TJ 509 TJ 519 18 01 2012 [PDF]

  • 0 0 0
  • Gefällt Ihnen dieses papier und der download? Sie können Ihre eigene PDF-Datei in wenigen Minuten kostenlos online veröffentlichen! Anmelden
Datei wird geladen, bitte warten...
Zitiervorschau

Teksan Generator Control Panels GENERATOR SET CONTROL PANELS All measured and statistical parameters,operating modes,warnings and alarms and the current status of the mains and generator set can be viewed from the generator set control panel. The control panels are manufactured with following features and dimensions. Structure:

The control panels are made of A1 quality steel sheet and painted with electrostatics powder against corrosion.

Control Panel Mounting:

The control panels are mounted on the base frame until 825 kVA generator sets. The control panels are mounted on the alternator isolated from the vibration for bigger sized generator sets.

Control Panel Dimensions: Width: 220 mm, Length: 600 mm, Height: 400 mm1 Please contact with Teksan for project based special panel and control systems. 1-Except TJ9MS5N,TJ10MS5N,TJ11MS5N,TJ15MS5N,TJ20MS5N,TJ10PE5N, TJ14PE5N

AUTOMATIC CONTROL PANEL - TJPA Automatic control panel, provided with emergency generator sets, starts and stops generator set automatically in case of a mains failure with complete control and protection functions. These functions are realized with micro processor based control module. The modes of operation are selected by pushing the front panel bottons.

MANUAL CONTROL PANEL - TJPM It is designed to be used when mains power is not available or when it is aimed to start/stop the generator set manually. Control and protection functions are realized with micro processor based control module. The modes of operation are selected by pushing the front panel bottons.

TJ509

1

TJ519

www.teksangenerator.com

18.01.2012

TJPA TJPM MANUAL PANEL AUTOMATIC PANEL

CONTROL PANEL PROPERTIES

• Manual operation • Automatic operation

x

• Control module type

TJ519

TJ509

• Emergency stop button • Phase - Neutral generator set voltage measurement [V] • Phase - Phase generator set voltage measurement [V] • 3 phase generator set current measurement [A] • Generator set frequency measurement [Hz]

x x x

• Phase - Neutral mains voltage measurement [V] • Phase - Phase mains voltage measurement [V] • Mains frequency measurement [Hz] • Battery DC voltage measurement [VDC] • 3 phase generator set active power measurement [kW] • Generator set total active power measurement [kW] • 3 phase generator set power factor measurement • Generator set total power factor measurement • Engine oil pressure measurement [bar]1 • Engine oil temperature measurement [°C] • Engine coolant temperature measurement [°C]1 • Engine speed measurement [rpm] • Fuel level measurement [%]2 • 12/24 VDC operation • Earth leakage protection • Battery charger (rectifier) • Automatic exerciser operation [daily/weekly/monthly] • Load shedding/Dummy load3 • Event logging with date-time stamp (number)

200

200

• Event logging with date-time stamp and complete measurements (number)

18

18

• Statistical counters : engine hours run,generator set total active power[kWh],engine hours to service,time to service,total engine cranks,total engine runs • 3 level password protection • Adjustable setting parameters • Remote monitoring (On RS-232 port through software) • Remote start operation with dry contact • RS-232 serial port • RS-485 serial port • MODBUS communications • Electronic engine control and monitoring through J1939 CAN • Alarm/Warning indicator • Periodic maintenance (service) request indicator • Graphic LCD display

x

2

: Standard

1-Except TJ9MS5N,TJ10MS5N,TJ11MS5N,TJ15MS5N,TJ20MS5N

: Optional

2-Analogue fuel level gauge exists on the base frame fuel tank.

: Not applicable : NA

3-The load shedding feature consists on the disconnection of the least crucial loads in a single step when the generator set power approaches to its programmed limits.An additional breaker is needed in the ATS panel for the disconnection.

www.teksangenerator.com

18.01.2012

TJPA TJPM MANUAL PANEL AUTOMATIC PANEL

CONTROL PANEL PROPERTIES

• Multiple language support • Mimic diagram indicating the current status of the mains and generator set voltages and contactors

x

• Configurable analogue inputs • Configurable digital inputs • Configurable digital outputs • Relay output expansion capability

up to 22

up to 22

• Dual generator set mutual standby operation • Lockable control panel door • Spring clamp type terminals • Alarm horn • Space heater • Lighting inside control panel • Lighting outside control panel • Analogue measurement gauges

x

3

: Standard : Optional : Not applicable : NA

www.teksangenerator.com

18.01.2012

TJPA TJPM MANUAL PANEL AUTOMATIC PANEL

CONTROL PANEL WARNINGS

• Generator set low/high speed • High coolant temperature • Low coolant temperature • Low oil pressure • High oil temperature

x

• Mains phase order fail • Battery charger (rectifier) failure • Charge alternator (or broken belt) failure • Low battery voltage • High battery voltage • Low fuel level • Stop fail • Reverse power • Service request

TJPM TJPA MANUAL PANEL AUTOMATIC PANEL

CONTROL PANEL ALARMS

• Generator set low/high speed • High coolant temperature • Low oil pressure • High oil temperature • High battery voltage • Low fuel level • Start fail • Overload • Excess power • Genset low/high voltage • Low coolant level (above 275 kVA) • Reverse power

x

4

: Standard : Optional : Not applicable : NA

www.teksangenerator.com

18.01.2012