SCOPE OF SUPPLY LIST, CARGO Product
Salwico Fire Alarm System CARGO
Our Ref. No.
SG-32779
Shipyard
Jinhai Heavy Industry Co Ltd
NB
J0231
Item number
Name
Order qty
F000-101-20104A
SALWICO CARGO (AE)
1
5100195-20A
CTRL/REPEATER M 4.3
1
5100096-20A
REPEATER M 4.3 MARIN
2
040005
EV-H/CS 84C HEAT DET
5
046916
SPB-ADAPT BASE PLATE
5
046950
2IP55 DETECTOR BASE
5
040020
EV-P OPTICAL SMOKE D
43
044445
UB-6 UNIVERSAL BASE
43
040020
EV-P OPTICAL SMOKE D
87
046916
SPB-ADAPT BASE PLATE
87
046950
2IP55 DETECTOR BASE
87
5200123-00A
EV-AD 2 ADDRESSING T
1
5200030-02B
MCP-A SCI (GB)
28
5200031-02B
MCP-A SCI WP (GB)
22
N1702
NS-ELR-33 END OF LIN
2
007102
GPT-65KP DOOR HOLDER
8
007107
GPT-AG ARMATURE DORR
8
5200276-00A
TC10 WP TIMER CONTRO
1
5200236-00A
SALWICO AC-IR-3FQ FL
17
5200237-00A
SALWICO AC-IR-3FQ AD
17
037174
SWM-1KL 140C HEAT DE
1
5200273-00A
IC10 WP ADDRESS UNIT
1
N1738
SOLO 330 SMOKE DET T
1
N1744
ADAPTER FOR N1738
1
009151
EXTENSION HANDLE 4 M
1
N1739K
TEST GAS CAN NEW TYP
1
5100509-00A
HEAT DETECTOR TESTER
1
5100553-00A
SALWICO IR TEST LAMP
1
MCP SPARE GLASS EN54
2
Spare Parts 5200075-00A
Supplier’s declaration of conformity
Product F000-101-20104A
Batch/Serial number 86535
System CCP FDS ANALOG
Software FDS_1.8.0
Other
This equipment is tested and meets with the test requirements of Consilium as of the date specified below. NB! This delivery test does not replace final test and adjustments after installation.
Date
Product verified by:
Gothenburg 2015-08-21
Issuer: Consilium Marine & Safety AB Mail address P.O. Box 8763 SE-402 76 Gothenburg Sweden
Visiting address Salsmästaregatan 21
Telephone +46 31 710 77 00
Telefax +46 31 710 78 00
Certificate no: 131584
Batch no:
86535 Product no:
F000-101-20104A Software: FDS_1.8.0
Date: 2015-08-21 Comments:
1(5)
DATA SHEET
Control/Repeater Panel M 4.3 Part no see below
System: Salwico Cargo, Salwico Cruise, Salwico LNG, Salwico Offshore, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht, Salwico Navy, OEM Extinguish
General Description
Data
The Control/Repeater Panel M 4.3 is a control panel with a 4.3" graphical colour display used to manage and supervise a system. Control/Repeater Panel M 4.3 mounts on any flat surface independently from a fire alarm cabinet. Control/Repeater Panel M 4.3 is equipped with communication buses for connecting to the system, and it provides the following features: • A backlit 4.3" graphical colour display • Alarm buzzer • LED status indicators • Backbone Bus Interface • Ethernet connection • RS-422/RS-485 interface • RS-232/RS-485 interface • Three USB interfaces • Two configurable powered I/Os • Two programmable relay outputs Refer to the User Guide for more information on operating Control/Repeater M 4.3. For details on assembling a system and definitions of common system terms, refer to the Installation Manual.
Operating voltage range Current consumption (at 24V) Ingress protection Operating temperature range Weight Display Ethernet USB Host USB Device Relays rating I/O 70 (as input) I/O 70 (as output) Cable terminals SD Memory Certified according to
Part No. Control/Repeater M 4.3 Cargo Control/Repeater M 4.3 Ro/Pax Control/Repeater M 4.3 Workboat Control/Repeater M 4.3 Yacht Control/Repeater M 4.3 Cruise
5100195-20A 5100195-30A 5100195-40A 5100195-50A 5100195-80A
19-30 VDC Normal 100 mA Max. 270 mA IP22 -5°C to +55°C 1250g 4.3", 480×272 pixels, TFT 10/100 Mbit, autosense USB 1.1 1 in front, 1 on back USB 1.1 1 on back Max. 30 VDC, 500 mA 24 VDC 5-70 mA 24 VDC Max. 70 mA 2.5 mm² (Optional) CE ROHS EN 54-2 (1999/ A1:2006) EN 60945 0845
Indicators Control/Repeater Panel M 4.3 indicators display system status. Refer to the User Guide for more information.
The specifications described herein are subject to change without notice.
Data sheet no: 5100195 Control/Repeater M 4.3.10 5.ME
www.consilium.se
2(5)
DATA SHEET
Address Switch This switch (see SW2 in figure Connection board) identifies modules in the system and sets the function. Control modules can serve as Bus Masters, i.e., operate in Controller Mode or in Managed Mode, for example repeaters and protocol converters. Address 1 and 2 are dedicated for control modules in Controller Mode. One control module per central shall be set in Controller Mode. If the system shall be reduntant it is required to have a second control module, also set in Controller Mode. Modes for Managed and Controller are set with DIP switches as described in the following table:
DIP 8
Managed Mode
Controller Mode
Controller Mode (off)
Controller Mode (on) Spare Master (on/off)
DIP 7 DIP 6 Module Address (0-127)
DIP 5 DIP 4 DIP 3 DIP 2 DIP 1
Central Address (0-31)
Control Modules have two different modes of operation, as determined by their DIP settings (normally preset from factory): Controller Mode Single Central System: Central 1 Primary (automatically module address 1)
Central 1 Secondary (optional) (automatically module address 2)
Multi Central System: Central 1 Primary (automatically module address 1)
Central 1 Secondary (optional) (automatically module address 2)
The specifications described herein are subject to change without notice.
www.consilium.se
Data sheet no: 5100195 Control/Repeater M 4.3.10 5.0(
3(5)
DATA SHEET
Central 30 Primary (automatically module address 1)
Central 30 Secondary (optional) (automatically module address 2)
Managed Mode
Module Address 3-125
Connections Control/Repeater Panel M 4.3 mounts outside of the central. Using ribbon cables, connect the Control/Repeater Panel M 4.3 to Terminal M (prefitted inside the Control/Repeater Panel M 4.3 casing, see Module Dimensions (mm)). All Control/ Repeater Panel M 4.3 connections are made on the Connection board, located at the back of the front panel. See figure Connection board. Figure 1. Connection board
Connector Function no. P4 P5 P6 P7 P8
Description
Connection to Terminal M Connection to Terminal M
Type A/ Host
P9 P10 P11
Type B/ Device
20-pol. Flat Cable * 10-pol. Flat Cable * Door Switch Ethernet USB USB Expansion Board USB External Buzzer (24V)
* See illustration below for connection to Terminal M.
The specifications described herein are subject to change without notice'DWDVKHHWQR&RQWURO5HSHDWHU00(
www.consilium.se
4(5)
DATA SHEET
RS485 Termination For RS485 Termination the built-in terminator (120 ohm) can be activated with the RS485 DIP switch located on the Connection board (see figure in Connections). For recommendations and examples on RS485 Termination, refer to the Installation Manual.
Table 1. DIP switch for RS485 Termination
DIP Switch No.
Description ON
OFF
1 2
Channel 3 Channel 4
Deactivated Deactivated
Active Active
The specifications described herein are subject to change without notice.
www.consilium.se
Data sheet no: 5100195 Control/Repeater M 4.3.10 5.0(
DATA SHEET
5(5)
Module Dimensions (mm)
Mounting Dimensions (mm)
The specifications described herein are subject to change without notice.
Data sheet no: 5100195 Control/Repeater M 4.3.10 5.0(
www.consilium.se
1(4)
DATA SHEET
Repeater M 4.3 Part no see below
System: Salwico Cargo, Salwico Cruise, Salwico LNG, Salwico Offshore, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht, Salwico Navy, OEM Extinguish
General Description
Data
The Repeater M 4.3 is a repeater panel with a 4.3" graphical colour display used to indicate system status for fire alarms, faults and disablements. Repeater M 4.3 can be mounted on any flat surface or flush mounted, independently from a fire alarm cabinet. Repeater M 4.3 is equipped with communication buses for connecting to the system, and it provides the following features: • A backlit 4.3" graphical colour display • Alarm buzzer • LED status indicators • Backbone Bus / Extension Bus interface • USB interface • Two inputs and three outputs Refer to the User Guide for more information on operating Repeater M 4.3. For details on assembling a system and definitions of common system terms, refer to the Installation Manual.
Operating voltage range Current consumption (at 24V) Ingress protection Operating temperature range Weight Display USB port Input Output SD Memory Certified according to
19-30 VDC 92 mA IP32 -5°C to +55°C 620 g 4.3", 480×272 pixels, TFT USB 1.1 Embedded Host 24 VDC, digital 24 VDC sinking, max. 40 mA (Optional) 0845
Indicators Refer to the User Guide for more information.
Part No. Repeater M 4.3 Marine
5100096-20A
The specifications described herein are subject to change without notice.
Data sheet no: 5100096 Repeater M 4.3.11 2.ME
www.consilium.se
2(4)
DATA SHEET
Connections Connect the Repeater M 4.3 to BBE or to Extension Bus. Note! See figure below for connection alternatives; i.e. Connection board or Front panel rear.
BBE = Backbone Bus External
The specifications described herein are subject to change without notice.
www.consilium.se
Data sheet no: 5100096 Repeater M 4.3.11 2.ME
3(4)
DATA SHEET
RS485 Termination
Addressing
For RS485 Termination the built-in terminator (120 ohm) can be activated with the RS485 DIP switch located on the rear of the front panel. For recommendations and examples on RS485 Termination, refer to the Installation Manual.
1
1.1 1.2
2
2.1 2.2
2.3
Press both arrow keys + to open the Enter Access Code menu. Approximate 4-5 seconds. Use the arrow keys to scroll and select the digits for the Access Code. Confirm with the Local Mute button (= Next digit or Enter). ( = Previous.) Proceed to choose address and layout for the Repeater module: • Enter Central Address • Enter Module Address • Enter Layout Reboot the Repeater module (it will take the module about 20 seconds to restart). For all menu alternatives use the arrow keys to scroll and select. Confirm with the Local Mute button. Follow the instructions on the lower part of the screen.
Table 1. DIP switch for RS485 Termination
DIP Switch No.
Description ON
OFF
1 2
BBE1 BBE2
Deactivated Deactivated
Active Active
The specifications described herein are subject to change without notice.
Data sheet no: 5100096 Repeater M 4.3.11 2.ME
www.consilium.se
4(4)
DATA SHEET
Module Dimensions (mm)
Mounting Dimensions (mm)
The specifications described herein are subject to change without notice.
www.consilium.se
Data sheet no: 5100096 Repeater M 4.3.11 2.ME
Heat detector Salwico EV-H 84°C Part no. 40005
System: Salwico CS3000, CS4000 and NSAC-1
Description
Data
Salwico EV-H is an analog addressable heat detector.
Function
Salwico EV-H is designed to give early warning for the presence of heat in the supervised area, and is available in two temperature classes: CS (fixed 84°C) and A1R (fixed 54°C + rate of rise 0.8°C/min), see separate part. no. for 54°C.
Nominal voltage Working voltage Working current Alarm current Remote output Ingress protection Cable terminals Temperature range Air humidity Material Colour Weight (w/o base) Standard Programming tool
Salwico EV-H is equipped with OMNIVIEW 360° LED indicator giving a clear, full 360° visibility of the red alarm indication. The detector can be placed in harsh environments if it is mounted on a splash proof base. See separate document “Base matrix Salwico units” for information about suitable base plate. The technical detector address is set with a special programming tool. Valid addresses are 1-254.
Heat, thermistor 84°C (Also available in 54°C version) 24 VDC 20-37 VDC 0.2 mA 5 mA max 3 mA Depends on base Depends on base -25°C to +70°C 0-95% RH PC/ABS White ~120 g EN54-5, CS Part no. 040300
Salwico EV-H is equipped with an output for external indication.
Dimensions (mm)
TYPICAL HEIGHT WITH: IP22 BASE = 63 IP55 BASE = 97
Connection 1(+) 6(-) 3(-)
Loop in
Loop out
3 mA remote output Specifications may be subject to change for improvement without prior notice
ÇConsilium
Consilium Marine AB P.O. Box 8763, SE-402 76 Göteborg Phone +46 31 7107700 Fax +46 31 7107800 www.consilium.se
Data sheet no: 40005.EV-H 84C.08.1.E
1(2)
DATA SHEET
Base Adapter
Salwico SPB-ADAPT Part no. 046916
System: All Salwico Fire Alarm Systems
General Description
Data
SPB-ADAPT is an adapter for the bases 2IP55 (part. no. 046950) and NS-2IP55 (part no. 046900).
Table 1. Title
SPB-ADAPT is developed to replace the adapters SPB-1 (part no. 046915) and NS-ADAPT (part no. N1421). Smoke, heat and flame detectors can be connected to this adapter. For more information about suitable bases, see separate document “Base matrix”.
Cable terminals
2.5 mm2
Ingress protection
IP55 (mounted on a base)
Material
PC/ABS
Colour
White
Weight
~110 g
The adapter can be used for all Salwico fire alarm systems.
Dimensions (mm)
The specifications described herein are subject to change without notice.
Data sheet no. 046916 SPB-ADAPT.12 1.ME
www.consilium.se
2(2)
DATA SHEET
Connection Connection of addressable detectors IA, OA, TDT and EV-PP series:
Connection of addressable detectors NS, CN and EV-series** (EV-PP excluded):
Connection of conventional detectors DIS3, DOS3, HC100,NS-DIR and NS-DUV:
Connection of conventional flame detectors EVC-IR (not NS-DIR or NS-DUV):
* All types of detectors do not have the remote output. Please refer to the data sheet for the detector in question. ** For loop units with short circuit isolators, see connection on data sheet for that unit.
The specifications described herein are subject to change without notice.
Data sheet no. 046916 SPB-ADAPT.12 1.ME
www.consilium.se
IP55 base Salwico 2IP55 Part no. 46950
System: All Salwico fire alarm systems
Description
Data
The 2IP55 is a base for all Salwico IP55 detector adapters. Together with the adapters it is possible to install smoke, heat and flame detectors in harsh environment with an ingress protection up to IP55. It can be used for both addressable and conventional fire alarm systems.
Cable diameter Ingress protection Fire class Temperature range Material Colour Weight
Ø6-14 mm IP55 V1 -30ºC to +100ºC Polyamide/glass (PA666, 15% GW) White ~100 g
Dimensions (mm)
Specifications may be subject to change for improvement without prior notice
ÇConsilium
Consilium Marine AB
P.O. Box 8763, SE-402 76 Göteborg, Sweden Phone +46 31 710 77 00 Fax +46 31 710 78 00 www.consilium.se
Data sheet no: 46950.03.1.E
Optical smoke detector Salwico EV-P Part no. 40020
System: Salwico CS3000, CS4000 and NSAC-1
Description
Data
Salwico EV-P is an analogue addressable smoke detector with an optical chamber.
Function
Salwico EV-P is designed to give early warning for the presence of smoke in the supervised area. At the same time the detector offers a high protection against unwanted alarms. Salwico EV-P is equipped with OMNIVIEW 360° LED indicator giving a clear, full 360° visibility of the red alarm indication. The technical detector address is set with a special programming tool. Valid addresses are 1-254. The detector can be placed in harsh environments if it is mounted on a splash proof base. See separate document “Base matrix Salwico units” for information about suitable base plate. Salwico EV-P has a fine pitch net which improves the response to smoke and also reduces the amount of dust etc entering the detector.
Nominal voltage Working voltage Working current Alarm current Remote output Ingress protection Cable terminals Temperature range Air humidity Material Colour Weight (w/o base) Standard Programming tool
Analogue, addressable, scattering light. 24 VDC 20-37 VDC 0.2 mA 5 mA max 3 mA Depends on base Depends on base -25°C to +70°C 0-95% RH PC/ABS White ~120 g EN54-7 Part no. 040300
Important notice: Do not remove the dust cover from the detector until all polluting (dusty) activities are finished and the area has been cleaned.
Salwico EV-P is equipped with an output for external indication.
Dimensions (mm)
TYPICAL HEIGHT WITH: IP22 BASE = 58 IP55 BASE = 92
Connection
1(+) 6(-) 3(-)
Loop in
Loop out
3 mA remote output Specifications may be subject to change for improvement without prior notice
ÇConsilium
Consilium Marine AB P.O. Box 8763, SE-402 76 Göteborg Phone +46 31 7107700 Fax +46 31 7107800 www.consilium.se
Data sheet no: 40020.EV-P.08.1.E
Base plate
Salwico UB-6 Part no. 044445
System: All Salwico fire alarm systems
Description
Data
UB-6 is a low profile base plate for smoke, heat and flame detectors.
Ingress protection Material Colour Weight
UB-6 is developed to replace the following bases: !
UB-1
!
UB-2
!
UB-5
!
NS-BNCL
IP22 PC/ABS Signal white, RAL 9003 ~65 g
Dimensions (mm)
Please see separate document “Base Matrix Salwico units” for information about suitable bases for detectors. The base plate is made for use in dry and clean spaces, and it can be used for both addressable and conventional fire alarm systems. Some detectors might require special bases. The cable entry is from the centre or from the side of the base. UB-6 is prepared for SUM-2 assembly. Detectors in the CN, EV and EVC series can be locked to the base using a 1,5 mm hexagon key.
Connection Connection of addressable detectors: IA, OA and TDT Loop in
L3 (+) C6 (-) P1 (+) R4 (-)
Connection of addressable detectors: NS, EV and CN
Loop out
Loop in
1 (+) 6 (-) 3 (-)
Loop out
Remote output Remote output*
Connection of conventional detectors: DIS3 and HC100
Connection of conventional detectors: EVC (not NS-DIR an NS-DUV)
Last detector From the fire alarm panel
L3 (+) C6 (-) P1 (-) R4 (-)
To the next unit
Rem ote output*
L3 (+) C6 (-) P1 (-) R4 (-)
End of line resi stor
From th e fire alarm pane l
Remote output*
3 (+) 1 (-) 6 (-) 5 (-)
To the next unit
Remote output*
Last detector 3 (+) 1 (-) 6 (-) 5 (-)
End of line resistor
Remote output*
* All types of detectors do not have the remote output. Please refer to the data sheet for the detector in question. Specifications may be subject to change for improvement without prior notice
ÇConsilium
Consilium Marine AB P.O. Box 8763, SE-402 76 Göteborg Phone +46 31 7107700 Fax +46 31 7107800 www.consilium.se
Data sheet no: 044445.UB-6.08.1.E
1(2)
DATA SHEET
Evolution Address Programmer
EV-AD2
Part no 5200123-00A
System: Salwico CS3000, CS4000, CCP, NSAC-1 fire alarms
General description
Data
The Evolution Address Programmer is used to set the address in Salwico Evolution fire alarm detectors in a marine environment (Customer Code 2). The detector is attached to the programmer. The procedure to set or change the address takes only a few seconds. The EV-AD2 requires two 9 V PP3 nonrechargeable alkaline batteries. The programmer indicates when the battery is low.
Power supply
CAUTION! • Use only the specified power supply. • Switch off the EV-AD2 when connecting or disconnecting the battery. • Do not dismantle or modify the EV-AD2. • Keep the EV-AD2 away from contact with water. NOTE! • Avoid subjecting the EV-AD2 to excessive vibration or shock. • Remove the batteries if the EV-AD2 is to be stored for a longer time. • Do not leave the EV-AD2 in direct sunlight, near hot surfaces, or in areas where magnetic or electromagnetic waves are generated. • Do not mix batteries of different type or capacity. • Avoid using in conditions of extreme humidity or temperature.
Operating temperature Humidity Dimensions Material Weight Test device
Error code E01 E02 E03 E04 E10 E11 E20
E21
E22
The specifications described herein are subject to change without notice.
18 VDC, 2 x PP3 Type alkaline batteries (not supplied) 24 VDC (using AC power unit) 0–40ºC Up to 85% RH (noncondensing) 230 x 65 x 120 mm ABS ~360 g (without batteries) One EV protocol device at a time
Receive frame error Receive frame bit error No communication Checksum error Write new address error EEPROM error Step-up transformer trouble or over current by short circuit of signal line. The EV-AD2 will switch to “Standby mode” to prevent damage. Low battery trouble. The EV-AD2 will switch to “Standby mode” to prevent damage. Low battery warning. Changes shortly to “Low battery trouble”. Insert new batteries.
Data sheet no: 5200123-00A EV-AD2.09 1.E
www.consilium.se
2(2)
DATA SHEET
Description of keys/connections
1 2
3
4
5
6 7 8 9 10
11 12 13
14
Base – for connecting the detector. “OK” Completed LED (Green) – lit when programming of new address is completed. “ERR” Error LED (Orange) – lit when programming of new address could not be completed. “ADDRESS” “100 10 1” 7-segment LED – displays the customer code, type code or address. “POWER” Power LED (Green) – lights when the power switch is ON. Blinks if the programmer is reporting “Low battery”. “Set Address” To write the address into the device. “+1” Increase address by one one. “+10” Increase address by ten. “+100” Increase address by hundred. “Search Address” To start transmission and find the address of the detector/module. RJ45 Socket – for connecting the module. Battery box for PP3 non-rechargeable alkaline batteries. “DC IN 24V” Plug adaptor – for the AC power unit (not supplied). “Power” To turn the EV-AD2 “ON” or “OFF”.
Instructions HINT! If there is no key operation for more than one minute, the EV-AD2 will switch to “Standby mode” for saving battery. Press any key to start from “Standby mode”.
The specifications described herein are subject to change without notice.
www.consilium.se
1. Before inserting the batteries, check polarity and confirm that the EV-AD2 is turned off. 2. Turn the power switch “ON”. For one second all LEDs are lit and the buzzer sounds. 3. Attach the detector to the EV-AD2. 4. Press “Search Address”. The buzzer sounds, then the EV-AD2 starts transmitting to the detector. Do not remove the detector during transmission. 5. Press any key at any time during the information collection cycle to force the EV-AD2 to display the address and await new address collection. The 7-segment LED reads.
The buzzer sounds, error LED “ERR” lights and the 7-segment LED displays an error code when an unsupported or defective detector is connected. The information cycles every second and stops while displaying the address at the end of the second cycle. 6. Select the new address by using the keys “+100”, “+10” and “+1”. 7. Press “Set Address”. The buzzer sounds and all LEDs are turned off. The EV-AD2 starts to transmit to the detector. Do not remove the detector during transmission. 8. The 7-segement LED shows the new address and the completed LED “OK” lights. The buzzer sounds, error LED “ERR” lights and the 7-segment LED displays an error code when an unsupported or defective detector is connected. 9. Remove the detector and repeat with a new one from step 3. 10. Finish by turning the power switch “OFF”. Data sheet no: 5200123-00A EV-AD2.09 1.E
1(3)
DATA SHEET
Manual Call Point
Salwico MCP-A SCI Part no. 5200030-02B
System: Salwico Cargo, Salwico Cruise, Salwico LNG, Salwico Offshore, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht, Salwico Navy, OEM Extinguish
General Description
Ambient humidity
0 to 95% RH
MCP-A SCI is an addressable manual call point for indoor environment, designed for Salwico fire alarm systems as specified above.
Material
PC/ABS
Colour
Red, RAL 3001
Weight
~160 g
Pressing the glass causing it to crack activates the fire alarm. A protective plastic coating on the glass prevents operator injury.
Cable dimension
Ø6-12 mm
An LED on the front of the call point indicates the fire alarm. The LED remains lit until the fire alarm has been reset on the fire alarm panel. The call point can be tested with a special key, included in the delivery.
Certified according to 0470/yy yy = year of production Spare glasses (10pcs.)
Part no. 5200075-00A
Connection Connection with short-circuit protection
The address of the call point is set with a DIP-switch. MCP-A SCI is developed to provide Short Circuit Protection. The Short Circuit Isolator function is fully transparent and do not require any setting. In order to achieve IP23 the MCP-A SCI shall be mounted on a smooth surface and the cable inlet/outlet shall be secured against leakage. NOTE! This product is not a compatible replacement for 5200030-01A MCP-A (GB)
Connection without short-circuit protection
Data Nominal voltage
34 VDC
Working voltage
20-38 VDC
Supervising current
0.25 mA
Alarm current
2.5 mA
Current when short circuited
12 mA
Ingress protection
IP23D
Temperature range
-25 °C to +70 °C
The specifications described herein are subject to change without notice.
Data sheet no. 5200030-02B_Salwico MCP-A SCI_M_EN_2013_B
www.consilium.se
DATA SHEET
2(3)
Test
Change Glass
Dimensions (mm)
The specifications described herein are subject to change without notice.
Data sheet no. 5200030-02B_Salwico MCP-A SCI_M_EN_2013_B
www.consilium.se
3(3)
DATA SHEET
Mounting Dimensions (mm)
Typical use Example 1
** = Max 25 detector heads Example 2
The specifications described herein are subject to change without notice.
Data sheet no. 5200030-02B_Salwico MCP-A SCI_M_EN_2013_B
www.consilium.se
1(3)
DATA SHEET
Manual Call Point IP67
Salwico MCP-A WP SCI Part no. 5200031-02B
System: Salwico Cargo, Salwico Cruise, Salwico LNG, Salwico Offshore, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht, Salwico Navy, OEM Extinguish
General Description
Material
PC/ABS
MCP-A WP SCI is an addressable manual call point, designed for Salwico fire alarm systems as specified above. The selected material PC/ABS and the encapsulation, with ingress protection IP67, makes it very suitable for harsh environment.
Colour
Red, RAL 3001
Weight
~240 g
Cable dimension
Ø6-12 mm
Pressing the glass causing it to crack activates the fire alarm. A protective plastic coating on the glass prevents operator injury. An LED on the front of the call point indicates the fire alarm. The LED remains lit until the fire alarm has been reset on the fire alarm panel.
Certified according to 0470/yy yy = year of production Spare glasses (10pcs.)
Part no. 5200075-00A
Connection Connection with short-circuit protection
The call point can also be tested with a special key, included in the delivery. The address of the call point is set with a DIP-switch. MCP-A WP SCI is developed to provide Short Circuit Protection. The Short Circuit Isolator function is fully transparent and do not require any setting. NOTE! This product is not a compatible replacement for 5200031-01A MCP-A WP (GB)
Connection without short-circuit protection
Data Nominal voltage
34 VDC
Working voltage
20-38 VDC
Supervising current
0.25 mA
Alarm current
2.5 mA
Current when short circuited
12 mA
Ingress protection
IP67
Temperature range
-25 °C to +70 °C
Ambient humidity
0 to 95% RH
The specifications described herein are subject to change without notice.
Data sheet no. 5200031-02B_Salwico MCP-A WP SCI_M_EN_2013_B
www.consilium.se
DATA SHEET
2(3)
Test
Cover removal
Remove the four cover fixing screws. Place the edge of a large flat bladed screwdriver into the slot between the cover and back box, as shown in picture, and gently twist until the latches are disengaged. Pull cover away from the back box.
Change Glass
The specifications described herein are subject to change without notice.
Data sheet no. 5200031-02B_Salwico MCP-A WP SCI_M_EN_2013_B
www.consilium.se
3(3)
DATA SHEET
Dimensions (mm)
Typical use Example 1
** = Max 25 detector heads Example 2
The specifications described herein are subject to change without notice.
Data sheet no. 5200031-02B_Salwico MCP-A WP SCI_M_EN_2013_B
www.consilium.se
Door holder magnet Salwico GPT-AG Part no.:
Magnet GPT Armature AG
7102 7107
System: All Salwico fire alarms
Description
Data
The magnetic door holder consists of two parts:
Nominal voltage Working voltage Holding power Working current Power consumption Cable dimension* Cable terminals Colour Weight, GPT+AG
• GPT, door holder magnet, mounted on the wall. • AG, armature, mounted on the door. When the power to the magnet is cut, the door is released and a door closer may close the door. The GPT magnet is equipped with a door release button for local door release.
24 VDC See Traction power below 650N 40 mA at 24 VDC 1W Ø 7-11 mm 1.5mm2 Grey ~700 g
*With the extension gland, part no. 7106, the cable dimension will be extended to max Ø 15 mm.
Dimensions (mm) AG
4xØ6.3 mounting holes
52
44
4xØ6.3 mounting holes
60
GPT
50
44 60
52
42
66
Connection
Traction power 750 700 650
(N)
600
DC in
550 500 450 400 350 300 12
14
16
18
20
22
24
26
28
30
(V) Specifications may be subject to change for improvement without prior notice
ÇConsilium
Consilium Marine AB P.O. Box 8763, SE-402 76 Göteborg Phone +46 31 7107700 Fax +46 31 7107800 www.consilium.se
Data sheet no: 7102 7107.GPT-AG.06.1.E
1(5)
DATA SHEET
Timer Control Unit
Salwico TC10 WP Part no. 5200276-00A
System: CS3000, CS3004, CS4000, Salwico Cargo, Salwico Cruise, Salwico LNG, Salwico Offshore, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht, Salwico Navy, OEM Extinguish
General Description
Max disconnection time
12 hours
The addressable timer control unit TC10 WP is used for temporarily disconnecting detectors, to prevent unwanted alarms, e.g. at service, welding etc. The timer is connected the same way as other loop units and communicates with the central the same way as they do.
Min disconnection time
15 minutes
The TC10 WP has an output with a potential free change-over relay. Loop address and function are set by DIP-switches. Disconnection times are programmable between 15 minutes and 12 hours via setup menu. When TC10 WP is power up the operate symbol is shown on the display.
Data
TC10 WP as a Replacement Unit Table 1. TC10 WP replaces the following discontinued products Part no.
Product
SW2 DIP1
SW2 DIP2
SW2 DIP3
SW2 DIP8
046400 UR-2K Timer 0-30 min
ON
OFF
ON
ON
046401 UR-2KN Timer with key 0-30 min
OFF
OFF
ON
ON
046401 UR-2KN -20* Timer with key 15+5 min
OFF
OFF
ON
ON
046401 UR-2KN -120 Timer with key 0-2h
OFF
OFF
ON
ON
ON
OFF
ON
ON
Output
1 change-over relay, max 30 VDC, 1 A
Loop nominal voltage
35 VDC
Loop working voltage
22 - 38 VDC
Loop working current
1.5 mA
Ingress protection
IP55
046410 UR-2K Timer 15 min
Relative Humidity
At low temperature 95% At high temperature 93% ± 3%
*Exact replacement unavailable, choose 15 or 30 min interval instead.
Ambient temperature
-40°C to +75°C
Time is adjustable by set up menu on display.
Cable terminals
2.5 mm2
Material
PC/ABS
Colour
Black
Weight
410 g
Certified according to
0845/yy yy = year of production
The specifications described herein are subject to change without notice.
NOTE! Physical dimensions between TC10 WP and the replaced products will differ. NOTE! Relay output max voltage 30 VDC current 1 A.
Data sheet no. 5200276-00A_Salwico TC10 WP_M_EN_2014_B
www.consilium.se
DATA SHEET
2(5) Table 2. The Setup menu
Timer Functions
Menu*
Description
MAX TIME
Maximum count down time that can be set (≥15min - ≤12hs)
DEF TIME
Initial value of count down timer
PIN CODE
PIN code used for entering a disconnection (Only used if SW2.1=OFF)
DET START**
Start address of disconnected units
DET END**
End address of disconnected units
Keyboard The numeric keyboard is used for entering setup mode or to unlock the timer in case the access authorization mode has been enabled with DIP switches. The time set keys decrease or increase the time in steps on the display. The timer unit is turned off if set time decreases to zero.
key.
If SW2.1=OFF a four digit PIN code has to be entered. The display shows the active countdown in hours, minutes and seconds. By pressing
**Only shown if SW2.3=ON.
Lamp test By simultaneously pressing keys and the buzzer turns on and a horizontal line scans the display. After a short while the unit returns to normal state.
Start disconnection The disconnection of loop units is started by pressing the
*Note: The MAX TIME can only be set larger than DEF TIME. DET END can only be set larger then DET START.
Address switch SW1
or
key the time can be adjusted. End disconnection The loop units are automatically reconnected when the timer reaches zero. To stop the timer and immediately reconnect the loop units, press the
key (repeatedly) and set time to zero.
If SW2.1=OFF the relay output can be locally muted. When display shows the message ‘6.0µm wavelength radiation.
Application Temperature Range
-25 °C to +75 °C
Humidity
Up to 95%
Sensor measures the hot carbon dioxide in a specific flame wavelength; the B and C sensors simultaneously measure the interference radiation in near wavelengths. This technique together with intelligent signal processing through microprocessor and custom algorithms, achieves excellent detection reliability while maintaining the highest immunity to interference radiation and sunlight. Testing For functional test, use Salwico IR Test lamp, part no. 001156. Due to the detectors high immunity to unwanted alarms, it is difficult to test the detector without the IR test lamp. Features • Triple Frequency IR Detector • Low current draw • Suitable for installation in damp environment • Easy Maintenance • Remote LED Option • Approved to UNI EN54-10 Ed. 2002
The specifications described herein are subject to change without notice.
Environmental Specifications
Mechanical Information Height
69 mm (including base)
Diameter
103 mm
Weight
250 g
Weight with IP65 Base
380 g
Wire Gauge for Terminals 2.5 mm2 Colour
White RAL9010
Material
Polycarbonate Flame Retarded Cl. UL94V0
IP Rating
IP65 (IP67 with locking screws)
Certified according to
0474/yy yy = year of production
Detector Base 5200235-00A Salwico AC-IR-3Fq Conventional Base 5200237-00A Salwico AC-IR-3Fq Addressable Base Test Equipment 001156 Salwico IR Test lamp
Data sheet no. 5200236-00A AC-IR-3Fq.12 4.ME
www.consilium.se
2(3)
DATA SHEET
Installation For featured wiring the detector is installed on a base, provided in IP65 proof version. The detector is connected to the base through a fast bayonet clutching and a flying connector. Certain factors need to be considered when designing an installation: 1. The sensors should be mounted so that objects do not block their field-of-view (FOV). This includes glass, Plexiglas and other visibly transparent materials. Contact Consilium for more information.
11. Care must be taken to avoid that sensor installation exceeds electromagnetic interference approval: in particular install detectors in places out-of-reach of personnel (including contractors and crew members). 12. It is important NOT to leave any extra cable slack when installing this detector. 13. Cable shield shall be connected to the ground on one side only. For outdoor mounting: Fit the detector screws on the base to ensure IP67 Protection Index. Angle of Reception
2. Whenever possible, sensors should be mounted so their ranges and fields-of-view overlap. 3. Sensors should be mounted so their FOV cannot be choppered by moving machinery or human operators during normal operations within the area. Therefore they should be installed as high as possible or on the ceiling. 4. Detector window should not be exposed to hot or cold intermittent airflow which could change the temperature of the detector itself or detector FOV background. 5. To ensure optimum sensitivity and performance, sensors should be mounted so they do not look at hot surfaces: if this is necessary first follow procedure of paragraph 3 and ensure no chopper is present.
Dimensions (mm)
6. The sensors should be mounted so that they are easily and safely accessible for inspection and maintenance. 7. If mechanical, high-temperature damage, or window contamination is likely to occur in the installed location, then the sensor should be protected. However the protection method cannot obstruct the sensors FOV with any material, including visibly transparent materials, such as glass and Plexiglas. 8. The sensor can be mounted in any orientation, as long as captive screws are removed or can be removed. 9. Mounting the sensor so that it points downwards is recommended as this generally results in minimal window contamination. 10. Care must be taken to avoid that sensor installation exceeds environmental approvals such as temperature, shocks, vibrations.
The specifications described herein are subject to change without notice.
Data sheet no. 5200236-00A AC-IR-3Fq.12 4.ME
www.consilium.se
3(3)
DATA SHEET
Settings S1 DIP-Switch setup
Figure 1. DIP-Switch Setting.
Use the 4-ways Dip-switch S1 to set the detector as Conventional or Addressable and preset sensitivity threshold (Class): Table . DIP-Switch Setting Sensitivity class
Sw.No.1 Sw.No.2 Sensitivity
Class 1
OFF
Class 2
ON
OFF
Medium up to 17 m
Class 3*
OFF
OFF
Low up to 12 m
ON
High up to 27 m
Table . Conventional Mode Mode
Sw.No.3
Sw.No.4
Conventional
ON
ON
Table . Addressable Mode Mode
Sw.No.3
Sw.No.4
Addressable*
OFF
OFF
* Default factory setting
The specifications described herein are subject to change without notice.
Data sheet no. 5200236-00A AC-IR-3Fq.12 4.ME
www.consilium.se
1(2)
DATA SHEET
Addressable Base for IR Flame Detector
Salwico AC-IR-3Fq Addr Base Part no. 5200237-00A System: CS3000, CS3004, CS4000, NSAC-1*, Salwico Cargo, Salwico Cruise, Salwico LNG, Salwico Offshore, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht, Salwico Navy, OEM Extinguish. * Requires LC1 R6 SW v.2.61.34 or later
General Description
Mechanical Information
AC-IR-3Fq Addressable Base is suitable for installation of AC-IR-3Fq Detector in a harsh environment. The base plate provides ingress protection up to IP67, when lock screws are used.
Material
The base provides a termination possibility, for detector set in Addressable mode. The address is set by an 8-way DIP-switch.
PCB Flame Ret. Class: CL UL94V0
Certified according to 0474/XX (XX = Year of Production) Detector
Features • IP65/IP67 Ingress protection
5200236-00A Salwico AC-IR-3Fq
• Low current draw
Switch Settings
• Suitable for installation in harsh environment
SW1 - Address Switch The address is set by an 8-way DIP-switch
Data
SW2 - Setting Switch
Electrical Specifications Supply Voltage
19-38 VDC
Working current
Max 0.6 mA
Alarm current
Max 1 mA (Including detector)
Remote output max
N.A.
Environmental Specifications Application Temperature Range
-25°C to +75°C
Humidity
Up to 95%
IP Rating
IP65 (IP67 w/locking screws)
DIP No.
Default Setting Explanation
1
OFF
IR-Detector
2
OFF
Not used
3
OFF
Not used
4
OFF
Not used
5
ON
SCI (Short Circuit Isolator) disabled
Mechanical Information WxLxH
130 x 110 x 37,5 mm
Diameter
100 mm
Weight
130 g +/- 10
Wire Gauge for terminal
0.75÷2.5 mm2
Colour
White RAL9010
The specifications described herein are subject to change without notice.
Data sheet no. 5200237-00A AC-IR-3Fq Addr Base.12 1.ME
www.consilium.se
2(2)
DATA SHEET
Dimensions (mm)
Flame Detector DIP-switch settings
Figure 1. AC-IR-3Fq Flame detector setting S1-DIP-Switch Mode
Sw.No.3
Sw.No.4
Addressable
OFF
OFF
Note 1: PG16 Cable-glands & stop-end are supplied in kit with base.
Connection
The specifications described herein are subject to change without notice.
Data sheet no. 5200237-00A AC-IR-3Fq Addr Base.12 1.ME
www.consilium.se
Heat Detector Salwico SWM-1KL 140 Part no. 37174
System: All Salwico Fire Alarm Systems
Description
Data
The SWM-1KL 140 is a fixed temperature heat detector, designed for use in damp spaces. It contains a bimetallic thermostat, which closes its contacts at alarm temperature.
Nominal voltage Working voltage Working current Alarm current
The detector is also available in versions with lower alarm temperature (57, 80 and 100°C) and in an intrinsically safe version, SWM-1KL/IS, see separate datasheets.
24 VDC 17 - 31 VDC 0.005 mA Max 100 mA at 24 VDC without end of line resistor Alarm resistance 470Ω Function Closing Alarm temp. 140°C Temperature range -10°C to +110°C Cable glands 6 - 11 mm Material Aluminium Ingress protection IP65 Colour Off-white Weight 250 g
Dimensions (mm)
Connection
From the fire alarm panel
SWM-1KL 140
Last unit
1(-) 2 (-) 3 (+) 4 (+)
1(-) 2 (-) 3 (+) 4 (+)
Specifications may be subject to change for improvement without prior notice
ÇConsilium
Consilium Marine AB P.O. Box 8763, SE-402 76 Göteborg Phone +46 31 7107700 Fax +46 31 7107800 www.consilium.se
End of line resistor
Data sheet no: 37174.SWM-1KL 140.07.1.E
1(4)
DATA SHEET
Address Unit
Salwico IC10 WP Part no. 5200273-00A
System: CS3000, CS3004, CS4000, Salwico Cargo, Salwico Cruise, Salwico LNG, Salwico Offshore, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht, Salwico Navy, OEM Extinguish
General Description The IC10 WP is an address unit for fire alarm systems. It has been designed for use in damp spaces. This unit allows the connection of different types of devices with closing digital function to the fire alarm system, for example high temp heat detector or sprinkler indication*. It is also possible to use IC10 WP as an indication unit.
Cable gland
TET M20 for cable Ø8-13 mm
Material
PC/ABS
Colour
Transparent/RAL7035
Weight
160 g
Certified according to 0845/yy yy = year of production
The loop address of the IC10 WP is set by a DIP-switch.
IC10 WP as a Replacement Unit
The active status is indicated by a LED on the front of the unit.
Table 1. IC10 WP replaces the following discontinued products
The type of connected device is set by an additional DIP-switch. The device type is shown on the control panel in case of fire or fault.
Part no. Product
ON
ON
The IC10 WP is a direct replacement for the discontinued AE-2 series (see replacement table).
046149 AE-2K Address unit
ON
ON
046258 AE-2K/I Address unit for door indication
OFF
ON
046259 AE-2K/I Address unit
OFF
ON
046350 VL-2K Indication unit
OFF
ON
* Please check the specification for the devices to be connected to IC10 WP before use.
Data Loop nominal voltage
35 VDC
Loop working voltage
22 – 38 VDC
Loop working current
0.2 mA
Minimum sub loop voltage 19 VDC nominal Output current limit
5 or 15 mA
Output function
Pulsed or steady
EOL (End of line units)
Not included
Ingress protection
IP66
Relative Humidity
At low temperature 95% At high temperature 93% ± 3%
Ambient temperature
-40°C to +70°C
Cable terminals
2.5 mm2
The specifications described herein are subject to change without notice.
046121 AE-2K-E Address unit
Note SW2 SW2 DIP6 DIP8 *
* IC10 WP can only be a replacement for AE-2K-E without external 24 VDC. NOTE! Physical dimensions will differ between IC10 WP and the replaced products. Hint! For type of connected device please refer to table 2. ID set by SW2 DIP 1 to 5.
Data sheet no. 5200273-00A_Salwico IC10 WP_M_EN_2014_D
www.consilium.se
DATA SHEET
DIP-Switches
2(4) Table 2. ID set by SW2 DIP 1 to 5 DIP Function switch setting
Sensor type
ID code
0
Heat detector
Conventional 127 detector, pulsed measuring or dry switch
1
Sprinkler
Dry switch, H2O 126
2
Sprinkler
Dry switch, CO2 125
3
Smoke detector Ion
Conventional detector
124
4
Flame detector IR
Conventional detector
123
5
Gas detector
Conventional detector
122
6
Sprinkler
Dry switch, Foam 121
7
Sprinkler
Dry switch, 120 pulsed measuring
8
Flame detector UV
Conventional detector
119
Address switch SW1 The loop address of the unit is set by DIP-switch SW1.
9
Heat detector
Conventional detector, steady measuring
118
Mode for SW2 To activate the high current mode (15mA), set SW2 DIP 6 to ON.
10
Door indication
Dry switch or inductive sensor
117
11
Manual call point Conventional detector
116
12
Gas sampling
Dry switch
115
13
Alarm from external central
Dry switch
114
14
General input
Steady measuring 113
15
General input
Pulsed measuring 112
16
Smoke detector Opto
Conventional detector
19
VL-2 series
Identification unit 108
20
Sprinkler
Dry switch, Halon
107
28
Smoke detector IS-3K
Conventional detector
99
29
Smoke detector IS
Conventional detector
98
Figure 1. Location of DIP-switches and connections on the PCB
The following functions are set by the DIP-switches. (Use a pointed tool of suitable size.)
NOTE! For replacements of AE-2 series by IC10 the SW2 DIP 6 must be set according to table 1. SW2 DIP 7 is not used. CAUTION! SW2 DIP 8 must always be ON! I/O Settings for SW2 The function for connected equipment are set by SW2 DIP 1 to 5. Use the DIP switch settings from the following table:
The specifications described herein are subject to change without notice.
111
Data sheet no. 5200273-00A_Salwico IC10 WP_M_EN_2014_D
www.consilium.se
3(4)
DATA SHEET
Connection Examples
* Detector, door switch, etc. ** SLZ Part no. 046632 (not included)
*** Proximity switch 2-wire (Omron E2E-X2D1-N or similar).
**** As replacement for VL-2/2K (no ELR fitted)
NOTE! This note applies for IS applications: • For replacement of the AE-21 series (ID: 99) in above configuration requires setting of the SW2 / DIP 6 = OFF (low current). ELR (End of Line Resistor) value should be 33 kΩ. •
For replacement of the AE-2 series (ID: 99) in above configuration requires setting of the SW2 / DIP 6 = ON (high current). ELR value should be 10 kΩ. For CCP (Loop M X) based systems only: ELR value should be 6.8 kΩ.
The specifications described herein are subject to change without notice.
Data sheet no. 5200273-00A_Salwico IC10 WP_M_EN_2014_D
www.consilium.se
DATA SHEET
4(4)
Dimensions (mm)
* Holes for wall mounting (x4): Max screw thread Ø4. Max screw head Ø8
The specifications described herein are subject to change without notice.
Data sheet no. 5200273-00A_Salwico IC10 WP_M_EN_2014_D
www.consilium.se
Smoke Detector Tester
Salwico Solo 330 Part no. N1738
System: All Salwico fire alarm systems
Description Insert the canister into the smoke dispenser. Lock into place using the screw mechanism. Place the cup over the detector and discharge spray (not more than 1 second) with a slight upward movement. Repeat this action without removing the cup every 10 seconds for max 1 minute, until the detector is in alarm.
Unit
Part no.
Detector tester Solo 330 Test gas Pole adapter Pole 1.2 - 2.5 m Pole 1.4 - 4 m Pole 3.0 - 12 m
N1738 9153 N1744 9150A 9151 9149
N1738
9153
N1744
Specifications may be subject to change for improvement without prior notice
ÇConsilium
Consilium Marine AB P.O. Box 8763, SE-402 76 Göteborg Phone +46 31 7107700 Fax +46 31 7107800 www.consilium.se
Data sheet no: N1738.Solo330.08.1.E
1(2)
DATA SHEET
Mains Heat Detector Tester
HL1910E Part no. 5100509-00A
System: All Salwico fire alarm systems
General Description The HL1910E is a mains heat detector tester for Salwico heat detectors. It is suitable for point type, rate of rise, fixed temperature and combination detectors up to 150 °C. The tester has variable temperature and airflow control for flexible use and maximum reliability. The HL1910E does require a power cord / mains lead of 230-240 VAC.
Instructions For Use
Table 1. Test specifications for stage II Detector Class
Minimum Static Response Temperature °C
Maximum Static Response Temperature °C
Thumbwheel Setting
A1
54
65
Step 2
A2
54
70
B
69
85
C
84
100
D
99
115
E
114
130
F
129
145
Step 3
Step 4
Distance from the detector The tester should be held in a distance of approximately 8 cm (3 inches) from the heat sensing element of the detector. If the response time gets long because of e.g. a strong wind, the tester can be kept closer to the heat sensor of the detector. After finishing the test Turn off the detector tester. 1. When using the heat detector tester connect the power cord to the mains outlet. 2. Switch on the three-stage speed / air flow control (A) to stage II.
DANGER! Please beware of the very hot part at the air outlet of the tester, which can cause personal injuries, damage material or create fire
3. Select the temperature with the thumbwheel (B) according to the detector class. Please refer to the following table.
The specifications described herein are subject to change without notice.
Data sheet no. 5100509-00A_HL1910E_M_EN_2014_B
www.consilium.se
DATA SHEET
2(2)
Data Mains voltage
230 – 240 V, 50 Hz
Output
2000 W
Stage 1: - Airflow - Temperature
150 l/min 50 °C
Stage 2: - Airflow - Temperature
300 l/min 50 – 600 °C
Stage 3: - Airflow - Temperature
500 l/min 50 – 600 °C
Temperatur setting
Contin. in 9 steps by thumbwheel
Protection class (without earth terminal)
II
Overheating protection
Thermal cut-out only
Emission sound pressure level
≤ 70 dB (A)
Total vibration value
≤ 2.5 m/s2 / K=0.08 m/s2
Weight
0.8 kg
Accessories
Figure 1. Part No. 5100515-00A Case for HL1910E. Note: Case only, heat detector tester is not included.
The specifications described herein are subject to change without notice.
Data sheet no. 5100509-00A_HL1910E_M_EN_2014_B
www.consilium.se
1(1)
DATA SHEET
IR Flame Detector Tester
Salwico IR Test lamp Part no. 5100553-00A
System: CS3000, CS3004, CS4000, NSAC-1, Salwico Cargo, Salwico Cruise, Salwico Offshore, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht, Salwico Navy, OEM Extinguish
General Description
Detector Test
The Salwico IR test lamp is used to perform function test on Salwico IR flame detectors.
There are two ways to test the detector:
The included extension rod makes it easy to test detectors in different locations.
Data Nominal voltage
6 VDC
Battery type
Alkaline LR6/AA x 4
Light source
Pliken bulb 4.8V 0.5A
Material: - Tester - Extension rod
Polycarbonate Aluminium
Colour
Black
Weight
1070 g (incl. carrying-box)
Dimension tester
W122 x H165 x D80 mm
Dimension box
W225 x H197 x D169 mm
Length ext. rod
1.4 - 4.0 m
Compatibility The Salwico IR test lamp is compatible to the following detectors: 5200236-00A
Salwico AC-IR-3Fq
5200039-00A
Salwico EVC-IR
N1122
Salwico NS-DIR
The specifications described herein are subject to change without notice.
(a) Press the Salwico IR test lamp against the detector until the trigger switch initiate test procedure with an intermittent buzzer sound. After about 15-30 seconds, check if the detector has reacted to the test. (b) Activate "continuous test mode" by setting the switch on top of the test lamp to "ON". This mode will initiate buzzer sound. Hold the Salwico IR test lamp close to the detector so the distance between the test lamp and the detector is within 5 cm. If the detector reacts within 30 seconds under this condition, the detector is functional.
If there is no response after 30 seconds in any of those tests there may be a problem with the detector (or the Salwico IR test lamp itself). Refer to troubleshooting in the corresponding manual. Special Note CAUTION! Do not touch the surface of the infrared filter with your fingers. If the surface needs to be cleaned, use a cotton swab with alcohol. Wipe gently. Be carefull not to scratch the glass.
Data sheet no. 5100553-00A_Salwico IR Test lamp_M_EN_2014_B
www.consilium.se