Schindler Escalator and Moving Walk MICONIC F 5 Controller Guide Q 409933_03 Edition 12-2013
Prepared
16.12.13
naidura
Reviewed
17.12.13
eckertmi
Norms chkd
18.12.13
plattle
Released
20.12.13
ludwigj2
Modification
01
KA No. KA Date
26.09.08
Lead Office
Classification
SC7
11xxx
Document Owner INVENTIO AG CH-6052 Hergiswil
02
03
107406
107508
27.08.10
20.12.13
Copyright © 2013 INVENTIO AG All rights reserved. INVENTIO AG, Seestrasse 55, CH-6052 Hergiswil, owns and retains all copyrights and other intellectual property rights in this manual. It shall only be used by SCHINDLER personnel or authorized SCHINDLER agents for purposes which are in the interest of SCHINDLER. Any reproduction, translation, copying or storing in data processing units in any form or by any means without prior permission of INVENTIO AG is regarded as infringement and will be prosecuted.
Table of Contents 1
2
3
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2.1 Safety Warnings . . . . . . . . . . . . . . . . . . . . . 1.2.2 Safety Guidelines . . . . . . . . . . . . . . . . . . . . 1.2.3 Safety Gear . . . . . . . . . . . . . . . . . . . . . . . . 1.3 Abbreviation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4 MICONIC Replacement Overview. . . . . . . . . . . . . . . MICONIC F 5S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1 Hardware PEM50.Q and PEM51.Q. . . . . . . . . . . . . . 2.1.1 Display and Button . . . . . . . . . . . . . . . . . . . 2.1.2 DIL Switches. . . . . . . . . . . . . . . . . . . . . . . . 2.1.3 Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1.4 Control Cabinet Sticker . . . . . . . . . . . . . . . . 2.2 Operating Messages . . . . . . . . . . . . . . . . . . . . . . . . . 2.3 Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4 Technical Tests with V51XX . . . . . . . . . . . . . . . . . . . 2.4.1 [t1] - Step/Pallet Absence PT . . . . . . . . . . . 2.4.2 [t2] - Step/Pallet Absence PB . . . . . . . . . . . 2.4.3 [t3] - Motor Speed Check . . . . . . . . . . . . . . 2.4.4 [t4] - Step/Pallet Band Speed PT . . . . . . . . 2.4.5 [t5] - Step/Pallet Band Speed PB . . . . . . . . 2.5 Technical Tests with V53XX . . . . . . . . . . . . . . . . . . . 2.5.1 [t3] - Motor Speed Check . . . . . . . . . . . . . . 2.5.2 [t4] - Step/Pallet Band Speed PT . . . . . . . . 2.5.3 [t5] - Step/Pallet Band Speed PB . . . . . . . . 2.5.4 [t6] - Motor Speed Check . . . . . . . . . . . . . . 2.6 Braking Distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.7 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.8 EoS Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.8.1 Activation, Deactivation . . . . . . . . . . . . . . . 2.9 Initiating the Learning Run . . . . . . . . . . . . . . . . . . . . 2.10 Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MICONIC F 5E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1 Hardware PEM52.Q . . . . . . . . . . . . . . . . . . . . . . . . . 3.1.1 Display and Button . . . . . . . . . . . . . . . . . . . 3.1.2 DIL Switches. . . . . . . . . . . . . . . . . . . . . . . . 3.1.3 Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1.4 Semi5-Card Reader . . . . . . . . . . . . . . . . . . 3.1.5 Control Cabinet Sticker . . . . . . . . . . . . . . . . 3.2 Operating Messages . . . . . . . . . . . . . . . . . . . . . . . . .
Q 409933_03
4 4 5 5 6 9 10 11 13 13 15 15 16 17 18 21 39 39 40 40 41 41 42 42 42 43 43 44 44 50 50 51 52 53 53 54 54 55 55 55 57 1
Copyright © 2013 INVENTIO AG
3.3 3.4 3.5
4 5
6
7
8
9
Warning Messages . . . . . . . . . . . . . . . . . . . . . . . . . . Error Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5.1 [U__C] - Error History . . . . . . . . . . . . . . . . . 3.5.2 [U__A] - Display of Operating Data . . . . . . 3.5.3 [U__t] - Technical Tests . . . . . . . . . . . . . . . 3.5.4 [U__P] - Parameters. . . . . . . . . . . . . . . . . . 3.5.5 [U__r] - Set RTC. . . . . . . . . . . . . . . . . . . . . 3.5.6 [U__d] - Data Update . . . . . . . . . . . . . . . . . 3.6 EoS Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.6.1 Activation, Deactivation . . . . . . . . . . . . . . . 3.6.2 Maintenance Operating Panel . . . . . . . . . . 3.7 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.7.1 Main Line Connection. . . . . . . . . . . . . . . . . 3.7.2 Checks before Initial Start-Up. . . . . . . . . . . 3.7.3 Initiating the Learning Run . . . . . . . . . . . . . 3.7.4 Replacement . . . . . . . . . . . . . . . . . . . . . . . Retrofit Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 MICONIC F 3 with PEM52.Q . . . . . . . . . . . . . . . . . . 4.2 MICONIC F 4 with PEM52.Q . . . . . . . . . . . . . . . . . . Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1 Semi5-Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.1 Activation . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.2 Application . . . . . . . . . . . . . . . . . . . . . . . . . 5.2 FCOM5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.2 Menu Overview. . . . . . . . . . . . . . . . . . . . . . 5.2.3 Data Update . . . . . . . . . . . . . . . . . . . . . . . . Starter SMC-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1 Functional Elements . . . . . . . . . . . . . . . . . . . . . . . . . 6.2 Error Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3 Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Vacon NXS and NXL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1 Functional Elements . . . . . . . . . . . . . . . . . . . . . . . . . 7.2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.4 Error Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.5 Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Esca-Scan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1 Functional Elements . . . . . . . . . . . . . . . . . . . . . . . . . 8.2 Function Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.3 Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Balustrade lighting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Copyright © 2013 INVENTIO AG
61 62 89 90 91 94 106 125 126 131 131 132 133 133 134 135 136 137 138 142 143 143 143 145 146 146 148 149 150 150 151 151 153 153 154 167 167 171 173 173 175 176 177
Q 409933_03
10 Lobby Vision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2 Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.3 RMS Box DIL Switches . . . . . . . . . . . . . . . . . . . . . . . 10.4 RMS Box Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.5 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Q 409933_03
178 178 179 179 180 182
3 Copyright © 2013 INVENTIO AG
1 1.1
General Information Introduction
The purpose of this reference guide is to provide the Schindler employee (who has attended a training before) with an appropriate tool to make configuration and diagnostic work easier. This reference guide does not claim to include all possibilities. The Schindler employee has to read, understand and follow the instruction in this reference guide in any case. This reference guide Schindler MICONIC F 5S and F 5E – gives an overview of the most important technical features. – contains information on troubleshooting. – is intended to make the correction of failures more easy. All given information are based on the following software version: – V5113, V5301 MICONIC F 5S – V5225, V5401 MICONIC F 5E – B5009 Bootloader – F1016 FCOM5 – 1V168 Vacon NXS – 5V257 Vacon NXL – 8783004 pDRIVE MX plus. Do not disclose this reference guide to third parties. Return the reference guide to the line manager when requested. For any questions and suggestions please contact your local branch office or national master trainer.
4 Copyright © 2013 INVENTIO AG
Q 409933_03
1.2
Safety
1.2.1
1
Safety Warnings
The following types of safety warnings are used in the present manual. DANGER Danger The safety warning with the signal word “Danger” is used to indicate a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING Warning The safety warning with the signal word “Warning” is used to indicate a hazardous situation which, if not avoided, could result in death or serious injury.
NOTICE Notice The safety warning with the signal word “Notice” is used to address practices that could lead to property damage but not to injury.
Q 409933_03
5 Copyright © 2013 INVENTIO AG
1.2.2
Safety Guidelines DANGER
Work inside Step/Pallet Band Do not perform any work inside the step/pallet band before switching off and padlock the main switch JHA. This will prevent starting the unit by mistake. DANGER Emergency Stop Button JHRE As a matter of principle, always press the emergency stop button JHRE at the location where work takes place. This will prevent starting the unit by mistake. DANGER Unauthorized Access Secure the unit against accidental or unauthorized access. Set up warning signs and barriers to alert passengers to the fact that the unit is not in use. DANGER Bypassing Contacts As a matter of principle, it is strictly prohibited to bypass any contacts. This will prevent the unit for unsafe condition. DANGER High Voltage Contact to high voltage will lead to death. Switch off the circuit breaker in the building and secure it against accidental or unauthorized access.
6 Copyright © 2013 INVENTIO AG
Q 409933_03
DANGER
1
No Passengers on the Unit During a Technical Test Passenger on the unit while running a technical test will result in death or serious injury. Do not allow any passengers on the unit while running a technical test. WARNING It is absolutely necessary to Perform the Learning Run before the First Run with the Key Switch If the learning run is not performed correctly, malfunctions and incorrect error diagnoses could occur later on. Do not interrupt the learning run at any time by turning off the unit or resetting any PCBs. NOTICE Electrostatic Sensitive Device Printed circuit boards (PCBs) are equipped with electrostatic sensitive semiconductors. Thus beware of electrostatic discharge and direct contact with the semiconductors. – Ground yourself by touching the control cabinet for electrostatic discharge. – Do not directly touch the PCB components. – Always use the original antistatic packing when transporting the PCBs. Only appropriate tools, devices and materials may be used. The specifications on the safety data sheet for lubricants (oils, greases, etc.) must be met.
Q 409933_03
7 Copyright © 2013 INVENTIO AG
All types The following five safety rules must be observed: 1
5
Before starting maintenance work, put up barriers to protect passers-by and "Out of Order" signs (if hinged floor covers are used, they must be properly opened and locked). As soon as a floor cover has to be removed (or folded up) and before entering the pit, connect the maintenance operating panel. Perform all trial runs with the maintenance operating panel. When carrying out maintenance work inside the step/pallet band, turn off and padlock the main switch in the machine room. Never turn on escalators or moving walks under load.
8
Q 409933_03
2 3 4
Copyright © 2013 INVENTIO AG
1.2.3
Safety Gear
1
All persons involved must know and follow all company and local safety regulations. In addition to protective clothing, wear the shown safety gear.
Hard hat or bump cap Safety goggles
Safety shoes
Q 409933_03
Hearing protection
Protective gloves
9 Copyright © 2013 INVENTIO AG
1.3
Abbreviation
Abbreviation
Explanation
_
Blank space
Wildcard character
[] or []
Display MICONIC F 5S or F 5E
[]/[]
Alternating display
ALCDG
Graphic plain text display
BMS
Building management system
Bus
Communication system
EoS
Engineer on Site
nEoS
Engineer on Site not active
MIC
MICONIC
FCOM
Maintenance software
Flash
Program, parameter and error memory
GFU
Frequency converter
IO
Inspection operation
Jumper
Bridge between two male connectors
LR
Learning run
P
Parameter
PCB
Printed circuit board
PA
PCB in the external control cabinet
PB
PCB in the bottom control cabinet
PT
PCB in the top control cabinet
P2
PCB, contract-specific position
P3
PCB, contract-specific position
PEM50.Q
PB for MICONIC F 5S
PEM51.Q
PT for MICONIC F 5S
PEM52.Q
PCB for MICONIC F 5E
10 Copyright © 2013 INVENTIO AG
Q 409933_03
Abbreviation
Explanation
RAM
Random access memory
RS-232
Interface for FCOM4 or BMS
1
RS-485 X2.9 - 13
Interface for connecting a number of PCBs
RS-485 X5.1 - 4
Interface for BMS or ALCDG
RTC
Real time clock
Semi5
Interface connector X8 for FCOM5
Semi5-Card
Memory card with access rights
0x0000
Number in hex format
O
Operator access level
M
Maintenance access level
S
Specialist access level
1.4
MICONIC Replacement Overview MICONIC Replacement Overview
PCB PEM4.Q
System Software
Use for
V35XX
MIC F 3
V40XX
MIC F 4
Service Software
Tool
FCOM4
RS232-Cable
FCOM5
Semi5-Cable
PEM50.Q
V51XX
PEM51.Q
V53XX
PEM52.Q Rev. A
V49XX
MIC F 3/F 4 FCOM4
RS232-Cable
V49XX
MIC F 3/F 4 FCOM4
RS232-Cable, Semi5-Card
V52XX V54XX
MIC F 5E
RS232-Cable, Semi5-Card
PEM52.Q Rev. B or higher
Q 409933_03
MIC F 5S
FCOM5
11 Copyright © 2013 INVENTIO AG
Software verification @ PEM52.Q The first two numbers of the software version must be identical with the control cabinet sticker. With software V5113, V5301, V5240 or V5414, the software version will be displayed at power up for two seconds. Set all DIL switches to the OFF position. Power up the PCB. – V49XX: The display shows [F_P0] – V52XX or V54XX: The display shows [F_P_]. PCB Identification The revision is marked by means of a black dot next to the ID. No.
[49632; 16.12.2013]
12 Copyright © 2013 INVENTIO AG
Q 409933_03
2 2.1
MICONIC F 5S Hardware PEM50.Q and PEM51.Q
29
Identification
2
X2 1
PEM50
OK
9
X8 1
X1 10
14
PP16 PP15 PP14
ON OFF
S7
1
15
RESE T
23
LED
PEM50.Q (PB) [27454; 16.12.2013]
Q 409933_03
13 Copyright © 2013 INVENTIO AG
29
Identification
X2 1
PEM51
OK
9
X7
1
X8 1
PP16 PP15 PP14
X1 10
14
15
RESE T
23
LED
PEM51.Q (PT) [27099; 16.12.2013]
14 Copyright © 2013 INVENTIO AG
Q 409933_03
2.1.1
Display and Button
The PCBs are equipped with a two-digit digital display (eight segments), an OK button to acknowledge errors, select and perform technical tests, a DIL switch array (only PB) and an LED which flashes when the software is running.
2 2.1.2
DIL Switches WARNING
Wrong DIL Switch Settings Wrong DIL switch settings could result in malfunctions. Always set the DIL switches according to the control cabinet sticker. Software V51XX: DIL Switch S7/1
Function No function
S7/2
ON
S7/3
ON
Copy parameters to PB
S7/4
ON
Copy parameters to PT
S7/5
ON
Activate technical test menu
S7/6
ON
Activate technical test
S7/7
ON
Activate learning run
S7/8
ON
Display of braking distance Bootloader if required
Q 409933_03
Update software to another PCB
15 Copyright © 2013 INVENTIO AG
Software V53XX: DIL Switch S7/1 S7/2 S7/3 S7/4
Function No function
ON
Update software to another PCB
ON
Activate technical test menu Copy parameters to PB, if required
ON
Activate technical test Copy parameters to PT, if required
S7/5
ON
Technical test for safety brake contact
S7/6
ON
Technical test for motor speed initiator
S7/7
ON
Activate learning run
S7/8
ON
Display of braking distance Bootloader if required
2.1.3
Jumper WARNING
Wrong Jumper Settings Wrong jumper settings could result in malfunctions. Always set the jumper according to the control cabinet sticker. Jumper PP14 - PP15 = RS-485 X2.9 - 13 terminated with 120 . Jumper PP15 - PP16 = RS-485 X2.9 - 13 not terminated.
16 Copyright © 2013 INVENTIO AG
Q 409933_03
2.1.4
Control Cabinet Sticker
The control cabinet sticker contains the DIL switch setting, the jumper setting, all unit-specific parameters and the software version. This software version indicates the minimum requirement. The unit may be equipped with a higher software version.
2
Example for PT
Example of Control Cabinet Sticker PT [27633; 14.06.2010]
Example for PB
Example of Control Cabinet Sticker PB [27635; 14.06.2010]
Q 409933_03
17 Copyright © 2013 INVENTIO AG
2.2
Operating Messages Operating messages marked with an asterisk []* are described in more details next to the overview. The operating state is shown on all displays alternately with the last error. Only the PCB display shows boot-up messages.
Display
Meaning
[bo]
No software installed
[_o]
System is busy. Wait until rotation stops
[oo]
Software is updating. Wait until rotation stops
[02] [38]
System boot-up (not all numbers are shown)
[J1]
Application start
[J2]*
DIL switches not in startup position
[J3]*
Parameters do not match
[J4]
Ready to copy parameters to PB
[J5]
Ready to copy parameters to PT
[J6]*
Software of PCBs is not compatible
[J7]*
Software versions of PCBs do not match
[J8]
Ready to copy software to PT
[J9]
Ready to copy software to PB
[JA]
Short circuit at +24 VDC output of PT
[Pt]
Display of PCB address during boot-up of PT
[Pb]
Display of PCB address during boot-up of PB
[..]
Engineer on Site
[r.0.]
Inspection operation
[d0]
Unit ready for operation
18 Copyright © 2013 INVENTIO AG
Q 409933_03
Display
Meaning
[d]
Continuous operation
[A]
Automatic operation
[d]
Down
[u]
Up
[00]
Key switch not in the OFF position
[o]
Learning run is active
2
[J2] - DIL switches not in startup position Set all DIL switches according to the control cabinet sticker. – An automatic boot-up is performed if all DIL switches are in the correct position.
[J3] - Parameters do not match No or all PCBs were replaced: – Use FCOM5 to set parameters to default – Set parameters according to the control cabinet sticker. Only PB was replaced: – Set the DIL switch S7/3 at PB to the ON position. The display shows [J4]. – Press the OK button at PB. The parameters are copied from PT to PB. After an automatic boot-up the display shows [J2]. – Set the DIL switches according to the control cabinet sticker. Only PT was replaced: – Set the DIL switch S7/4 at PB to the ON position. The display shows [J5]. – Press the OK button at PT. The parameters are copied from PB to PT. After an automatic boot-up the display shows [J2]. – Set the DIL switches according to the control cabinet sticker.
Q 409933_03
19 Copyright © 2013 INVENTIO AG
[J6] - Software of PCBs is not compatible Check if the correct PCBs are used. Check with FCOM5 if the first two numbers of the software version of all PCBs are identical and according to the control cabinet sticker.
[J7] - Software versions do not match The software of the PCBs is compatible but the versions are different. Update the software between the PCBs: Set the DIL switch S7/2 at PB to ON position. An alternating display shows the following information: – PCB with the higher software version ([J8] = PB, [J9] = PT) – Blank display – First two digits of higher software version ([51] for V5102) – Last two digits of higher software version ([02] for V5102) – Blank display. Press the OK button at the PCB with the lower software version. The OK button works only at the PCB with the lower software version. The software will be copied to the PCB where the OK button was pressed. The display on the source PCB will show [_o] in a rotating manner, the target PCB [oo]. The software update takes some time. Set the DIL switches according to the control cabinet sticker.
20 Copyright © 2013 INVENTIO AG
Q 409933_03
2.3
Error Messages Recurring errors are electronically interlocked.
Confirm Errors When an error is shown on the display permanently, the cause of the error still exists and the error cannot be confirmed until the cause of the error has been removed. When an error is shown flashing at the display it can be confirmed by pressing the OK button or DRES1 for at least one second. The display shows the next error if additional errors have occurred. Display
Error Message
Abbr.
[01]
24-VDC short circuit PT
P0T
[10]
Combplate contact, top left
KKP-TL
Q 409933_03
Note Interlocked
Correction Check 24-VDC
Check: Combs for damage Steps for damage Combplate: – returns to initial position – side adjusting screws are set too tightly – touches skirt panel – antilift screws are set too low – support plate is very dirty
21 Copyright © 2013 INVENTIO AG
2
Display
Error Message
Abbr.
Note
Correction
[11]
Handrail entry contact, top left
KHLE-TL
Check: Handrail entry for trapped objects Rubber collar for damage Rubber collar for correct setting Contact setting
[12]
Skirt contact, top
KSL-T
Check: Objects trapped between step and skirting Visible damage of steps or skirting
[14]
Emergency stop
DH
Check stop button for damage
[15]
Combplate contact, bottom left
KKP-BL
Check: Combs for damage Steps for damage Combplate: – returns to initial position – side adjusting screws are set too tightly – touches skirt panel – antilift screws are set too low – support plate is very dirty
22 Copyright © 2013 INVENTIO AG
Q 409933_03
Display [16]
[17]
[18]
[19]
Error Message
Abbr.
Handrail entry contact, bottom left
KHLE-BL
Chain tension contact
KKS-B
15% Motor overspeed
Drive chain contact, top right
Note
Correction Check: Handrail entry for trapped objects Rubber collar for damage Rubber collar for correct setting Contact setting
Interlocked
Confirm error
INBMG, INMH
Interlocked
Confirm error
KAK-T
Interlocked
Confirm error Release safety brake (if installed)
INAK-TR
Check: Step band Contact setting Spring tension Check: INBMG, INMH Sensor setting
Check: Chain tension Chain for excessive elongation Chain damage [1C]
Motor underspeed
INBMG, INMH
Interlocked Cause: Phase failure
Q 409933_03
Confirm error Check: INBMG, INMH Sensor setting All three phases of motor to ground
23 Copyright © 2013 INVENTIO AG
2
Display
Error Message
Abbr.
Note
Correction
Stop button, top
JH-T
Release JH-T
Step upthrust contact, top
KUS-T
Check for trapped objects: between riser and rear edge of next step between riser and skirting (during down travel)
[1F]
Skirt contact, bottom
KSL-B
Check: Objects trapped between step and skirting Visible damage of steps or skirting
[24]
PTC resistor, top
WTHM-T
Check motor temperature
[25]
Contactor dropout check
[28]
Step level contact, bottom
KKA-B
[2A]
PT: Stop button, top
JH-T
Release JH-T
[2C]
PB: Stop button, bottom
JH-B
Release JH-B
[1d]
24 Copyright © 2013 INVENTIO AG
Check if motor and brake contactors are dropped out Interlocked
Confirm error Check steps for damage and deflection
Q 409933_03
Display [2d]
Error Message Controlled drive failure
Abbr.
Note
GFU, GPH
Correction Check error message at GFU Bypass device if defective
[2F]
PT: Floor cover contact, top
KDMR-T
Check: Proper fit of floor cover in frame Contact setting
[30]
PT: 15% overspeed
INVK-T/B Interlocked
Confirm error
PT: underspeed
INVK-T/B Interlocked
Confirm error
[31]
[32]
PB: Handrail INHL-L monitor, left
Q 409933_03
2
Check: INVK-T, INVK-B Sensor setting Power supply of sensors Check: Drive chain for damage INVK-T, INVK-B Power supply of sensors Sensor setting Main contactors pick up All three phases of motor to ground Check: INHL-L Handrail speed Try to stop handrail manually
25 Copyright © 2013 INVENTIO AG
Display
Error Message
Abbr.
Note
Correction
[33]
PB: Handrail INHL-R monitor, right
Check: INHL-R Handrail speed Try to stop handrail manually
[34]
Service brake contact
Check: Power supply of brake solenoid Brake solenoid for malfunction
[35]
Safety brake MGBA
V53XX: Interlocked
Check: Pawl setting Pawl for free movement Lifting solenoid of pawl
[36]
Step level contact, top
KKA-T
Interlocked
Confirm error Check steps for damage and deflection
[38]
Initiator for braking distance measurement
INBMG
Initiator defective
Check: INBMG Sensor setting
[39]
PT: Missing step or pallet, top
INVK-T
Interlocked
Confirm error
26 Copyright © 2013 INVENTIO AG
MGB
Check: Step or pallet band for completeness INVK-T Power supply of sensors Sensor setting Q 409933_03
Display [3A]
Error Message
Abbr.
Note
Correction
PT: Initiator defective, top
INVK-T
PT: Missing step or pallet, bottom
INVK-B
[3C]
PT: Initiator defective, bottom
INVK-B
Check: INVK-B Power supply of sensors Sensor setting
[3E]
PB: 15% overspeed
INVK-T/B Interlocked
Confirm error
[3b]
Q 409933_03
Check: INVK-T Power supply of initiator Initiator setting Interlocked
2
Confirm error Check: Step or pallet band for completeness INVK-B Power supply of sensors Sensor setting
Check: INVK-T, INVK-B Power supply of sensors Sensor setting
27 Copyright © 2013 INVENTIO AG
Display [3F]
Error Message PB: underspeed
Abbr.
Note
INVK-T/B Interlocked
Correction Confirm error Check: Drive chain for damage INVK-T, INVK-B Power supply of sensors Sensor setting Main contactors pick up All three phases of motor to ground
[40]
PT contactor dropout check
Check if motor and brake contactors are dropped out
[41]
Key switch stop
Start unit
[44]
Parameter not set
Set parameter according to control cabinet sticker
[45]
RRE-A dropout check error
RRE-A
SRE-A dropout check error
SRE-A
Inspection outlet cover open
28 Copyright © 2013 INVENTIO AG
Close inspection cover Activate “Engineer on Site” Open inspection cover Check function of RRE-A Check function of SRE-A
Q 409933_03
Display
Error Message
Abbr.
Note
Correction
Handrail entry contact, top right
KHLE-TR
[49]
Handrail entry contact, bottom right
KHLE-BR
Check: Handrail entry for trapped objects Rubber collar for damage Rubber collar for correct setting Contact setting
[4A]
Combplate contact, top right
KKP-TR
Check: Combs for damage Steps for damage Combplate: – returns to initial position – side adjusting screws are set too tightly – touches skirt panel – antilift screws are set too low – support plate is very dirty
[48]
Q 409933_03
Check: Handrail entry for trapped objects Rubber collar for damage Rubber collar for correct setting Contact setting
29 Copyright © 2013 INVENTIO AG
2
Display
Error Message
Abbr.
Note
Correction
[4b]
Combplate contact, bottom right
KKP-BR
Check: Combs for damage Steps for damage Combplate: – returns to initial position – side adjusting screws are set too tightly – touches skirt panel – antilift screws are set too low – support plate is very dirty
[4E]
PT: Floor cover contact, bottom
KDMR-B
Check: Proper fit of floor cover in frame Contact setting
[4F]
Shutdown
Start unit
[50]
PT: Handrail INHL-L monitor, left
Check: INHL-L Handrail speed Try to stop handrail manually
[51]
PT: Handrail INHL-R monitor, right
Check: INHL-R Handrail speed Try to stop handrail manually
[57]
Engineer on EOS Site
Check if error is electronically interlocked
30 Copyright © 2013 INVENTIO AG
Q 409933_03
Display [62]
Error Message
Abbr.
Note
Correction
Crawling speed too slow
INBMG
[6C]
PT: SB dropout check
I-SB
Check that the SB contactor is in idle state
[6d]
PT: SR-U dropout check
I-SR-U
Check SR-U, SR1U
[6E]
PT: SR-D dropout check
I-SR-D
Check SR-D, SR1D
[6F]
PT: Dropout check of motor contactors
I-SANTR
Check SY, SD, SFU, SN
[73]
PT: Service brake dropout check
MGB-L
[7C]
PB: Service brake dropout check
MGB-L
Check service brake for malfunction
[7d]
PB: SB dropout check
I-SB
Check SB
[7E]
PB: SR-U dropout check
I-SR-U
Check SR-U, SR1U
Q 409933_03
Check: Mechanical movement of unit Power of unit without load Parameter of GFU Function of GFU
Interlocked
Check service brake for malfunction
31 Copyright © 2013 INVENTIO AG
2
Display
Error Message
Abbr.
Correction Check SR-D, SR1D
[7F]
PB: SR-D dropout check
[80]
PB: Dropout I-SANTR check of motor contactors
Check SY, SD, SFU, SN
[81]
PT: SB pickup check
I-SB
Check SB picks up during travel
[82]
PB: SB pickup check
I-SB
Check SB picks up during travel
[83]
PT: SR-U pickup check
I-SR-U
Check SR-U, SR1-U pick up during travel
[84]
PB: SR-U pickup check
I-SR-U
Check SR-U, SR1-U pick up during travel
[85]
PT: SR-D pickup check
I-SR-D
Check SR-D, SR1-D pick up during travel
[86]
PB: SR-D pickup check
I-SR-D
Check SR-D, SR1-D pick up during travel
[87]
PT: Pickup check of motor contactors
I-SANTR
Check SY, SD, SFU, SN pick up during travel
[88]
PB: Pickup check of motor contactors
I-SANTR
Check SY, SD, SFU, SN pick up during travel
32 Copyright © 2013 INVENTIO AG
I-SR-D
Note
Q 409933_03
Display
Error Message
Abbr.
Note
Correction Check RB relay drops out
[89]
PB: RB contactor dropout check
RB
[8A]
PB: Motor underspeed
INMH
Interlocked
Check all three phases (measure between ground and phase) Check INMH – activate inspection operation – check speed – check sensor setting Confirm error
[8b]
PB: 15% motor overspeed
INBMG INMH
Interlocked
Confirm error
PB: 30% motor overspeed
INBMG INMH
Interlocked
Confirm error
PB: Floor cover contact, top
KDMR-T
[8C]
[8d]
Q 409933_03
2
Check: INBMG, INMH Sensor setting All three phases of motor to ground Check: INBMG, INMH Sensor setting All three phases of motor to ground Check: Proper fit of floor cover in frame Contact setting
33 Copyright © 2013 INVENTIO AG
Display
Error Message
Abbr.
Note
Correction
[8E]
PB: Floor cover contact, bottom
KDMR-B
[8F]
PB: Step level contact, top
KKA-T
Interlocked
Confirm error Check steps for damage and deflection
[90]
PT: Step level contact, bottom
KKA-B
Interlocked
Confirm error Check steps for damage and deflection
[91]
PT: Stop button, bottom
JH-B
[92]
PB: Service MGB brake pickup check
[94]
Stop button, top PT
[A0]
PB hardware reset
Check +24 VDC at P01
[A1]
PT hardware reset
Check +24 VDC at P01
[A6]
PB bus retry reset
Check: Bus connection Jumper setting
[A7]
PT bus retry reset
Check: Bus connection Jumper setting
34 Copyright © 2013 INVENTIO AG
JH-T
Check: Proper fit of floor cover in frame Contact setting
Release JH-B
Interlocked
Check: Power supply of brake solenoid Brake solenoid for malfunction Release JH-T
Q 409933_03
Display
Error Message
Abbr.
Note
Correction
[AC]
PB buffer full reset
Check parameter setting
[Ad]
PT buffer full reset
Check parameter setting
[b2]
PB wrong message reset
Update software
[b3]
PT wrong message reset
Update software
[b8]
PB-PB reset
Check +24 VDC at P01
[b9]
PT-PB reset
Check +24 VDC at P01
[bE]
PB time-out reset
Check jumper setting
[bF]
PT time-out reset
Check jumper setting
[C4]
PB-FCOM5 reset
Press RESET button on PB
[C5]
PT-FCOM5 reset
Press RESET button on PT
[CA]
PB-PT PCB reset
Press RESET button on PB and PT
[Cb]
Voltage reset
Check +24 VDC at P01
Q 409933_03
35 Copyright © 2013 INVENTIO AG
2
Display [CC]
Error Message
Abbr.
30% Motor overspeed
INBMG, INMH
Note Interlocked
Correction Confirm error Release safety brake (if installed) Check: INBMG, INMH Power supply of sensors Sensor setting
[CE]
PT: 30% overspeed
INVK-T/B Interlocked
Confirm error Release safety brake (if installed) Check: INVK-T, INVK-B Power supply of sensors Sensor setting
[CF]
PB: 30% overspeed
INVK-T/B Interlocked
Confirm error Release safety brake (if installed) Check: INVK-T, INVK-B Power supply of sensors Sensor setting
[d3]
Phase failure
36 Copyright © 2013 INVENTIO AG
RKPH
Measure all three phases to ground
Q 409933_03
Display
Error Message
Abbr.
Step upthrust contact, bottom
KUS-B
[dA]
Stop button, customerprovided
RHBS
[E7]
PB: Missing step or pallet, bottom
INVK-B
Braking distance exceeded
INBMG
PB: Initiator defective, top
INVK-T
[d8]
[EA]
[EC]
Q 409933_03
Note
Correction Check for trapped objects: – between riser and rear edge of next step – between riser and skirting (during down travel) Check function of RHBS
Interlocked
Confirm error
Interlocked
Confirm error
Check: Step or pallet band for completeness INVK-B Power supply of sensor Sensor setting Check: Braking distance INBMG Power supply of sensor Sensor setting Check: INVK-T Power supply of sensor Sensor setting
37 Copyright © 2013 INVENTIO AG
2
Display [F0]
Error Message
Abbr.
Note
Confirm error
PB: Missing step or pallet, top
INVK-T
[F1]
PB: Initiator defective, bottom
INVK-B
[F2]
PT system check
Check parameter setting
[F3]
PB system check
Check parameter setting
[F4]
PT system check
Check parameter setting
[F5]
PB system check
Check parameter setting
[F6]
RB contactor dropout check
RB
Interlocked
Confirm error Check function of RB
[F7]
RGBA contactor dropout check
RGBA
Interlocked
Confirm error Check function of RGBA and RGBA1
38 Copyright © 2013 INVENTIO AG
Interlocked
Correction
Check: Step or pallet band for completeness INVK-T Power supply of sensor Sensor setting Check: INVK-B Power supply of sensor Sensor setting
Q 409933_03
2.4
Technical Tests with V51XX With FCOM5 additional technical tests are available.
2.4.1
[t1] - Step/Pallet Absence PT
Remove one maintenance step/pallet. Set the DIL switch S7/5 at PB to the ON position and wait until the display shows [t1]. Set the DIL switch S7/6 at PB to the ON position to activate the technical test and wait until the display shows [t1]. Start the unit with the key switch in the UP direction and wait until the unit stops. Set the DIL switches S7/5 and S7/6 at PB to the OFF position. An error will be shown on the display: – Error [3.9.] (missing step/pallet top) if PT detects a missing step/pallet at the top. – Error [3.b.] (missing step/pallet bottom) if PT detects a missing step/pallet at the bottom. Confirm the error. Repeat the process to verify the opposed stop. Install the missing maintenance step/pallet.
Q 409933_03
39 Copyright © 2013 INVENTIO AG
2
2.4.2
[t2] - Step/Pallet Absence PB
Remove one maintenance step/pallet. Set the DIL switch S7/5 at PB to the ON position and wait until the display shows [t1]. Press the OK button at PB one time until the display shows [t2]. Set the DIL switch S7/6 at PB to the ON position to activate the technical test and wait until the display shows [t2]. Start the unit with the key switch in the UP direction and wait until the unit stops. Set the DIL switches S7/5 and S7/6 at PB to the OFF position. An error will be shown on the display: – Error [F.0.] (missing step/pallet top PB) if PB detects a missing step/pallet at the top. – Error [E.7.] (missing step/pallet bottom PB) if PB detects a missing step/pallet at the bottom. Confirm the error. Repeat the process to verify the other function. Install the missing maintenance step/pallet.
2.4.3
[t3] - Motor Speed Check
Set the DIL switch S7/5 at PB to the ON position and wait until the display shows [t1]. Press the OK button at PB two times until the display shows [t3]. Set the DIL switch S7/6 at PB to the ON position to activate the technical test and wait until the display shows [t3]. Start the unit with the key switch in up direction and let it run for 20 seconds. Activate and hold the following controls until the unit stops: – Key switch in DOWN direction for error [1.C.] (motor underspeed). – Key switch in UP direction for error [1.8.] (motor overspeed 15%). – OK button on PB for error [C.C.] (motor overspeed 30%). Set the DIL switches S7/5 and S7/6 at PB to the OFF position. Confirm the error. To release the pawl of the safety brake - if installed - start the unit in the UP direction. Repeat the process to verify all other functions. 40 Copyright © 2013 INVENTIO AG
Q 409933_03
2.4.4
[t4] - Step/Pallet Band Speed PT
Set the DIL switch S7/5 at PB to the ON position and wait until the display shows [t1]. Press the OK button at PB three times until the display shows [t4]. Set the DIL switch S7/6 at PB to the ON position to activate the technical test and wait until the display shows [t4]. Start the unit with the key switch in up direction and let it run for 20 seconds. Activate and hold the following controls until the unit stops: – Key switch in DOWN direction for error [3.1.] (PT underspeed). – Key switch in UP direction for error [3.0.] (PT overspeed 15%). – OK button on PB for error [C.E.] (PT overspeed 30%). Set the DIL switches S7/5 and S7/6 at PB to the OFF position. Confirm the error. To release the pawl of the safety brake - if installed - start the unit in the UP direction. Repeat the process to verify all other functions.
2.4.5
[t5] - Step/Pallet Band Speed PB
Set the DIL switch S7/5 at PB to the ON position and wait until the display shows [t1]. Press the OK button at PB four times until the display shows [t5]. Set the DIL switch S7/6 on PB to the ON position to activate the technical test and wait until the display shows [t5]. Start the unit with the key switch in up direction and let it run for 20 seconds. Activate and hold the following controls until the unit stops: – Key switch in DOWN direction for error [3.F.] (PB underspeed). – Key switch in UP direction for error [3.E.] (PB overspeed 15 %). – OK button on PB for error [C.F.] (PB overspeed 30 %). Set the DIL switches S7/5 and S7/6 at PB to the OFF position. Confirm the error. To release the pawl of the safety brake - if installed - start unit in the UP direction. Repeat the process to verify all other functions. Q 409933_03
41 Copyright © 2013 INVENTIO AG
2
2.5
Technical Tests with V53XX With FCOM5 additional technical tests are available.
2.5.1
[t3] - Motor Speed Check
Set the DIL switch S7/3 at PB to the ON position and wait until the display shows [t3]. Set the DIL switch S7/4 at PB to the ON position to activate the technical test and wait until the display shows [t3]. Start the unit with the key switch in up direction and let it run for 20 seconds. Activate and hold the following controls until the unit stops: – Key switch in DOWN direction for error [1.C.] (motor underspeed). – Key switch in UP direction for error [1.8.] (motor overspeed 15%). – OK button on PB for error [C.C.] (motor overspeed 30%). Set the DIL switches S7/3 and S7/4 at PB to the OFF position. Confirm the error. Repeat the process to verify all other functions.
2.5.2
[t4] - Step/Pallet Band Speed PT
Set the DIL switch S7/3 at PB to the ON position and wait until the display shows [t3]. Press the OK button at PB until the display shows [t4]. Set the DIL switch S7/4 at PB to the ON position to activate the technical test and wait until the display shows [t4]. Start the unit with the key switch in up direction and let it run for 20 seconds. Activate and hold the following controls until the unit stops: – Key switch in DOWN direction for error [3.1.] (PT underspeed). – Key switch in UP direction for error [3.0.] (PT overspeed 15%). – OK button on PB for error [C.E.] (PT overspeed 30%). Set the DIL switches S7/3 and S7/4 at PB to the OFF position. Confirm the error. Repeat the process to verify all other functions.
42 Copyright © 2013 INVENTIO AG
Q 409933_03
2.5.3
[t5] - Step/Pallet Band Speed PB
Set the DIL switch S7/3 at PB to the ON position and wait until the display shows [t3]. Press the OK button at PB until the display shows [t5]. Set the DIL switch S7/4 on PB to the ON position to activate the technical test and wait until the display shows [t5]. Start the unit with the key switch in up direction and let it run for 20 seconds. Activate and hold the following controls until the unit stops: – Key switch in DOWN direction for error [3.F.] (PB underspeed). – Key switch in UP direction for error [3.E.] (PB overspeed 15%). – OK button on PB for error [C.F.] (PB overspeed 30%). Set the DIL switches S7/3 and S7/4 at PB to the OFF position. Confirm the error. Repeat the process to verify all other functions.
2.5.4
[t6] - Motor Speed Check
Set the DIL switch S7/3 at PB to the ON position and wait until the display shows [t3]. Press the OK button at PB until the display shows [t6]. Set the DIL switch S7/4 at PB to the ON position to activate the technical test and wait until the display shows [t6]. Start the unit with the key switch in up direction and let it run for 20 seconds. Activate and hold the following controls until the unit stops: – Key switch in DOWN direction for error [8.A.] (motor underspeed). – Key switch in UP direction for error [8.b.] (motor overspeed 15%). – OK button on PB for error [8.C.] (motor overspeed 30%). Set the DIL switches S7/3 and S7/4 at PB to the OFF position. Confirm the error. Repeat the process to verify all other functions.
Q 409933_03
43 Copyright © 2013 INVENTIO AG
2
2.6
Braking Distance With software version < V5113 or < V5301, measure the braking distance manually or with FCOM5.
Set DIL switch S7/8 at PB to the ON position. Start the unit with the key switch in down direction and let it run for 20 seconds. Interrupt the safety circuit. – The display shows the braking distance [-*]/[**] = *** centimeters. Set the DIL switch S7/8 to OFF position.
2.7
Parameters Parameter settings are only possible via FCOM5. Incorrect settings may cause malfunctions. Any change of a parameter must be approved by the Escalator Competence Center in Vienna and must be documented on all control cabinet stickers. LR indicates a parameter which is calculated during the learning run.
Establish the connection with FCOM5. Choose menu [Configure] - [Parameters] to change, load, save and set parameter values to default. Par. No. P000
Parameter YDMAXTIME
Default 70
Range [Unit] 1–100 [0.1 s]
P001
HANDRAILTIME
50
0–100 [0.1 s]
P002
ECOMAXTIME
44 Copyright © 2013 INVENTIO AG
60
Description Maximum starting time in Y operation Delay of handrail speed monitor errors
60–1000 Maximum operation time [s]
Q 409933_03
Par. No.
Parameter
P008
LUBRICATIONPAUSE-KM
25
AUTOMATICTIME
V51XX: 12–9999 Time for 60 automatic [s] operation V53XX:
P016
Default
Range [Unit] 5–9999
Description Lubrication pause
[km]
2
9999 P017
DHBUZZERTIME
V51XX: 0–9999 0 [s]
P041
SWITCHOVER TIME SFU SN
V53XX: 60–2000 Switchover time 100 [ms] SFU SN
P042
SWITCHOVER TIME SN SFU
V53XX: 60–2000 Switchover time 400 [ms] SN SFU
P047
INAK DELAY
V5111 0–400 V53XX: [ms] 200
Delay for INAK
P060
KOMPARA
0x 0000
0x00010xFFFF
Contract-specific parameter
P070
LEARNINGOFF
0
0–1
0: Learning run not completed
LR
Buzzer activation time after emergency stop
1: Learning run completed P080
SAFETYBRAKE
0
0–1
0: No safety brake 1: Safety brake installed
Q 409933_03
45 Copyright © 2013 INVENTIO AG
Par. No.
Parameter
P084
VALVE LUBRICATION
Default 2
Range [Unit] 0–2
Description Lubrication: 0: No electric 1: Downdraft with valve for pallet chain 2: Downdraft with multiple valve unit control
P085
BUZZERBEFORE START
V51XX: 0–1 0
0: No buzzer before start-up 1: Buzzer before start-up
P088 LR
HANDRAIL MONITORING
V51XX: 0–1 1
0: Handrail speed monitor inactive 1: Handrail speed monitor active
P089
BROKEN CHAIN SENSOR
0
P092
STEPABSENCE
P096
OPERATION MODE
0
0: KAK-T
1
1: INAK-TR
1
1
1: Steps
3
3: Pallets
0
0–1
0: No automatic operation
3
1: Automatic operation active 3: Automatic operation with skirt light barriers P097
AUTO_DRIVE ONLY
0
0–1
0: Continuous/ automatic operation 1: Automatic operation only
46 Copyright © 2013 INVENTIO AG
Q 409933_03
Par. No. P102
Parameter DOWN_ONLY
Default 0
Range [Unit] 0–1
Description 0: Key switch start in UP direction 1: Key switch start in UP direction not possible
P103
UP_ONLY
0
0–1
0: Key switch start in DOWN direction 1: Key switch start in DOWN direction not possible
P190
R&D SIMULATE
V51XX: 0 0
Only for development
P192
SPEEDEDGE NUMBER
2
Number of edges per 400 mm
2 6
2: Escalators 6: Moving walks P193
DRIVE
2
1
1: Y-starting
2
2: Direct starting
7
7: Y operation with switching to
12 13
12: GFU-C for escalators 13: GFU-C for moving walks
P201
DRIVE OPTION
V51XX: 0–1 0
0: Direct starting permissible 1: Y-starting required
P217
G-COUNTER RESET TIME
Q 409933_03
5
5–600 [min]
Time for recurring errors 47 Copyright © 2013 INVENTIO AG
2
Par. No.
Parameter
Default
Range [Unit] 0–20
Description
P218
COUNTER INTERLOCK (+G)
5
Number of recurring errors before interlocking
P250
HANDRAIL ROLLER SIZE
V53XX: 100–450 Handrail roller 340 size 750–850 [mm]
P251
NOMINAL SPEED
V53XX: 350–775 Rated speed 500 [mm/s]
P252
NUMBER MOTOR POLE PAIRS
V53XX: 4 6 6
Number of motor pole pairs
P253
RPM IMPULSES
V53XX: 6 6 12
6: Two holes in flywheel 12: Four holes in flywheel
P254 P256
RPM ECO CRAWLING
18
SPEEDRATED
V51XX: 10–5000 Nominal speed 10 [ms]
RPMRATED
10
LR P257
[%]
LR P258 P260
0–100
10–1000 Nominal speed of flywheel [ms]
RPMYDSWITCHIN 95 G
0–100
RPMECOLOW
0–100
95
[%] [%]
P261
RPMECOHIGH
105
0–120 [%]
P263 LR
BRAKEMEASURE FC
48 Copyright © 2013 INVENTIO AG
10
Minimum crawling speed
1–9999
Switching limit for Y-during start Lower switching limit for ECO Upper switching limit for ECO Conversion factor for braking distance measurement Q 409933_03
Par. No.
Parameter
P264
STEPLENGTH
V51XX: 0–9999 10
Step length factor for missing-step check
P265
GFUP-SPEED-01
V53XX: 50–60 50
Frequency for transportation speed
P268
BRAKEDISTANCE-MAX
V51XX: 0–300 120 [cm]
Maximum braking distance
P279
HANDRAIL MONITORING FACTOR
V51XX: 0–9999 10
Conversion factor for handrail speed check
HANDRAIL MONITORING ERROR
V51XX: 1–99 15 [%]
Tripping threshold for handrail speed error
LR P280
Q 409933_03
Default
Range [Unit]
Description
49 Copyright © 2013 INVENTIO AG
2
2.8
EoS Mode For inspection run and maintenance work the EoS mode must be activated.
2.8.1
Activation, Deactivation This functions are working only if the unit does not have a dedicated EoS switch. After 30 minutes of normal operation the EoS mode is deactivated if no technical test is activated and no button is pressed.
Activation Press and hold the emergency stop button DH while turning the key switch to both directions. – All displays showing [..] to indicate the EoS mode is active. Deactivation Press and hold the emergency stop button DH while turning the key switch to both directions. – All displays showing [] to indicate the EoS mode is not active.
50 Copyright © 2013 INVENTIO AG
Q 409933_03
2.9
Initiating the Learning Run It might be necessary to initiate the learning run after a software update.
The unit is ready to be started with the key switch and the display shows [d0] and the last error. Set the DIL switch S7/7 at PB to the ON position and wait until the display shows [Lr]. Set the DIL switch S7/7 at PB to the OFF position. All PCBs are rebooted. Wait until the display shows [d0] and the last error. Start the unit with the key switch. The unit will carry out the learning run indicated by a rotating [o*] on the display. Verify the correct indication of travel direction. After two minutes run without any stop the learning run will be completed and the standard display is activated.
Q 409933_03
51 Copyright © 2013 INVENTIO AG
2
2.10 Replacement
Press the emergency stop button at the bottom control cabinet. Switch off and padlock the main switch JHA. Mark all connectors before disconnection. Replace the defective PCB. Reconnect all connectors. Set the DIL switches and jumper according to the control cabinet sticker. Switch on the main switch JHA. Follow the display instruction. FCOM5 is required, if all PCBs were replaced: Set parameters to default Set parameters according to the control cabinet sticker. Release the emergency stop button at the bottom control cabinet. Initiate the learning run, if all PCBs were replaced.
52 Copyright © 2013 INVENTIO AG
Q 409933_03
3 3.1
MICONIC F 5E Hardware PEM52.Q
X3
X6
PEM52.Q revision A is only suitable for MIC F 3 or F 4 replacement but not for MIC F 5E.
1
1
29
A B C D
1
X1 1
RS232
X2 1
PP33 PP32 PP31 X5
ESC DOWN UP
5
OK
9
X7
1
X8 1
PP16 PP15 PP14
10
14
S7 ON OFF
1
15
RESET
20
21
23
X15 X12
LED
Identification
33
X11
3
PEM52.Q [27456; 09.12.2013]
Q 409933_03
53 Copyright © 2013 INVENTIO AG
3.1.1
Display and Button
The PCB is equipped with a four-digit digital display (eight segments), four buttons (ESC, DOWN, UP, OK) to operate the menu, set parameters, acknowledge errors, an DIL-switch array and an LED which flashes when the software is running.
3.1.2
DIL Switches WARNING
Wrong DIL switch settings Wrong DIL switch settings could result in malfunctions. Always set the DIL switches according to the control cabinet sticker. DIL Switch
Function
PCB address PT
PB
PA
P2
P3
S7/1
PCB address
S7/2
PCB address
OFF ON OFF ON
S7/3
PCB address
OFF OFF ON OFF ON
S7/4
Default parameter record
S7/5
Default parameter record
S7/6
No function
S7/7
ON = Set parameters to default
S7/8
ON = Copy software from Semi5-Card
54 Copyright © 2013 INVENTIO AG
ON OFF OFF ON OFF ON
Q 409933_03
3.1.3
Jumper WARNING
Wrong jumper settings Wrong jumper settings could result in malfunctions. Always set the jumper according to the control cabinet sticker. Jumper PP14 - PP15 = RS-485 X2.9 - 13 terminated with 120 . Jumper PP15 - PP16 = RS-485 X2.9 - 13 not terminated.
3
Jumper PP31 - PP32 = RS-485 X5.1 - 4 terminated with 120 . Jumper PP32 - PP33 = RS-485 X5.1 - 4 not terminated.
3.1.4
Semi5-Card Reader
A Semi5-Card, a memory card with an authorized access level, can be used to read and write data from or to the Semi5-Card and give access to different main menu function.
3.1.5
Control Cabinet Sticker
The control cabinet sticker contains the DIL switch setting, the jumper setting, all unit-specific parameters, required PCB revision and the software version. The PCB revision and software version indicates only the minimum requirement. The unit may be equipped with a higher PCB revision and software version. Example for PT
Example of Control Cabinet Sticker PT [34136; 19.05.2010]
Q 409933_03
55 Copyright © 2013 INVENTIO AG
Example for PB
Example of Control Cabinet Sticker PB [34137; 19.05.2010]
Example for PA
Example of Control Cabinet Sticker PA [34135; 19.05.2010]
56 Copyright © 2013 INVENTIO AG
Q 409933_03
3.2
Operating Messages Operating messages marked with an asterisk []* are described in more details next to the overview. The operating state is shown on all displays alternately with the last error.
Display
Meaning
[F1]
Initializing after power on
[Fb]
Wrong or no message from PB
[FC]
Wrong or no message from PA
3
[Fd]
Wrong or no message from P2
[FE]
Wrong or no message from P3
[F0] [F5]
System boot-up (not all numbers are shown)
[FA]
Restoring history
[FP]
Indicates the PCB during boot-up
[__P]
Indicates the PCB
[J000]
Application start
[FALS]
Error during boot-up
[boot] [StAY] [hErE]
Display of PEM4.Q. Invalid mix of PEM4.Q and PEM52.Q
[dIL_] [J002]*
Wrong DIL switch setting
[IPL_] [J003]*
Double input assignment. Two parameter numbers are shown additionally.
[OPL_] [J004]*
Double output assignment. Two parameter numbers are shown additionally.
[rtc_] [J006]*
Real time clock not set
Q 409933_03
57 Copyright © 2013 INVENTIO AG
Display
Meaning
[PArA] [J007]*
Parameter do not match. Value of P0060 of all PCBs are shown additionally.
[StIC] [J011]*
Contract-specific parameters not set
[Soft] [J220]*
Software versions of PCBs do not match. Software version of all PCBs are shown additionally.
[Prin] [__P*]
Wrong boot loader or hardware
[too_] [hot_]
Temperature value exceeded
[CAUt]
Warning message
[Lub_]
Lubrication warning
[done]
Operation completed
[FdEL]
Set parameter to default
[P060]
Parameter P0060
[bo]*
No software installed
[b]
Normal operation. The last error is shown additionally.
[.]
Safety circuit interruption @ EoS
[.]
JREMACT off
[..]
EoS mode
[r]
EoS mode
[nEoS]
EoS mode not activated
[r.0.]
Inspection operation
[d0]
Unit ready for operation
[d]
Continuous operation
[A]
Automatic operation
[c]
Direction change operation
[d]
Down direction
58 Copyright © 2013 INVENTIO AG
Q 409933_03
Display
Meaning
[u]
Up direction
[L]
Learning run in progress
[00]
Checks in progress
[LC]
Light curtain active
[oF]
“Operation possible” deactivated. Remote control active.
[b_oF]
Semi5-Card in the slot while EoS is off.
[CArd]
Semi5-Card in the slot with DIL S7/8 in ON position.
3
[J002] - DIL switches not in startup position Set all DIL switches according to the control cabinet sticker. An automatic boot-up is performed if all DIL switches are in the correct position.
[J003] - Double input assignment Verify that the indicated parameters are according to the control cabinet sticker.
[J004] - Double output assignment Verify that the indicated parameters are according to the control cabinet sticker.
[J006] - Set RTC Set the RTC to local time. – Refer to the chapter “[U__r] - Set RTC”.
Q 409933_03
59 Copyright © 2013 INVENTIO AG
[J007] - Parameters do not match Press the OK button. The display shows [__Pt]. Use the DOWN button to select the PCB which contains the parameter P0060 according to the control cabinet sticker. Press the UP button to confirm the selected PCB. – The display starts to flashing. Press the OK button to copy the parameters from the selected PCB to all other PCBs.
[J011] - Parameters not set Press the UP and DOWN buttons simultaneously to continue the boot-up. Set all parameters to default. Set all parameters according to the control cabinet sticker.
[J220] - Software versions do not match The display will show the software version on all PCBs one by one. Press the OK button. The display shows [__Pt]. Use the DOWN button to select the source PCB. – The PCB must contain a software version according to the control cabinet sticker. Press the UP button to confirm the selected PCB. – The display starts to flashing. Press the OK button to copy the software from the selected PCB to all other PCBs.
[bo] - No software installed PEM52.Q revision A is only suitable for MIC F 3 or F 4 replacement but not for MIC F 5E. Verify that the revision of the PCB meets the requirements according to the control cabinet sticker. Copy new software according to the control cabinet sticker. 60 Copyright © 2013 INVENTIO AG
Q 409933_03
3.3
Warning Messages Warning messages which are not reset automatically can be reset by pressing the OK button while the unit is in EoS mode.
Display
Meaning
[CAUt]
Warning
[Lub_]
Lubrication warning
[LU01]
Oil level too low
[LU02]
System leakage
[LU03]
Oil level 2 too low
[LU11]
MGSKS-R does not open
[LU12]
MGSKS-L does not open
[LU13]
MGSKA-R does not open
[LU14]
MGSKA-L does not open
[LU15]
MGSKHL does not open
[LU16]
MGSKHL-R does not open
[LU17]
MGSKHL-L does not open
[LU18]
Lubrication, pressure not built up
[LU21]
MGSKS-R has not opened at least once
[LU22]
MGSKS-L has not opened at least once
[LU23]
MGSKA-R has not opened at least once
[LU24]
MGSKA-L has not opened at least once
[LU25]
MGSKHL has not opened at least once
[LU26]
MGSKHL-R has not opened at least once
[LU27]
MGSKHL-L has not opened at least once
[t_r0]/ [_oFF]
Maintenance period exceeded
Q 409933_03
3
61 Copyright © 2013 INVENTIO AG
Display [too_]/ [hot_]/ [__P]
3.4
Meaning Overtemperatur warning for P PCB
Error Messages A recurring error is electronically interlocked.
Reset according to EN 115 When an error is shown on the display permanently, the cause of the error still exists and the error cannot be confirmed until the cause of the error has been removed. When an error is shown flashing in the display it can be confirmed with the OK button or DRES1 or DRES2. The display shows an error again if additional errors have occurred. Reset according to ANSI The display shows [E_Er] if an interlocked error has occurred. Press DRES2 or DRES3 to show the respective error code. Press the OK button or DRES1 to show the respective error code. The display shows [E_Er] again if additional interlocked errors have occurred. Display Error Message
Abbr.
Note
Correction
[E_01]
PT: 24-VDC short circuit
P0T
Interlocked
Check 24 VDC at PT
[E_02]
PB: 24-VDC short circuit
P0B
Interlocked
Check 24 VDC at PB
[E_03]
PA: 24-VDC short circuit
P0A
Interlocked
Check 24 VDC at PA
[E_04]
PT: 24-VDC short circuit
P0T
Interlocked
Check 24 VDC at PT
62 Copyright © 2013 INVENTIO AG
Q 409933_03
Display Error Message
Abbr.
[E_05]
PB: 24-VDC short circuit
P0B
[E_10]
Combplate KKP-TL contact, top left
Note Interlocked
Correction Check 24 VDC wiring at PB Check: Combs for damage Steps for damage Combplate: – returns to initial position – side adjusting screws are set too tightly – touches skirt panel – antilift screws are set too low – support plate is very dirty
[E_11]
Handrail entry KHLEcontact, top left TL
Check: Handrail entry for trapped objects Rubber collar for damage Rubber collar for correct setting Contact setting
[E_12]
Skirt contact, top
KSL-T
Check: Objects trapped between step and skirting Visible damage of steps or skirting
[E_14]
Emergency stop
DH
Check stop button for damage
Q 409933_03
63 Copyright © 2013 INVENTIO AG
3
Display Error Message
Abbr.
Note
Correction
[E_15]
Combplate KKP-BL contact, bottom left
Check: Combs for damage Steps for damage Combplate: – returns to initial position – side adjusting screws are set too tightly – touches skirt panel – antilift screws are set too low – support plate is very dirty
[E_16]
Handrail entry KHLEcontact, bottom BL left
Check: Handrail entry for trapped objects Rubber collar for damage Rubber collar for correct setting Contact setting
[E_17]
Chain tension contact
KKS-B
Interlocked
Confirm error
PT: 15% motor overspeed
INMH-R Interlocked
Confirm error
[E_18]
64 Copyright © 2013 INVENTIO AG
Check: Step band Contact setting Spring tension Check: INMHR Sensor setting Speed via [A_31] and [A_32] Q 409933_03
Display Error Message [E_19]
Drive chain contact, top right
Abbr. INAKTR KAKTR
Note Interlocked
Correction Confirm error Release safety brake (if installed) Check: Chain tension Chain for excessive elongation Chain damage
3
[E_1A]
Smoke detector, top
KBFMT
Check: Smoke formation Cause of smoke Respective component
[E_1b]
Handrail rupture, left
KHLB-L
Check handrail: Breakage or damage Tension
[E_1C]
PT: Motor underspeed
INMH-R Interlocked
Confirm error
Step upthrust contact, top
KUS-T
Check for trapped objects: – between riser and rear edge of next step – between riser and skirting (during down travel)
[E_1d]
Q 409933_03
Check: INMH-R Sensor setting Speed via [A_31] and [A_32] All three phases of motor to ground
65 Copyright © 2013 INVENTIO AG
Display Error Message [E_1E]
Abbr.
Combplate ITH-B heating, bottom
Note
Correction Remove ice and snow Check: Heating element PT100 sensor
[E_1F]
Skirt contact, bottom
KSL-B
Check: Objects trapped between step and skirting Visible damage of steps or skirting
[E_20]
Contact flywheel cover
KHR
Check contact setting
[E_22]
Stop button 1, top
JH1-T
Release JH1-T
[E_23]
Combplate contact, vertical, NYC, top
KKPYVT
Check: Combs for damage Steps for damage Combplate: – returns to initial position – side adjusting screws are set too tightly – touches skirt panel – antilift screws are set too low – support plate is very dirty
[E_24]
PT: PTC resistor, top
WTHMT
Check motor temperature
66 Copyright © 2013 INVENTIO AG
Q 409933_03
Display Error Message
Abbr.
Note
Correction Release JH1-B
[E_27]
Stop button 1, bottom
[E_28]
PT: Step level KKA-B contact, bottom
[E_29]
Combplate KKPYVcontact, B vertical, bottom
Check: Combs for damage Steps for damage Combplate: – returns to initial position – side adjusting screws are set too tightly – touches skirt panel – antilift screws are set too low – support plate is very dirty
[E_2A]
PT: Stop button, top
JH-T
Release JH-T
[E_2b]
Handrail rupture, right
KHLBR
Check handrail: Breakage or damage Tension
[E_2C]
PB: Stop button, bottom
JH-B
Release JH-B
[E_2d]
Controlled drive failure
KSGFU
Check error message at GFU Bypass device if defective
Q 409933_03
JH1-B Interlocked
Confirm error Check steps for damage and deflection
67 Copyright © 2013 INVENTIO AG
3
Display Error Message
Abbr.
Note
Correction
[E_2E]
Stop button, JH-A external control cabinet
Release JH-A
[E_2F]
PT: Floor cover KDMRcontact, top T
Check: Proper fit of floor cover in frame Contact setting
[E_30]
PT: 15% overspeed
INVK-T
InterINVK-B locked
Confirm error
PT: underspeed
INVK-T
InterINVK-B locked
Confirm error
PB: Handrail monitor, left
INHL-L
Check: INHL-L [t_07] Handrail speed Try to stop handrail manually
[E_31]
[E_32]
68 Copyright © 2013 INVENTIO AG
Check: INVK-T, INVK-B Sensor setting [t_05], [t_06] Power supply of sensors Check: Drive chain for damage INVK-T, INVK-B Power supply of sensors Sensor setting [t_05], [t_06] Main contactors pick up All three phases of motor to ground
Q 409933_03
Display Error Message
Abbr.
[E_33]
PB: Handrail monitor, right
INHL-R
[E_34]
PT: Service brake contact
MGB
[E_35]
Safety brake
MGB-L
Note
V54XX: Interlocked
MGBA
Check: Power supply of brake solenoid Brake solenoid for malfunction Check: Pawl setting Pawl for free movement Lifting solenoid of pawl
MGBAL
PT: Step level contact, top
[E_37]
Stop button 1, JH1-A external control cabinet
Release JH1-A
[E_38]
Drive motor initiator, right
Check: INMH-R Sensor setting Speed via [A_31] and [A_32]
INMH-R
Interlocked
Confirm error Check steps for damage and deflection
[E_36]
Q 409933_03
KKA-T
Correction Check: INHL-R [t_07] Handrail speed Try to stop handrail manually
69 Copyright © 2013 INVENTIO AG
3
Display Error Message
Abbr.
Note
Correction
PT: Missing step or pallet, top
INVK-T
InterINMH-R locked
Confirm error
[E_3A]
PT: Initiator defective, top
INVK-T
Check: INVK-T [t_05], [t_06] Power supply of initiator Initiator setting
[E_3b]
PT: Missing step or pallet, bottom
INVK-B InterINMH-R locked
Confirm error
PT: Initiator defective, bottom
INVK-B
Check: INVK-B [t_05], [t_06] Power supply of sensors Sensor setting
[E_39]
[E_3C]
70 Copyright © 2013 INVENTIO AG
Check: Step or pallet band for completeness Sensor [t_05], [t_06] Power supply of sensors Sensor setting
Check: Step or pallet band for completeness Sensor [t_05], [t_06] Power supply of sensors Sensor setting
Q 409933_03
Display Error Message [E_3E]
[E_3F]
Abbr.
Note
Correction
PB: 15% overspeed
INVK-T InterINVK-B locked
Confirm error
PB: underspeed
INVK-T InterINVK-B locked
Confirm error
Check: INVK-T, INVK-B [t_05], [t_06] Power supply of sensors Sensor setting
3
Check: Drive chain for damage INVK-T, INVK-B [t_05], [t_06] Power supply of sensors Sensor setting Main contactors pick up All three phases of motor to ground
[E_41]
Key switch stop
Restart unit
[E_42]
Skirt contact, KSLmiddle section, MT top
Check Trapped objects between step and skirting Visible damage of steps or skirting
[E_43]
Oil level main motor
Check oil level of main motor
[E_44]
Parameters lost
Q 409933_03
KOMH
Set parameter according to control cabinet sticker
71 Copyright © 2013 INVENTIO AG
Display Error Message [E_45]
Abbr.
RRE-A dropout RRE-A check error SRE-A dropout SRE-A check error Inspection outlet cover open
Note
Correction Close inspection cover Activate “Engineer on Site” Open inspection cover Check function of RRE-A, SRE-A JREMACT is off
[E_47]
Remote stop
JREMS TOP
Restart unit
[E_48]
Handrail entry contact, top right
KHLETR
Check: Handrail entry for trapped objects Rubber collar for damage Rubber collar for correct setting Contact setting
[E_49]
Handrail entry KHLEcontact, bottom BR right
Check: Handrail entry for trapped objects Rubber collar for damage Rubber collar for correct setting Contact setting
72 Copyright © 2013 INVENTIO AG
Q 409933_03
Display Error Message [E_4A]
[E_4b]
Combplate contact, top right
Abbr. KKPTR
Combplate KKPcontact, bottom BR right
Q 409933_03
Note
Correction Check: Combs for damage Steps for damage Combplate: – returns to initial position – side adjusting screws are set too tightly – touches skirt panel – antilift screws are set too low – support plate is very dirty Check: Combs for damage Steps for damage Combplate: – returns to initial position – side adjusting screws are set too tightly – touches skirt panel – antilift screws are set too low – support plate is very dirty
73 Copyright © 2013 INVENTIO AG
3
Display Error Message
Abbr.
Note
Correction
Safety circuit interruption
[E_4E]
PT: Floor cover KDMRcontact, bottom B
[E_4F]
Shutdown
[E_50]
PT: Handrail monitor, left
INHL-L
Check: INHL-L [t_07] Handrail speed Try to stop handrail manually
[E_51]
PT: Handrail monitor, right
INHL-R
Check: INHL-R [t_07] Handrail speed Try to stop handrail manually
[E_52]
Entrance monitoring
IRAD-T
Check: Entrance monitoring Activate display of operating data [A_03]
[E_53]
Seismic monitor
74 Copyright © 2013 INVENTIO AG
RSK
Check: No feedback Proper fit PCB of safety connector contacts Voltage along safety circuit
[E_4C]
Check: Proper fit of floor cover in frame Contact setting Restart unit
IRAD-B
KSEIS
Check Relay External evaluation
Q 409933_03
Display Error Message
Abbr. PHTK_ B
Note
Correction
[E_54]
Pit light barrier
[E_55]
Braking resistor KTHWF U
Check Contamination Resistance value
[E_56]
Glass cladding monitor
KGL
Check Proper seat of glass panel Contact setting
[E_57]
Engineer on Site
EOS
Check if error is electronically interlocked
[E_58]
Light curtain active too long
LV1-PE
Check Display of light curtain controller for defective light barriers Step band in the light curtain area for error
LV2-PE
Check Reflector Setting of light barrier
3
[E_62]
Crawling speed GFU-C too slow
Check: Mechanical movement of unit Power of unit without load Parameter of GFU Function of GFU
[E_63]
Water level monitor, top
KWS-T
Check drive station pit for water
[E_64]
Emergency stop, bottom
DH-B
Check stop button
Q 409933_03
75 Copyright © 2013 INVENTIO AG
Display Error Message
Abbr.
Note
Correction
[E_65]
Start command pending
Check key switches or start button for damage Check connection to BMS
[E_66]
Remote stop via communication
Check connection to BMS
[E_67]
PA system status
Check parameter setting
[E_68]
PB-PA system check
Check parameter setting
[E_69]
PA-PT system check
Check parameter setting
[E_6A]
PA-PB system check
Check parameter setting
[E_6b]
PT-PA system check
Check parameter setting
[E_6C]
PT: SB dropout I-SB check
Check function of SB
[E_6d]
PT: SR-U dropout check
I-SR-U
Check function of SR-U and SR1-U
[E_6E]
PT: SR-D dropout check
I-SR-D
Check function of SR-D and SR1-D
[E_6F]
PT: Dropout check motor contactors
ISANTR
Check function of SY, SD, SFU, SN
[E_70]
SGBF dropout check
I-SGBF
Check function of SGBF
[E_71]
SR1-U dropout I-SR1-U check
Check function of SR-U, SR1-U
[E_72]
SR1-D dropout I-SR1-D check
Check function of SR-D, SR1-D
76 Copyright © 2013 INVENTIO AG
Q 409933_03
Display Error Message [E_73]
PT: Service brake dropout check
Abbr. MGB MGB-L
Note V54XX: Interlocked
Correction Check function of service brake, MGB, MGB-L
[E_74]
Drive shut down
Restart unit
[E_75]
Drive chain INAKIntercontact, top left TL locked KAK-TL
Confirm error Release safety brake (if installed) Check: Chain tension Chain for excessive elongation Chain damage
[E_76]
Overheat monitoring of truss
PB board X6.1
Check: LHDC cable for short circuit 24 VDC 2–6.4 VDC at PB X 6.1
[E_77]
Evacuation
IEVAK1
Check: Safety relay Inputs
IEVAK2 [E_78]
[E_79]
End of evacuation
Fuse 110 VAC
Q 409933_03
IEVAK1
Interlocked
Confirm error
IEVAK2
Check: Reason for evacuation travel Error history
SIS2
Check 110 VAC control voltage
77 Copyright © 2013 INVENTIO AG
3
Display Error Message
Abbr.
Note
Correction
[E_7A]
Fuse main motor
SIHM
Check main motor fuses Check at double drive: – Equal load conditions
[E_7b]
Stop button, customerprovided
DHBS2
Check customerprovided stop button
[E_7C]
PB: Service brake dropout check
MGB-L
[E_7d]
PB: SB dropout I-SB check
Check SB
[E_7E]
PB: SR-U dropout check
I-SR-U
Check SR-U, SR1-U
[E_7F]
PB: SR-D dropout check
I-SR-D
Check SR-D, SR1-D
[E_80]
PB: Dropout check of motor contactors
ISANTR
Check SY, SD, SFU, SN
[E_81]
PT: SB pickup check
I-SB
Check SB picks up during travel
[E_82]
PB: SB pickup check
I-SB
Check SB picks up during travel
[E_83]
PT: SR-U pickup check
I-SR-U
Check SR-U, SR1-U pick up during travel
[E_84]
PB: SR-U pickup check
I-SR-U
Check SR-U, SR1-U pick up during travel
[E_85]
PT: SR-D pickup check
I-SR-D
Check SR-D, SR1-D pick up during travel
78 Copyright © 2013 INVENTIO AG
Interlocked
Check brake for malfunction
Q 409933_03
Display Error Message
Abbr.
Note
Correction
[E_86]
PB: SR-D pickup check
I-SR-D
Check SR-D, SR1-D pick up during travel
[E_87]
PT: Pickup check of motor contactors
ISANTR
Check SY, SD, SFU, SN pick up during travel
[E_88]
PB: Pickup check of motor contactors
ISANTR
Check SY, SD, SFU, SN pick up during travel
[E_89]
PB: RB contactor dropout check
RB
Check RB relay drops out
[E_8A]
PB: Motor underspeed
INMH-R Interlocked
Confirm error
PB: 15% motor INMH-R Interoverspeed locked
Confirm error
[E_8b]
Q 409933_03
Check: INMH-R Sensor setting Speed via [A_31] and [A_32] All three phases of motor to ground Check: INMHR Sensor setting Speed via [A_31] and [A_32]
79 Copyright © 2013 INVENTIO AG
3
Display Error Message [E_8C]
Abbr.
Note
PB: 30% motor INMH-R Interoverspeed locked
Correction Confirm error Release safety brake (if installed) Check: INBMG Speed via [A_31], [A_32] Power supply of sensors Sensor setting
[E_8d]
PB: Floor cover KDMRcontact, top T
Check: Proper fit of floor cover in frame Contact setting
[E_8E]
PB: Floor cover KDMRcontact, bottom B
Check: Proper fit of floor cover in frame Contact setting
[E_8F]
PB: Step level contact, top
KKA-T
Interlocked
Confirm error Check steps for damage and deflection
[E_90]
PB: Step level KKA-B contact, bottom
Interlocked
Confirm error Check steps for damage and deflection
[E_91]
PT: Stop button, bottom
JH-B
[E_92]
PB: Service brake pickup check
MGB
80 Copyright © 2013 INVENTIO AG
Release JH-B Interlocked
Check: Power supply of brake solenoid Brake solenoid for malfunction
Q 409933_03
Display Error Message
Abbr.
Note
Correction
[E_94]
PT: Stop button, top
JH-T
Release JH-T
[E_9d]
Emergency stop
DH-M
Check DH-M for damage
[E_9E]
Service brake control error
I-SBCERR
Check service brake control unit for error message
[E_9F]
Revision control error
I-RECERR
Check revision control unit for error message
[E_A0]
PB hardware reset
Check +24 VDC at P01
[E_A1]
PT hardware reset
Check +24 VDC at P01
[E_A2]
PA hardware reset
Check +24 VDC at P01
[E_A3]
P2 hardware reset
Check +24 VDC at P01
[E_A4]
P3 hardware reset
Check +24 VDC at P01
[E_A5]
Blocking device, left
[E_A6]
Step chain KKS-BL Intertension contact locked bottom, left
Confirm error
Step chain link contact, left
Check: Step chain Lubrication of step chain
[E_A7]
Q 409933_03
KBV-L
KKL-L
3
Remove blocking device Check: Step band Contact setting Spring tension
81 Copyright © 2013 INVENTIO AG
Display Error Message
Abbr.
Correction
Step chain link contact, right
[E_A9]
Communication RS232/ error RS4852
Check P0049
[E_b0]
PT reset
Check next error entry and correct
[E_b1]
PB reset
Check next error entry and correct
[E_b2]
PA reset
Check next error entry and correct
[E_b3]
P2 reset
Check next error entry and correct
[E_b4]
P3 reset
Check next error entry and correct
[E_b8]
Bus retry reset
Check connecting line
[E_b9]
Buffer full reset
Check of quickly activated inputs
[E_bA]
Wrong message reset
Check: Connecting line Incorrect devices connected
[E_bb]
Time-out reset
Check connecting line
82 Copyright © 2013 INVENTIO AG
KKL-R
Note
[E_A8]
Check: Step chain Lubrication of step chain
Q 409933_03
Display Error Message
Abbr.
Note
Correction
[E_bC]
Flash reset
Set parameter to default Program parameter according to control cabinet sticker
[E_Cb]
22 VAC voltage reset
Check 22 VAC supply
[E_CC] PT: 30 % Motor INMH-R Interoverspeed locked
3
Confirm error Release safety brake (if installed) Check: INBMG Speed via [A_31], [A_32] Power supply of sensors Sensor setting
[E_CE] PT: 30% overspeed
INVK-T InterINVK-B locked
Confirm error Release safety brake (if installed) Check: INVK-T, INVK-B [t_05], [t_06] Power supply of sensors Sensor setting
Q 409933_03
83 Copyright © 2013 INVENTIO AG
Display Error Message [E_CF]
PB: 30% overspeed
Abbr. INVK-T
Note
InterINVK-B locked
Correction Confirm error Release safety brake (if installed) Check: INVK-T, INVK-B [t_05], [t_06] Power supply of sensors Sensor setting
[E_d1]
Smoke detector, bottom
KBFMB
Check: Smoke formation Cause of smoke Respective component
[E_d2]
Skirt contact, middle
KSL-M
Check Trapped objects between step and skirting Visible damage of steps or skirting
[E_d3]
Phase failure
RKPH
Measure all three phases to ground Check direction of rotation of main line
[E_d4]
Rubber belt contact, top
KGB-T
Check rubber belt
[E_d5]
Rubber belt KGB-B contact, bottom
Check rubber belt
[E_d6]
Blocking device KBV
Check blocking device
84 Copyright © 2013 INVENTIO AG
Q 409933_03
Display Error Message [E_d7]
Combplate heating, top
Abbr. ITH-T
Note
Correction Remove ice and snow Check: Heating element PT100 sensor
[E_d8]
Step upthrust KUS-B contact, bottom
Check for trapped objects: – between riser and rear edge of next step – between riser and skirting (during down travel)
[E_d9]
Brake lining monitor
INBB
Check brake lining Replace brake lining if minimum is reached
[E_dA]
Stop button, customerprovided
DH-BS
Check function of RHBS
[E_db]
Water level KWS-B monitor, bottom
Check tension station pit for water
[E_dF]
Shutdown with lubrication failure
Check lubrication system: – level switch – tubes for kinks
[E_E4]
PB: Overtemperature
Q 409933_03
KDS
Tension station too warm Cool tension station
85 Copyright © 2013 INVENTIO AG
3
Display Error Message
Abbr.
Note
Correction
[E_E5]
PT: Overtemperature
Drive station too warm Cool drive station
[E_E6]
PA: Overtemperature
Machine room too warm Cool machine room
[E_E7]
PB: Missing step or pallet, bottom
INVK-B Interlocked
Confirm error Check: Step or pallet band for completeness INVK-B [t_05], [t_06] Power supply of sensor Sensor setting
[E_E8]
PT: Monitor, controlled brake
Check: GFU parameters GFU activation
[E_E9]
Monitor, controlled brake 2
Check: GFU parameters GFU activation
[E_EA] PT: Braking distance exceeded
[E_Eb]
Consecutive operation
86 Copyright © 2013 INVENTIO AG
INMH-R Interlocked
Confirm error Check: Braking distance INMH-R Speed via [A_31], [A_32] Power supply of sensor Sensor setting Start the next unit in line Q 409933_03
Display Error Message
Abbr.
Note
Correction
[E_EC] PB: Initiator defective, top
INVK-T
Check: INVK-T [t_05], [t_06] Power supply of sensor Sensor setting
[E_Ed]
Emergency stop 2
DH
Unit specific
[E_Er]
Elec-tronically interlocked error
[E_F0]
PB: Missing step or pallet, top
INVK-T Interlocked
Confirm error
[E_F1]
PB: Initiator defective, bottom
INVK-T
Check: INVK-B [t_05], [t_06] Power supply of sensor Sensor setting
[E_F2]
PT system status
Interlocked
Check parameter setting
[E_F3]
PB system status
Interlocked
Check parameter setting
[E_F4]
PT-PB system check
Q 409933_03
3 ANSI
Press DRES2 or DRES3 to show the error Check: Step or pallet band for completeness INVK-T [t_05], [t_06] Power supply of sensor Sensor setting
Check parameter setting
87 Copyright © 2013 INVENTIO AG
Display Error Message
Abbr.
Note
Correction Check parameter setting
[E_F5]
PB-PT system check
[E_F6]
PT: RB contactor dropout check
RB
Interlocked
Confirm error Check function of RB
[E_F7]
RGBA contactor dropout check
RGBA
Interlocked
Confirm error Check function of RGBA and RGBA1
88 Copyright © 2013 INVENTIO AG
Q 409933_03
3.5
Main Menu Some menu functions can only be activated by the Semi5Card with the corresponding access level or via FCOM5. Only in EoS mode all menu functions are available. If the EoS mode is not active the display will show [nEoS] while inserting the Semi5-Card into the slot X11. The operator level is always accessible without the Semi5Card and EoS mode.
Activate the EoS mode. Insert the Semi5-Card into the slot X11 or connect FCOM5. To enter the main menu press the ESC and OK buttons simultaneously until the display shows [U__C]. Use the UP or DOWN button to select the desired function. Press the OK button to activate the function. The ESC button can be used at any time to abort the function and return to the previous selection if not mentioned different. Display Function [U__C]
Error history
[U__A]
Display of operating data
[U__t]
Technical tests
[U__P]
Parameters
[U__r]
Set RTC
[U__d]
Data update
Q 409933_03
89 Copyright © 2013 INVENTIO AG
3
3.5.1
[U__C] - Error History This functions shows the most recently stored errors. While entering this function the last stored error is shown.
Use the UP button to show the next older error or DOWN button to show the next younger error. Press the ESC button to leave the function. A marker [_SFd] is set at the beginning. Display
Function
[C]
Error history identifier
[CSFd]
Marker where the history was read out
[CStA]
Beginning of history reached
[CEnd]
End of history reached
[C_]
Error entry
[C3]
Operating state on
[C312]
Evacuation operation on
90 Copyright © 2013 INVENTIO AG
Q 409933_03
3.5.2
[U__A] - Display of Operating Data
Use the UP or DOWN button to select the desired function. Press the OK button to show the value of the function. The ESC button can be used at any time to abort the function and return to the previous selection if not mentioned different.
* = Function accessible with software version > V5242 or > V5417. Display
Function [Unit]
Access Level O
M
*
S
[A_01]
Braking distance [cm]
[A_02]
Automatic time [s]
[A_03]
Automatic state (see next table)
[A_05]
Service hour meter [h]
[A_11]
Service hour meter, up travel [h]
[A_12]
Service hour meter, down travel [h]
[A_13]
Service hour meter, crawling [h]
[A_14] PT, PB, PA, P2, P3 software version [A_18]
[A_20]
Minimum required FCOM5 version
[A_21]
PB step band speed [m/s] PT step band speed [m/s]
* *
[A_22] [A_23]
Combplate temperature, bottom [°C]
[A_24]
Combplate temperature, top [°C]
[A_25]
PT machine room temperature [°C]
[A_26]
PB machine room temperature [°C]
[A_27]
PA machine room temperature [°C]
[A_29]
Motor speed [rpm]
[A_30]
Step chain running [km] Display [__]/[] = km
Q 409933_03
91
Copyright © 2013 INVENTIO AG
3
Display
Function [Unit]
Access Level O
M
S
[A_31]
Minimum motor speed [rpm]
[A_32]
Maximum motor speed [rpm]
[A_35]
SRECS checksum
[A_03] - Automatic State Display
Function
[0]
No transmitter malfunction
[1]
No transmitter malfunction. The entrance monitoring system was interrupted. Waiting for the signal from the skirt light barrier.
[2]
Entrance monitoring defective
[3]
Skirt light barrier defective
[00]
No automatic start of the automatic time (see next table)
92 Copyright © 2013 INVENTIO AG
Q 409933_03
Automatic start of the automatic time Display
Function
[01]
Since lubrication is active
[02]
Since heating is active
[03]
Due to KGGFU
[04]
Due to JFUD
[07]
Due to CO-GO-B/T
[08]
Due to continuous operation
[09]
Due to a LR
[10]
Due to automatic operation with skirt light barriers and without GFU
[11]
Due to too low temperatures, top
[12]
Due to too slow speed in crawling mode
[13]
Due to technical test
[14]
Due to evacuation
3
Entrance monitoring system sensors If more than one sensor is interrupted, numbers are added.
Display
Passenger Detection
[]
No detection
[1]
IRAD-T detection
[2]
PHSE-T detection
[4]
PHSE-B detection
[8]
IRAD-B detection
Q 409933_03
93 Copyright © 2013 INVENTIO AG
3.5.3
[U__t] - Technical Tests DANGER
No Passengers on the Unit during a Technical Test. Passenger on the unit while running a technical test will result in death or serious injury. Do not allow any passengers on the unit while running a technical test. Technical tests marked with an asterisk [t_]* are described in more details next to the overview. The column “IO” indicates, that the test can NOT be performed during the inspection operation. Procedure of technical tests if not mentioned separately: Use the UP or DOWN button to select the desired technical test. Press the OK button to confirm the selected test. The display shows [t_d.0.]. Start the unit in the desired direction. Wait until the unit stops after a short time of travel. Press the ESC button several times until the display shows [E_..]. Verify the correct error display. Clear the error with the OK button.
94 Copyright © 2013 INVENTIO AG
Q 409933_03
* = Function available with software version > V5242 or > V5417. Technical tests might not be present due to different software version.
Display
Access Level
Test
Error
IO
[t_01]
15% PB overspeed
[E_3E]
[t_02]
15% PT overspeed
[E_30]
[t_03]
PB underspeed
[E_3F]
[t_04]
PT underspeed
[E_31]
[t_05]*
Check of INVK at PB
[t_06]*
Check of INVK at PT
[t_07]*
Check of INHL at PB
[t_10]*
Service brake under load
[t_11]*
Safety brake under load
[t_15]
Delete history
[t_16]
15% motor overspeed
[E_18]
[t_17]
Motor underspeed
[E_1C]
[t_18]
Fine tuning for GFUP
[t_21]
30% motor overspeed
[t_24] [t_25] [t_26]*
O
M
S
* * * *
* *
Combplate heating, bottom
[t_27]*
Combplate heating, top
[t_28]
Missing step, bottom, PT (V52XX) [E_3b]
[t_29]
Missing step, bottom, PB (V52XX)
[E_CC]
30% PT overspeed
[E_CE]
30% PB overspeed
[E_CF]
Q 409933_03
[E_F0]
* * *
95 Copyright © 2013 INVENTIO AG
3
Display
Test
Error
IO
Access Level O
M
S
[t_30]
Missing step, top, PT (V52XX)
[E_39]
[t_31]
Missing step, top, PB (V52XX)
[E_E7]
[t_32]*
Speed test 1 (V52XX)
[t_33]*
Speed test 2 (V52XX)
[t_35]*
Controller cooling
[t_36]*
Controller heating
[t_37]*
Lubrication
[t_46]
Initiate LR. Press ESC to exit the menu.
[t_48]
Safety brake test GFUP
[t_49]
Service brake test GFUP
[t_50]
Start-up via board buttons
[t_51]
Acknowledging maintenance monitoring
[t_52]
15% PB motor overspeed (V54XX)
[t_53] [t_54]
* *
[E_8b]
PB motor underspeed (V54XX)
[E_8A]
30% PB motor overspeed (V54XX)
[E_8C]
[t_55]
SRECS (V54XX)
[E_F2]/ [E_F3]
[t_56]
Safety brake contact (V54XX)
[t_57]
Motor speed initiator (V54XX)
96 Copyright © 2013 INVENTIO AG
[E_1C]
Q 409933_03
[t_05] [t_06] [t_07] - Functional Checks [t_05] for INVKs is only shown on PB. [t_06] for INVKs is only shown on PT. [t_07] for INHLs is only shown on PB. Select the desired technical test. Run the unit with the maintenance control panel. The display will show the function of the INVKs / INHLs. [t_05/06]
[t_07]
[0]
Display
0 V = no detection
Function
INVK-B
INHL-R
[1]
24 V = material detected
INVK-B
INHL-R
[0]
0 V = no detection
INVK-T
INHL-L
[1]
24 V = material detected
INVK-T
INHL-L
[0] [7]
Increments the value at each change (value 7 0)
INVK-B
INVK-B
[0] [7]
Increments the value at each change (value 7 0)
INVK-T
INVK-L
Q 409933_03
97 Copyright © 2013 INVENTIO AG
3
[t_10] [t_11] - Brake under Load [t_10] for service brake. [t_11] for safety brake. The display [t] shows the last braking distance in centimeter. At [t_11] the safety brake engages without delay using the emergency stop button DH. At [t_11] the service brake must remain released manually. – Single motor 15 kW: The motor starts in direct mode using the key switch. – Single motor 15 kW: The motor starts in - mode using the key switch. The - switching time is set to two seconds. Starting in up direction at full load is not permissible.
[t_26] [t_27] - Combplate Heating [t_26] for combplate heating bottom. – Only possible if P0061 > 999. – Suppresses error [E_1E] for two hours. [t_27] for combplate heating top. – Only possible if P0062 > 999. – Suppresses error [E_d7] for two hours. Verify if the corresponding heating device is working. Display [t1]
Function Shutdown due to frost
[t1]
Combplate temperature > +70 °C
[t1]
Combplate temperature < -30 °C
98 Copyright © 2013 INVENTIO AG
Q 409933_03
[t_32] - Speed Test 1 This test cannot be performed with direct starting (P0193 = 2). – Single motor 15 kW: The motor starts in direct mode using the key switch. – Single motor 15 kW: The motor starts in - mode using the key switch. The - switching time is set to two seconds.
3
Underspeed Start the unit without load in the desired direction. Press the UP button to initiate a shutdown. – The motor is deactivated and the brake remains released. – The unit decelerates and is shut down via the underspeed check. Press the OK button several times until the display shows [E_..]. Verify the correct error display. Clear the error with the OK button. 15% Overspeed Start the unit with braking test load only in down direction. Press the UP button to initiate a shutdown. – The motor is deactivated and the brake remains released. – The unit accelerates and is shut down via the 15% overspeed check. Press the OK button several times until the display shows [E_..]. Verify the correct error display. Clear the error with the OK button.
Q 409933_03
99 Copyright © 2013 INVENTIO AG
[t_33] - Speed Test 2 This test cannot be performed with direct starting (P0193 = 2). The 15% overspeed check is deactivated. – Single motor 15 kW: The motor starts in direct mode using the key switch. – Single motor 15 kW: The motor starts in - mode using the key switch. The - switching time is set to two seconds. 30% Overspeed Start the unit with braking test load only in down direction. Press the UP button to initiate a shutdown. – The motor is deactivated and the brake remains released. – The unit accelerates and is shut down via the 30% overspeed check. Press the OK button several times until the display shows [E_..]. Verify the correct error display. Clear the error with the OK button.
100 Copyright © 2013 INVENTIO AG
Q 409933_03
[t_35] [t_36] - Cooling/Heating [t_35] for cooling fans: At least one of the outputs VVEK1 - 3 must be assigned to a hardware pin. [t_36] for heating devices: At least one of the outputs VEH1, RHE-B, RHE-T must be assigned to a hardware pin. The outputs can be activated individual by using the UP button. Verify if the corresponding cooling or heating device is working.
3
Output Active
Display
[t_35]
[t_36]
[t__0]
VVEK1, VVEK2, VVEK3
VEH1, RHE-B, RHE-T
[t__1]
VVEK1
VEH1
[t__2]
VVEK2
RHE-B
[t__3]
VVEK3
RHE-T
[t_37] - Lubrication Possible messages that may occur during a subtest: Press the OK button to confirm the message. Display
Function
[L_0]
Subtest not yet activated
[L_1]
Subtest running
[L_2]
Subtest completed
[L_3]
Subtest stopped manually
[L_4]
Subtest aborted: Low oil level
[L_5]
Subtest aborted: Leak or pressure cannot be decreased
[L_6]
Subtest not possible at the moment
Q 409933_03
101 Copyright © 2013 INVENTIO AG
Downdraft lubrication with multiple valves Only possible if P0084 = 2. Press the OK button to start the selected subtest. Press the UP button to stop a running subtest. Press the OK button to confirm the result of the subtest. Possible subtests: Display
Function
[LACt]
Automatic lubrication cycle is active
[L2_]
Opens the step chain valves for P0003 seconds
[L4_]
Opens the drive and handrail drive chain valves for P0006 seconds
[LA_]
Lubrication pause is deleted: Lubrication starts at travel
[Lb_]
Initial lubrication: Lubrication starts at travel (step chain for 60, drive and handrail drive chain for 12 minutes)
[LC_]
Current overtravel stopped
[Ld_]
Set lubrication pause
102 Copyright © 2013 INVENTIO AG
Q 409933_03
Automatic lubrication with piston pump Only possible if P0084 = 3 or 4. Press the OK button to start the selected subtest. Press the UP button to switch over to the next subtest. Press the ESC button to stop a running subtest. Possible subtests: Display
3
Function
[LACt]
Automatic lubrication cycle is active
[L0_]
Fill lubrication system
[L1_]
Leakage test
[L2_]
Right step chain
[L3_]
Left step chain
[L4_]
Right drive chain
[L5_]
Left drive chain
[L6_]
Handrail drive chain
[L7_]
Right handrail drive chain
[L8_]
Left handrail drive chain
[L9_]
Fill distributor
[LA_]
Lubrication pause is deleted: Lubrication starts at travel
[Lb_]
Initial lubrication: 3 lubrication cycles starts at travel
[LC_]
Current overtravel stopped
[Ld_]
Set lubrication pause
Q 409933_03
103 Copyright © 2013 INVENTIO AG
Lubricant dosing system Only possible if P0084 = 5. Press the OK button to start the selected subtest. Press the UP or ESC button to stop a running subtest. Possible subtests: Display
Function
[LACt]
Automatic lubrication cycle is active
[L2_]
Opens the step chain valves for 12 minutes
[L4_]
Opens the drive and handrail drive chain valves for 12 minutes
[LA_]
Lubrication pause is deleted: Lubrication starts at travel
[LC_]
Current overtravel stopped
[Ld_]
Set lubrication pause
104 Copyright © 2013 INVENTIO AG
Q 409933_03
Automatic lubrication with gear pump Only possible if P0084 = 6. Press the OK button to start the selected subtest. Press the UP button to stop a running subtest. Possible subtests: Display
Function
3
[LACt]
Automatic lubrication cycle is active
[L2_]
Opens the step chain valves for P0003 seconds
[L4_]
Opens the drive and handrail drive chain valves for P0006 seconds
[LA_]
Lubrication pause is deleted: Lubrication starts at travel
[Lb_]
Initial lubrication: Lubrication starts at travel (step chain for 60, drive and handrail drive chain for 12 minutes)
[LC_]
Current overtravel stopped
[Ld_]
Set lubrication pause
Q 409933_03
105 Copyright © 2013 INVENTIO AG
3.5.4
[U__P] - Parameters Parameter settings depend on the unit. Incorrect settings may cause malfunctions. Any change of a parameter must be approved by the Escalator Competence Center in Vienna and must be documented on all control cabinet stickers. To load the default parameter set or change the default parameter record refer to the end of this chapter.
Activate the EoS mode. Insert the Semi5-Card into the slot X11 or connect FCOM5. Use the UP or DOWN button to select the desired authorization (see next table). Press the OK button to confirm the selection. Use the UP or DOWN button to select the desired parameter. Press the OK button to confirm the parameter. The current value of the parameter is shown. Use the UP or DOWN button to change the value of the parameter. Store the new value: – With the ESC button, no changes are stored. – With the OK button, the changed value is stored. Press the ESC button until the display shows [U---]. A boot-up is triggered automatically.
Display
Authorization
Access Level O
M
S
[PP00]
Read-only. No parameters are editable
[PP22]
Parameters P0000 - P0743 are editable
[PP55]
Parameters P0000 - P0999 are editable
[PP99]
All parameters are editable
106 Copyright © 2013 INVENTIO AG
Q 409933_03
Parameters might not be present due to different software version. Default value in brackets () = ANSI-CSA. LR indicates a parameter which is calculated during the learning run. Not all parameters are listed. Par. No.
Parameter
P0000 YDMAXTIME
Default 70
Range [Unit] 1–100 [0.1 s]
Maximum starting time in Y operation
P0001 HANDRAILTIME
60
10–120 Delay of handrail speed monitor [0.1 s] errors
P0002 ECOMAXTIME
60
60– 1000 [s]
3
Description
Maximum operation time for ECO
P0003 LUBRICATIONTIME 1
720
0–9999 Downdraft lubrication time for [s] step chain
P0006 LUBRICATIONTIME 2
720
0–9999 Downdraft lubrication time for [s] handrail and drive chain
P0008 LUBRICATIONPAUSE-KM
25
5–9999 Lubrication pause
P0009 RUNNING METER AFTER LUBRICATION
500
10– 2000
P0010 LUBRICATIONMGSKS-R
0
0–9999 Lubrication strokes for right step chain
Q 409933_03
[km] Overtravel after lubrication
[m]
107 Copyright © 2013 INVENTIO AG
Par. No.
Parameter
Default
Range [Unit]
Description
P0011 LUBRICATIONMGSKS-L
0
0–9999 Lubrication strokes for left step chain
P0012 LUBRICATIONMGSKA-R
0
0–9999 Lubrication strokes for right drive chain
P0013 LUBRICATIONMGSKA-L
0
0–9999 Lubrication strokes for left drive chain
P0014 LUBRICATIONMGSKHL
0
0–9999 Lubrication strokes for handrail drive chain
P0015 LUBRICATIONMGSKHL-R
0
0–9999 Lubrication strokes for right handrail drive chain
P0016 AUTOMATICTIME
9999 12– 9999
P0017 DHBUZZERTIME
0
0–9999 Buzzer activation time after [s] emergency stop
P0020 GFU-RSF-TIME
0
0
Time for automatic operation
[s]
10– 9999
Time for crawling 0: No limit
[s] P0024 KBFM-TIME
0
0–300 [s]
Delay time for smoke detector
P0025 BUZZERTIME ENTR. 0 MONITORING
0–30
P0026 LUBRICATIONMGSKHL-L
0–9999 Lubrication strokes for left handrail drive chain
108 Copyright © 2013 INVENTIO AG
0
[s]
Buzzer time when entered from wrong side
Q 409933_03
Par. No.
Parameter
Default
Range [Unit]
Description
P0027 LIGHTCURTAIN MAX 600 TIME
0–9999 Maximum monitoring time of [min] light curtain 0: No limit
P0029 TEMPERATURE FOR CRAWLING SPEED
0
15
5–40 [°C]
Minimum temperature in drive station for crawling speed 0: No limit
P0030 HEAT ERROR DELAY
0
P0032 START SPEED
0
0–300 [s] 0–1
Buzzer and delay time for heating errors 0: Start with nominal speed 1: Start with crawling speed
P0033 STOP SPEED
0
0–1
P0034 START MODE
0
0–3
0: Coasting to stop 1: Service brake 0: Without light curtain 1: Remote start with light curtain 2: Always with light curtain 3: Remote start with light curtain, local start with light curtain if active
Q 409933_03
109 Copyright © 2013 INVENTIO AG
3
Par. No.
Parameter
P0035 REMOTE STOP MODE
Default 0
Range [Unit] 0–3
Description 0: No function 1: Stop only during travel 2: Stop without persons 3: Stop after announcement
P0037 LIGHTCURTAIN START MODE
1
0–1
0: Start only with next person 1: Start after troubleshooting
P0038 INSPECTION PERIOD
0
0–24
0: Monitoring inactive 1–24: Maintenance visits per year
P0039 VSKA-R TIME
200
0–9999 Lubrication time for [s] drive and handrail chain
P0041 SWITCHOVER TIME SFU SN
0
0 60– 2000 [ms]
Switchover time from SFU to SN
P0042 SWITCHOVER TIME SN SFU
0
0 60– 2000 [ms]
Switchover time from SN to SFU
P0043 VOICE ANN. TIME REM START
0
0–30 [s]
Voice announcement time for remote start
P0044 VOICE ANN. TIME REM STOP
0
0–30 [s]
Voice announcement time for remote stop
110 Copyright © 2013 INVENTIO AG
Q 409933_03
Par. No.
Parameter
Default
Range [Unit]
Description
P0045 BUZZERTIME ENTR. 0 MONITORING 2
0–30 [s]
Buzzer time when entered from correct side
P0046 Ride Through
0–1
0: Standard
0
1: Ride through with GFU P0047 INAK TIME
200
0–400 [ms]
Time for delay of INAK
P0054 VHE1TEMPERATURE
7
5–100
Temperature of control cabinet heating
P0055 VVEK1TEMPERATURE
40
P0056 VVEK2TEMPERATURE
40
P0057 VVEK3TEMPERATURE
40
[°C] 5–100 [°C] 5–100 [°C] 5–100 [°C]
Temperature of machine room fan 1 Temperature of machine room fan 2 Temperature of machine room fan 3
P0058 ERROR OVER TEMP 70 VALUE
5–100
P0059 WARNING OVER TEMPERATURE VALUE
50
5–100
P0060 KOMPARA
0x 0x0001- Contract-specific 0000 0xFFFF parameter
Q 409933_03
[°C] [°C]
3
Shutdown overtemperature Warning overtemperature
111 Copyright © 2013 INVENTIO AG
Par. No.
Parameter
P0061 HKB
Default
Range [Unit]
0007 0000– 0025
Description Heating of combplate.
1000– 1025
First digit:
3000– 3025
1: Heating without frost check
P0062 HKT
0: No heating
3: Heating with frost check Third and fourth digits: Temperature setting for heating [°C]
P0068 COMM. PROT. PT RS232
0
0 9–11
0: FCOM5 9: Modbus-GLT 10: Modbus-ALCD 11: Modbus-FIP
112 Copyright © 2013 INVENTIO AG
Q 409933_03
Par. No.
Parameter
P0069 GLT REMOTE COM
Default 0
Range [Unit] 0–20
Description 0: No remote control possible Remote control without command unlock via: 1: PT RS-232
3
2: PT RS-485-2 3: PB RS-232 4: PB RS-485-2 5: PA RS-232 6: PA RS-485-2 7: P2 RS-232 8: P2 RS-485-2 9: P3 RS-232 10: P3 RS-485-2 Remote control with command unlock via: 11: PT RS-232 12: PT RS-485-2 13: PB RS-232 14: PB RS-485-2 15: PA RS-232 16: PA RS-485-2 17: P2 RS-232 18: P2 RS-485-2 19: P3 RS-232 20: P3 RS-485-2
Q 409933_03
113 Copyright © 2013 INVENTIO AG
Par. No.
Parameter
P0070 LEARNINGOFF
Default 0
Range [Unit] 0–1
LR
Description 0: Learning run not completed 1: Learning run completed
P0080 SAFETYBRAKE
0
0–1
P0084 VALVE LUBRICATION
2
0: No safety brake 1: Safety brake installed
(1) 0
Lubrication:
2–7
0: No 2: Downdraft with multiple valves 3: One stroke piston pump 4: Two stroke piston pump 5: Dosing system 6: Gear pump 7: Pump with dosing elements
P0085 BUZZER BEFORE START
0
P0088 HANDRAIL MONITORING LR
1
0–15 [s] 0–1
Buzzer time before start-up 0: Handrail speed monitor inactive 1: Handrail speed monitor active
P0092 STEP ABSENCE
1
1
1: Steps
3–5
3: Short pallets 4: Long pallets 5: Very short pallets
114 Copyright © 2013 INVENTIO AG
Q 409933_03
Par. No.
Parameter
P0096 OPERATION MODE
Default 0
Range [Unit] 0–3
Description 0: No automatic operation 1: Automatic operation active 2: Direction change operation 3: Automatic operation with skirt light barriers
P0097 AUTOMATIC OPTION
0
0–3
0: Continuous/ automatic operation 1: Automatic operation only 2: Automatic operation only and JFUD switch 3: Automatic operation or direction change
P0100 LIGHTCURTAIN TYPE
0
0–1
0: No light curtain
P0102 DIRECTION LOCK
0
0–2
0: No limit
1: Esca-Scan 1: Key switch start in UP direction not possible 2: Key switch start in DOWN direction not possible
Q 409933_03
115 Copyright © 2013 INVENTIO AG
3
Par. No.
Parameter
P0104 ENTRANCE MONITORING
Default 0
Range [Unit] 0 20
Description If automatic transmitter are actuated against travel direction: 0: Unit accelerates to nominal speed 20: No action
P0107 LUBRICATION ERROR
0
0–2
0: Normal function 1: Shutdown due to lubrication after travel 2: Immediate shutdown
P0109 INDICATOR DIRECTION FUNCTION
0
0–3
0: Standard 1: Red at EoS 2: Red flashing with light curtain restart 3: Flashing for start and direction change
116 Copyright © 2013 INVENTIO AG
Q 409933_03
Par. No.
Parameter
P0110 COMM. PROT. PT RS485-2 P0111 COMM. PORT. PB RS232 P0112 COMM. PROT. PB RS485-2
Default 0
Range [Unit] 0
Description
6
0: No communication
9–11
6: group bus 9: Modbus-GLT 10: Modbus-ALCD 11: Modbus-FIP
3
P0113 COMM. PROT. PA RS232 P0114 COMM. PROT. PA RS485-2 P0115 COMM. PROT. P2 RS232 P0116 COMM. PROT. P2 RS485-2 P0117 COMM. PROT. P3 RS232 P0118 COMM. PROT. P3 RS485-2
Q 409933_03
117 Copyright © 2013 INVENTIO AG
Par. No.
Parameter
P0119 COMM. ADDRESS PT RS485-2
Default
Range [Unit]
Description
0
0–255
Communication address
P0190 R&D SIMULATE
0
0 3
Only for development
P0192 SPEEDEDGE NUMBER
2
2
Number of edges per 400 mm
P0120 COMM. ADDRESS PB RS485-2 P0121 COMM. ADDRESS PA RS485-2 P0122 COMM. ADDRESS P2 RS485-2 P0123 COMM. ADDRESS P3 RS485-2 P0124 COMM. ADDRESS PT RS232 P0125 COMM. ADDRESS PB RS232 P0126 COMM. ADDRESS PA RS232 P0127 COMM. ADDRESS P2 RS232 P0128 COMM. ADDRESS P3 RS232
6
2: Escalators 6: Moving walks
118 Copyright © 2013 INVENTIO AG
Q 409933_03
Par. No.
Parameter
P0193 DRIVE
Default 2
Range [Unit]
Description
1–4
1: Y-starting
7
2: Direct starting
10
3: GFU Plus
12
4: GFU Standard
13
7: Y operation with switching to
15 16
10: GFU Multi speed, up only 12: Y operation with switching to or GFU-C 13: Y-starting with switching to GFU-C 15: Y operation with switching to or GFU-C and slow inspection speed 16: Y-starting with switching to GFU-C and slow inspection speed
P0197 GFU SPEED CHOOSE
0
0–2
GFU Speed selection system: 0: Switches 1: Buttons 2: Single button
P0199 GFU SPEED SUPPLY FREQU.
1
0–4
Line frequency is nominal speed: 0: No function 1–4: Speed 1–4
Q 409933_03
119 Copyright © 2013 INVENTIO AG
3
Par. No.
Parameter
P0201 DRIVE OPTION
Default 0
Range [Unit] 0–1
Description 0: Direct starting permissible 1: Y-starting required
P0216 TRUSS HEAT DETECTION
0
0–1
0: Inactive 1: Overheat monitoring of truss
P0217 G-COUNTER RESET 5 TIME
5–600
P0218 COUNTER INTERLOCK (+G)
5
0–20
Number of recurring errors before interlocking
P0224 RESETMODE
0 (1)
0–1
0: EN 115
P0231 EEPROM DEFAULT
90
0–2
0: Standard
[min]
Time for recurring errors
1: ANSI-CSA 1: ASA 2: ANSI-CSA
P0232 PANEL TYPE
0 (13)
0
Operating panel:
13
0: Standard 13: Double cable run
P0243 AUTHORIZATION
0 (1)
0–1
P0250 HANDRAIL ROLLER CIRCUMFER.
340
100– 400 750– 850 [mm]
Circumference of handrail measuring roller
P0251 NOMINAL SPEED
500
400– 775 [mm/s]
Rated speed
120 Copyright © 2013 INVENTIO AG
0: Standard 1: ANSI
Q 409933_03
Par. No.
Parameter
Default
P0252 NUMBER MOTOR POLE PAIRS
6
P0253 RPM IMPULSES
6
Range [Unit]
Description
4 6
Number of motor pole pairs
6
Holes in flywheel:
12
6: 2 12: 4
P0254 RPM ECO CRAWLING
18
P0255 INMH PULSES PER SEC LR
9999 1–9999 Pulses per second from INMH
P0256 STEP SPEED RATED 10 LR
15–100 Minimum crawling speed [%]
10– 5000
Nominal speed
[ms] P0257 RPM RATED
10
LR
10– 1000
P0258 RPM YD SWITCHING 96
1–100
Nominal speed of flywheel
[ms] [%] P0260 RPM ECO LOW
95
1–100 [%]
P0261 RPM ECO HIGH
105
1–120 [%]
Switching speed for Y-during run-up Lower switching limit for ECO Upper switching limit for ECO
P0262 GFUP-SPEED-04
35
5–100 Frequency for V54XX: nominal speed 4 5-60
P0263 BRAKEMEASURE FACTOR LR
10
1–9999 Conversion factor for braking distance measurement
[Hz]
Q 409933_03
121 Copyright © 2013 INVENTIO AG
3
Par. No.
Parameter
P0264 STEPLENGTH
Default
Range [Unit]
Description
LR
9999 0–9999 Step length factor for missing-step check
P0265 GFUP-SPEED-01
50
5–100 Frequency for V54XX: nominal speed 1 50-60
P0266 GFUP-SPEED-02
45
5–100 Frequency for V54XX: nominal speed 2 5-60
P0267 GFUP-SPEED-03
40
5–100 Frequency for V54XX: nominal speed 3 5-60
P0268 BRAKE-DISTANCEMAX
120
50–300 Maximum braking distance [cm]
P0279 HANDRAIL MONITORING LR DIFFERENCE
10
0–9999 Conversion factor for handrail speed check
P0280 HANDRAIL MONITORING ERROR
15
1–99
[Hz]
[Hz]
[Hz]
122 Copyright © 2013 INVENTIO AG
[%]
Tripping threshold for handrail speed error
Q 409933_03
Load Default Parameter Set All parameters, the history and the RAM at the desired PCB will be deleted. Do not connect the connector X2.9-13 until all desired PCBs are set to default. A PCB without default parameters will automatically copy its parameter set to PCBs with default parameters. Use menu [dPdE] to set parameters on all connected PCBs to default.
Press the emergency stop button at the bottom control cabinet Turn off the main switch JHA. Disconnect the connector X2.9 - 13. Set the DIL switch S7/7 to the ON position at the desired PCB. Turn on the main switch JHA. The display shows [FdEL]. Press the UP button. The display flashes. Press the OK button. The memory will be cleared. The display shows [donE]. Turn off the main switch JHA. Set the DIL switch S7/7 to the OFF position at the desired PCB. Connect the connector X2.9 - 13. Turn on the main switch JHA and follow the display instructions. Release the emergency stop button at the bottom control cabinet
Q 409933_03
123 Copyright © 2013 INVENTIO AG
3
Default Parameter Record It is absolutely necessary to obtain a new control cabinet sticker from the supplying factory before changing the default parameter record.
Set all parameters to default. Turn off the main switch JHA. Set DIL switches at PB for the new default parameter record. Turn on the main switch JHA. Set all parameters according to the new control cabinet sticker. Fix the new control cabinet sticker to all control cabinets. DIL Switch PB
Designation Standard
ASA
ANSI-CSA
S7/4
OFF
ON
OFF
S7/5
OFF
OFF
ON
124 Copyright © 2013 INVENTIO AG
Q 409933_03
3.5.5
[U__r] - Set RTC The errors are only stored in line with the times if the RTC is set to the local time.
Use the UP or DOWN button to select the desired range. Press the OK button to activate the range. Use the UP or DOWN button to change the value of the range. Press the OK button to save the value and leave the range.
Display
Function Year
0–99
[r001]
Month
1–12
[r002]
Day
1–31
[r003]
Day of the week
0 1 2 3 4 5 6
[r004]
Hour
0–23
[r005]
Minute
0–59
[r006]
Second
0–59
Q 409933_03
3
Range
[r000]
Sunday Monday Tuesday Wednesday Thursday Friday Saturday
125 Copyright © 2013 INVENTIO AG
3.5.6
[U__d] - Data Update
Use the UP or DOWN button to select the desired function. Press the OK button to confirm the selected function. The display starts to flash. Press the OK button again to start the function.
Display
Function
Access Level O
M
S
[dCco]
Copy history to the Semi5-Card
[dPco]
Copy parameters to the Semi5-Card
[dPLd]
Load parameters to the PCB
[dPdE]
Set parameters and RAM to default of all PCBs
[dSLd]
Load software to all PCBs
[dCco] - Copy History As soon as the display shows [donE], the data were stored on the Semi5-Card in the directory FCOM5\History. The file name is composed of the contract number stored in P1513 - P1517 and the extension “.TxT”. The following errors may occur: Display
Meaning
[Err1]
Invalid parameter P1513 - P1517. Set parameter P1513 P1517 according to the control cabinet sticker.
[Err2]
No Semi5-Card inserted
[Err3]
Error when accessing the Semi5-Card
126 Copyright © 2013 INVENTIO AG
Q 409933_03
[dPco] - Copy Parameters As soon as the display shows [donE], the data were stored on the Semi5-Card in the directory FCOM5\Parameter. The file name is composed of the contract number stored in P1513 - P1517 and the extension “.Cf1”. The following errors may occur: Display
Meaning
[Err1]
Invalid parameter P1513 - P1517. Set parameter P1513 P1517 according to the control cabinet sticker.
[Err2]
No Semi5-Card inserted
[Err3]
Error when accessing the Semi5-Card
Q 409933_03
127 Copyright © 2013 INVENTIO AG
3
[dPLd] - Load Parameters The parameter file must be located on the Semi5-Card in the directory FCOM5\Parameter. The file name must be composed of the contract number stored in P1513 - P1517 and the extension “.Cf1”. After completion an automatic reset will be carried out. The following errors may occur: Display
Meaning
[Err1]
Invalid parameter P1513 - P1517. Set parameter P1513– P1517 according to the control cabinet sticker.
[Err2]
No Semi5-Card inserted
[Err3]
Error when accessing the Semi5-Card
[Err4]
Parameter file is not available
[Err5]
Lines are too long
[Err6]
Wrong file identifier
[Err7]
Wrong file structure
[Err8]
Parameters cannot be set
[Err9]
Value not permissible for the parameters
[dPdE] - Default Parameters and RAM The parameters, error history and service hour meter are cleared on ALL connected PCBs. After completion an automatic reset will be carried out.
128 Copyright © 2013 INVENTIO AG
Q 409933_03
[dSLd] - Load Software The software file must be located on the Semi5-Card in the directory FCOM5\Software. Use the DIL switch S7/8 for the fastest method to update the software onto a PCB (see next page). If the Semi5-Card contains more than one software file, use the UP or DOWN button for the selection. Press the OK button to confirm the selection. The display starts to flash alternately with the selected software version. Press the OK button again to load the software to the PCBs. The following errors may occur: Display
Meaning
[Err1]
No Semi5-Card inserted
[Err2]
No software file found
[Err3]
Software file is defective
[Err4]
Software file is not valid for this PCB
[Err5]
Software is not valid for this application
Q 409933_03
129 Copyright © 2013 INVENTIO AG
3
Software update with DIL switch S7/8 Press the emergency stop button at the bottom control cabinet. Turn off the main switch JHA. Disconnect the connector X2.9 - 13. Set the DIL switch S7/8 to the ON position. Insert the Semi5-Card containing the software. Turn on the main switch JHA. Wait until the display shows [CArd] and press the OK button. Use the UP or DOWN button to select the desired software version if more than one is stored on the Semi5-Card. Press the OK button to load the selected software to the PCB. Wait until the display shows [donE]. Turn off the main switch JHA. Remove the Semi5-Card. Set the DIL switch S7/8 to the OFF position. Connect the connector X2.9 - 13. Proceed from the beginning to update another PCB. Turn on the main switch JHA and follow the display instructions. Release the emergency stop button at the bottom control cabinet.
130 Copyright © 2013 INVENTIO AG
Q 409933_03
3.6
EoS Mode For the inspection run and maintenance work the EoS mode must be activated. In the EoS mode no error codes will be stored in the error log or send to the building management.
3.6.1
Activation, Deactivation
3
This functions are working only if the unit does not have a dedicated EoS switch. After 30 minutes of normal operation the EoS mode is deactivated if no technical test is activated and no button is pressed. After 30 minutes of standstill in the EoS mode the safety brake engages. Activation Turn the EoS switch to the ON position if present. If no EoS switch is present, press and hold the emergency stop button DH while turning the key switch to both directions. – All PCB displays showing [r] and the external display [r] to indicate the EoS mode is active. Deactivation Turn the EoS switch to the OFF position if present. If no EoS switch is present, press and hold the emergency stop button DH while turning the key switch to both directions. – All PCB displays showing [] and the external display [] to indicate the EoS mode is not active.
Q 409933_03
131 Copyright © 2013 INVENTIO AG
3.6.2
Maintenance Operating Panel DANGER
Emergency Stop Button JHRE As a matter of principle, always press the emergency stop button JHRE on the maintenance operating panel when not in use. This will prevent starting the unit by mistake. If the error message [E_45] is shown while opening the cover of the inspection outlet, the EoS mode is not active. To reset the error close the inspection cover again. A restart is blocked for up to 4 seconds with direct drives and when the panel buttons are pressed in rapid succession. This is necessary to prevent the fuses from tripping. The step/pallet band, handrail and brake monitor are not active during inspection operation. The motor speed is only monitored for overspeed. Make sure the unit is in the EoS mode, the safety circuit is closed and no unacknowledged errors are present (except for a floor cover contact error). Open the cover of the inspection outlet on top of the control cabinet. – The display shows [r_r0] after a short time. – The safety brake - if installed - is released. – Now the unit can be operated by the maintenance operating panel.
132 Copyright © 2013 INVENTIO AG
Q 409933_03
3.7 3.7.1
Commissioning Main Line Connection DANGER
High Voltage Contact to high voltage will lead to death. Switch off the circuit breaker in the building and secure it against accidental or unauthorized access.
3
Switch off the circuit breaker and secure it against access. Connect the three-phase cable. Observe the correct direction of rotation. The motor circuit wiring is adjusted to the unit and must not be altered. This applies to the wiring of: – the motor – the GFU (optional) – the drive contactors – the main fuse – the ground-fault circuit interrupter (optional) – the phase monitoring relay (optional) – the main switch JHA Connect the lighting circuit. It must be fused by the customer. Connect the heating circuit. It must be fused by the customer. Switch off the circuit breaker and secure it against access.
Q 409933_03
133 Copyright © 2013 INVENTIO AG
3.7.2
Checks before Initial Start-Up WARNING
Wrong DIL switch and jumper settings Wrong DIL switch and jumper settings could result in malfunctions. Always set the DIL switches and jumpers according to the control cabinet sticker.
Switch off the circuit breaker SIS2 to interrupt the safety circuit. Press the emergency stop button at the bottom control cabinet Check that all DIL switch and jumper settings on the PCBs are according to the control cabinet sticker. Turn on the main switch JHA. Boot-up the PCBs. – PB, PA, P2, P3 shows [F_P] – PT reading increments from [F_02] to [F_60] (not all numbers are displayed). – Once the system has booted, the error message [E_2C] appears to indicate that the emergency stop button at the bottom control cabinet has been actuated. Switch on circuit breaker SIS2. Release the emergency stop button at the bottom control cabinet. – An automatic contactor dropout check is carried out. – The system automatically checks whether the key switches are in the OFF position. – Once the anti-reversing device has deactivated, the unit is ready for operation. The display shows [b_d0]. Set the RTC. Initiate the learning run. Verify the correct indication of travel direction.
134 Copyright © 2013 INVENTIO AG
Q 409933_03
3.7.3
Initiating the Learning Run WARNING
It is absolutely necessary to Perform the Learning Run before the First Run with the Key Switch. If the learning run is not performed correctly, malfunctions and incorrect error diagnoses could occur later on. Do not interrupt the learning run at any time by turning off the unit or resetting any PCBs. It might be necessary to initiate the learning run after updating the software. The learning run can only be initiated with the Semi5-Card with the corresponding access level or via FCOM5. The unit is ready to be started with the key switch and the display shows [b_d0] and the last error. Activate the EoS mode. The display shows [r_d0]. Insert the Semi5-Card into the slot X11 or connect FCOM5. Press the ESC and OK buttons simultaneously until the display shows [U__C]. Use the UP or DOWN button to select the menu [U__t]. Press the OK button to confirm the selection. Use the UP or DOWN button to select the menu [t_46]. Press the OK button. The display shows [LEAr]. Press the ESC button until the display shows [U---]. All PCBs are rebooted. Wait until the display shows [rLd0]. Start the unit with the key switch. The unit will carry out the learning run. Verify the correct indication of travel direction. After two minutes run without any stop the learning run will be completed and the standard display is activated.
Q 409933_03
135 Copyright © 2013 INVENTIO AG
3
3.7.4
Replacement Order number: 50606956 for PEM52.Q PCB with software V52XX. Order number: 50646131 for PEM52.Q PCB with software V54XX.
Press the emergency stop button at the bottom control cabinet. Switch off and padlock the main switch JHA. Mark all connectors before disconnection. Replace the defective PCB. Reconnect all connectors except X2.9 - 13. Set all jumper and DIL switches according to the control cabinet sticker. Set the DIL switch S7/7 on the new PCB to the ON position to set the parameters to default. Switch on the main switch JHA. – Wait until the display shows [FdEL]. Press the UP button. – The display starts flashing. Press the OK button. – The display shows [donE]. Set the DIL switch S7/7 to the OFF position. Switch off the main switch JHA. Connect the connector X2.9 - 13. Switch on the main switch JHA. Follow the display instruction. – Verify that the software version of the PCBs is according or higher than the version indicated on the control cabinet sticker. Set all parameters according to the control cabinet sticker and RTC if all PCBs were replaced. Release the emergency stop button at the bottom control cabinet. Initiate the learning run if all PCBs were replaced.
136 Copyright © 2013 INVENTIO AG
Q 409933_03
4
Retrofit Instructions NOTICE
Electrostatic Sensitive Device Printed circuit boards (PCBs) are equipped with electrostatic sensitive semiconductors. Thus beware of electrostatic discharge and direct contact with the semiconductors. – Ground yourself by touching the control cabinet for electrostatic discharge. – Do not directly touch the PCB components. – Always use the original antistatic packing when transporting the PCBs.
4
Set all parameters to default before programming the parameter according to the control cabinet sticker. For a software update and the parameter settings at a workshop, read the chapter “Preparation @ Workshop”.
Q 409933_03
137 Copyright © 2013 INVENTIO AG
4.1
MICONIC F 3 with PEM52.Q All PCBs must be replaced by PEM52.Q PCBs. The PEM52.Q PCBs will be delivered with the software version V49XX. Order number: – 50606954: 2 pieces PEM52.Q PCBs including 1 mounting bracket for replacement of one PEM1.Q and one PES1.Q PCB. – 50606955: 1 piece PEM52.Q PCB for additional replacement. A new control cabinet sticker is required for the retrofit: Click on Sticker MICF Configuration @ Schindler Intranet Escalators > Tools > ComDoc DataBase > Electr. Docs. Enter the commissioning number of the desired unit and click on the search button. Print out the new control cabinet sticker. Correct the new control cabinet sticker: – Change word PEM4 to PEM52. – Change software version V35XX to V49XX.
138 Copyright © 2013 INVENTIO AG
Q 409933_03
Press the emergency stop button at the bottom control cabinet. Switch off and padlock the main switch JHA. Mark all connectors before disconnection. Remove all PCBs. At PT separate the empty connector X1.37 and the left side cover from the connector block X1.34 - X1.37:
X1.34
X1.37
4
X1.34
X1.36
X1.37
Connector X1.34 - X1.37 of PT [34768; 12.12.2013]
Q 409933_03
139 Copyright © 2013 INVENTIO AG
At PT combine the connector blocks X1.29 - X1.33 and X1.34 X1.36 together to get the connector block X1.29 - X1.36:
X1.29
X1.29
X1.33
X1.34
X1.36
X1.36
Connector X1.29 - X1.36 of PT [34769; 12.12.2013]
At PB combine the connector block X1.29 - X1.35 with the empty connector X1.37 from PT together to get the connector block X1.29 - X1.36:
X1.29
X1.29
X1.35
X1.36
X1.36
Connector X1.29 - X1.36 of PB [34770; 12.12.2013]
140 Copyright © 2013 INVENTIO AG
Q 409933_03
Replace the mounting bracket of the control cabinet at the bottom station with the new one. Install the PEM52.Q PCBs. Reconnect all connectors except X2.9 - 13. Set all jumper and DIL switches according to the control cabinet sticker. Set the DIL switch S7/1 and S7/8 on all PCBs to the ON position to set the parameters to default. Switch on the main switch JHA. – Wait until the display shows [FdEL]. Press the UP button. – The display starts flashing. Press the OK button. – The display shows [donE]. Set the DIL switches according to the control cabinet sticker. Switch off the main switch JHA. Connect the connector X2.9 - 13. Switch on the main switch JHA. Follow the display instruction. – Verify that the software version of the PCBs is according or higher than the version indicated on the control cabinet sticker. Set all parameters according to the new control cabinet sticker. Set RTC. Release the emergency stop button at the bottom control cabinet. Initiate the learning run if all PCBs were replaced.
Q 409933_03
141 Copyright © 2013 INVENTIO AG
4
4.2
MICONIC F 4 with PEM52.Q All PCBs must be replaced by PEM52.Q PCBs. Order number: 50606955 for 1 piece PEM52.Q PCB. The PCBs will be delivered with the software version V49XX.
Press the emergency stop button at the bottom control cabinet. Switch off and padlock the main switch JHA. Correct all control cabinet stickers: – Change word PEM4 to PEM52. – Change software version V40XX to V49XX. Mark all connectors before disconnection. Replace all PCBs. Reconnect all connectors except X2.9 - 13. Set all jumper and DIL switches according to the control cabinet sticker. Set the DIL switch S7/1 and S7/8 on all PCBs to the ON position to set the parameters to default. Switch on the main switch JHA. – Wait until the display shows [FdEL]. Press the UP button. – The display starts flashing. Press the OK button. – The display shows [donE]. Set the DIL switches according to the control cabinet sticker. Switch off the main switch JHA. Connect the connector X2.9 - 13. Switch on the main switch JHA. Follow the display instruction. – Verify that the software version of the PCBs is according or higher than the version indicated on the control cabinet sticker. Set all parameters according to the control cabinet sticker if all PCBs were replaced. Set RTC. Release the emergency stop button at the bottom control cabinet. Initiate the learning run if all PCBs were replaced.
142 Copyright © 2013 INVENTIO AG
Q 409933_03
5 5.1
Tools Semi5-Card Every Semi5-Card is personalized with a MICF-KEY file which does not work on another SD-Card. Every Semi5Card can be used on any MIC F 5E controller.
5.1.1
Activation
Requirements Standard size SD-Card from company SanDisk with maximum speed class 4. Activation procedure Enter the SD-Card into the card slot X11 of a PCB of a powered MIC F 5E. – The LED on the PCB should change from blinking to flashing for some seconds. Enter the SD-Card into the card reader of a computer. – The SD-Card should contain the following:
[49614; 12.12.2013]
Open the website Schindler Intranet Escalators > Tools > MICONIC F > Software and Keys > Semi5-Card Key. Choose the correct access level. Enter the name of the owner of the Semi5-Card into the field “Description”. Click on [Browse…] and choose the MICF.KEY file from the SDCard. Click on [Open] to upload link to the MICF.KEY file.
Q 409933_03
143 Copyright © 2013 INVENTIO AG
5
Click on Confirm the following message.
[49616; 12.12.2013]
Position the mouse curser over the MICF.Key file in the lower left corner of the website:
[49617; 12.12.2013]
Open the contest menu with a right mouse click and choose [Save target as…]. Save the MICF.Key file onto the SD-Card by replacing the old file.
144 Copyright © 2013 INVENTIO AG
Q 409933_03
5.1.2
Application
[49614; 12.12.2013]
An existing file with the same file name will be overwritten without warning. History folder “History” folder stores the history of the data when using [dCco] menu. The text file containing the history data is named after the commissioning number of the unit from where it was copied and the date from the RTC in the structure YYYYMMDD. Project folder “Project” folder stores the parameter set when using [dPco] menu. The Cf1 file name is the commissioning number of the unit from which it was copied. To load a parameter set from the Semi5-Card to the PCB: The Cf1 file must be stored in the “Project” folder. The file name must be identical to the commissioning number indicated on the control cabinet sticker. The parameter P1513 – P1517 on the PCB must be set according to the control cabinet sticker. Software folder “Software” folder is the storage to load software to all PCBs using [dSLd] menu or to a single PCB using DIL switch S7/8. More than one software version can be stored in the “Software” folder. It is not possible to copy software from the PCB to the Semi5-Card.
Q 409933_03
145 Copyright © 2013 INVENTIO AG
5
5.2
FCOM5 For installation of FCOM5 software, admin rights are required. A personal computer with FCOM5 software can only be connected to the MIC F 5S via Semi5 connector X8 with the Schindler Semi5-Cable (order no. 50606922). Do NOT use any other adapter.
5.2.1
Installation Find all information about escalator software @ Schindler Intranet Escalators > Tools > MICONIC F > Software and Keys.
Click on [Downloads - Software] at the FCOM Keys website. Click on [FCOM5 incl. Semi5 cable driver]. Download the latest FCOM5 software Install-FCOM5.exe. Install the FCOM5 software on your device. Click on [Ignore] at the error request. Start the FCOM5 software. Acknowledge the message “The software isn’t registered...”. A window with the pc-hardware-code will turn up. Write down the pc-hardware-code. Enter the FCOM Keys website. Click on “...create it yourself immediately”. Enter the pc-hardware-code into the field “Hardware Key”. Enter your name or device ID into the field “Machine ID”. Click the button [compute Software-Key]. A window with the software-key will turn up. Write down the software-key. Click [OK] at the window with the pc-hardware-code. A window to enter the software-key will turn up. Enter the software-key and click [OK]. Now the FCOM5 software can be used at any time.
146 Copyright © 2013 INVENTIO AG
Q 409933_03
Installation of Semi5-Cable Driver Only for original Semi5-Cable. Plug in the Semi5-Cable into the USB plug of the personal computer. The Windows Hardware Wizard will become active. Choose “Yes, this time only” and click on [Next]. Choose “Install from a list...” and click on [Next]. Click on [Browse] and choose the cable driver at the location: C:\FCOM5\Driver\4N-GX-CDM 2.04.06 WHQL Certified Follow the instruction of the Hardware Wizard. – The USB driver will be installed by the Hardware Wizard after the installation of the Semi5-Cable driver. The USB driver is located at the same directory as the Semi5-Cable driver.
5
Q 409933_03
147 Copyright © 2013 INVENTIO AG
5.2.2
Menu Overview Set the COM port at the FCOM5 menu [Settings] [Interface] to the corresponding COM port of the Windows device manager [Start] - [Settings] - [Control Panel] [System] - [Hardware] - [Device Manager] - [Ports (COM and LPT)]. Set the COM port to “None”, if no device is connected.
Main Menu
Submenu
Function
File
Quit
Exit FCOM program.
Configure
Set RTC
Set real time clock.
Parameters
Parameter setting. Load, send, open and save projects. Compare with default parameter set.
Set default parameters
Set all parameter values to default. Thereafter all parameters must be set according to the control cabinet sticker.
Program PEM5
Load MIC F 5 software to the PCBs.
Information Display
Display of the selected operating data.
Technical Tests
Activation of the technical tests.
Show History
Display the last 255 errors and running statistic. Load, open and save the error history.
Settings
Interface
COM interface setting (see hint above).
Input/ Output
Available PCBs
Display the signals at all input and output from all available PEM52.Q PCBs.
148 Copyright © 2013 INVENTIO AG
Q 409933_03
Main Menu Windows
Help
5.2.3
Submenu
Function
Cascade
Arrange windows behind each other.
Split horizontally
Arrange windows horizontal to each other.
Split vertically
Arrange windows vertical to each other.
Arrange
No function.
Shows all open windows
Select windows to activate.
IPL/OPL Calculator
Calculates the input or output of an entered hex-number.
Help
Information how to use FCOM.
About
Display the FCOM version.
Support
Responsible person.
5
Data Update
Press the emergency stop button at the bottom control cabinet. Establish the connection with FCOM5. For a software update choose the latest software by menu [Configure] - [Program PEM5] - [Select] Confirm the selection. Click on [Transfer] to program the PCB. This may take a while. For the parameter settings choose menu [Configure] - [Parameters] to change, load and save parameter values. After programming disconnect the FCOM5. Restart the system and follow the display instructions. Release the emergency stop button at the bottom control cabinet.
Q 409933_03
149 Copyright © 2013 INVENTIO AG
6 6.1
Starter SMC-3 Functional Elements 1 2
1 2 3 4 5
Reset button DIL Switches Sticker Type A or B Potentiometer LED
3 4 5
[33899; 19.02.2010]
150 Copyright © 2013 INVENTIO AG
Q 409933_03
6.2
Error Messages Press the reset button to reset an error.
LED
Meaning
Normal operation
ON
Flashes 1x Motor overload Flashes 2x Overtemperatur Flashes 3x Phase reversal Flashes 4x Phase failure or motor not connected Flashes 5x Current asymmetry Flashes 6x Thyristor shorted Flashes 7x Test run
6.3
Replacement
SMC-3
6
Two different SMC-3 are present: Type A and Type B. Type A: DIL switch 15 = OFF position Type B: DIL switch 15 = ON position
Switch off and padlock the main switch JHA. Replace the defective starter. Adjust the potentiometer (4) to the nominal motor current. Set all DIL switches according to the control cabinet sticker. Set to DIL switch 15 to the position according type A or B. – The type could be identified on the sticker of the SMC-3. – Note changes on the control cabinet sticker. Switch on the main switch JHA. Perform a test run.
Q 409933_03
151 Copyright © 2013 INVENTIO AG
10005025
Fan of SMC-3 Switch off the main switch JHA. Follow the instructions below.
[33898; 19.02.2010]
Switch on the main switch JHA. Verify the turn of the fan.
152 Copyright © 2013 INVENTIO AG
Q 409933_03
7 7.1
Vacon NXS and NXL Functional Elements
Display
1 2 3 4 5 6 NXS [33968; 24.02.2010]
1
4 2,3,5 7
7
NXL [33970; 24.02.2010]
1 2 3 4 5 6 7
Q 409933_03
Drive status Menu location Description line Control source Value line LEDs Unit
153 Copyright © 2013 INVENTIO AG
Buttons Button
Usage
Move through the menu. Edit value of the parameter select
Toggle between the last two indications (only NXS)
enter
Confirm selections. Press 3 seconds to reset the error history
reset
Reset an active error
start
Start the motor if the keypad is the active control source
stop
Stop the motor if the keypad is the active control source
7.2
Operation
Operating Messages Display
Meaning
RUN
Motor is running
Motor rotation
STOP
Motor not running
READY
Power is supplied and no error
ALARM
Motor is running outside the limit
FAULT
Drive stopped because of unsafe running condition
I/O term
GFU controlled by the I/O terminal
Keypad
GFU controlled by the keypad
Bus/ Comm
GFU controlled by the field bus
LED (only NXS)
Meaning
ready (green)
Power is supplied
run (green)
Motor is running
fault (red)
Drive stopped because of unsafe running condition
154 Copyright © 2013 INVENTIO AG
Q 409933_03
Main Menu Code
Identifier
NXS NXL
Submenu
M1
M1 Monitor
M2
P2
M3
K3 Keypad Control
M4
F4
M5
H5 Fault history Storage of the last 30 errors in the order of their appearance
M6
S6
System
Language selection, re-/store parameters, show counters
M7
E7
Expander boards
Parameter for additional boards
Parameters
Shows several operating values Edit parameters Select different control sources
Active faults Storage of the last 10 errors in the order of their appearance
7
Q 409933_03
155 Copyright © 2013 INVENTIO AG
NXS: Main menu [34291; 17.03.2010]
156 Copyright © 2013 INVENTIO AG
Q 409933_03
7 NXL: Main menu [34288; 17.03.2010]
Q 409933_03
157 Copyright © 2013 INVENTIO AG
Submenu Monitor Code
Meaning [Unit]
NXS
NXL
V1.1
V1.1 Output frequency [Hz]
V1.2
V1.2 Reference frequency [Hz]
V1.3
V1.3 Motor speed [rpm]
V1.4
V1.4 Motor current [A]
V1.5
V1.5 Motor torque [% of nominal torque]
V1.6
V1.6 Motor power [% of nominal power]
V1.7
V1.7 Motor voltage [V]
V1.8
V1.8 DC link voltage [V]
V1.9
V1.9 GFU temperature [°C]
V1.10 V1.10 Analog input 1 V1.11 V1.11 Analog input 2 V1.12 V1.15 Digital input status DIN1, DIN2, DIN3 – DIN1 = Start forward – DIN2 = Start reverse – DIN3 = Acceleration/braking time V1.13
Digital input status DIN4, DIN5, DIN6 – DIN4 = Selection of multispeed – DIN5 = Selection of multispeed – DIN6 = Selection of multispeed
V1.14
Digital and relay output status DO1, RO1, RO2 – DO1 = Generator operation – RO1 = Fault – RO2 = Overload generator operation
V1.15 V1.12 Analog output current [mA] V1.13 Analog output current 1 @ expander board [mA] V1.14 Analog output current 2 @ expander board [mA]
158 Copyright © 2013 INVENTIO AG
Q 409933_03
Code NXS
NXL
Meaning [Unit]
V1.16 Digital input status DIE1, DIE2, DIE3 – DIE1 = Selection of multispeed – DIE2 = Selection of multispeed – DIE3 = Selection of multispeed V1.17 Relay output 1 status RO1 – RO1 = Fault V1.18 Relay output status ROE1, ROE2, ROE3 – ROE1 = Overload generator operation V1.19 Digital output 1 status @ expander board DOE1 V1.20 PID Reference [% of maximum process reference] V1.21 PID Actual value [% of maximum actual value] V1.22 PID Error value [% of maximum error value] V1.23 PID Output [% of maximum output value] V1.24 Used only for pump or fan control V1.25 Mode
7
Q 409933_03
159 Copyright © 2013 INVENTIO AG
NXS: Example monitor menu [34293; 17.03.2010]
NXL: Example monitor menu [34289; 17.03.2010]
160 Copyright © 2013 INVENTIO AG
Q 409933_03
Submenu Parameters
Not all parameter can be modified if the start command is given. The parameter must be unlocked to change their value. Lock the parameter after their change. Unlock the parameter:
NXS: Unlock parameter [33976; 17.03.2010]
7
NXL: Unlock parameter [33978; 24.02.2010]
Q 409933_03
161 Copyright © 2013 INVENTIO AG
Change the parameter values:
NXS: Example change parameter [33979; 24.02.2010]
NXL: Example change parameter [33980; 24.02.2010]
162 Copyright © 2013 INVENTIO AG
Q 409933_03
Store the parameter
NXS only: Use this function to copy parameters from one device to another with same parameter set.
NXS: Store parameter to keypad [34262; 12.05.2010]
NXL: Store parameter [34260; 18.03.2010]
Q 409933_03
7
163 Copyright © 2013 INVENTIO AG
Load the parameter WARNING Stop drive
The drive has to be stopped before loading any parameters.
At NXS the parameter P6.7.2 (Fan control) will be set to 0 (continuous run). Change the parameter manually if necessary.
NXS: Load parameter from keypad [34279; 12.05.2010]
NXL: Load parameter [34258; 18.03.2010]
164 Copyright © 2013 INVENTIO AG
Q 409933_03
Reset the parameter to default
NXS: Reset parameter to default [34261; 16.03.2010]
NXL: Reset parameter to default [34257; 16.03.2010]
7
Q 409933_03
165 Copyright © 2013 INVENTIO AG
Lock the parameter
NXS: Lock parameter [34263; 17.03.2010]
NXL: Lock parameter [34259; 16.03.2010]
166 Copyright © 2013 INVENTIO AG
Q 409933_03
7.3
Troubleshooting
Manual Control
For troubleshooting the keypad can be activated to control the GFU. Change value P3.1 from 1 to 2. – NXS: Menu M3 “Keypad control” – NXL: Menu K3. Set the value P3.2 to nominal frequency. Press the START button on the GFU. The display shows [RUN]. Start the unit with the key switch. Vary the value of P3.2 with the UP or DOWN button.
7.4
Error Messages An error remains active until it is cleared with the reset button or via reset signal from the I/O terminal.
Type
Meaning
A
Alarm: Unusual operating condition. No impact on the drive. Only shown for 30 seconds.
F
Fault: Drive stopped. Measures must be taken to restart the drive.
AR
Autoreset: Drive stopped and automatically restarted.
FT
Fault trip: See error type F.
Q 409933_03
7
167 Copyright © 2013 INVENTIO AG
Error Codes Code
Possible Cause
Correction
1
Overcurrent Check the motor load – Sudden load increase Check the motor output – Short circuit of cable Check the motor cable – Motor not suitable
2
Overvoltage Extend the deceleration time – Deceleration time too Install an additional brake chopper short – Spikes in power supply system
3
Ground fault – Insulation fault in cables or motor
Check the motor and cables
5
Charging contactor – Open at start – Component failure
Perform a restart Replace the GFU
6
Emergency stop – Option board send stop signal
7
Saturation error – Component failure
Disconnect the GFU from power supply Do NOT switch on the GFU
8
System error – Component failure
Perform a restart Replace the GFU
9
Undervoltage Check the power supply – Power supply too low Perform a restart – Internal error
10
Line phase missing
Check the power supply and cable
11
Phase current missing
Check the motor and cable
12
Brake chopper defective
Check the brake resistor Check the brake chopper
168 Copyright © 2013 INVENTIO AG
Q 409933_03
Code
Possible Cause
Correction
13
Undertemperature – Heat sink temperate below -10 °C
14
Overtemperature – Heat sink temperate over 90 °C
Check the cooling quality and air flow Check the heat sink for dust
15
Motor stalled
Check the motor
16
Overtemperatur in motor
Decrease the motor load Check the parameter of motor temperature model
17
Motor underload
22
EEPROM error
24
Counter display defective
25
Microprocessor error
Perform a restart Replace the GFU
26
Drive cannot start up
Delete the start-up inhibition
29
Thermistor fault
Check the motor load and cooling Check the thermistor connection (Input of the expansion card must be shorted if not used)
32
Cooling fan defective
Replace the GFU
34
CAN Bus error
Ensure the same parameter on the second device
36
Control unit
Replace the control unit
37
Device replacement
Reset
38
Device added
Reset
39
Device removed
Reset
40
Device unknown
Replace the GFU
41
IGBT overtemperature
Check the motor load
Q 409933_03
169 Copyright © 2013 INVENTIO AG
7
Code
Possible Cause
Correction
42
Overtemperature in brake resistor
Extend the deceleration time Use an external brake resistor
43
Encoder fault
Observe the deviating error time log: 1 = Channel A missing 2 = Channel B missing 3 = Both channels missing 4 = Encoder reversed Check the encoder connection Check the encoder board
44
Device replacement
Reset
45
Device added
Reset
50
No signal at analog input
Check the circuit of analog input Check if the cables are broken or loose
51
External error
Check the circuit of digital inputs
52
Communication error
Check the control panel connection Check the control cable
53
Field bus error
Check the board installation Replace the GFU
54
Board connection error
Check the board and slot Replace the GFU
55
Monitoring of actual value
170 Copyright © 2013 INVENTIO AG
Q 409933_03
7.5
Replacement The replacement must meet the motor requirements.
Enter the parameters according to the control cabinet sticker after a replacement or upon “Loading the default values”. The motor parameter must be set according to the motor rating plate if not indicated on the control cabinet sticker.
5
1 2 3 4 Example motor rating plate [33990; 26.02.2010]
1 2 3 4 5
Nominal motor speed Nominal motor current Nominal motor voltage Power factor cos Nominal motor frequency
Q 409933_03
7
171 Copyright © 2013 INVENTIO AG
Submenu Parameter Parameter NXS
1.10
P2.1.6
P2.1.6 Nominal motor voltage
1.11
P2.1.7
P2.1.7 Nominal motor frequency
1.12
P2.1.8
P2.1.8 Nominal motor speed
1.13
P2.1.9
P2.1.9 Nominal motor current
-
NXL
Identifier
CXL
P2.1.10 P2.1.10 Power factor cos
1.17 P2.1.15 P2.1.19 Nominal speed 1.19 P2.1.17 P2.1.21 Crawling speed 1.21 P2.1.19 P2.1.23 Inspection operation speed -
P2.10.1 P2.9.1 DC Level = Nominal motor voltage 1.625
Switch off and padlock the main switch JHA. Replace the defective device. Switch on the main switch JHA. NXS only: Verify the presents of the “SchindlerMSS” application (menu S6.2). Set all parameters accordingly. Initiate the learning run.
172 Copyright © 2013 INVENTIO AG
Q 409933_03
8
Esca-Scan
8.1
Functional Elements
LEDs Function
Color
CONTROLLER Fail Red
Meaning
Self test. Power or controller failure
Ready
Green No light barrier is interrupted
Sync
Yellow Light curtain test
Data
Red
Light curtain feedback
8
Q 409933_03
173 Copyright © 2013 INVENTIO AG
Display Display
Meaning
[0 0 ]
No light barrier is interrupted
[]
Number of the first interrupted light barrier
[.]
Transmitter chain is defective
[.]
Receiver chain is defective
[..]
Control unit is defective
234 Detect
ESCA-SCAN CONTROLLER Ready
1
Sync Data +V +V SynLE DAT
SC
CONTROLLER Fail
5 [49606; 11.12.2013]
1 2 3 4 5
174 Copyright © 2013 INVENTIO AG
Display Data LED Sync LED Ready LED Error LED
Q 409933_03
8.2
Function Check
Switch on the power supply of the light curtain. Cover the top- and bottom-most light barrier of the light curtain. Start the unit with the key switch. Stop the unit with the stop button. – The display of the light curtain control unit must show [01] = Unit occupied. Remove the cover from the bottom-most light barrier. – The display must show the number of the top-most light barrier. Remove the cover from the top-most light barrier. – The display must show [00] = Unit not occupied. – The unit should start automatically.
8
Q 409933_03
175 Copyright © 2013 INVENTIO AG
8.3
Replacement Check the skirt lenses for dirt and scratches which can be the cause of the malfunction before replacing a transmitter or receiver. Transmitter circuit is colored in black. Receiver circuit is colored in red. Do not mix.
Switch off and padlock all power supply switches (JHA, light circuit, heating). Alternately loosen the two fixing screws of the defective device. Disconnect the defective device from the ribbon cable. Remove the O-ring and check it for damage. Replace it if damaged. Insert the O-ring into the new device. Connect the new device to the ribbon cable. Secure the connector with the fixing screws. Do not use force. Fit the device to the bracket. Switch on the unit and check the function.
176 Copyright © 2013 INVENTIO AG
Q 409933_03
9
Balustrade lighting DANGER
High Voltage Contact to high voltage will lead to death. Switch off the circuit breaker in the building and secure it against accidental or unauthorized access.
Troubleshooting Switch off and padlock the power supply of the balustrade lighting. Bridge one tube at the time with a high voltage insulated cable. Switch on the power supply. – If the tubes light up the bridged tube is defective. Switch off and padlock the power supply of the balustrade lighting. Replace defective tube and silicone caps.
9
Q 409933_03
177 Copyright © 2013 INVENTIO AG
10 Lobby Vision 10.1 Requirements Units should be equipped with the latest software version. RMS box should be equipped with software version X582340_09 (version 1009). The communication cable must meet the specification of order number 183918. Maximum allowed cable length is 1000 meter in total. Otherwise a repeater is required. Both ends of the communication line must be terminated with a 120 Ohm resistor (Jumper on 31/32). Maximum 7 units connected in one string when a PEM4.Q PCB is within this string (RMS box is a PEM4.Q PCB). Otherwise a repeater is required. Maximum 30 units connected in one string when no PEM4.Q PCB is within this string. Maximum 30 units connected to one RMS box. Communication cable connection according to the wiring diagram.
178 Copyright © 2013 INVENTIO AG
Q 409933_03
10.2 Parameter Unit Parameters: P0069 indicates the PCB connected to the communication line. 2 = PT, 4 = PB, 6 = PA, 8 = P2, 10 = P3. P0110 = 6 if P0069 = 2 P0112 = 6 if P0069 = 4 P0114 = 6 if P0069 = 6 P0116 = 6 if P0069 = 8 P0118 = 6 if P0069 = 10 P0119 = Unique unit address (1–30) per RMS box if P0069 = 2 P0120 = Unique unit address (1–30) per RMS box if P0069 = 4 P0121 = Unique unit address (1–30) per RMS box if P0069 = 6 P0122 = Unique unit address (1–30) per RMS box if P0069 = 8 P0123 = Unique unit address (1–30) per RMS box if P0069 = 10. RMS Box Parameter: After switch-on, the display will show the address of the RMS box (P001).
P000 = Number of units (1–30) connected to the RMS box P001 = Unique RMS box address (1–XX) P008 = 3 P009 = 3.
10.3 RMS Box DIL Switches Position S7/
ON 1
ON 2
ON 3
OFF 4
OFF 5
OFF 6
OFF 7
OFF 8
10 Q 409933_03
179 Copyright © 2013 INVENTIO AG
10.4 RMS Box Menu To enter the main menu press the ESC and OK buttons simultaneously until the display shows [U__A]. Use the UP or DOWN button to select the desired function. Press the OK button to activate the function. The ESC button can be used at any time to abort the function and return to the previous selection if not mentioned different.
Display
Function
[U__A]
Display of operating data
[U__P]
Parameters
[U__r]
Set RTC
[U__A] – Display of operating data: [A_01] – shows the number of units with active communication. [A_02] – shows if communication with the Lobby Vision is active (0 = inactive, 1 = active). [A_03] – shows the software version installed on the RMS PCB. Example [1009] = Software X582340_09. [A_04] – shows the address of the last communication request between the RMS box and the units (1-P000). [A_11-[A_40] shows the status of communication between the RMS box and each single unit. [A_11] for unit with address 1 up to [A_40] for unit with address 30.
Display
Status of Communication
[_000]
Unit never communicated
[_001]
Communication buildup
[_010]
Communication activated
[_020]
Communication lost
180 Copyright © 2013 INVENTIO AG
Q 409933_03
[U__P] – Parameters: Use the UP or DOWN button to select the desired authorization (see next table). Press the OK button to confirm the selection. Use the UP or DOWN button to select the desired parameter. Press the OK button to confirm the parameter. The current value of the parameter is shown. Use the UP or DOWN button to change the value of the parameter. Store the new value: – With the ESC button, no changes are stored. – With the OK button, the changed value is stored. Press the ESC button until the display shows [U---]. A boot-up is triggered automatically. Display
Authorization
[PP00]
Read-only. No parameters are editable
[PP22]
Parameters are editable
[U__r] – Set RTC: Refer to the corresponding chapter at MIC F 5E.
10 Q 409933_03
181 Copyright © 2013 INVENTIO AG
10.5 Troubleshooting Check the units and RMS box for latest software version. Connect X5.1 of the RMS box directly to X5.1 of the PCB foreseen for the communication of the unit with address 1. Connect X5.2 of the RMS box directly to X5.2 of the PCB foreseen for the communication of the unit with address 1. Use RMS box menu [A_11] if the communication is active. Display should show [_010] after a short time. If not, check parameter setting of the unit and the RMS box. Connect X5.1 of the RMS box directly to X5.1 of the PCB foreseen for the communication of the unit with address 2. Connect X5.2 of the RMS box directly to X5.2 of the PCB foreseen for the communication of the unit with address 2. Use RMS box menu [A_12] if the communication is active. Display should show [_010] after a short time. If not, check parameter setting of the unit. – Proceed step by step with all units. Connect the unit with address 1 and the unit with address 2 to the RMS box. Use RMS box menu [A_11] and [A012] if the communication is active. Display should show [_010] after a short time. If not, check communication cable for correct connection and termination. – Proceed step by step until all units are connected and active. Connect the RMS box to the Lobby Vision. Use RMS box menu [A_02] if the communication to the Lobby Vision is active. Display should show [___1] after a short time.
182 Copyright © 2013 INVENTIO AG
Q 409933_03
Personal notes