Step 9 Disconnect the ground cable for the ESD wrist strap, and remove the ESD wrist strap and ESD gloves. ----End
Follow-up Procedure Pack the removed component and have it sent to the local Huawei warehouse.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
90
SMU02C V500R003C10 Site Monitoring Unit User Manual
6 Hardware Replacement
6.9 Replacing a CIM02C Prerequisites
An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and required tools are available.
The new CIM02C is intact.
Procedure Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD gloves. Step 2 Record the connection positions of cables on the CIM02C panel and disconnect the cables. Step 3 Loosen the screws on both sides of the CIM02C panel. Step 4 Pull the handle rightwards and take out the CIM02C. Figure 6-19 Removing a CIM02C
Step 5 Place the new CIM02C at the entry to the appropriate slot in the monitoring unit subrack, and push the CIM02C until its front panel is flush with the front panel of the monitoring unit subrack. Step 6 Push the handle inwards until it is engaged, and then tighten the screws. Figure 6-20 Installing a CIM02C
Step 7 Reconnect the cables to the new CIM02C panel based on the recorded information.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
91
SMU02C V500R003C10 Site Monitoring Unit User Manual
6 Hardware Replacement
Step 8 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist strap and ESD gloves. ----End
Follow-up Procedure Pack the removed component and have it sent to the local Huawei warehouse.
6.10 Replacing a GIM01C Prerequisites
An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and required tools are available.
The new GIM01C is intact.
Procedure Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD gloves. Step 2 Record the connection positions of cables on the GIM01C panel and disconnect the cables. Step 3 Loosen the screws on both sides of the GIM01C panel. Step 4 Pull the handle rightwards and take out the GIM01C. Step 5 Place the new GIM01C at the entry to the appropriate slot in the monitoring unit subrack, and push the GIM01C until its front panel is flush with the front panel of the monitoring unit subrack. Step 6 Push the handle inwards until it is engaged, and then tighten the screws. Step 7 Reconnect the cables to the new GIM01C panel based on the recorded information. Step 8 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist strap and ESD gloves. ----End
Follow-up Procedure Pack the removed component and have it sent to the local Huawei warehouse.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
92
SMU02C V500R003C10 Site Monitoring Unit User Manual
A Parameter Lists
A
Parameter Lists
When you set parameters such as DG startup/shutdown, air conditioner startup/shutdown, LLVD/BLVD voltage, AC circuit breaker capacity, mains capacity, load connection/disconnection control, battery connection/disconnection control, HVDC/PSU/SSU/MIMO/24 V module startup/shutdown, DG capacity, and rectifier power limit on the WebUI, the site power supply may be affected.
The menu hierarchy and parameter display depend on the power supply scenario, system type, system parameter settings, and device connections.
# indicates that the parameter is displayed only when related devices are connected or related parameters are set.
A.1 LCD Menu Hierarchy Figure A-1 LCD menu hierarchy
Table A-1 LCD menu description Menu Item
Description
Active Alarm
Views active alarms in the system.
Running Information
Views the operating status of the power system, rectifiers, batteries, and other modules in the system.
Setting Wizard
Quickly sets common parameters, such as the number of battery strings, rated battery capacity, date, time, and network parameters.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
93
SMU02C V500R003C10 Site Monitoring Unit User Manual
A Parameter Lists
Menu Item
Description
Parameters Settings
Sets parameters for the power system, rectifiers, batteries, and other modules in the system.
Running Control
Manually controls the power system, rectifiers, batteries, and other modules in the system, such as switching between equalized charging and float charging, starting or shutting down rectifiers, clearing historical alarms, and restarting the SMU.
Site Maintain
Performs USB-based operations such as upgrade, export, and site setup.
User Management
Change LCD login password, user logout.
A.2 Running Information Table A-2 Running Information menu hierarchy Second-Leve l Menu
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Site Unit
Basic Information
AC Input Power
-
DC Output Power
-
Total AC Comsuption
-
Total DC Generation
-
ATS 1 State
-
NOTE This parameter is displayed only when the DG is connected.
DC Power
DC Power
DC Output Distribution
DC Output Voltage
-
Total Load Current
-
Current Supply Type
-
DC Output Voltage
-
Total Load Current
-
DC Load n Pwr. Cons
-
NOTE This parameter is displayed only when Load Shunts is set to 1, 2, 3, 4 or 5.
Shared Load Cons
-
NOTE This parameter is displayed only when Include Public Load is set to Yes.
Shared Load Curr
-
NOTE This parameter is displayed only when
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
94
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Leve l Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Include Public Load is set to Yes.
DC Load n Current
-
NOTE This parameter is displayed only when Load Shunts is set to 1, 2, 3, 4 or 5.
Load n Last Mnth Elec.
-
NOTE This parameter is displayed only when Load Shunts is set to 1, 2, 3, 4 or 5.
Load n Real-time Cur
-
NOTE This parameter is displayed only when Load Shunts is set to 1, 2, 3, 4 or 5.
Last Mth Share Cons
-
NOTE This parameter is displayed only when Include Public Load is set to Yes.
Load n Last Mnth Cons
-
NOTE This parameter is displayed only when Load Shunts is set to 1, 2, 3, 4 or 5.
Load Fuse Status
-
Load n Power
-
NOTE This parameter is displayed only when Load Shunts is set to 1, 2, 3, 4 or 5.
LLVD Number
-
Shared Load Power
-
NOTE This parameter is displayed only when Include Public Load is set to Yes.
AC Distribution
Total Load Power
-
Total Load Energy Consumption
-
Phase L1 Voltage
-
NOTE This parameter is displayed only when AC Mode is set to 3-Phase 4-Wire.
Phase L2 Voltage
-
NOTE This parameter is displayed only when AC Mode is set to 3-Phase 4-Wire.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
95
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Leve l Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Phase L3 Voltage
-
NOTE This parameter is displayed only when AC Mode is set to 3-Phase 4-Wire.
Phase L1 Current
-
NOTE This parameter is displayed only when AC Mode is set to 3-Phase 3-Wire or 3-Phase 4-Wire.
Phase L2 Current
-
NOTE This parameter is displayed only when AC Mode is set to 3-Phase 3-Wire or 3-Phase 4-Wire.
Phase L3 Current
-
NOTE This parameter is displayed only when AC Mode is set to 3-Phase 3-Wire or 3-Phase 4-Wire.
AC Voltage
-
NOTE This parameter is displayed only when AC Mode is set to 1-Phase or 2-Phase 2-Wire.
AC Current
-
NOTE This parameter is displayed only when AC Mode is set to 1-Phase or 2-Phase 2-Wire.
Line L1-L2 Voltage
-
NOTE This parameter is displayed only when AC Mode is set to 3-Phase 3-Wire.
Line L2-L3 Voltage
-
NOTE This parameter is displayed only when AC Mode is set to 3-Phase 3-Wire.
Line L3-L1 Voltage
-
NOTE This parameter is displayed only when AC Mode is set to 3-Phase 3-Wire.
Issue 01 (2020-05-30)
AC Frequency
-
Active Power
-
Total Energy Consum
-
Copyright © Huawei Technologies Co., Ltd.
96
SMU02C V500R003C10 Site Monitoring Unit User Manual
A Parameter Lists
Second-Leve l Menu
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
UIM
DO Control Status
ALM n Control Status
-
Controller
NetEco Link Mode
-
-
Rectifier
Rectifier Group
Total DC Output Current
-
Total DC Out Power
-
Total AC Input Power
-
Rectifier n
DC Outp. Term. Volt.
Rectifier Info
DC Output Current DC Out Power AC Volotage Rated Efficiency Real-time Efficiency Rectifier Temp. Cur. Limiting Status Run Status PSU Brand Hardware Version Software Version Bar Code Mains #
Mains State
-
-
Phase L1 Volt
-
-
-
-
-
-
NOTE This parameter is displayed only when AC Model is set to 3-Phase 4-Wire.
Phase L2 Volt NOTE This parameter is displayed only when AC Model is set to 3-Phase 4-Wire.
Phase L3 Volt NOTE This parameter is displayed only when AC Model is set to 3-Phase 4-Wire.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
97
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Leve l Menu
A Parameter Lists
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Phase L1 Curr
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTE This parameter is displayed only when AC Model is set to 3-Phase 3 Wire or 3-Phase 4-Wire.
Phase L2 Curr NOTE This parameter is displayed only when AC Model is set to 3-Phase 3 Wire or 3-Phase 4-Wire.
Phase L3 Curr NOTE This parameter is displayed only when AC Model is set to 3-Phase 3 Wire or 3-Phase 4-Wire.
AC Voltage NOTE This parameter is displayed only when AC Model is set to 1-Phase or 2-Phase 2-Wire.
AC Curr NOTE This parameter is displayed only when AC Model is set to 1-Phase or 2-Phase 2-Wire.
Line L1-L2 Volt NOTE This parameter is displayed only when AC Model is set to 3-Phase 3-Wire.
Line L2-L3 Volt NOTE This parameter is displayed only when AC Model is set to 3-Phase 3-Wire.
Line L3-L1 Volt NOTE This parameter is displayed only when AC Model is set to 3-Phase
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
98
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Leve l Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
AC Freq
-
-
Active Power
-
-
Phase L1 Factor
-
-
Phase L2 Factor
-
-
Phase L3 Factor
-
-
Grid Quality Grade
-
-
Total Consumption
-
-
Total Supply Time
-
-
Genset Group
Total Energy Yield
-
Genset n
Total Energy Yield
-
NOTE This parameter is displayed only when an intelligent DG is connected.
Genset State
-
Total Runtime
-
Switch Reason
-
Phase L1 Voltage
-
Phase L2 Voltage
-
Phase L3 Voltage
-
Phase L1 Current
-
Phase L2 Current
-
Phase L3 Current
-
Output Power
-
AC Frequency
-
Phase L1 Factor
-
Phase L2 Factor
-
Phase L3 Factor
-
Genset Batt Volt
-
Coolant Temp
-
Rotation Speed
-
Cabin Temp
-
Load Rate
-
3-Wire.
Genset #
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
99
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Leve l Menu
Battery
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Switch Rate
-
Oil Pressure
-
Oil Level
-
Last Maint Time
-
Hourly Fuel Consum
-
Remain Runtime
-
Genset n
Total Energy Yield
-
NOTE This parameter is displayed only when a traditional DG is connected.
Genset State
-
Total Runtime
-
Switch Reason
-
Phase L1 Voltage
-
Phase L2 Voltage
-
Phase L3 Voltage
-
Phase L1 Current
-
Phase L2 Current
-
Phase L3 Current
-
Output Power
-
AC Frequency
-
Load Rate
-
Last Maint Time
-
Hourly Fuel Consum
-
Remain Runtime
-
Battery Status
-
Total Batt. Current
-
Total Rated Cap.
-
Remaining Cap.
-
Remain Cap. Percent
-
Backup Time
-
Cur. Limiting Status
-
Test Status
-
Battery Group
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
100
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Leve l Menu
Third-Level Menu
Battery String
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Battery Temp. 1
-
Total Dis Cap.
-
Total Dis Times
-
Battery Type
-
Battery String n
Rated Capacity Middle Voltage
GPS
Battery Test Records
-
-
Backup Power Info
-
-
Longitude
-
-
Latitude
-
-
Altitude
-
-
CollectorName
-
-
-
-
-
-
Total Batt. Current
-
Battery Status
-
Battery Temp. N
-
Battery Status
-
Batt Voltage
-
Batt Current
-
Temperature
-
NOTE This parameter is displayed only when the GPS is connected.
Factory Soft Version NOTE This parameter is displayed only when the GPS is connected.
Factory Name NOTE This parameter is displayed only when the GPS is connected.
Low Cap Li-ion Batt #
Li-ion Battery Group
NOTE This parameter is displayed only when Battery Model is set to BBS 4840Z.
Li Battery #
Li Battery Group
NOTE This parameter is displayed only when Battery
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
101
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Leve l Menu
Third-Level Menu
Model is set to ESM-A, ESU-A or ESM-BX.
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Normal Comm. BMUs
-
Total Capacity
-
Remain Cap. Percent
-
Bakcup Time
-
Total Discharge Times
-
Total Dis Cap.
-
Test Status
-
NOTE This parameter is displayed only when Battery Model is set to ESU-A or ESM-A.
DTS #
DCDB #
Battery Test Records
-
-
DTS Group
-
-
DTS n
Comm Status
-
Running Mode
-
Main Battery Voltage
-
Back Battery Voltage
-
Combined Voltage
-
Power Supply Mode
-
Hardware Version
-
Software Version
-
DCDB Number
-
Total Load Number
-
Unused Load Number
-
Basic Information
Comm Status
DCDB Group
DCDB n
Input Voltage Total Load Number Unused Load Number Total Output Current Total Output Power DCDB Slot No. Load n
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
Load n Used
102
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Leve l Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu Load n Current Load n Power
Asset Info
Software Version Hardware Version
Comm. Ex. Board #
iBOX #
NIM01C3 n
iBOX Equip n
Comm State
-
Hardware Version
-
Software Version
-
COM1 Power Volt
-
COM2 Power Volt
-
DIP Switch Address
-
Hardware Version
-
Software Version
-
Communication Status
-
RF Software Version
-
NIM02D
-
-
-
Efuse Group #
EFUSE n
Basic Information
Input Voltage
Load n
Load n Used Load n Current Load n Status Load n Power Load n Consumption
Asset Info
Software Version Hardware Version EFUSE Name
Temp. Control Info.
Sensor
Temp. Control Group
Indoor Vent Temp.
-
Outdoor Amb Temp.
-
Fan Group
Fan n Speed
-
Heater Device
Control Status
-
Door Sensor #
Door Status
-
Water Sensor #
Water Status
-
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
103
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Leve l Menu
AIM n #
A Parameter Lists
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Smoke Sensor #
Smoke Sensor Status
-
Infrared Sensor #
IR Sensor Status
-
Humiture Sensor #
Ambient Temperature
-
Ambient Humidity
-
Glass Brk Snsr #
Glass Broken Status
-
Vibration Sensor #
Vibration Sensor Status
-
AC Frequency
-
-
Phase L1 Voltage
-
-
Phase L2 Voltage
-
-
Phase L3 Voltage
-
-
Phase L1 Current
-
-
Phase L2 Current
-
-
Phase L3 Current
-
-
Active Power
-
-
Total Power Factor
-
-
Phase L1 Pwr. Factor
-
-
Phase L2 Pwr. Factor
-
-
Phase L3 Pwr. Factor
-
-
Active Electricity
-
-
SoftWare Version
-
-
Hardware Version
-
-
BootLoader Version
-
-
Phase L1 Power
-
-
Phase L2 Power
-
-
Phase L3 Power
-
-
Phase L1 Reactive Power
-
-
Phase L2 Reactive Power
-
-
Phase L3 Reactive Power
-
-
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
104
SMU02C V500R003C10 Site Monitoring Unit User Manual
A Parameter Lists
Second-Leve l Menu
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
ATS #
ATS n
Running Mode
-
Power Supply Mode
-
Work Scenario
-
Software Version
-
Hardware Version
-
Wireless Public IP
-
-
Virtual Network IP
-
-
MIMO 1
12DC Output Voltage
-
12DC Output Current
-
24AC Output Voltage
-
24AC Output Current
-
Software Version
-
Hardware Version
-
FSU
MIMO Module #
Historical Alarm
-
-
-
Performance
Total AC Consumption
Total AC Consumption
-
Total DC Generation
Total DC Generation
-
Total Consumption
Total Consumption
-
Acid Batt Dis. Cap.
Acid Batt Dis. Cap.
-
Batt Grou1 Dischg
-
-
Batt Grou2 Dischg
-
-
BackBatt3 Dis. Cap.
-
-
Solar Power Supply
-
-
Li Batt Dis. Cap.
-
-
Controller
Monitor Brd Barcode
-
PowerSubrack Barcode
-
Cabinet Barcode
-
Ext. Board Barcode
-
Rectifier n
Bar Code
-
EFUSE n
Barcode
-
ATS n
Barcode Info
-
Barcode Info NOTE Only the information about connected components is displayed.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
105
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Leve l Menu
A Parameter Lists
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
GMU n
GMU Barcode
-
AIM n
Barcode
-
Battery Group
TCB Barcode
-
Comm. Ex. Board
NIM01C3 1
Comm Ex Brd Barcode
NIM02D
Barcode Info
-
Camera #
Camera Group
Camera n
-
NOTE Applies when the serial port camera is connected.
Camera n
Software Version
-
Vendor Type
-
Port number
-
Camera #
Camera Group
Camera n
-
NOTE Applies when the IP camera is connected.
Camera n
Software Version
-
Vendor Type
-
IP Address
-
Connection Status
-
-
Signal Strength
-
-
Data Mode
-
-
IP Address
-
-
Current SIM Card
-
-
SIM Card 1 Status
-
-
SIM Card 1 IMSI
-
-
SIM Card 1 Number
-
-
SIM 1 On-day Traffic
-
-
SIM Card 2 Status
-
-
SIM Card 2 IMSI
-
-
SIM Card 2 Number
-
-
SIM 2 On-day Traffic
-
-
iRELAY 1
SIREN-S Ctrl State
-
SIREN-L Ctrl State
-
12V DC Volt State
-
Hall n Current
-
Mobile Data Info
Other Device Info
iDATA 1
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
106
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Leve l Menu
Third-Level Menu
5G Blade Power n
iACMETER
Issue 01 (2020-05-30)
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
DC Voltage
-
COM n State
-
Port n D n State
-
DI n State
-
48V DC Voltage
-
48V DC Load Current
-
48V Port Current
-
System Type
-
Software Version
-
Hardware Version
-
Phase L1 Voltage
-
Phase L2 Voltage
-
Phase L3 Voltage
-
Phase L1 Current
-
Phase L2 Current
-
Phase L3 Current
-
Power Unit n 57V Port DC Voltage
-
Power Unit n 57V Port Load Current
-
Power Frame Barcode
-
Total Consumption
-
Total Load Energy Consumption
-
Input n AC Frequency
-
Input n phase L1 V.
-
Input n phase L2 V.
-
Input n phase L3 V.
-
Ch n Ph L1 Current
-
Ch n Ph L2 Current
-
Ch n Ph L3 Current
-
Ch n Active Power
-
Ch n Power Factor
-
Copyright © Huawei Technologies Co., Ltd.
107
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Leve l Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Ch n Power Consump
-
Dry Contact n Statuse
-
WIM01C1
Current Net Standard
-
DG Comm Ex Board
Comm Status
-
Hardware Version
-
Software Version
-
Barcode Info
-
Consumption Readings
-
AC Power Consumption
-
Air Condition Runtime
-
Running State
-
Remaining Fuel
-
Fuel Level
-
Total Fuel Consump
-
Consump After Refuel
-
Total Refueling
-
Air Conditioner n
Fuel Tank
A.3 Setting Wizard Table A-3 Setting Wizard menu hierarchy Second-Level Menu
Third-Level Menu
Default Value
Value Range
Site Unit
Battery Vendor
Other
AGISSON, Coslight, Dengta, Eltek, EnerSys, Exide, LEOCH, Narada, NorthStar, Shoto, Other
Battery Model
12V VRLA
DCB-A, DCB-A1, DCB-B, DCB-Y, ESU-A, ESM-A, ESM-BX, FCB-A, FCB-B, SCB-A, SCB-A1, TCB-A, TCB-B, TCB-C, 12V VRLA, 2V VRLA, FLOOD, 6-GFM-X, 6-GFMF, Rebak-F4899T, 12TD-F, SBS-F, M12V-FT, LPF12-H, 6-GFM-F, 12NDF, Blue, Red,
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
108
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Level Menu
Third-Level Menu
A Parameter Lists
Default Value
Value Range 6-FMX, 6-XFMJ, GFM, BBS 4840Z
Mains Qty
1
0 to 2
Genset Qty
0
0 to 2
Tank Qty
1
0 to 4
Battery N Connected
Yes
Yes, No
Single-String Cap.
150 Ah
5-10000
Battery Cable Length
1m
0-100
Batt Cable CS Area
35 mm2
1-1000
Configuration Mode
Active/Standby
Active/Standby, Mutual Backup
Schedule Mode
Cycle Mode
Cycle Mode, Tradition Mode, No Control Mode
Genset n Parameters
Rated Power
12.5 kW
1.0 to 5000.0
Date and Time
Time Zone
UTC +08:00 Beijing
-
Date and Time
-
-
NTP Enable
No
Yes, No
NTP Primary IP
127.0.0.1
-
127.0.0.1
-
123
1-65535
1 Min
1-1440
NOTE This parameter is displayed only when DG Number is set to 2.
Batt Parameters
Genset Group Para.
NOTE This parameter is displayed only when NTP Enable is set to Yes.
NTP Backup IP NOTE This parameter is displayed only when NTP Enable is set to Yes.
NTP Port Nummber NOTE This parameter is displayed only when NTP Enable is set to Yes.
NTP Sync. Interval NOTE This parameter is displayed
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
109
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Level Menu
Third-Level Menu
A Parameter Lists
Default Value
Value Range
NetEco Primary IP
192.168.0.10
-
NetEco Backup IP
192.168.0.10
-
Site ID
-
-
IP Type
IPv4
IPv4, IPv6
IP Address
192.168.0.10
-
Subnet Mask
255.255.255.0
-
Default Gateway
192.168.0.1
-
IPv4 DSCP
46
0 to 63
VLAN Enable
No
Yes, No
VLAN ID
0
0 to 4094
VLAN Priority
5
0 to 7
Carrier Operator
Automatic
Automatic, Others
SIMn Acc Point Name
-
A maximum of 28 characters, including lowercase English letters (a-z), uppercase English letters (A-Z), digits (0-9), and special characters (@_#*-.).
only when NTP Enable is set to Yes.
NetEco Parameters
Network Parameters
Dial Parameters
NOTE This parameter is displayed only when Carrier Operator is set to Others.
SIMn Access Point No
*99#
NOTE This parameter is displayed only when Carrier Operator is set to Others.
SIMn User Name
3GNET
NOTE This parameter is displayed only when Carrier Operator is set to Others.
SIMn User Password
-
NOTE This parameter is displayed only when Carrier Operator is set to Others.
A maximum of 27 characters, including lowercase English letters (a-z), uppercase English letters (A-Z), digits (0-9), and special characters (@_#*-.). It is recommended that the password contain at least two types of characters and the length exceed six characters.
Rect Addr Setting
Issue 01 (2020-05-30)
Rect. Address Setting
No
Copyright © Huawei Technologies Co., Ltd.
Yes, No
110
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-Level Menu
A Parameter Lists
Third-Level Menu
Default Value
Value Range
n. Rectifire Address
-
-, 1~60
Yes
Yes
NOTE This parameter is displayed only when Rect. Address Setting is set to Yes.
Saving Settings NOTE This parameter is displayed only when Rect. Address Setting is set to Yes.
A.4 Parameters Settings Table A-4 Parameters settings menu hierarchy SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Site Unit
Basic Parameters
Site ID
-
-
-
Mains Qty
-
1
0 to 2
Genset Qty
-
0
0 to 2
Tank Qty
-
1
0 to 4
Turn-on Power Limit
-
NO
YES, NO
iMix Enabled
-
Enable
Enable, Disable
AC Voltage Mode
-
Voltage Mode
Percentage Mode, Voltage Mode
AC Phase OV Thres.
-
280 V
60 to 300
NOTE This parameter is displayed only when Genset Qty is set to 2.
DC Power n
DC Power
NOTE This parameter is displayed only when Hybrid Scenario is set to YES.
AC Distribution
NOTE This parameter is
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
111
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
-
180 V
60 to 300
-
130%
110-200
-
80%
1-90
-
280 V
60 to 600
displayed only when AC Voltage Mode is set to Voltage Mode and AC Model is 1-Phase, 2-Phase 2-Wire or 3-Phase 4-Wire.
AC Phase UV Thres. NOTE This parameter is displayed only when AC Voltage Mode is set to Voltage Mode and AC Model is 1-Phase, 2-Phase 2-Wire or 3-Phase 4-Wire.
AC Phase OV Thres. NOTE This parameter is displayed only when AC Voltage Mode is set to Percentage Mode and AC Model is 1-Phase, 2-Phase 2-Wire or 3-Phase 4-Wire.
AC Phase UV Thres. NOTE This parameter is displayed only when AC Voltage Mode is set to Percentage Mode and AC Model is 1-Phase, 2-Phase 2-Wire or 3-Phase 4-Wire.
AC Line OV
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
112
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
-
180 V
60 to 600
-
220 V
60-600
-
130%
110-200
-
80%
1-90
Thres. NOTE This parameter is displayed only when AC Voltage Mode is set to Voltage Mode and AC Model is 3-Phase 3-Wire.
AC Line UV Thres. NOTE This parameter is displayed only when AC Voltage Mode is set to Voltage Mode and AC Model is 3-Phase 3-Wire.
Rated Line Volt NOTE This parameter is displayed only when AC Voltage Mode is set to Percentage Mode and AC Model is 3-Phase 3-Wire.
AC Line OV Thres. NOTE This parameter is displayed only when AC Voltage Mode is set to Percentage Mode and AC Model is 3-Phase 3-Wire.
AC Line UV Thres. NOTE This parameter is displayed only when AC Voltage Mode is set to Percentage Mode and AC
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
113
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
Rated AC Frequency
-
50 Hz
40 to 70
Over AC Freq
-
110%
105 to 130
Uder AC Freq
-
90%
70 to 95
LLVD n Enabled
-
Enable
Enable, Disable
LLVD n Mode
-
Voltage Mode
Voltage Mode, Capacity Mode, Time Mode
-
44.0 V
36.0 to 56.0
-
51.5 V
37.0 to 58.0
-
15%
0 to 99
-
360 min
5 to 1000
Model is 3-Phase 3-Wire.
DC Output Distribution
NOTE This parameter is displayed only when LLVD n Enabled is set to Enable.
LLVD n Voltage NOTE This parameter is displayed only when LLVD n Enabled is set to Enable.
LLVD n Recon Volt NOTE This parameter is displayed only when LLVD n Enabled is set to Enable.
LLVDn Capacity NOTE This parameter is displayed only when LLVD n Mode is set to Capacity Mode.
LLVDn Time NOTE This parameter is displayed only when LLVD n Mode is set to Time Mode.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
114
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Load Shunts
-
0
0-5
LLVD PD Enb
-
Disable
Enable, Disable
LLVD PD Time
-
23:00:00
00:00:00-23:00:00
-
480 min
1 to 1439
LLVD HTD Enb
-
Disable
Enable, Disable
LLVD HTD Temp
-
65.0 degC
25.0 to 80.0
-
60 s
5 to 90
DC Over Voltage
-
58.0 V
53.0 to 60.0
DC Under Volt
-
45.0 V
36.0 to 57.0
Ultra Over Volt
-
59.0 V
53.0
Ultra Under Volt
-
44.0 V
36.0 to 57.0
DG 1 ON/OFF Control Do
-
-
ALM2
ALM1 to ALM8, None
DG 1 Auxi
-
-
None
ALM1 to ALM8,
NOTE This parameter is displayed only when LLVD PD Enb is set to Enable.
LLVD PD Duration NOTE This parameter is displayed only when LLVD PD Enb is set to Enable.
NOTE This parameter is displayed only when LLVD HTD Enb is set to Enable.
LLVD Delay Time NOTE This parameter is displayed only when LLVD Enabled is set to Enable.
UIM NOTE This paramete
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
to 60.0
115
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu r varies with the system type.
Controller
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Preheat DO
Value Range
None
DG 1 Run. Status Det.
-
-
DIN4
DIN1 to DIN6, None
DG 2 ON/OFF Control Do
-
-
ALM4
ALM1 to ALM
DG 2 Auxi Preheat DO
-
-
None
ALM1 to ALM8, None
DG 2 Run Status Det.
-
-
DIN5
DIN1 to DIN6, None
ATS 1 Run Deterction
-
-
DIN3
DIN1 to DIN6, None
ATS 2 Run Deterction
-
-
DIN6
DIN1 to DIN6, None
ATS DI Cond. AC Fail
-
-
Close
Open, Close
Dry Contact Open DG
-
-
DIN1
DIN1 to DIN6, None
Buzzer Enable
-
-
No
Yes, No
Buzzer Alm. Duration
-
-
10 min
1 to 100
IP Network Priority
-
-
High
High, Medium, Low
Inband Net Priority
-
-
Medium
High, Medium, Low
Wireless Net Priority
-
-
Low
High, Medium, Low
Run. Time Sw. Net.
-
-
60 min
1 to 1440
Traffic Fluct
-
-
50 MB/Day
0 to 10000
8, None
NOTE This parameter is displayed only when Buzzer Enable is set to Yes.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
116
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Heartbeat Duration
-
-
120s
10 to 180
IP Net. Timeout
-
-
5 min
5 to 1440
Inband Net. Timeout
-
-
5 min
5 to 1440
Wire. Net. Timeout
-
-
30 min
30 to 1440
North MS Config
-
-
Enable
Enable, Disable
Rectifier Group
Default Output Volt
-
53.5 V
48.0 to 58.0
OV Prot.Thres.
-
59.5 V
56.0 to 60.5
Sequential St. Int
-
0s
0 to 20
High Rect. Capacity
-
5%
0 to 150
Low Rect. Capacity
-
75%
0 to 150
Max. Limited Current
-
121%
10 to 121
Thres.
Rectifier
NOTE The default output voltage of rectifiers after the communication with the monitoring unit fails.
NOTE Interval for starting the rectifiers sequentially.
NOTE Percentage of the expected maximum rectifier output current to the rated rectifier output current. For example, if a power system is configured with three 50 A rectifiers, and you need an output current of 120 A, then set this parameter to 80%, which is obtained from 120 A/(50 A x 3).
WALK-IN
Issue 01 (2020-05-30)
-
No
Copyright © Huawei Technologies Co., Ltd.
Yes, No
117
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
-
8s
8 to 200
-
NO
Yes, No
Enable WALK-IN Time NOTE This parameter is displayed only when WALK-IN Enable is set to Yes.
Energy Saving
Hibernation Enable
NOTE No: Hibernation is disabled.
Hibernation Mode
-
Intelligent Mode
NOTE This parameter is displayed only when Hibernation Enable is set to Yes.
Hiber. Without Batt.
Intelligent Mode, High Efficiency Mode, Time Mode NOTE Time Mode: Rectifiers with shorter runtime take precedence for work.
-
No
NOTE This parameter is displayed only when Hibernation Enable is set to Yes.
Issue 01 (2020-05-30)
Yes: The monitoring unit hibernates rectifiers when the hibernation condition is met.
Copyright © Huawei Technologies Co., Ltd.
High Efficiency Mode: Rectifiers with higher real-time efficiency take precedence for work.
Intelligent Mode: The monitoring unit instructs rectifiers to hibernate based on the rectifier runtime and real-time efficiency.
Yes, No NOTE Indicates whether hibernation is enabled when batteries are not connected. NOTE If you enable hibernation when batteries are not connected to the power
118
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
system, the loads may experience power failures. Exercise caution when using this function.
Min. Rdnt. Coef.
-
0.20
NOTE This parameter is displayed only when Hibernation Enable is set to Yes.
Min. Working Rects.
NOTE Ratio of the minimum redundant current to the rated rectifier current. For example, if the rated rectifier current is 50 A and a redundant current of 10 A is required, set Min. Redundant Coefficient to 0.2 (10 A/50 A = 0.2).
-
2
-
55%
-
72.0 h
-
7 Day
NOTE
Issue 01 (2020-05-30)
0.5 to 168.0 NOTE All rectifiers stop hibernation if the power system experiences an exception. After the power system recovers, rectifiers attempt to hibernate again when the time specified by Hibernation Stop Duration has elapsed.
NOTE This parameter is displayed only when Hibernation Enable is set to Yes.
Circulation Period
10 to 100 NOTE Percentage of the rectifier loading capacity to the rated capacity, at which the rectifier reaches maximum efficiency.
NOTE This parameter is displayed only when Hibernation Enable is set to Yes.
Hiber. Stop Duration
1 to 100 NOTE Minimum number of working rectifiers allowed after hibernation is enabled.
NOTE This parameter is displayed only when Hibernation Enable is set to Yes.
Best Efficiency Pt.
0.05 to 1.00
Copyright © Huawei Technologies Co., Ltd.
1 to 365 NOTE Period for alternating
119
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
This parameter is displayed only when Hibernation Enable is set to Yes.
Phase Balance
hibernating rectifiers with working rectifiers. When the period expires, the monitoring unit starts all rectifiers. When the rectifiers have worked for 2 hours, the monitoring unit instructs some of them to hibernate again.
-
Disable
NOTE This parameter is displayed only when Hibernation Enable is set to Yes.
Staggerin g Elec Para
Value Range
Relative Balance, Absolute Balance, Disable NOTE If the configuration of rectifiers meets the three-phase balance requirement and intelligent rectifier hibernation is enabled in a three-phase power system, the rectifiers corresponding to the three phases try to hibernate.
Absolute Balance: The same quantity of rectifiers must correspond to any two phases.
Relative Balance: The difference in quantity between the working rectifiers corresponding to any two phases must be less than or equal to 1.
Rectifier n
PSU Brand
-
-
-, 0 to 9, a-z, A-Z
Stag Elec Enb
-
-
Disable
Enable, Disable
Battery Disc Mode
-
-
Battery Life Priority
Battery Life Priority, Staggering Priority
NOTE This parameter is displayed only when Stag Elec Enb is set to Enable.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
120
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
A Parameter Lists
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Max Disc Times Per Day
-
-
2
1 to 10
-
-
10%
5 to 50
-
-
Automatic Mode
Automatic Mode, Manual Mode
-
-
2000-01-01 00:00:00
-
-
-
2000-01-01 00:00:00
-
NOTE This parameter is displayed only when Stag Elec Enb is set to Enable.
Max Disc Cap Per Day NOTE This parameter is displayed only when Stag Elec Enb is set to Enable.
Schedule Mode NOTE This parameter is displayed only when Stag Elec Enb is set to Enable.
Star Time NOTE This parameter is displayed only when Schedule Mode is set to Manual Mode.
End Time NOTE This parameter is displayed only when Schedule Mode is set to Manual
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
121
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
-
-
Disable
Enable, Disable
-
-
48.0 V
45.0 to 53.0
-
-
60%
0 to 90
-
-
3
1 to 20
-
-
15 min
1 to 600
Mode.
Batt Abn Disable Stag NOTE This parameter is displayed only when Stag Elec Enb is set to Enable.
End Volt of Stag Elec NOTE This parameter is displayed only when Batt Abn Disable Sta is set to Enable.
End SOH of Stag Elec NOTE This parameter is displayed only when Batt Abn Disable Sta is set to Enable.
Time of Disable Stag NOTE This parameter is displayed only when Batt Abn Disable Sta is set to Enable.
Duration of Disable Stag NOTE This parameter is displayed
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
122
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Mains Peak Shave Enb
-
No
Yes, No
Cap for Peak Shave
-
200.0 kW
1.0 to 999.0
-
1000 A
1 to 10000
-
0.8
0.1 to 1.0
Rated Phase Volt
-
220 V
60 to 300
Peak Shaving SOC
-
30%
15 to 90
Peak Shaving SOC (Mix.)
-
15%
15 to 90
Power-On Hysteresis for LLVD in Peak Shaving
-
20%
10 to 85
Batt Backup Enable
-
Yes
Yes, No
Allow A/C Shutdown in Peak Shaving
-
No
Yes, No
only when Batt Abn Disable Sta is set to Enable.
AC Peak Shaving
AC Parameters
NOTE This parameter is displayed only when Mains Peak Shave Enb is set to YES.
Breaker Rated Curr NOTE This parameter is displayed only when Mains Peak Shave Enb is set to YES.
Derating Coef NOTE This parameter is displayed only when Mains Peak Shave Enb is set to YES.
Peak Shaving Para
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
123
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Mains #
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Allow LLVD n Disconnection in Peak Shaving
-
Yes
Yes, No
AC Mode
-
-
3-Phase 4-Wire
2-Phase 2-Wire, 1-Phase, 3-Phase 4-Wire, 3-Phase 3-Wire
AC Volt Mode
-
-
Voltage Mode
Voltage Mode, Percentage Mode
Main Line OV Thres.
-
-
286 V
242 to 760
-
-
176 V
2 to 342
-
-
220 V
104 to 520
NOTE This parameter is available only when AC Volt Mode is Voltage Mode and AC Model is 3-Phase 3-Wire.
Main Line UV Thres. NOTE This parameter is available only when AC Volt Mode is Voltage Mode and AC Model is 3-Phase 3-Wire.
Rated AC Line Volt NOTE This parameter is available only when AC Volt Mode is Percentage Mode and AC Model is 3-Phase
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
124
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
-
-
130%
110 to 200
-
-
80%
1 to 90
-
-
286 V
242 to 440
-
-
176V
2 to 198
3-Wire.
Main Line OV Thres. NOTE This parameter is available only when AC Volt Mode is Percentage Mode and AC Model is 3-Phase 3-Wire.
Main Line UV Thres. NOTE This parameter is available only when AC Volt Mode is Percentage Mode and AC Model is 3-Phase 3-Wire.
Main Phase OV Thres. NOTE This parameter is displayed only when AC Volt Mode is Voltage Mode and AC Model is 1 Phase, 2-Phase 2-Wire or 3-Phase 4-Wire.
Main Phase UV Thres. NOTE This parameter is displayed
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
125
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
-
-
220 V
60 to 300
-
-
130%
110 to 200
-
-
80%
1 to 90
only when AC Volt Mode is Voltage Mode and AC Model is 1 Phase, 2-Phase 2-Wire or 3-Phase 4-Wire.
Rated AC Volt NOTE This parameter is displayed only when AC Volt Mode is Percentage Mode and AC Model is 1 Phase, 2-Phase 2-Wire or 3-Phase 4-Wire.
Main Phase OV Thres. NOTE This parameter is displayed only when AC Volt Mode is Percentage Mode and AC Model is 1 Phase, 2-Phase 2-Wire or 3-Phase 4-Wire.
Main Phase UV Thres. NOTE This parameter is displayed only when AC Volt Mode is
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
126
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
AC High Freq Thres.
-
-
66Hz
40 to 70
AC Low Freq Thres.
-
-
45Hz
40 to70
Power Limit Enb
-
-
No
Yes, No
Mains Maximum Power
-
-
5000.0 kW
2.0 to 5000.0
-
-
100.0%
0.0~100.0
-
-
100.0%
10.0 to 150.0
-
-
95.0%
90.0 to 98.0
Percentage Mode and AC Model is 1 Phase, 2-Phase 2-Wire or 3-Phase 4-Wire.
NOTE This parameter is displayed only when Power Limit Enb is set to Enable.
Power Limitation Rated NOTE This parameter is displayed only when Power Limit Enb is set to Enable.
Imbalance Ratio NOTE This parameter is displayed only when Power Limit Enb is set to Enable.
PSU Conv Eff
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
127
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
UVT Point
-
-
39%
39 to 100
OVT Point
-
-
140%
100 to 159
Genset Group
DOD to Start
-
60%
5 to 90
NOTE This parameter is displayed only when Power Limit Enb is set to Enable.
Genset
NOTE The DG is started when the battery DOD reaches the value of this parameter. This ensures that the battery capacity stays above the preset DOD, thereby ensuring the battery life and backup time.
Min Chg Time
-
0 min
The voltage when batteries discharge to the DOD varies with the environment and battery conditions.
0 to 2880 NOTE Minimum DG runtime.
Max Chg Time
-
1440 min
60 to 2880 NOTE Maximum DG runtime.
On/Off Judge Time
-
4 min
3 to 30 NOTE Minimum interval between DG shutdown and startup. DG ON Judge Time is the prerequisite for DG soft-start. This avoids fast startup and shutdown within a short period, which will affect the DG service life.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
128
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
HT Start Enb
-
Disable
Enable, Disable NOTE Indicates whether to enable DG startup upon high temperature.
HT Start Temp
-
45 degC
NOTE This parameter is displayed only when HT Start Enb is set to Enable.
HT Stop Temp
NOTE The DG is started when the onsite ambient temperature exceeds the value of this parameter.
-
29 degC
NOTE This parameter is displayed only when HT Start Enb is set to Enable.
Min HT Runtime
25 to 60 NOTE The DG is shut down when the onsite ambient temperature is below the value of this parameter.
-
480 min
0 to 1440 NOTE Minimum DG runtime after the DG is started upon high temperature.
NOTE This parameter is displayed only when HT Start Enb is set to Enable.
LT Start Enb
30 to 65
-
Disable
Enable, Disable NOTE Indicates whether to enable DG startup upon low temperature.
LT Start Temp
-
5 degC
NOTE This parameter is displayed only when LT Start Enb is set to Enable.
LT Stop Temp
NOTE The DG is started when the onsite ambient temperature is below the value of this parameter.
-
20 degC
NOTE This parameter is displayed only when LT Start Enb is set to Enable.
Issue 01 (2020-05-30)
-10 to +15
Copyright © Huawei Technologies Co., Ltd.
0 to 25 NOTE The DG is shut down when the onsite ambient temperature exceeds the value of this parameter.
129
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Min. LT Runtime
-
480 min
0 to 1440 NOTE Minimum DG runtime after the DG is started upon low temperature.
NOTE This parameter is displayed only when LT Start Enb is set to Enable.
Time to Stop Enabled
-
Disable
Enable, Disable NOTE Indicates whether to enable scheduled DG startup and shutdown. To prevent the disturbance of DG operation, ensure that the DG is used after the battery is fully charged.
Stop Time
-
22:00:00
NOTE This parameter is displayed only when Time to Stop Enabled is set to Enable.
Runtime to Stop
HH:MM:SS NOTE Time for scheduled DG shutdown.
-
360 min
NOTE This parameter is displayed only when Time to Stop Enabled is set to Enable.
0 to 720 NOTE Interval between scheduled DG startup and scheduled DG shutdown. For example, if Runtime Before Timed DG Stop is 6 h and DG Off Time is 22 h, DG On Time is 16:00.
Night Mode End
Enable
Enable, Disable
Night Finish Time
16:00:00
HH:MM:SS
Night DG Start Volt.
45 V
36.0 to 51.0
1 min
1 to 5
Soft Start Time
-
NOTE This parameter is related to the DG startup time and stop time. The DG soft-start time is equal to
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
130
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
or greater than the DG startup time. You can adjust the parameter as required.
Disch Time Protect
-
Max Discharge Time
-
Disable
NOTE Indicates whether to enable discharge time protection to prevent excessive battery discharge.
1440 min
0 to 2880 NOTE The DG is started when the battery discharge time exceeds the value of this parameter.
NOTE This parameter is displayed only when Disch Tiem Protect is set to Enable.
TMDS Enabled
Enable, Disable
-
Enable
Enable, Disable NOTE Enables or disables scheduled D.G. maintenance.
TMDS Interval
-
7 Day
NOTE This parameter is displayed only when TMDS Enable is set to Enable.
TMDS Duration
1 to 30 NOTE Indicates the time interval between two adjacent times of scheduled D.G. maintenance.
-
15 min
NOTE This parameter is displayed only when TMDS Enable is set to Enable.
10 to 300 NOTE Indicates the D.G. runtime during each time of scheduled D.G. maintenance.
Start by DI Enabled
-
Enable
Enable, Disable
Preheat Enabled
-
Disable
Enable, Disable NOTE Indicates whether the low-temperature emergency power backup function is started when the preset conditions are met.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
131
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
DOD Diff for Preheat
-
10%
0 to 100 NOTE The DG preheating function is started when the battery DOD reaches the value of this parameter.
NOTE This parameter is displayed only when Preheat Enabled is set to Enable.
Preheat Temp
-
-5 degC
NOTE This parameter is displayed only when Preheat Enabled is set to Enable.
NOTE The DG preheating function is started when the temperature of water in the DG radiator falls below the value of this parameter.
RBC for LTE Enb
-
Temp for LTE
-
Disable
-5 degC
-25 to -5 NOTE The low-temperature emergency power backup function is started when the ambient temperature of the DG falls below the value of this parameter.
Start by Volt Enb
-
Voltage to Start
-
Disable
Enable, Disable NOTE Indicates whether to enable the monitoring unit to start the DG based on battery voltage.
47.5 V
NOTE This parameter is displayed only when Start by Volt Enb is set to Enable.
Issue 01 (2020-05-30)
Enable, Disable NOTE Indicates whether the low-temperature emergency power backup function is started when the preset conditions are met.
NOTE This parameter is displayed only when RBC for LTE Enb is set to Enable.
Imbalance Rate
-25 to +10
36.0 to 51.0 NOTE The DG is started when the battery voltage reaches the value of this parameter.
-
100.0%
Copyright © Huawei Technologies Co., Ltd.
10.0 to 150.0
132
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
NOTE Imbalance between the three phases of the DG.
Configuration Mode
-
Active/Standby
Active/Standby, Mutual Backup
Schedule Mode
-
Cycle Mode
Cycle Mode, Tradition Mode, No Control Mode NOTE DG startup/shutdown control logic.
No Control Mode: The DG startup or shut down is not controlled.
Tradition Mode: The DG is started when the mains power fails and is shut down when the mains power is normal.
Cycle Mode: Execute the DG startup/shutdown control logic in cyclic mode.
Backup Genset Enb
-
Disable
Enable, Disable
HBT Start Enb
-
Disable
Enable, Disable
HBT Start Temp
-
45 degC
30 to 65
-
29 degC
25 to 60
-
480 min
0 to 1440
NOTE This parameter is displayed only when HBT Start Enb is set to Enable.
HBT Stop Temp NOTE This parameter is displayed only when HBT Start Enb is set to Enable.
BMin HT Runtime NOTE
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
133
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
LBT Start Enb
-
Disable
Enable, Disable
LBT Start Temp
-
5 degC
-10 to +15
-
20 degC
0 to 25
-
480 min
0 to 1440
-
Disable
Enable, Disable
-
Disable
Enable, Disable
-
12.5 kW
1.0 to 5000.0
This parameter is displayed only when HBT Start Enb is set to Enable.
NOTE This parameter is displayed only when LBT Start Enb is set to Enable.
LBT Stop Temp NOTE This parameter is displayed only when LBT Start Enb is set to Enable.
BMin LT Runtime NOTE This parameter is displayed only when LBT Start Enb is set to Enable.
Low Load Stop Enb NOTE This parameter is displayed only when the DG expansion board of V110 or a later version is connected and the Schedule Mode is set to Cycle Mode.
Solar Enb NOTE This parameter is displayed only when the SSU is connected.
Genset n
Issue 01 (2020-05-30)
Rated Power
Copyright © Huawei Technologies Co., Ltd.
134
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu NOTE This parameter is displayed only when an intelligent DG is connected.
Issue 01 (2020-05-30)
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
NOTE Rated output power of a single DG.
Power Limit Rate
-
80.0%
0.0 to 100.0
Rated Phase Volt
-
230V
60 to 300
Rated Current
-
22A
1 to 10000
Rated Frequency
-
50Hz
45 to 65
Rated Speed
-
1500 r/min
100 to 4000
Over Voltage
-
120%
110 to 200
Under Voltage
-
80%
0 to 90
Over Freq
-
110%
96 to 150
Under Freq
-
94%
85 to 108
Volt Unbal Rate
-
10%
1 to 200
Curr Unbal Rate
-
70%
1 to 200
Batt Under Volt
-
10.0V
8.0 to 36.0
Overload Rate
-
115%
0 to 200
SC Curr Rate
-
200%
100 to 500
Run Hour for Maint
-
9999h
0 to 10000
Days for Maint
-
500h
0 to 30000
Run Hour lst Maint
-
20h
0 to 1000
Oil Under Level
-
20%
0 to 100
Press Sensor UL
-
0.0 Kpa
0.0 to 100.0
Press Sensor LL
-
-10.0 Kpa
-100.0 to 0.0
AirIn Over Pressure
-
-4.0 Kpa
-100.0 to 100.0
AC Mode
-
3Ph4Wire
Single Phase, D-live Lines, 3Ph4Wire
NOTE Load rate of the DG with optimal fuel consumption.
Copyright © Huawei Technologies Co., Ltd.
135
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Genset n NOTE This parameter is displayed only when a traditional DG is connected.
GPS
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
UV to Trip
-
87%
70 to 100
OV to Trip
-
125%
100 to 140
Manufacturer
-
-
-
Brand
-
-
-
Installation Time
-
2010-01-01
YYYY-MM-DD
Rated Power
-
12.5 kW
1.0 to 5000.0 NOTE Rated output power of a single DG.
Power Limit Rate
-
Rated Phase Volt
-
230V
60 to 300
Rated Frequency
-
50Hz
45 to 65
Over Voltage
-
120%
110 to 200
Under Voltage
-
80%
0 to 90
Over Freq
-
110%
96 to 150
Under Freq
-
94%
85 to 108
Run Hour for Maint
-
9999h
0 to 10000
Days for Maint
-
500h
0 to 30000
AC Mode
-
3Ph4Wire
Single Phase, D-live Lines, 3Ph4Wire
UV to Trip
-
87%
70 to 100
OV to Trip
-
125%
100 to 140
Manufacturer
-
-
-
Brand
-
-
-
Installation Time
-
2010-01-01
YYYY-MM-DD
Longitude
-
-
-
-
Latitude
-
-
-
-
Altitude
-
-
0m
-500 to +10000
Issue 01 (2020-05-30)
80.0%
0.0 to 100.0 NOTE Load rate of the DG with optimal fuel consumption.
Copyright © Huawei Technologies Co., Ltd.
136
SMU02C V500R003C10 Site Monitoring Unit User Manual
A Parameter Lists
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Battery
Basic Parameters
Battery N Connected
-
Yes
Yes, No
Single-String Cap.
-
150 Ah
5 to 10000
Float Charge Voltage
-
53.5 V
42.0 to 58.0
Boost Charge Voltage
-
Charge Limit Coef.
-
NOTE When temperature compensation is effective, the valid voltage range is 51.5–55.5 V.
56.4 V
NOTE Charge voltage at which lead-acid batteries are being charged in equalized mode.
0.15 C10
0.05 to 0.50 NOTE Battery charge current limit
NOTE This parameter is not displayed for the fast charge battery (FCB). The monitoring unit automatically adjusts the parameter based on the battery charging status and the ambient temperature.
Issue 01 (2020-05-30)
42.0 to 58.0
Intelligent Dormancy
-
Disable
Disable, Enable
Battery Cable Length
-
1m
0 to 100
Batt Cable CS Area
-
35 mm2
1 to 1000
SOC/SOH Calcu Scene
-
Backup Scene
Backup Scene, Cyclic Scene
Attenuation
-
0.80
0.00 to 1.00
NOTE Indicates whether to enable intelligent battery hibernation management.
Copyright © Huawei Technologies Co., Ltd.
137
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
Block Voltage
-
2V
2 V, 12 V
TC Coefficient
-
80 mV/degC
0 to 150
Coef
Temp. Comp. Para.
NOTE This parameter is: For 48 V battery string, the amplitude of the battery float charge voltage that needs to be adjusted for each change of 1°C. Set this parameter based on the actual specifications of the battery. For example, if the temperature compensation coefficient of each 2 V battery is 3.33 mV/degC and each 48 V battery string comprises 24 2 V batteries, then set this parameter to 80 mV/degC, which is calculated as follows: 3.33 x 24 = 80.
BLVD Parameters
Nominal Temperature
-
25 degC
5 to 45
TC Upper Thres.
-
45 degC
40 to 45
TC Lower Thres.
-
5 degC
0 to 25
BLVD General Discon.
-
Enable
Enable, Disable
BLVD Disconnect Mode
-
Voltage Mode
Voltage Mode, Capacity Mode, Time Mode
NOTE This default value varies in accordance with the battery performance. 35 degC is set by default for the TCBs.
NOTE This parameter is displayed only when BLVD General Discon. is set to Enable.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
138
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
BLVD LVD Voltage
-
43.2 V
36.0 to 56.0 NOTE If the battery voltage is below the value of this parameter, the BLVD route is disconnected.
NOTE This parameter is displayed only when BLVD General Discon. is set to Enable.
BLVD Con. Volt.
The value of BLVD Voltage must be lower than the value of BLVD Connection Voltage.
-
51.5 V
NOTE If the system voltage exceeds the value of this parameter, the BLVD route is connected.
NOTE This parameter is displayed only when BLVD General Discon. is set to Enable.
BLVD Low Capacity
37.0 to 58.0
The value of BLVD Connection Voltage must be higher than the value of BLVD Voltage.
-
5%
0 to 99
-
480min
5 to 1000
-
60s
3 to 90
-
Reduce DC Voltage
Reduce DC Voltage, Disable, Disconnect Battery
NOTE This parameter is displayed when BLVD Disconnect Mode is set to Capacity Mode.
BLVD Time NOTE This parameter is displayed when BLVD Disconnect Mode is set to Time Mode.
BLVD Delay Time NOTE This parameter is displayed only when BLVD General Discon. is set to Enable.
Temp. Prot. Para.
Issue 01 (2020-05-30)
Very HT Prot. Mode
Copyright © Huawei Technologies Co., Ltd.
139
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Charge Parameters
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Very HT Prot. Volt.
-
51.5V
42.0 to 53.0
HT Alarm Thres.
-
50 degC
25 to 80
Very HT Alarm Thres.
-
LT Alarm Thres.
-
-10 degC
-20 to +20
Very LT Alarm Thres.
-
-20 degC
-20 to +20
Auto. BC Enable
-
Enable
Enable, Disable
NOTE This default value varies in accordance with the battery performance. 55 degC is set by default for the TCB.
53 degC
25 to 80
NOTE This default value varies in accordance with the battery performance. 58degC is set by default for the TCB.
NOTE Indicates whether to enable automatic equalized charging.
FC-BC Cur. Coef.
-
0.05 C10
0.01 to 0.25
-
30 min
2 to 1440
NOTE This parameter is displayed only when Auto. BC Enable is set to Enable.
FC-BC Cur. Duration NOTE This parameter is displayed only when Auto. BC Enable is set to Enable.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
140
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
FC-BC Cap. Percent
-
70%
50 to 100
Timed BC Enabled
-
Enable
Enable, Disable
Timed BC Inteval
-
30 Day
1 to 365
-
9h
1 to 24
BC-FC Cur. Coef.
-
0.01 C10
0.01 to 0.25
BC-FC Cur. Duration
-
30 min
2 to 540
BC Max Duration
-
18 h
5 to 48
NOTE This parameter is displayed only when Auto. BC Enable is set to Enable.
NOTE Indicates whether to enable scheduled equalized charging.
NOTE This parameter is displayed only when Timed BC Enabled is set to Enable.
Max Timed BC Duration NOTE This parameter is displayed only when Timed BC Enabled is set to Enable.
Issue 01 (2020-05-30)
NOTE If the duration within which the battery charge current is lower than Equalized to Float Charge Current Coefficient exceeds the value of Equalized to Float Charge Current Duration, batteries automatically enter float charging.
Copyright © Huawei Technologies Co., Ltd.
NOTE If the equalized charging duration exceeds the
141
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
value of this parameter, batteries automatically enter float charging.
Mains Reco BC En.
-
AC Fail EC Duration
-
Disable
Disable, Enable NOTE Indicates whether to perform equalized charging after the AC power is restored.
10 min
0 to 30 NOTE If the AC power failure duration exceeds the value of this parameter, batteries automatically enter equalized charging after the AC power is restored.
NOTE This parameter is displayed only when Mains Recovery EC En is set to Enable.
Fast Charge Coef.
-
0.40 C10
0.25 to 0.50
Load Temp. Limit En.
-
Disable
Disable, Enable
-
Disable
Disable, Enable
AC Fail Test Enable
-
Disable
Disable, Enable
Time Test Mode
-
NOTE This parameter is displayed only in the temperature control scenario.
Batt. Temp. Limit En. NOTE This parameter is displayed only in the temperature control scenario.
Standard Test Para.
NOTE Indicates whether the standard battery test is allowed if an AC power outage occurs.
Disable
Disable, Scheduled Test, Planned Test NOTE The mode in which the monitoring unit starts an automatic test on schedule or as planned.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
142
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Sche. Test St. Time
-
21:00:00
HH:MM:SS NOTE Time when a scheduled test starts.
NOTE This parameter is displayed only when Time Test Mode is set to Scheduled Test.
Sche. Test Period
-
90 Day
NOTE Interval for starting a scheduled test.
NOTE This parameter is displayed only when Time Test Mode is set to Scheduled Test.
Annual Battery Tests
-
0
0 to 6 NOTE Number of planned tests within a year.
NOTE This parameter is displayed only when Time Test Mode is set to Planned Test.
Pre-BC Enable
2 to 999
-
Enable
Disable, Enable NOTE Indicates whether the monitoring unit allows charging batteries in equalized mode before a standard battery test starts.
Constant Cur. Test
-
Constant Test Cur.
-
Disable
NOTE Indicates whether batteries are allowed to discharge at a constant current in a standard battery test.
9999 A
Issue 01 (2020-05-30)
1 to 9999 NOTE Batteries discharge at this current in a standard battery test.
NOTE This parameter is displayed only when Constant Cur. Test is set to Enable.
Test End
Disable, Enable
-
46.0 V
Copyright © Huawei Technologies Co., Ltd.
44.2 to 53.0
143
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Voltage
Value Range
NOTE If the battery voltage is below the value of this parameter, the battery test ends.
Test End Capacity
-
Test End Time
-
20%
0 to 99 NOTE If the battery capacity is below the value of this parameter, the battery test ends.
480 min
1 to 6000 NOTE If the standard battery test duration reaches the value of this parameter, the battery test ends.
Short Test Para.
Test End Temperature
-
5degC
-5 to +15
Short Test Enable
-
Short Test Period
-
30 Day
1 to 360
-
5 min
1 to 240
NOTE If the battery temperature is lower than Test End Temperature, the battery test ends.
Disable
Disable, Enable NOTE Indicates whether to allow the monitoring unit to perform short tests automatically.
NOTE This parameter is displayed only when Short Test Enable is set to Enable.
Short Test Time NOTE This parameter is displayed only when Short Test Enable is set to Enable.
Short Test End Volt.
Issue 01 (2020-05-30)
NOTE If the test duration exceeds the value of this parameter, the monitoring unit exits from the short test.
-
45.0 V
Copyright © Huawei Technologies Co., Ltd.
44.2 to 53.0 NOTE
144
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
If the battery voltage is below the value of this parameter, the monitoring unit exits from the short test.
NOTE This parameter is displayed only when Short Test Enable is set to Enable.
Alarm Parameters
Value Range
Overcur. Alm. Thres.
-
0.25 C10
0.05 to 1.00
Low Cap. Alm. Thres.
-
30%
0 to 90
Volt Unbalance Mode
-
Percentage Mode
Percentage Mode, Voltage Mode
Volt. Imb. Thres
-
10%
5 to 30
Cur. Imb. Thres.
-
0.05 C10
0.00 to 1.00
Volt. Imb. Thres
-
2.0 V
0.1 to 3.0
Batt Incorrect Curr.
-
5.0 A
1.0 to 100.0
Batt Incorrect Time
-
5 min
1 to 60
Battery Install Time
-
2010-01-01
YYYY-MM-DD
Product Time
-
2010-01-01
YYYY-MM-DD
Volt. Detect Mode
-
Middle Point Volt.
Middle Point Volt., Cell Volt. None
NOTE This parameter is displayed only when Volt Unbalance Mode is set to Percentage Mode.
NOTE This parameter is displayed only when Volt Unbalance Mode is set to Voltage Mode.
Other Parameters
NOTE When connecting a signal cable for monitoring middle point voltages, select Middle Point Volt.. When
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
145
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
connecting a signal cable for monitoring battery voltages, select Cell Volt..
Power Backup Mode
-
Time Mode
Time Mode, Capacity Mode NOTE Specifies a mode for detecting power backup capability.
LLVD Backup Time
-
180 min
Time Mode: based on backup time.
Capacity Mode: based on backup capacity
0 to 9999 NOTE Sets the expected duration from when batteries start to supply power to when loads are disconnected.
NOTE This parameter is displayed only when Power Backup Mode is set to Time Mode.
For example, if you require that loads be powered for 200 minutes since batteries start to supply power, set this parameter to 200Min. If the actual power supply duration is shorter than the expected duration, the monitoring unit generates a Backup Warning alarm.
BLVD Backup Time
-
480 min
NOTE Sets the expected duration from when batteries start to supply power to when batteries are disconnected.
NOTE This parameter is displayed only when Power Backup Mode is set to Time Mode.
LLVD Backup
Issue 01 (2020-05-30)
0 to 9999
If the actual power supply duration is shorter than the expected duration, the monitoring unit generates a Backup Warning alarm.
-
75%
Copyright © Huawei Technologies Co., Ltd.
5 to 100
146
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
-
95%
5 to 100
Battery Cable Length
-
1m
0 to 100
Battery Cable CS Area
-
35 mm2
1 to 1000
SOC/SOH Calcu Scene
-
Backup Scene
Cyclic Scene, Backup Scene
Attenuation Coef
-
0.80
0.00 to 1.00
Block Voltage
-
2V
2, 12
Genset Qty
-
0
0 to 2
Tank Qty
-
1
1 to 4
A/C Off for Small DG
-
Disable
Disable, Enable
TCB auto-sensing
-
Yes
Yes, No
Hybrid Scenario
-
No
Yes, No
AC Supply Priority
-
Mains Supply Priority
Mains Supply Priority, DG Supply Priority
Battery Vendor
-
Other
AGISSON, Coslight, Dengta, Eltek, EnerSys, Exide,
Capacity NOTE This parameter is displayed only when Power Backup Mode is set to Capacity Mode.
BLVD Backup Capacity NOTE This parameter is displayed only when Power Backup Mode is set to Capacity Mode.
Setup Parameter
Basic Parameters
NOTE This parameter is related to the system type.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
147
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
LEOCH, Narada, NorthStar, Shoto, Other Battery Mode
-
12 V VRLA
DCB-A, DCB-A1, DCB-B, DCB-Y, ESU-A, ESM-A, ESM-BX, FCB-A, FCB-B, SCB-A, SCB-A1, TCB-A, TCB-B, TCB-C, 12V VRLA, 2V VRLA, FLOOD, 6-GFM-X, 6-GFMF, Rebak-F4899T, 12TD-F, SBS-F, M12V-FT, LPF12-H, 6-GFM-F, 12NDF, Blue, Red, 6-FMX, 6-XFMJ, GFM, BBS 4840Z NOTE This parameter is related to battery manufacturers.
Load Elec Stat Src
-
No
No, DCDB, DC Ammeter, EFUSE, Shunt
Include Public Load
-
No
Yes, No
-
1
1 to 28
NOTE This parameter is displayed only when Load Elec Stat Src is set to DCDB, DC Ammeter, EFUSE or Shunt.
Load Elec Stat Star NOTE This parameter is displayed only when Load Elec Stat Src is set to DCDB, DC Ammeter, EFUSE or Shunt.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
148
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Mobile Genset Para
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Enable Sign Verify
-
Enable
Enable, Disable
TLS 1.0
-
Disable
Enable, Disable
Report Hist. Alarms
-
Disable
Enable, Disable
Non-smart ATS Qty
-
0
0 to 2
Back Network Port Enable
-
Yes
Yes, No
Mobile DG Auto-Sense
-
Disable
Enable, Disable
Mobile DG Chg. Batt
-
Enable
Enable, Disable
-
50.0 Hz
40.0 to 70.0
-
0.5 Hz
0.1 to 5.0
AC SPD
-
Yes
Yes, No
DC SPD
-
Yes
Yes, No
Door Sensor
-
Yes
Yes, No
Water Sensor
-
No
Yes, No
Smoke Sensor
-
No
Yes, No
Ambient Temp.
-
No
Yes, No
NOTE This parameter is available only when Mobile DG Auto-Sense is Enable and Genset Qty is 0.
Read Mains Freq NOTE This parameter is displayed only when Mobile DG Auto-Sense is set to Enable.
Mains Freq Fluct Rng NOTE This parameter is displayed only when Mobile DG Auto-Sense is set to Enable.
Sensor Config
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
149
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
Ambient Humi. Sensor
-
No
Yes, No
Temp1 Sensor
-
No
Yes, No
Temp2 Sensor
-
No
Yes, No
Batt. Temp. Sensor 1
-
No
Yes, No
Batt. Temp. Sensor 2
-
No
Yes, No
Vibration Sensor
-
No
DIN1-6, No
Audible Visual Alarm
-
No
ALM1-7, No
IR sensor connected
-
No
DIN1-6, No
Glass Brk Snsr Cnnct
-
No
DIN1-6, No
Water Sensor connect
-
No
DIN1-6, No
Smoke Sensor connect
-
No
DIN1-6, No
Nonintelligent Lock
-
No
Yes, No
No
DIN1-6, No
-
No
ALM1-8, No
-
Yes
Yes, No
Sensor
Door Lock State NOTE This parameter is displayed only when Nonintelligent Lock is set to YES.
Nonintel. Lock ALM NOTE This parameter is displayed only when Nonintelligent Lock is set to YES.
DTS #
DTS Group
Issue 01 (2020-05-30)
Backup Batt Enable
Copyright © Huawei Technologies Co., Ltd.
150
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
DTSn
DCDB #
DCDB n
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
LeBatt Transfer Mode
-
Discharge apart
Discharge apart, Discharge together
LiBatt Transfer Mode
-
Active/Standby
Active/Standby, Mutual backup
DTS Transfers Limit
-
20
1 to 100
MainBatt Swit. Volt
-
43.2 V
35.0 to 56.0
BackBattN Swit. Volt
-
43.2 V
35.0 to 56.0
MainBatt UV Thres
-
46.0 V
46.0 to 57.0
MainBatt UV HY
-
1.0
1.0 to 5.0
BackBatt UV Thres
-
46.0 V
46.0 to 57.0
BackBatt UV HY
-
1.0
1.0 to 5.0
Basic Parameters
Load Setting Mode
All Branch
All Branch, Single Branch
Load Off Mode
Voltage Mode
Voltage Mode, Time Mode
Load Off Enable
Yes
Yes, No
Yes
Yes, No
No
Yes, No
Load Off Enable
NOTE This parameter is available only when Load Setting Mode is All Branch.
Load N Off Enable NOTE This parameter is available only when Load Setting Mode is Single Branch.
Load TD Enable
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
151
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
No
Yes, No
51.5 V
37.0 to 58.0
51.5 V
37.0 to 58.0
43.2 V
36.0 to 56.0
43.2 V
36.0 to 56.0
NOTE This parameter is available only when Load Setting Mode is All Branch.
Load N TD Enable NOTE This parameter is available only when Load Setting Mode is Single Branch.
Load On/Off Para.
Load On Voltage NOTE This parameter is available only when Load Setting Mode is All Branch.
Load N On Volt NOTE This parameter is available only when Load Setting Mode is Single Branch.
Load Off Voltage NOTE This parameter is available only when Load Setting Mode is All Branch.
Load N Off Volt NOTE This parameter is available only when Load Setting
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
152
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
6000 min
0 to 6000
6000 min
0 to 6000
HH:MM:SS
HH:MM:SS
HH:MM:SS
HH:MM:SS
480 min
1 to 1439
Mode is Single Branch.
Load Off Time NOTE This parameter is available only when Load Setting Mode is All Branch and Load Off Mode is Time Mode.
Load N Off Time This parameter is available only when Load Setting Mode is Single Branch and Load Off Mode is Time Mode. Load TD Time NOTE This parameter is available only when Load Setting Mode is All Branch.
Load N TD Time NOTE This parameter is available only when Load Setting Mode is Single Branch.
Load TD Duration NOTE This parameter is available only when Load Setting Mode is All
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
153
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
480 min
1 to 1439
Yes
Yes, No
Yes
Yes, No
30 A
3 to 40
30 A
3 to 40
Yes
Yes, No
Branch.
Load N TD Duration NOTE This parameter is available only when Load Setting Mode is Single Branch.
Load Overcur Thres
Load OvCur Prot En NOTE This parameter is available only when Load Setting Mode is All Branch.
Load N OvCur Prot En NOTE This parameter is available only when Load Setting Mode is Single Branch.
Load Br OC Thres. NOTE This parameter is available only when Load Setting Mode is All Branch.
Load N OC Thres. NOTE This parameter is available only when Load Setting Mode is Single Branch.
Load OvTmp Para.
Issue 01 (2020-05-30)
Load OvTmp Proc En
Copyright © Huawei Technologies Co., Ltd.
154
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
Yes
Yes, No
No
No, User 1 to User 6
No
No, User 1 to User 6
No
No, Branch 1 to Branch 6
NOTE This parameter is available only when Load Setting Mode is All Branch.
Load N OvTmp Proc En NOTE This parameter is available only when Load Setting Mode is Single Branch.
Consumption Config
Load User Config NOTE This parameter is available only when Load Setting Mode is All Branch.
Load N to User Config NOTE This parameter is available only when Load Setting Mode is Single Branch.
Load N to Branch NOTE This parameter is available only when Load Setting Mode is Single Branch.
Low Cap Li-ion Batt #
Basic Parameters
NOTE This
Issue 01 (2020-05-30)
Rated Capacity
-
40 Ah
1 to 300
Charging Voltage
-
54.0 V
53.5 to 56.5
BLVD Enable
-
Yes
Yes, No
Copyright © Huawei Technologies Co., Ltd.
155
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu paramete r is displayed only when Battery Model is set to BBS 4840Z.
Third-Level Menu
BLVD Parameters
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Battery N Connected
-
Yes
Yes, No
BLVD Mode
-
Voltage Mode
Voltage Mode, Time Mode
BLVD Time
-
480 min
5 to 1000
BLVD Capacity
-
5%
0 to 100
BLVD Voltage
-
43.2 V
35.0 to 47.8
BLVD Con. Volt.
-
51.5 V
37.0 to 53.0
HT Alarm Thres.
-
50 degC
25 to 80
LT Alarm Thres.
-
-10 degC
-35 to +20
Installation Time
-
2010-01-01
YYYY-MM-DD
Shunt Max. Volt.
-
75 mV
5 to 150
Shunt Max. Cur.
-
300 A
5 to 3000
Battery N Connected
-
No
Yes, No
Batt Atten Coef
-
0.80
0.00 to 1.00
Discharge Mode
-
Constant Volt Dischg
Auto, Constant Volt Dischg
Priority Charger
-
Enable
Enable, Disabale
iLock Enable
-
Lock Disable
Lock Enable, Lock Disable
-
Host Manage
Host Manage, Auto Manage
NOTE This parameter is displayed only when BLVD Mode is set to Time Mode.
Alarm Parameters
Other Parameters
Li Battery #
A Parameter Lists
Basic Parameters
NOTE This para meter is displ ayed only when Batte ry Mod el is set to ESM -A, ESU -A or ESM -BX.
NOTE This parameter is displayed only when the battery anti-theft function is supported.
BMU Manage Model NOTE
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
156
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Ther e are differ ences in the defau lt para meter s of the batter y when the Batte ry Mod el or Batte ry Capa city is differ ent.
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
-
72
8 to 720
Battery Group Vendor
-
-
-
BMU Quantity
-
0
0 to 32
Cycle Mode
-
Li-Ion primary
Li-Ion And Acid cycle, Li-Ion primary, Li-Ion standby
-
1.00
0.80 to 1.00
-
52.1V
42.0 to 58.0
Chg Curr Limit Coef
-
0.15 C10
0.05 to 1.00
Load Temp.Limit En.
-
Disable
Disable, Enable
This parameter is displayed only when the battery anti-theft function is supported.
iLock Verify Timeout NOTE This parameter is displayed only when the battery anti-theft function is supported.
NOTE This parameter only displayed when iMix Enabled is set to Enable.
Charge Parameters
Charge Efficiency NOTE This parameter only displayed when Hybrid Scenario is set to No.
EC Voltage NOTE This parameter only displayed when Hybrid Scenario is set to No.
NOTE This parameter is displayed only in
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
157
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
-
Disable
Disable, Enable
HT Alarm Thres.
-
50 degC
35 to 70
LT Alarm Thres.
-
0
-50 to 10
Low Cap. Alm. Thres.
-
30%
0 to 90
Image Quality
-
Excellent
Average, Fair, Good, Excellent
the temperature control scenario.
Batt. Temp.Limit En. NOTE This parameter is displayed only in the temperature control scenario.
Alarm Parameters
Camera # NOTE Applies when the serial port camera is connecte d.
Camea # NOTE Applies when the IP camera is connecte d.
iBOX
Camera Equip n
NOTE Image definition.
Image Format
-
640 x 480
160 x 120, 320 x 240, 640 x 480
Snapshot Interval
-
20s
1 to 600
Number After Alarm
-
Cabinet Name
-
-
-
Forbid Camera
-
No
Yes, No
Camera Equip n
Capture Interval
-
40s
20 to 60
Forbid Camera
-
No
Yes, No
iBOX Equip n
iBAT Number Per Cell
-
1
1 to 8
Issue 01 (2020-05-30)
NOTE Interval for taking pictures.
5 Pcs
1 to 30 NOTE Sets how many pictures taken after alarm generation will be saved.
Copyright © Huawei Technologies Co., Ltd.
158
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Efuse Group #
Third-Level Menu
EFUSE n
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
iBAT Volt. Rec. En.
-
No
No, Yes
iBAT Res. Rec. En.
-
No
No, Yes
iBAT Temp. Rec. En.
-
No
No, Yes
iBAT SOH Rec. En.
-
No
No, Yes
Basic Parameters
Load Off Mode
Voltage Mode
Time Mode, Voltage Mode
On/Off Setting
Single
All, Single
Load Overcur Setting
Single
All, Single
Load n Off Enable
Yes
Yes, No
No
Yes, No
No
Yes, No
No
Yes, No
NOTE This parameter is displayed only when On/Off Setting is Single.
Load Off Enable NOTE This parameter is displayed only when On/Off Setting is ALL.
Load n TD Enable NOTE This parameter is displayed only when On/Off Setting is Single.
Load TD Enable NOTE This parameter is displayed only when On/Off Setting
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
159
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
43.2 V
35.0 to 56.0
43.2 V
35.0 to 56.0
51.5 V
37.0 to 58.0
51.5 V
37.0 to 58.0
6000 min
0 to 6000
6000 min
0 to 6000
is ALL.
Load Off Voltage
Load n Off Volt NOTE This parameter is displayed only when On/Off Setting is Single.
Load Off Voltage NOTE This parameter is displayed only when On/Off Setting is All.
Load On Voltage
Load n On Volt NOTE This parameter is displayed only when On/Off Setting is Single.
Load On Voltage NOTE This parameter is displayed only when On/Off Setting is All.
Load Off Time NOTE This parameter is displayed only when Load Off Mode is Time Mode.
Load n Off Time NOTE This parameter is displayed only when On/Off Setting is Single.
Load Off Time NOTE This parameter is displayed only when On/Off Setting is All.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
160
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Load Time Down
Load TD Time
-
-
480 min
1 to 1439
-
-
480 min
1 to 1439
15.0 A
0.5 to 20.0
15.0 A
0.5 to 20.0
NOTE This parameter is displayed only when Load TD Enable is Yes.
NOTE This parameter is displayed only when On/Off Setting is All.
Load TD Duration NOTE This parameter is displayed only when On/Off Setting is All.
Load n TD Time NOTE This parameter is displayed only when On/Off Setting is Single.
Load n TD Duration NOTE This parameter is displayed only when On/Off Setting is Single.
Load Overcur Thres
Load n Overcur Thres NOTE This parameter is displayed only when Load Overcur. Setting is Single.
Load Overcur. Thres. NOTE This parameter is displayed only when Load Overcur.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
161
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
All Loads to User
None
None, User 1-6
Load n to User
None
Setting is All.
Consumption Config
When the actual current exceeds the 1.2 times of the load overcurrent threshold, the EFUSE automatical ly enables or disables the output. The appropriate current can be manually resumed only after the overcurrent fault is rectified.
NOTE User SNs must be consecutive; In a multi-LLVD scenario, use SNs must map to LLVD SNs.
NOTE This parameter is displayed only when Load Elec Stat Src is EFUSE.
Load n to Branch
None, User 1-6 NOTE User SNs must be consecutive.
None
None, Branch1-10
58.0 V
58.0 to 60.0
NOTE This parameter is displayed only when Load Elec Stat Src is No EFUSE.
Other Parameters
Issue 01 (2020-05-30)
Input OV Thres
Copyright © Huawei Technologies Co., Ltd.
162
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Temp. Control
Third-Level Menu
Temp. Control Group
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
Input UV Thres
42.0 V
38.0 to 45.0
Set Cabinet Name
-
-
Indoor Vent TS
-
Yes
Yes, No
Outdoor Amb. TS
-
No
Yes, No
TC Mode
-
Standard Mode
Standard mode, Mute mode
-
Disable
Enable. Disable
-
Disable
Enable. Disable
-
Disable
Enable. Disable
In_Recycle Work Temp
-
35 degC
-20 to 50
In_Recycle Stop Temp
-
30 degC
-20 to 50
Ex_Recycle Work Temp
-
35 degC
-20 to 50
Ex_Recycle Stop Temp
-
30 degC
-20 to 50
NOTE This parameter is displayed only in the temperature control scenario.
Backup Mode enable NOTE This parameter is displayed only in the temperature control scenario.
A/C Config. Mode En NOTE This parameter is displayed only in the temperature control scenario.
Low-Temp Mode Enable NOTE This parameter is displayed only in the temperature control scenario.
Fan Group
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
163
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Dr. Alm. Fan Stp. En
-
Disable
Enable. Disable
Heater Start Temp.
-
5 degC
-10 to 5
Heater Stop Temp.
-
15 degC
5 to 15
AC Rated Frequency
-
-
50
50, 60
Detected Object
-
-
AC Total Input
AC Total Input, None, AC Other Equipment, AC TC Equipment, AC Main Equipment
AC OV Thres.
-
-
280V
60~300
AC UV Thres.
-
-
180V
60~300
AC Source
-
-
Other
Other, DG, Mains
ATS Group
AC Supply Priority
-
DG Supply Priority
DG Supply Priority, Mains Supply Priority
ATS 1
Work Scenario
-
Mains+DG
Mains+DG, DG1+DG2
Mains UVT
-
39%
39 to 100
Mains OVT
-
140%
100 to 159
DG UVT
-
87%
70 to 100
DG OVT
-
125%
100 to 140
Amb. HT Thres
-
55 degC
25 to 80
Amb. LT Thres
-
-20 degC
-20 to +20
Amb. Ultra HT Thres.
-
70 degC
25 to 80
Amb. HH Thres.
-
95%
0 to 100
Amb. LH Thres.
-
5%
0 to 100
Env HT Count Point
-
55 degC
25 to 80
Env LT Count Point
-
-20 degC
-20 to +20
Heater Device
AIM n
ATS
Sensor
A Parameter Lists
Humiture Sensor #
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
164
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
MIMO Group #
Other Device Config
A Parameter Lists
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Water Sensor #
Water Alarm Cond
-
Close
Close, Open
Door Sensor #
Door Alarm Cond
-
Open
Close, Open
Smoke Sensor #
Smoke Alarm Cond
-
Close
Close, Open
Glass Brk Snsr #
Glass Brk Snsr Cond
-
Close
Close, Open
IR Sensor #
IR Sensor Cond
-
Close
Close, Open
Vibration Sensor #
Vibration Sensor Cond
-
Close
Close, Open
12DC Out. Volt.
-
-
12.0 V
12.0 to 13.2
24AC Out. Volt.
-
-
24.0 V
24.0 to 26.3
iRELAY 1
Blink Duration
-
30s
5 to 120
RF-A Max Tran. P.
-
8 dBm
0 to 15
Duration to Connect
-
720 min
1 to 1440
iFUEL-RS48 5
-
-
-
-
iDATA n
Blink Duration
-
30s
5 to 120
DI n Alm. Cond.
-
Closed
Open, Closed
PORT n – DI n Alm Cond
-
Closed
Open, Closed
Node A Max Power
-
8 dBm
0 to 15
Node B Max Power
-
6 dBm
0 to 15
Port n Config
-
DI_MODE
DI_MODE, IR _MODE, Smoke_MODE, Voltage_MODE, NTC_MODE
I/O n Config
-
INPUT_MODE
INPUT_MODE, OUTPUT_MODE
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
165
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
DO n Alarm Action
-
Closed
Opened, Closed
Hall n Type
-
100A
100A, 200A
PORT n-NTC
-
TF820E10J
TF820E10J, NTSA0103FZD19A
48V Side DC Input Type
-
DC Power
DC Power, Li Batt, Normal Lead Acid
AC Mode
-
Three Phases
Single Phase, D-Live Lines
Dynamic Adjust Voltage Enabled
-
Disable
Enable, Disable
AC Overvolt. Thres.
-
280 V
60-305
AC Undervolt. Thres.
-
180 V
60-305
48V DC Overvolt. Thres.
-
58.0 V
53.0-60.0
48V DC Undervolt. Thres.
-
45.0 V
36.0-57.0
47V DC Overvolt. Thres.
-
73.0 V
58.0-75.0
47V DC Undervolt. Thres.
-
53.0 V
50.0~59.0
Time Set
-
2000-01-01 00:00:00
-
LLVD n Enabled
-
Enable
Enable, Disable
LLVD n Mode
-
Voltage Mode
Voltage Mode, Time
NOTE This parameter is displayed only when I/O n Config is set to OUTPUT_MO DE.
NOTE This parameter is displayed only when PORT is set to NTC.
5G Blade Power n
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
166
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Voltage
NOTE This parameter is displayed only when LLVD n Enabled is set to Enable.
LLVD n Voltage
Value Range
-
44.0 V
36.0~56.0
-
51.5V
37.0~58.0
48V Disconnect Voltage
-
45.0 V
35.0~56.0
48V Port Set Volt
-
53.5 V
48.0~55.0
AC Peak Shaving Enabled
-
Disable
Enable, Disable
AC Capacity
-
1000 kW
1-10000
-
1000 A
1-10000
-
0.8
0.1-1.0
NOTE This parameter is displayed only when LLVD n Enabled is set to Enable.
LLVD n Recon Volt NOTE This parameter is displayed only when LLVD n Enabled is set to Enable.
NOTE This parameter is displayed only when AC Peak Shaving Enabled is set to Enable.
Breaker Rated Curr NOTE This parameter is displayed only when AC Peak Shaving Enabled is set to Enable.
Derating Coef NOTE This parameter is
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
167
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
-
220 V
60-300
Power Unit n Output Voltage
-
57.0 V
57.0-60.0
Duration to Connect
-
720 min
1 to 1440
RF-A Max Tran. P
-
8 dBm
0 to 15
RF-B Max Tran. P
-
6 dBm
0 to 15
WAN Port Settings
-
No
No, GE 2, GE 1
Mains Detect Enable
-
Disable
Enable, Disable
Fuel Level UL
-
300.0 cm
0.0 to 1000.0
Fuel Level LL
-
0.0 cm
0.0 to 1000.0
AI 1 Insert Sensor
-
Tank 1 Oil Level
None, Tank 1 Oil Level, Tank 2 Oil Level, Dg1 AirIn Press, Dg2 AirIn Press
AI 2 Insert Sensor
-
Tank 2 Oil Level
None, Tank 1 Oil Level, Tank 2 Oil Level, Dg1 AirIn Press, Dg2 AirIn Press
Fuel Level UL AI1
-
300.0 cm
0.0-1000.0
Fuel Level LL AI1
-
0.0 cm
0.0-1000.0
Fuel Level UL AI2
-
300.0 cm
0.0-1000.0
displayed only when AC Peak Shaving Enabled is set to Enable.
Rated Phase Volt NOTE This parameter is displayed only when AC Peak Shaving Enabled is set to Enable.
WIM n
DG Controller n
DG Comm Ex Board
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
168
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fuel Tank n
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Fuel Level LL AI2
-
0.0 cm
0.0-1000.0
Tank Type
-
Cuboid
Horizontal Cylinder, Vertical Cylinder, Irregular, Cuboid
Tank Length
-
1.50 m
0.50 to 20.00 NOTE This parameter is displayed only when Tank Type is set to Horizontal Cylinder.
Cyl Tank Diameter
-
Cuboid Tank Lenght
-
Cuboid Tank Width
-
Tank Height
-
1.13 m
0.00 to 4.00 NOTE This parameter is displayed only when Tank Type is set to Vertical Cylinder or Horizontal Cylinder.
1.00 m
0.00 to 10.00 NOTE This parameter is displayed only when Tank Type is set to Cuboid.
1.00 m
0.00 to 10.00 NOTE This parameter is displayed only when Tank Type is set to Cuboid.
1.50 m
0.0 to 10.0 NOTE This parameter is displayed only when Tank Type is set to Vertical Cylinder or Cuboid.
Rated Capacity
-
1500.00 L
0.00 to 6000.00 NOTE This parameter is displayed only when Tank Type is set to Irregular.
Under Fuel Level
Issue 01 (2020-05-30)
-
15.0%
Copyright © Huawei Technologies Co., Ltd.
0.0 to 50.0
169
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Refuel Level
-
20.0%
0.0 to 50.0
Abnor Change Thres
-
3.0 cm
1.0 to 1000.0
Abnor Change Dur
-
10.0 min
1.0 to 60.0
Level Filter Time
-
30 min
1 to 1440
Calibration Num
-
10
1 to 100 NOTE This parameter is displayed only when Tank Type is set to Irregular.
Height H n
Volum V n
EPS-D Interface Brd n
Issue 01 (2020-05-30)
-
-
0.00 cm
0.00 to 200.00
NOTE Set this parameter to H0. Set other parameters based on site requirements.
NOTE This parameter is displayed only when Tank Type is set to Irregular.
0.00 L
0.00 to 6000.00
NOTE Set this parameter to H0. Set other parameters based on site requirements.
NOTE This parameter is displayed only when Tank Type is set to Irregular.
Level Filter Thres
-
3.00 cm
0.00 to 10.00
Refuel Calc Enb
-
Yes
Yes, No
Fuel Sensor Type
-
Current type
Current type, Smart Type, Resistance type
Oil Pump Runtime
-
4s
1 to 8
OilClean Period
-
2h
1 to 50
Auto Add Oil
-
Yes
Yes, No
Fuel Level UL
-
25.7 cm
0.0 to 1000.0
Fuel Level LL
-
2.7 cm
0.0 to 200.0
Fuel Tank Capacity
-
300.0 L
0.0 to 600.0
Copyright © Huawei Technologies Co., Ltd.
170
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Alarm Parameter s
Third-Level Menu
DI Dry Contact Para.
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Tank CSA
-
1.20 m2
0.00 to 10.00
Heater Alarm Asso.
-
DIN5
DIN1-6, None
-
None
None, Heater Fault
-
None
None, LLVD Forcibly Connection, TCUA Alarm, TEC Alarm
NOTE This parameter varies with the system type.
DIN5 Reuse NOTE This parameter varies with the system type.
DIN6 Reuse NOTE This parameter varies with the system type.
DO Dry Contact Para.
ALM n Alarm Action
-
Close
Close, Open
Alarm Config
Site Unit
-
-
-
UIM
-
-
-
Controller
-
-
-
Door Sensor
-
-
-
Smoke Sensor
-
-
-
Other Virtual Equip
-
-
-
Rectifier
-
-
-
Rectifier Group
-
-
-
Battery Group
-
-
-
Battery String
-
-
-
Temp. Control Group
-
-
-
Fan Group
-
-
-
Heater Device
-
-
-
Comm. Ex. Board Group
-
-
-
Comm. Ex.
-
-
-
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
171
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
Mains
-
-
-
Genset Summary
-
-
-
Genset
-
-
-
EFUSE
-
-
-
EFuse Group
-
-
-
AIM
-
-
-
ATS Group
-
-
-
ATS
-
-
-
GPS
-
-
-
Nonintelligent Lock
-
-
-
DG
-
-
-
5G Blade Power
-
-
-
5G Blade Power Group
-
-
-
DG Comm Ex Board
-
-
-
AC Distribution
-
-
-
DC Output Distribution
-
-
-
DC Power
-
-
-
Fuel Tank
-
-
-
SIEE Data
-
-
-
Cri. Alm. Asso. DO
-
No
No, ALM1-ALM8
Major Alm. Asso. DO
-
No
No, ALM1-ALM8
Minor Alm. Asso. DO
-
No
No, ALM1-ALM8
Warn. Alm. Asso. DO
-
No
No, ALM1-ALM8
Board
Controller
Alarm Level DO Para.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
172
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Comm. Parameter s
A Parameter Lists
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Clear ALM Asso.
Clear ALM n Asso.
-
Yes
Yes
Clear DI Asso.
Clear DIN n Asso.
-
Yes
Yes
Network Parameters
IP Type
-
IPv4
IPv4, IPv6
IP Address
-
192.168.0.10
-
Subnet Mask
-
255.255.255.0
-
Default Gateway
-
192.168.0.1
-
IPv4 DSCP
-
46
0 to 63
VLAN Enable
-
No
Yes, No
VLAN ID
-
0
0 to 4094
VLAN Priority
-
5
0 to 7
NetEco Primary IP
-
192.168.0.10
-
NetEco Backup IP
-
192.168.0.10
-
NetEco Port Number
-
31220
1 to 65535
FAE Tel Number 1
-
-
:, _, 0 to 9, a to z, A to Z
FAE Tel Number 2
-
-
:, _, 0 to 9, a to z, A to Z
FAE Tel Number 3
-
-
:, _, 0 to 9, a to z, A to Z
FAE Tel Number 4
-
-
:, _, 0 to 9, a to z, A to Z
FAE Tel Number 5
-
-
:, _, 0 to 9, a to z, A to Z
Northbound
Port Mode
Manual
Manual, Automatic
Protocol Type
Modbus Protocol
M/S Protocol, YDN1363 Protocol, Modbus Protocol
Serial Port
NOTE This parameter is displayed only when Port Mode is set to Manual.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
173
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
A Parameter Lists
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
YDN1363 Protocol
Baud Rate
-
9600
1200, 2400, 4800, 14400, 115200, 9600, 19200
Comm. Address
-
1
1 to 254
Baud Rate
-
9600
1200, 2400, 4800, 14400, 115200, 9600, 19200
Comm. Address
-
33
0 to 254
Baud Rate
-
9600
1200, 2400, 4800, 14400,115200,9600,19 200
Comm. Address
-
3
0 to 31
Carrier Operator
-
Automatic
Automatic, Others
SIMn Acc Point Name
-
-
A maximum of 28 characters, including lowercase English letters (a to z), uppercase English letters (A to Z), digits (0 to 9), and special characters (@_#*-.).
-
-
-
-
-
-
Modbus Protocol
M/S Protocol
Mobile Data
NOTE This parameter is displayed only when Carrier Operator is set to Others.
SIMn Access Point No NOTE This parameter is displayed only when Carrier Operator is set to Others.
SIMn User Name NOTE This parameter is displayed only when Carrier Operator is set to Others.
SIMn User Password NOTE This parameter is displayed only when Carrier Operator is set
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
A maximum of 27 characters, including lowercase English letters (a to z), uppercase English letters (A to Z), digits (0 to 9), and special
174
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
to Others.
Value Range
characters (@_#-.). It is recommended that the password contain at least two types of characters and the length exceed six characters.
WiFi Settings NOTE This paramete r is displayed only when the WIFI is connecte d.
WIFI Enable
-
-
Enable
Enable, Disable
Wifi SSID
-
-
HUAWEI_SITE
A maximum of 31 characters, including lowercase English letters (a to z), uppercase English letters (A to Z), digits (0 to 9), and special characters (@_#-.).
Password
-
-
Changeme
A maximum of 31 characters, including lowercase English letters (a to z), uppercase English letters (A to Z), digits (0 to 9), and special characters (@_#-.). It is recommended that the password contain at least two types of characters and the length exceed eight characters.
Local Parameter s
Language
-
-
English
English, Chinese, Russian, Spanish, Portuguese, French, Italian, German, Turkish, Japanese
Site ID
Site ID
-
-
-
System Type
-
-
-
-
Date and Time
Time Zone
-
UTC +08:00 Beijing
Time zones of all the major cities in the world. For details, see the WebUI.
Date and Time
-
-
-
NTP Enable
-
No
Yes, No
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
175
SMU02C V500R003C10 Site Monitoring Unit User Manual
SecondLevel Menu
Third-Level Menu
Fourth-Level Menu
A Parameter Lists
Fifth-Level Menu
Default Value
Value Range
127.0.0.1
-
-
127.0.0.1
-
-
123
1 to 65535
-
1 min
1 to 1440
NTP Primary IP NOTE This parameter is displayed only when NTP Enable is set to YES.
NTP Backup IP NOTE This parameter is displayed only when NTP Enable is set to YES.
NTP Port Number NOTE This parameter is displayed only when NTP Enable is set to YES.
NTP Sync. Tnterval NOTE This parameter is displayed only when NTP Enable is set to YES.
LCD Contrast
Contrast
-
5
0 to 10
Reset Web Password
-
-
-
-
-
-
Yes
Yes
NOTE Only displayed when logged in as an administrator.
Restore Settings
Restore Factory Set.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
176
SMU02C V500R003C10 Site Monitoring Unit User Manual
A Parameter Lists
A.5 Running Control Table A-5 Running Control menu hierarchy Second-L evel Menu
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Site Unit
-
-
-
-
-
DC Power
DC Power
Control Mode
-
Automatic
Automatic, Manual, Maintenance
DC Output Distribution
-
-
-
-
Block Alarm
-
-
No
Yes, No
Reset SMU
-
-
Yes
Yes
Switch to IP Net.
-
-
Yes
Yes
Sw. to WirelssNet.
-
-
Yes
Yes
-
-
Yes
Yes
Upload Sensor Logs
-
-
Stop
Start, Stop
Rectifier Group
OV Lock Reset
-
Yes
Yes
Collect Fault Info
-
Yes
Yes
Rectifier n
-
-
-
-
Delete Mains
-
-
Yes
Yes
Controller
NOTE This parameter is displayed only when the Comm Exp Board is connected.
Sw. to Inband Net. NOTE This parameter is displayed only when the BBU is connected.
Rectifier
NOTE This parameter is displayed only when the rectifier type is a CAN communications module.
Mains
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
177
SMU02C V500R003C10 Site Monitoring Unit User Manual
A Parameter Lists
Second-L evel Menu
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Genset
Genset Group
Control Mode
-
Automatic
Automatic, Manual
Genset n
Fault Reset
-
Yes
Yes
Maint Confirm
-
Yes
Yes
Genset Self Check
Confirm Self Check
-
Yes
Yes
BC Control
-
-
Stop
Stop, Start
Reset Batt. Capacity
-
-
Yes
Yes
Battery Standard Tes
-
-
Stop
Stop, Start
Short Test Control
-
-
Stop
Stop, Start
Clear Test Log
-
-
Yes
Yes
Fast Charge Control
-
-
Stop
Stop, Start
Clear Backup Log
-
-
Yes
Yes
Clear Battery Alarm
-
-
All
All, Current Imb., Test Cancelled, Lost,
Battery
BC Protection, Imbalance Comm Exp Board
NIM01C #
Module Reset
-
Yes
Yes
NIM01C3 #
Module Reset
-
Yes
Yes
iBOX #
iBOX Equip n
Del. Com. Fail Dev
-
Yes
Yes
-
Yes
Yes
NOTE This parameter appears only if a communications failure iBOXalarm is generated.
GPS
Del Com. Fail GPS
-
NOTE This parameter is displayed only when the GPS fails to communicate.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
178
SMU02C V500R003C10 Site Monitoring Unit User Manual
A Parameter Lists
Second-L evel Menu
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
DTS #
DTS Group
DTS Control
-
Auto
Auto, To Battery Group1-4
-
Yes
Yes
NOTE This parameter is displayed only when Batt Transfer Mode is set to Discharge Apart or Discharge together .
Del Com. Fail DTS NOTE This parameter appears only if a communications failure alarm is generated.
DCDB #
DTSn
Reset
-
Reset
Reset
DCDB Group
Delete Com Fail DCDB
-
Yes
Yes
-
Yes
Yes
DCDB Reset
-
Yes
Yes
Basic Control
Reset
Yes
Yes
Load Consum Clr Ctl
All Load Consum Clr
Yes
Yes
Load n Consum Clear
Yes
Yes
NOTE This parameter appears only if a communications failure alarm is generated.
Clear DCDB Loss Alm. NOTE This parameter appears only if a DCDB loss alarm is generated.
DCDBn
Camera
Camera Group
-
-
-
-
Low Cap Li-ion Batt
-
-
-
-
-
NOTE This
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
179
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-L evel Menu
A Parameter Lists
Third-Level Menu
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Li Battery Group
Battery Standard Test
-
Stop
Start, Stop
Clear Test Log
-
Yes
Yes
Delete BMU
-
Yes
Yes
-
Yes
Yes
parameter is displayed only when Battery Model is set to BBS 4840Z.
Li Battery # NOTE This parameter is displayed only when Battery Model is set to ESM-A, ESU-A or ESM-BX.
NOTE This parameter appears only if a communications failure alarm is generated.
Clear BMU Loss Alm. NOTE This parameter appears only if an ESMU loss alarm is generated.
AIM n
Board Reset
-
-
Yes
Yes
Nonintellig ent Lock
DO Open Door
-
-
Yes
Yes
Rset Illg DrOpen Alm
-
-
Yes
Yes
ATS
ATS Group
-
-
-
-
ATS n
-
-
-
-
Efuse Group
Clear EFUSE #
-
Yes
Yes
Efuse Group #
Temp. Control
NOTE This parameter is displayed only when the EFUSE fails to communicate.
EFUSE n
-
-
-
-
Fan Group
Fan Control Mode
-
Automatic
Manual, Automatic
Heater Device
Control Mode
-
Automatic
Manual, Automatic
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
180
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-L evel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
Heater Control
-
Off
On. Off
NOTE This parameter is displayed only when Control Mode is set to Manual.
Sensor
Smoke Sensor #
Reset Smoke Sensor
-
Yes
Yes
MIMO Module
MIMO Group
Turn On/Off
-
Module On
Module On, Turn Off
Clear Mod Loss Alarm
-
Yes
Yes
-
Yes
Yes
Turn On/Off
-
On
On, Off
24V AC Output Control
-
On
On, Off
12V DC Output Control
-
On
On, Off
NOTE This parameter is displayed only when there is an MIMO Lost alarm.
Clr Comm. Fail Equip NOTE This parameter is displayed only when the MIMO fails to communicate.
MIMO n
Clear Alarm
Historical Alarm
Delete His. Alarms
-
Yes
Yes
Active Alarm
-
-
Clear Alarm
Clear Alarm
Clear Batt. Test Log
Clear Test Log
-
-
Yes
Yes
Output Relay Test
Test Enable
-
-
No
No, Yes
Test Duration
-
-
1 min
1-15
-
-
Open
Open, Close
NOTE This parameter is displayed only when Test Enable is set to Yes.
ALMn
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
181
SMU02C V500R003C10 Site Monitoring Unit User Manual
Second-L evel Menu
Third-Level Menu
A Parameter Lists
Fourth-Level Menu
Fifth-Level Menu
Default Value
Value Range
NOTE This parameter is displayed only when Test Enable is set to Yes.
Hiber. Test Para.
Rect. Hiber. Speedup
-
-
-
-
Other Device Control
iRELAY
Ctrl to connect Nodes
-
Stop
Star, Stop
Single Board Reset
-
Yes
Yes
Blink Control
-
Star
Star, Stop
SIREN-S Ctrl
-
Opened
Opened, Closed
SIRNE-L Ctrl
-
Opened
Opened, Closed
iFUEL-RS485 1
-
-
-
-
iDATA
Board Reset
-
Yes
Yes
Blink Ctr.
-
Star
Star, Stop
Board Reset
-
Yes
Yes
Sensor Blink
-
Star
Star, Stop
Auto Adjust Sequence
-
Yes
Yes
Ctrl to connect Nodes
-
Star
Star, Stop
Board Reset
-
Yes
Yes
WiFi Switch
-
Off
On, Off
DG Comm Ex Board
-
-
-
-
5G Blade Power
Del Comm Failed Eq
-
Yes
Yes
iACMETER
WIM01C1
A.6 Site Maintain Table A-6 Site Maintain menu hierarchy Second-Level Menu
Issue 01 (2020-05-30)
Third-Level Menu
Fourth-Level Menu
Default Value
Copyright © Huawei Technologies Co., Ltd.
Value Range
182
SMU02C V500R003C10 Site Monitoring Unit User Manual
A Parameter Lists
Second-Level Menu
Third-Level Menu
Fourth-Level Menu
Default Value
Value Range
U Disk Upgrade/Cfg
-
-
-
-
U Disk Hist Record
Last Export Result
-
-
-
Upgrade/Cfg Result
-
-
-
Export File to USB
-
-
-
-
Genset Self Check
Confirm Self Check
-
Yes
Yes
Module Check
Check Result
Comm OK Equip Num
-
-
Comm Fail Equip Num
-
-
Normal Equip List
-
-
-
Abnormal Equip List
-
-
-
A.7 User Management Table A-7 User Management menu hierarchy Second-Level Menu
Default Value
Range
Change Password
-
0-9, a-z, A-Z
User Logout
Yes
Yes
NOTE Log out the current user.
This parameter is displayed only when you log in as an administrator or engineer.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
183
SMU02C V500R003C10 Site Monitoring Unit User Manual
B
B Technical Specifications
Technical Specifications
Table B-1 SMU02C technical specifications Category
Item
Specifications
Environmental conditions
Operating temperature
–40°C to +70°C
Transportation temperature
–40°C to +70°C
Storage temperature
–40°C to +70°C
Operating humidity
5%–95% RH (non-condensing)
Storage humidity
5%–95% RH (non-condensing)
Altitude
0–4000 m When the altitude ranges from 3000 m to 4000 m, the operating temperature decreases by 1ºC for each additional 200 m.
Power supply
Structure
Input voltage range
36–72 V DC
Maximum current
0.5 A DC
Dimensions (H x W x D)
40.8 mm x 99 mm x 194.3 mm
Weight
≤ 1.5 kg
MTBF (mean time between failures)
Issue 01 (2020-05-30)
≥ 250,000 hours
Copyright © Huawei Technologies Co., Ltd.
184
SMU02C V500R003C10 Site Monitoring Unit User Manual
C FAQ
C
FAQ
C.1 How Do I Prepare the WebUI Operating Environment? Before logging in to the WebUI, you need to prepare the WebUI operating environment to connect to the monitoring unit.
Operating Environment Supported operating system: Windows 10 or later Browser: Internet Explorer 8.0 or later, FireFox 13 or later, and Chrome 20
Internet Explorer is used as an example to illustrate all WebUI operations mentioned in this document.
Setting a LAN
If the monitoring unit is connected to a LAN and a proxy server has been selected, cancel the proxy server settings. If the monitoring unit is connected to the Internet but your computer is connected to a LAN, do not cancel the proxy server settings. Otherwise, you cannot access the SMU. To cancel proxy server settings, perform the following steps: 1.
Open Internet Explorer.
2.
Choose Tools > Internet Options.
3.
Choose Connections tab, click LAN Settings.
4.
Clear Use a proxy server for your LAN.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
185
SMU02C V500R003C10 Site Monitoring Unit User Manual
C FAQ
Figure C-1 Canceling proxy server settings
5.
Click OK.
Setting Internet Explorer Security
Set Internet Explorer security before you perform the following operations:
Export historical logs, historical data, statistics, and battery test records.
Upload system configuration files.
Download system configuration files.
Upgrade software.
To set Internet Explorer security, perform the following steps: 1.
Open Internet Explorer.
2.
Choose Tools > Internet Options.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
186
SMU02C V500R003C10 Site Monitoring Unit User Manual
C FAQ
3.
Choose Security Tab.
4.
Click Internet and click Custom level. After you specify Internet security settings, click Local intranet and click Custom level. Figure C-2 Internet Explorer security
5.
Specify the security settings. Enable the following: −
Initialize and script ActiveX controls not marked as safe for scripting
−
Allow previously unused ActiveX controls to run without prompt
−
Include local directory path when uploading files to a server
Figure C-3 Internet Explorer security setting 1
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
187
SMU02C V500R003C10 Site Monitoring Unit User Manual
C FAQ
Figure C-4 Internet Explorer security setting 2
Figure C-5 Internet Explorer security setting 3
6.
Click OK.
7.
Click the Advanced tab, and select Use SSL 3.0, Use TLS 1.0, Use TLS 1.1, and Use TLS 1.2.
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
188
SMU02C V500R003C10 Site Monitoring Unit User Manual
C FAQ
Figure C-6 Internet Explorer security setting 5
8.
Click OK.
C.2 What Should I Do If I Forgot the Password? The monitoring unit allows users to change passwords mutually on the WebUI and LCD. For example, if you forgot the WebUI login password, you can change the WebUI password on the LCD. Table C-1 Resetting the WebUI password on the LCD Main Menu
Second-Level Menu
Third-Level Menu
Setting
Parameters Settings
Local Parameters
Reset Web Password
Set based on site requirements.
NOTE The menu is displayed only when the login account is an administrator account.
For details about how to change the LCD password on the WebUI, see 5.2.5 Changing a User Password. Select the user whose login source is LCD for changing.
Issue 01 (2020-05-30)
There are 2 LCD account, see 3.1.4 Password.
The WebUI account is admin and the password is Changeme by default.
Copyright © Huawei Technologies Co., Ltd.
189
SMU02C V500R003C10 Site Monitoring Unit User Manual
D
D Acronyms and Abbreviations
Acronyms and Abbreviations
A
-
AC
Alternating current
B
-
BBU
Baseband unit
BLVD
Battery low voltage disconnected
C
-
CAN
Control area network
D
-
DC
Direct current
DCB
Deep cycle battery
DIN
Dry contact input
DOD
Depth of discharge
DTS
DC transfer switch
E
-
ESD
Electrostatic discharge
ESM
Energy storage module
ESU
Energy storage unit
F
-
FCB
Fast charge battery
FE
Fast Ethernet
H
-
HTTPS
Hypertext Transfer Protocol Secure
I
-
IMEI
international mobile equipment identity
Issue 01 (2020-05-30)
Copyright © Huawei Technologies Co., Ltd.
190
SMU02C V500R003C10 Site Monitoring Unit User Manual
D Acronyms and Abbreviations
IP
Internet Protocol
L
-
LCD
Liquid crystal display
LLVD
Load low voltage disconnected
N
-
NMS
Network management system
S
-
SCB
Solar cycle battery
SMU
Site monitoring unit
SNMP
Simple Network Management Protocol
SOH
State of health
SPM
Site Power Management
U
-
UI
User interface
UIM
User interface module
USB
Universal Serial Bus