45 3 7MB
Copyright © 2019 NR. All rights reserved. NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR trademarks may be used without written permission. NR products appearing in this document may be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and benefits afforded under P.R. China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation. NR Engineering Co., Ltd. is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights. The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified. Information in this document is subject to change without prior notice. To the extent required the products described herein meet applicable IEC and IEEE standards, but no such assurance is given with respect to local codes and ordinances because they vary greatly. Although every reasonable effort is made to present current and accurate information, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please do not hesitate to contact us.
Preface
Preface About This Manual The technical manual describes the protection, automation, control, and supervision functions of PCS S series device for line differential protection, and contains operation principle descriptions, and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data, sorted per function, as well as the hardware of the device. The manual can be used as a technical reference during the engineering phase and during normal service. In addition, the manual also includes a glossary that lists and defines technical terms used throughout the manual.
Safety Information This manual is not a complete index of all safety measures required for operation of the equipment (module or device). However, it comprises important information that must be followed for personal safety, as well as to avoid material damage. Information is highlighted and illustrated as follows according to the degree of danger: Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury. Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury or equipment damage. Indicates that property damage can result if the measures specified are not taken. Important information about the device, product handling or a certain section of the documentation which must be given particular attention.
Instructions and Warnings The following hazard statements apply to this device.
Disconnect or de-energize all external connections BEFORE opening this
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
I
Preface
device. Contact with hazardous voltages and currents inside this device can cause electrical shock resulting in injury or death.
Contact with instrument terminals can cause electrical shock that can result in injury or death.
Use of this equipment in a manner other than specified in this manual can impair operator safety safeguards provided by this equipment.
Have ONLY qualified personnel service this equipment. If you are not qualified to service this equipment, you can injure yourself or others, or cause equipment damage.
This device is shipped with default passwords. Default passwords should be changed to private passwords at installation. Failure to change each default password to a private password may allow unauthorized access. NR shall not be responsible for any damage resulting from unauthorized access.
DO NOT look into the fiber (laser) ports/connectors.
DO NOT look into the end of an optical cable connected to an optical output.
DO NOT perform any procedures or adjustments that this instruction manual does not describe.
During installation, maintenance, or testing of the optical ports, ONLY use
II
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
Preface
the test equipment qualified for Class 1 laser products!
Incorporated components, such as LEDs, transceivers, and laser emitters, are NOT user serviceable. Return units to NR for repair or replacement.
Equipment components are SENSITIVE to electrostatic discharge (ESD). Undetectable permanent damage can result if you do not use proper ESD procedures. Ground yourself, your work surface, and this equipment BEFORE removing any cover from this equipment. If your facility is not equipped to work with these components, contact NR about returning this device and related NR equipment for service.
Insufficiently rated insulation can deteriorate under abnormal operating conditions and cause equipment damage. For external circuits, use wiring of SUFFICIENTLY RATED insulation that will not break down under abnormal operating conditions.
SEVERE power and ground problems can occur on the communications ports of this equipment as a result of using non-standard cables. Please use the wiring method recommended in the manual for communication terminals.
DO NOT connect power to the relay until you have completed these procedures and receive instruction to apply power. Equipment damage can result otherwise.
Use of controls or adjustments, or performance of procedures other than those specified herein, may RESULT IN hazardous radiation exposure.
The firmware may be upgraded to add new features or enhance/modify
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
III
Preface
existing features, please MAKE SURE that the version of this manual is compatible with the product in your hand.
Document Conventions
The abbreviations and acronyms in this manual are explained in “Appendix A Glossary”. The Glossary also contains definitions of important terms.
Menu path is connected with the arrow "→" and bold. For example: the access path of protection settings is: MainMenu -> Settings -> Protection Settings
Settings not in the table should be placed in brackets. For example: the system setting [Opt_SysFreq]
Cross-references are presented in italics. For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed meanings, should be written in double quotes and bold. For example: press the button "ENT".
Symbols
AND Gate
&
&
&
>=1
>=1
OR Gate
>=1
Comparator
Binary signal Input BI
IV
xxx
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
Preface
Signal input SIG
Setting input SET
xxx
Enable input EN
xxx
xxx
Timer Optional definite-time or inverse-time characteristic Timer t t
Timer Fixed delay pickup (10ms), fixed delay drop-off (2ms) 10ms
2ms
Timer Settable delay pickup, fixed delay drop-off [Tset1]
0ms
Timer Fixed delay pickup, settable delay drop-off 0ms
[Tset2]
Timer Settable delay pickup, settable delay drop-off [Tset1]
[Tset2]
Generator
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
V
Preface
G
Transformer
Reactor
Motor
M
Capacitor
C
Busbar
Circuit breaker
52
Current transformer 3CT
*
VI
Voltage transformer
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
Preface
3VT
Disconnector
Earth
Three-phase Corresponding Relationship Basic A, B, C
L1, L2, L3
R, Y, B
AN, BN, CN
L1N, L2N, L3N
RN,YN, BN
ABC
L123
RYB
U (voltage)
V
U Example
Ia, Ib, Ic, I0
IL1, IL2, IL3, IN
IR, IY, IB, IN
Ua, Ub, Uc
VL1, VL2, VL3
UR, UY, UB
Uab, Ubc, Uca
VL12, VL23, VL31
URY, UYB, UBR
U0, U1, U2
VN, V1, V2
UN, U1, U2
Copyright Copyright © 2018 NR. All rights reserved. We have all the intellectual property rights of this manual and its content. Except with the express authorization, copy or distribution to third parties is prohibited. We verify regularly the content of this manual. In future versions, some amendments will be necessary. But inevitably, there will be errors. Thank you to propose your advice for improvement. We reserve the rights of technical improvement without prior notice.
Trademarks NR® is a registered trademark of NR Electric Co., Ltd. Any unauthorized use is illegal. The other brands or product names are trademarks or registered trademarks of their respective owners. All products of NR Electric referenced in this document are registered trademarks of NR Electric.
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
VII
Preface
Warranty This product is covered by the standard NR 10-year warranty. For warranty details, please consult the manufacturer or agent for warranty information.
Declaration This content does not form part of a contract or of business relations, and nor does it change these. All the obligations of NR are stipulated in the contractual agreements. NR reserves the rights to revise this manual from time to time. The product documents of NR can be sent and received separately from other goods. Therefore, this manual is provided to ensure that the information of the product are perfectly understood by the recipient. Before performing a job, user must be familiar with the contents of this manual and carefully read the chapters.
Document Structure This manual is a comprehensive work covering the theories of protection, control, supervision, measurement, etc. and the structure & technical data of relevant hardware. Read the sections that pertain to your application to gain valuable information about using the PCS-915SC. To concentrate on the target sections of this manual as your job needs and responsibilities dictate. An overview of each manual section and section topics follows.
1 Introduction Introduces PCS-915SC features, summarizes functions and applications of the device.
2 Technical Data Lists device specifications, type tests, and ratings.
3 Protection Functions Describes the function of various protection elements, gives detailed specifics on protection scheme logic, provides the relevant logic diagrams.
4 Measurement Provides information on viewing fundamental and rms metering quantities for voltages and currents.
5 Supervision Describes self-supervision technique to help diagnose potential difficulties should these occur.
6 System Function Describes how to perform fundamental operations such as clock synchronization, communicating with the device, switching active setting group, checking relay status, reading event reports and SER (Sequential Events Recorder) records.
7 Hardware
VIII
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
Preface
Describes the hardware of the PCS series device family and provides general information on the product structure and the modules technical data.
8 Settings Provides a list of all PCS-915SC settings and their ranges, unit, steps, defaults. The organization of the settings is similar to the settings organization in the device and in the PCS-Studio configuration tool.
Appendix A Glossary Describes the abbreviations adopted in this manual.
Disclaimer This document has been subjected to rigorous technical review before being published, but the deviations cannot be totally excluded. It is revised at regular intervals, and any modifications and amendments are included in the subsequent issues. In the case where errors are detected, the reader is requested to inform the manufacturer. The content of this manual has been compiled for information purposes only. Although NR has done its best to ensure that the document remains the most precise and the most up-to-date as possible, NR shall not assume any liability for defects and damage which result through use of the information contained herein.
Document Revision History PN: ZL_PCS-915SC_X_Technical Manual_EN_Overseas General_X Current version: R1.00 Corresponding Version Date Document
Software
R1.00
R1.00
R1.01
R1.00
2019-01-29
Description of change
Form the original manual.
The current settings conversion description is added;
The setting range of the system setting [Active_Grp] is modified;
2019-03-11
The binary input [87B.BI_ExtBlk] and the alarm signal [87B.Alm_BI_ExtBlk] are deleted;
The logics of 87B, 50DZ, 50SOTF are modified.
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
IX
Preface
X
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
1 Introduction
1 Introduction
1
Table of Contents 1.1 Application ....................................................................................................... 1-1 1.2 Functions ......................................................................................................... 1-1 1.3 Features ............................................................................................................ 1-4
List of Figures Figure 1.2-1 Functional diagram of PCS-915SC....................................................................... 1-1
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
1-a
1 Introduction
1
1-b
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
1 Introduction
1.1 Application PCS-915SC centralized busbar relay integrates busbar differential protection, bus coupler/section protection (includes overcurrent protection, switch-onto-fault protection, dead zone fault protection and breaker failure protection) and feeder protection (includes overcurrent protection, dead zone fault protection and breaker failure protection). With its flexibility and the powerful PCS-Studio configuration tool, PCS-915SC offers future-oriented busbar solutions with high investment security and low operating costs.
1.2 Functions The function diagram of this relay is shown in Figure 1.2-1.
} 3 CTs
87B
50BF
50DZ
FR
50/51
3 CTs
3 CTs * 52
* 52
Bay 1
Bay 2
……
* 52
}
Bay n *
Busbar 1
50SOTF
3 CTs 52
Busbar 2
Bus coupler
Figure 1.2-1 Functional diagram of PCS-915SC
1
Protection Functions
The functions of this relay include protective functions and auxiliary testing functions, and the functions of this relay are listed in the following tables. No.
Function
Remark
Steady-state
percentage
ANSI restraint
busbar
differential protection 1
Busbar differential protection
87B
DPFC percentage restraint busbar differential protection
2
Breaker failure protection (50BF)
50BF
Dead zone fault protection (50DZ)
50DZ
Bus coupler/section protection
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
1-1
1
1 Introduction
1 3
4
Feeder protection
Switch-onto-fault protection (50SOTF)
50SOTF
Overcurrent protection (50/51)
50/51
Breaker failure protection (50BF)
50BF
Dead zone fault protection (50DZ)
50DZ
Overcurrent protection (50/51)
50/51
Dynamic busbar replica
CT circuit supervision
VT circuit supervision
Disconnector position alarm
Auxiliary function
DPFC is the abbreviation of “deviation of power frequency component”. When a fault occurs in the power system, the fault current consists of three parts: the pre-fault power frequency components, the power frequency variables during the fault and the transient variables during the fault. DPFC is the power frequency variables during the fault. 2
Measurement functions
Phase angle measurement
Differential current calculation
Sequence component calculation
Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision events, 256 control logs and 1024 device logs.
Disturbance recorder including 32 disturbance records with waveforms (The file format of disturbance recorder is compatible with international COMTRADE file.)
3
Supervision functions
Self diagnostic
Frequency supervision
DC power supply supervision
CT circuit supervision
VT circuit supervision
Disconnector supervision
1-2
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
1 Introduction
4
Communication
Up to four 10Base-T/100Base-TX copper Ethernet ports using IEC 61850, DNP3.0 or IEC 60870-5-103 over TCP/IP
Up to four 100Base-FX optical Ethernet ports using IEC 61850, DNP3.0 or IEC 60870-5-103 over TCP/IP
Two RS-485 serial ports using IEC 60870-5-103, DNP3 or Modbus
One RS-485 serial port for clock synchronization
Support GOOSE communication module using IEC 61850-8-1 GOOSE
Full compatibility between IEC 61850 Editions 1 and 2
Redundancy protocols PRP and HSR
One RS-485 serial port for clock synchronization
5
User Interface
Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and set-point adjustment
4 Programmable operator pushbuttons with user-configurable labels
Up to 18 programmable target LEDs with user-configurable labels
1 RS-232 or RS-485 rear ports for printer
Language switchover—English+ selected language
Configuration tool—PCS-Studio
6
Additional functions
User programmable logic
Fault phase selection
System phase sequences rotation function (ABC or ACB)
Clock synchronization
IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fiber interface
PPS: Pulse per second (PPS) via RS-485 differential level or binary input
PPM: Pulse per minute (PPM) via RS-485 differential level or binary input
IEEE1588: Clock message based on IEEE1588 via optical fiber interface
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
1-3
1
1 Introduction
1
SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network
SNTP (BC): Broadcast SNTP mode via Ethernet network
Message (IEC103/Modbus/DNP3.0): Clock messages through IEC103 protocol, Modbus protocol and DNP3.0 protocol
Cyber security
NERC CIP
IEC 62351
IEC 62443
IEEE 1686
1.3 Features
Unified software and hardware platform, comprehensive power grid solutions of protection, control, measurement and monitoring, easy to use and maintain.
High reliability and redundancy design for drive systems of the sampling circuit and the output circuit ensure that overall reliability of the device is high. Real-time sampling based on dual AD can mutually check and detect the potential abnormality in the sampling circuit in time. The control power supply of the output relay is independent with the control circuit of trigger signals, which can prevent from undesired operation caused by the abnormality of drive circuit of output relays.
Various function modules can satisfy various situations according to the different requirements of users. Flexible and universal logic programming, user-defined configuration of BI/BOs, buttons and LEDs and powerful analog programming are supported.
Modularized hardware design makes the device be easily upgraded or repaired by a qualified service person. It can be mixed with different I/O modules, with online self-check and monitoring function, and the device can be restored from abnormal operation only need to replace a single abnormal module.
Support memory check and error correction function, ensure high reliability and safety.
Support the internet communication protocol of native PRP/HSR and RSTP.
Fully compatible with IEC 61850 edition 1 & edition 2, support MMS service, IEC 62351 communication service, GOOSE communication in station level & process level, SV
1-4
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
1 Introduction
communication with multi-sampling rate.
Full comply with cyber security standards, including IEC62443, IEC62351, IEEE1686, NERC-CIP, support role based access control (RBAC), security audit, security encryption communication and security tool, improve the cyber security capability of devices.
Powerful COMTRADE fault and disturbance recording function is supported. The whole recording time is automatically configurable by the fault duration, which is convenient to fault analysis and replay. The recording sample rate is up to 9.6kHz.
Settable secondary rated current (1A/5A) and settable voltage threshold of binary input
Support flush mounting, semi-flush mounting, surface mounting, wall mounting and other mounting methods.
Cross screw IO, CT/VT terminals can support AWG12 specification connector and 4mm2 lead
Protection class of front side is up to IP54
PCS-Studio configuration tool is the application software on the user’s PC for the interface with PCS S series devices providing all the related functionality. It ranges from device configuration to full substation design of bay integration.
Support IEEE1588, IRIG-B clock synchronization
Support actual system phase sequence, either ABC or ACB, incorrect connection of actual phase sequence can automatically be verified and relevant protection functions can be blocked.
Equipped with high-speed large capacity output relay, its operation speed is less than 1ms and its break capacity is up to 10A. The real-time supervision for output drive circuit can detect the abnormality in advance.
Support setup up to 40 users and allow each user to own different password and access authority.
Applicable for single busbar, single bus with bus section, double busbar, double busbar with bus section, etc. busbar arrangement, and the busbar differential protection can connect up to 4 busbars and 32 bays.
Comprehensive functionality including phase segregated current differential protection, breaker failure protection, overcurrent protection and dead zone protection, etc.
The phase segregated differential protection adopts both of deviation of power frequency
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
1-5
1
1 Introduction
component (DPFC) and steady-state component, that can guarantees fast and reliable performance during CT saturation. It can ensure no mal-operation of external fault and fast
1
operation of internal fault in the case of the correct transfer time of CT is no less than 3ms.
With patented adaptive-weight anti-saturation algorithm and harmonic restrain algorithm, the DPFC differential protection operates fast and not affected by load current, the typical operation time is within 15ms.
Voltage blocking is an option for the current differential protection and breaker failure protection, which will improve the reliability of current differential protection and breaker failure protection.
With CT circuit supervision function, once CT circuit failure is detected, the user can choose discrimination zone or check zone differential protection blocking.
Both of phase segregated and three phase breaker failure binary inputs can be connected for breaker failure protection, users can choose whether or not blocked by the current criterion. The overcurrent element of breaker failure protection have been especially treated, the drop-off time of it is no more than 12ms.
Selectable IEC, ANSI inverse-time characteristic curves, also the curve can be defined by users and the inverse-time drop-off curve selection is supported.
With the disconnector position status monitor and memory function, the device can check the rationality of the memorized disconnector position status and automatically correct the error.
Users can disable the discrimination zone differential element by the external binary input during the busbar maintenance. Also the bay can be disabled by the external binary input when it is in maintenance.
LCD can display real-time main wiring diagram, the number of each bay, the state of each breaker and disconnector, current and power flow, etc.
1-6
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
2 Technical Data
2 Technical Data Table of Contents 2.1 Electrical Specifications ................................................................................. 2-1 2.1.1 AC Current Input ................................................................................................................... 2-1 2.1.2 AC Voltage Input ................................................................................................................... 2-1 2.1.3 Power Supply ....................................................................................................................... 2-2 2.1.4 Binary Input .......................................................................................................................... 2-2 2.1.5 Binary Output........................................................................................................................ 2-3
2.2 Mechanical Specifications .............................................................................. 2-4 2.3 Ambient Temperature and Humidity Range .................................................. 2-5 2.4 Communication Port ....................................................................................... 2-5 2.4.1 EIA-485 Port ......................................................................................................................... 2-5 2.4.2 Ethernet Port ........................................................................................................................ 2-5 2.4.3 Optical Fiber Port ................................................................................................................. 2-5 2.4.4 Print Port ............................................................................................................................... 2-6 2.4.5 Clock Synchronization Port .................................................................................................. 2-6
2.5 Type Tests ........................................................................................................ 2-6 2.5.1 Environmental Tests ............................................................................................................. 2-6 2.5.2 Mechanical Tests .................................................................................................................. 2-6 2.5.3 Electrical Tests ...................................................................................................................... 2-7 2.5.4 Electromagnetic Compatibility .............................................................................................. 2-7
2.6 Certifications .................................................................................................... 2-9 2.7 Terminals .......................................................................................................... 2-9 2.7.1 Ring Ferrule .......................................................................................................................... 2-9 2.7.2 Pin Ferrule ............................................................................................................................ 2-9
2.8 Measurement Scope and Accuracy ............................................................... 2-9 2.9 Management Function................................................................................... 2-10 2.9.1 Clock Performance ............................................................................................................. 2-10 PCS-915SC Centralized Busbar Relay Date: 2019-03-11
2-a
2
2 Technical Data
2.9.2 Fault and Disturbance Recording....................................................................................... 2-10 2.9.3 Binary Input Signal ............................................................................................................. 2-10
2.10 Protective Functions ................................................................................... 2-10 2.10.1 Busbar Differential Protection (87B)................................................................................. 2-10
2
2.10.2 Dead Zone Fault Protection (50DZ) ................................................................................. 2-10 2.10.3 Switch-onto-fault Protection (50SOTF) ............................................................................ 2-10 2.10.4 Breaker Failure Protection (50BF) ................................................................................... 2-10 2.10.5 Phase Overcurrent Protection (50/51P) ........................................................................... 2-11 2.10.6 Earth Fault Protection (50/51G) ....................................................................................... 2-11
2-b
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
2 Technical Data
2.1 Electrical Specifications
“System phase sequence”, which can be set by PCS-Studio, this setting informs the device of the actual system phase sequence, either ABC or ACB. CT and VT inputs on the device, labeled as A, B and C, must be connected to system phase A, B and C for correct operation.
2.1.1 AC Current Input Phase rotation
ABC or ACB
Nominal frequency (fn)
50Hz, 60Hz
Rated current (In)
1A/5A (settable)
Linear to
0.05In~40In
Thermal withstand -continuously
4In
-for 10s
30In
-for 1s
100In
-for half a cycle
250In
Burden
=1 &
& &
3
SET
[87B.Opt_CTS_Blk]=3
BI
@BBx.87B.BI_ExtBlk DS Alarm Block 87B_BBx
SIG
87B.On
SI G
87B.Alm_X_Off
SIG
@BBx.87B.Alm_X_Off
SIG
DPFC DIF_X
SI G
DPFC DIF_X BB1
SIG
DPFC_X current FD element
SI G
DPFC_X voltage FD element
SI G
SP DIF_X (K=0.2)
SIG
SP DIF_X BB1 (K=0.2)
EN
[87B.En_DPFC]
SI G
HM REL_X BB1
& @BBx.87B.Alm_C_Off
>=1
CT saturation detector 1
SIG
>=1
>=1
&
&
& 87B.Op_Trp@BB1_DPFC
&
>=1 & 500ms 0
SI G
SP DIF_X BB1
SI G
HM REL_X
&
& 87B.Op_Trp@BB1_Biased
>=1
>=1
&
Diff_BB1
500ms 0 SI G
SP DIF_X
SI G
87B.Valid
SIG
VCE_BBP Rls BB1
SIG
VCE_BBP Rls BBx
SIG
VCE_BBP Rls BBx & BBx is in service
EN
[87B.En_Dly_Biased]
SIG
SP DIF_X BBx
SI G
Δsi>ΔSI Float+0.5In
SI G
Δu>ΔUFloat+0.05Un
SET
ID>[87B.I_Pkp]
& 87B.Op_Trp@BC1
&
&
>=1
240ms 0
87B.Op_Dly1
480ms 0
87B.Op_Dly2
& 87B.FD
Figure 3.3-6 Logic of busbar differential protection
3-24
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
Where: X=A, B or C, means phase-A, phase-B or phase-C. Fail_Device: The device fails. The signal is issued with other specific alarm signals that will block the device. DS Alarm Block 87B_BBx: Bay n disconnector position alarm signal which will block busbar differential protection of BBx, please refer to Section 3.12.3.5. DPFC_X current FD element: please refer to Section 3.3.1.1. DPFC_X voltage FD element: please refer to Section 3.3.1.1.
3
DPFC DIF_X: phase-X DPFC percentage restraint differential element for check zone. DPFC DIF_X BB1: phase-X DPFC percentage restraint differential element for bus zone No.1. SP DIF_X: phase-X steady-state percentage restraint differential element for check zone. SP DIF_X BB1: phase-X steady-state percentage restraint differential element for bus zone No.1. SP DIF_X BBx: Steady-state percentage restraint differential element for any bus zone. HM REL_X: phase-X harmonic release element for check zone. HM REL_X BB1: phase-X harmonic release element for bus zone No.1. VCE_BBP Rls BB1: Busbar differential protection is not controlled by VCE_BBP or voltage controlled element of BBP of BB1 operates, please refer to Section 3.3.1.3 for details. VCE_BBP Rls BBx: Busbar differential protection is not controlled by VCE_BBP or voltage controlled element of BBP of any busbar operates, please refer to Section 3.3.1.3. VCE_BBP Rls BBx & BBx is in service: Busbar differential protection is not controlled by VCE_BBP or voltage controlled element of BBP of any energized busbar operates, please refer to Section 3.3.1.3. Diff_BB1: Differential element of BB1 (not controlled by voltage controlled element) operates. Δu>ΔUFloat+0.05Un, Δsi>ΔSIFloat+0.5In, ID> [87B.I_Pkp]: Please refer to Section 3.3.1.1. 87B.FD: Any FD element for busbar differential protection picks up. Different from BC, busbar differential protection operating to trip BS is not controlled by the voltage control element.
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-25
3 Protection Functions
3
SI G
BBx is in service
SIG
Ua[@BC1.50DZ.I_Set]
SIG
Ic_BC1>[@BC1.50DZ.I_Set]
SIG
BBP trip brea ker side BB
&
& >=1
[50DZ.t_Ack_TrpCB] 0
BC1 current is excluded from busbar differential current calculation
& @BC1.50DZ.Op
BBP trip CT side BB
Figure 3.4-1 Logic of BC/BS dead zone fault protection when BC/BS breaker is closed
DIF_CZ: Check zone percentage restraint differential element. BBP trip breaker side BB: busbar differential protection operates to trip the circuit breaker on the breaker side busbar, i.e. the signal “87B.Op_Trp@BBx_Biased” or “87B.Op_Trp@BBx_DPFC” (x=1 or 2, it is decided by the CT installation location). BBP trip CT side BB: busbar differential protection operates to trip the circuit breaker on the CT side busbar, i.e. the signal “87B.Op_Trp@BBx_Biased” or “87B.Op_Trp@BBx_DPFC” (x=1 or 2, it is decided by the CT installation location).
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-33
3 Protection Functions SIG
@BC1.BI_Cls
SIG
Ia_BC1[@Bayn.50DZ.I_Set]
SIG
Bayn.50DZ.Valid
@Bayn.50DZ.Pkp
>=1
& [Fdr.50DZ.t_Op] 0
@Bayn.50DZ.Op @Bayn.Op_TT
Figure 3.5-1 Logic of feeder dead zone fault protection when feeder breaker is closed
Where: @Bayn.50DZ.Pkp: FD element for feeder bay n dead zone fault protection picks up. TBD of bay n is closed: transfer bus disconnector (TBD) of bay n is closed.
3.5.5 Settings
Dead Zone Fault Protection Setting
Access path: MainMenu Settings Protection Settings 50DZ Settings Table 3.5-2 Settings of feeder dead zone fault protection No.
Name
Range
Default value
Unit
Step
1
Fdr.50DZ.t_Op
0.000~0.400s
0.020
s
0.001
2
50DZ.t_Ack_TrpCB
0.000~10.000s
0.100
s
0.001
3-38
Remark
Time delay for feeder dead zone fault protection, 20ms is recommended. The
breaker
open
position
confirmation time for feeder dead
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions zone
fault
protection
condition that
feeder
under
the
breaker
is
closed, 100ms is recommended. Current setting for feeder dead zone 3
Bayn.50DZ.I_Set
0.05In ~20.00In
0.100
A
0.001
fault protection of bay n, 0.1In is recommended. Logic setting of feeder dead zone fault protection of bay n
4
Bayn.50DZ.En
Disabled Enabled
Disabled
1: Enabling feeder dead zone fault protection of bay n 0: Disabling feeder dead zone fault protection of bay n
All the current settings in above table are converted according to the CT ratio of each bay.
3.6 BC/BS Switch-onto-fault (SOTF) Protection (50SOTF)
The bay label of displayed alarm signals, tripping signals, binary input signals, settings and sampled values related with each bay will change with the corresponding label settings. In this section, “@Bayn” is used to refer to the label setting of corresponding bay. For a bus coupler bay, “@BCy” is also used to refer to the label setting of corresponding bus coupler. For a bus section bay, “@BSz” is also used to refer to the label setting of corresponding bus section.
3.6.1 Function Description When a busbar is first energized via a BC/BS after maintenance or newly installed, the BC/BS SOTF protection can make the device trip the BC/BS immediately when it is closed on to a fault. BC/BS SOTF protection is not controlled by voltage controlled element. SOTF protection is enabled if the following conditions are met. 1.
The BC/BS breaker is in open position
2.
BC/BS three phase currents are smaller than 0.04In.
3.
Any of the two connected busbars is out of service.
If any of the following conditions is met, SOTF protection will be blocked after 300ms
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-39
3
3 Protection Functions
1.
The position status of BC/BS breaker changes from open to closed.
2.
BC current changes from being smaller than 0.04In to being larger than 0.04In.
3.
Both connected busbars are in service.
BC/BS SOTF protection will operate to trip BC/BS breaker without controlled by voltage controlled element.
3.6.2 Function Block Diagram 50SOTF
3
Ia_Bayn, Ib_Bayn, Ic_Bayn Ua_BBx, Ub_BBx, Uc_BBx @BCy.BI_52a
@BCy.50SOTF.Op_Trp @BCy.50SOTF.Alm_Pkp
@BCy.BI_52b
@BCy.50SOTF.Block @BCy.50SOTF.Enable
For a BS, Just use “BSz” to instead of “BCy” in the above function block diagram.
3.6.3 I/O Signal Table 3.6-1 Input/Output signals of BC/BS SOTF protection No.
Input Signal
Description
1
@BCy.50SOTF.Enable
Binary input of enabling SOTF of BCy
2
@BSz.50SOTF.Enable
Binary input of enabling SOTF of BSz
3
@BCy.50SOTF.Block
Binary input of disabling SOTF of BCy
4
@BSz.50SOTF.Block
Binary input of disabling SOTF of BSz
No.
Output Signal
Description
1
@BCy.50SOTF.Op_Trp
SOTF protection of BCy operates
2
@BSz.50SOTF.Op_Trp
SOTF protection of BSz operates
3
@BCy.50SOTF.Alm_Pkp
4
@BSz.50SOTF.Alm_Pkp
Alarm signal indicating that FD element for SOTF protection of BCy picks up for over 10s Alarm signal indicating that FD element for SOTF protection of BSz picks up for over 10s
3.6.4 Logic The logic of BC/BS SOTF protection is shown as follows (Takes BC1 in Figure 3.2-6 as an example). 3-40
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
&
EN
[@BC1.50SOTF.En]
SIG
@BC1.50SOTF.Enable
SIG
@BC1.50SOTF.Block
SIG
Fail_Device
@BC1.50SOTF.On
& @BC1.50SOTF.Blocked
≥1
& @BC1.50SOTF.Valid
SIG
Bre ake r of BC1 is o pen
SIG
BB1 is in service
SIG
BB2 is in service
SIG
Ia_BC1>0.04In
3 &
& 0 300ms
SIG
Ib_BC1>0.04In
SIG
Ic_BC1>0.04In
SIG
SET
&
& & @BC1.50SOTF.Op_Trp
>=1
@BC1.50SOTF.Vali d
Ia_BC1>[@BC1.50SOTF.I_Set]
SET
Ib_BC1>[@BC1.50SOTF.I_Set]
SET
Ic_BC1>[@BC1.50SOTF.I_Set]
& @BC1.50SOTF.Pkp
>=1
Figure 3.6-1 Logic of SOTF protection
Where: @BC1.50SOTF.Pkp: FD element for BC/BS SOTF protection picks up BBx is in service: Please refer to Figure 3.11-1.
3.6.5 Settings
Switch-onto-fault Protection Setting
Access path: MainMenu Settings Protection Settings SOTF Settings Table 3.6-2 Settings of switch-onto-fault protection No.
1
2
Name
Range
Bayn.50SOTF.I_Set
0.05In ~20.00In
Bayn.50SOTF.En
Disabled Enabled
Default value 1.000
Unit
Step
A
0.001
Remark
Current setting for BC/BS SOTF protection Logic setting of SOTF protection of
Disabled
bay n 1: Enabling SOTF protection of bay n
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-41
3 Protection Functions (only for BC/BS bay) 0: Disabling SOTF protection of bay n (only for BC/BS bay)
All the current settings in above table are converted according to the CT ratio of each bay.
3
3.7 Breaker Failure Protection (50BF)
The bay label of displayed alarm signals, tripping signals, binary input signals, settings and sampled values related with each bay will change with the corresponding label settings. In this section, “@BBx” is used to refer to the label setting of corresponding busbar and “@Bayn” is used to refer to the label setting of corresponding bay. For a bus coupler bay, “@BCy” is also used to refer to the label setting of corresponding bus coupler. For a bus section bay, “@BSz” is also used to refer to the label setting of corresponding bus section. When the bay protection or the busbar protection operates to trip the breaker of a bay, but the breaker fails, the breaker failure protection of the bay needs to be initiated. When the breaker failure protection operates, it will re-trip the circuit breaker of the bay with the first time delay, then it will trip all the breakers on the busbar that connected to the bay with the second time delay, and transfer trip the breaker of the remote end of a line or inter-trip the breakers on other sides of a main-transformer. Users can choose whether breaker failure protection is blocked by the current criterion or the voltage control element. Breaker failure protection of each bay can be enabled or disabled independently, the breaker failure current setting and the corresponding time delay of breaker failure protection of each bay can be set independently.
3.7.1 Function Description 3.7.1.1 Current Criterion of Breaker Failure Protection 1.
Phase current criterion
Phase current is greater than the setting [Bayn.50BF.I_Set] The phase current criterion is always enabled, but it can be blocked due to residual current if the logic setting [Bayn.50BF.En_3I0_1P] is set as “1”; or it will be blocked due to negative-sequence current if the logic setting [Bayn.50BF.En_I2_1P] is set as “1”. 2.
3-42
Residual current criterion
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
Residual current is greater than the setting [Bayn.50BF.3I0_Set] The logic setting [Bayn.50BF.En_3I0] is used to enable or disable the residual current criterion. 3.
Negative-sequence current criterion
Negative-sequence current is greater than the setting [Bayn.50BF.I2_Set] The logic setting [Bayn.50BF.En_I2] is used to enable or disable the negative-sequence current criterion.
When calculating all the current setting of each bay, the primary current should be converted to the secondary value according to the reference CT ratio instead of the actual CT ratio of each bay. 3.7.1.2 Voltage Control Element of Breaker Failure Protection (VCE_BFP) Voltage control element is used as an auxiliary condition. The criteria are: UP≤[50BF.VCE.U_Set]
Equation 3.7-1
3U0≥[50BF.VCE.3U0_Set]
Equation 3.7-2
U2≥[50BF.VCE.U2_Set]
Equation 3.7-3
If any of above equation is met, the voltage blocking of breaker failure protection will be released. Where: UP: Phase voltage 3U0: Residual voltage U2: Negative-sequence voltage [50BF.VCE.U_Set]: Phase voltage setting for releasing the voltage blocking of breaker failure protection [50BF.VCE.3U0_Set]: Residual voltage setting for releasing the voltage blocking of breaker failure protection [50BF.VCE.U2_Set]: Negative-sequence voltage setting for releasing the voltage blocking of breaker failure protection When the protective device is applied to an unearthed system, i.e. the system setting [Opt_UnearthedSys_Mode] is set as “1”, the criteria of voltage control element will change.
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-43
3
3 Protection Functions
UPP ≤ 3 [50BF.VCE.U_Set]
Equation 3.7-4
U2 ≥[50BF.VCE.U2_Set]
Equation 3.7-5
Where: UPP: Phase-to-phase voltage U2: Negative-sequence voltage
3
[50BF.VCE.U_Set]: Phase-to-ground voltage setting for releasing the voltage blocking of breaker failure protection [50BF.VCE.U2_Set]: Negative voltage setting for releasing the voltage blocking of breaker failure protection VCE_BFP will be controlled by the logic setting [50BF.VCE.En], if it is set as “0”, VCE_BFP will be disabled and bay breaker failure protection will not controlled by VCE_BFP If voltage concerned function is disabled, VCE_BFP will quit and related settings will be hidden, bay breaker failure protection will not controlled by voltage element. Only if voltage concerned function is enabled and the logic setting [50BF.VCE.En] is set as “1”, VCE_BFP is enabled. A binary input for releasing voltage control element for breaker failure protection [50BF.BI_RlsVCE] is provided. If the logic setting [Bayn.50BF.En_BI_RlsVCE] is set as “1” and the releasing voltage control element binary input “50BF.BI_RlsVCE” is energized, the voltage blocking for breaker failure protection of bay n will be released. If VCE_BFP or VCE_BBP of BBx operates for over 3s (i.e. the voltage blocking of breaker failure protection or busbar differential protection is released for over 3s), an alarm signal “@BBx.Alm_VCE” will be issued. 3.7.1.3 Circuit Breaker Error Binary Input Circuit breaker error binary input is generally used to connect the breaker control circuit failure binary input, or tripping pressure low binary input etc. If breaker failure protection is initiated and the circuit breaker error binary input is “0”, breaker failure protection will operate to re-trip the circuit breaker of the bay with the time delay of [Bayn.50BF.t_ReTrp], then it will trip all the breakers on the busbar that connected to the bay with the time delay of [Bayn.50BF.t_TrpBB], and transfer trip the breaker of the remote end of a line or inter-trip the breakers on other sides of a main-transformer. If breaker failure protection is initiated and the circuit breaker error binary input is “1”, breaker failure protection will operate to trip all the breakers on the busbar that connected to the bay with the time delay of [Bayn.50BF.t_TrpBB_CBErr], and transfer trip the breaker of the remote end of a line or inter-trip the breakers on other sides of a main-transformer. 3-44
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
3.7.1.4 Initiating Element of Breaker Failure Protection The initiating elements of breaker failure protection of each bay include the following:
Other protection of the device operates to initiate breaker failure protection 1.
BBP operates to trip bay n (controlled by the logic setting [87B.En_Init50BF])
2.
Overcurrent protection [50/51.En_Init50BF])
3.
BC/BS switch-onto-fault protection operates to trip the BC/BS
of
bay
n
operates
(controlled
by the
logic
setting
3
External binary input initiate breaker failure protection 1.
Phase-segregated breaker failure initiating (BFI) binary input “@Bayn.BI_A_BFI”: The binary input for initiating BFP of phase A of bay n, it corresponds to the signal that external device operates to trip phase-A “@Bayn.BI_B_BFI”: The binary input for initiating BFP of phase B of bay n, it corresponds to the signal that external device operates to trip phase-B “@Bayn.BI_C_BFI”: The binary input for initiating BFP of phase C of bay n, it corresponds to the signal that external device operates to trip phase-C emote end of a line or inter-trip the breakers on other sides of a main-transformer.
2.
Three-phase breaker failure initiating (BFI) binary input “@Bayn.BI_BFI”: The binary input for three-phase tripping to initiate BFP, it is mainly used in the case where the bay breaker has no phase-segregated tripping contacts, such as a transformer bay.
3.
Three-phase breaker failure initiating (BFI) binary input that is not controlled by current criterion “@Bayn.BI_ExTrp_WOI_BFI”: The three-phase breaker failure initiating binary input that is not controlled by current criterion, it is mainly used for mechanical protection operates to initiate BFP. This binary input is not controlled by the current criterion, but it is controlled by the breaker position of the bay.
After breaker failure protection is initiated, it will be widened for 500ms. If the external breaker failure initiate binary input is energized for over 10s, the BFI binary input alarm signal “@Bayn.Alm_ExTrp_WOI_BFI” will be issued, and the external binary input initiating breaker failure protection function will be exited at the same time. 3.7.1.5 Operating Element of Breaker Failure Protection
Other protection of the device operates to initiate breaker failure protection When other protection of the device operates to trip the bay, if the current criterion of breaker failure protection is met, and the voltage blocking for breaker failure protection is released,
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-45
3 Protection Functions
the breaker failure protection will operates to re-trip the circuit breaker of the bay with the time delay of [Bayn.50BF.t_ReTrp], then it will trip all the breakers on the busbar that connected to the bay with the time delay of [Bayn.50BF.t_TrpBB], and transfer trip the breaker of the remote end of a line or inter-trip the breakers on other sides of a main-transformer. When breaker failure protection is initiated, if the circuit breaker error binary input is “1” at the same time, breaker failure protection will operate to trip all the breakers on the busbar that connected to the bay with the time delay of [Bayn.50BF.t_TrpBB_CBErr], and transfer trip the breaker of the remote end of a line or inter-trip the breakers on other sides of a main-transformer.
3
External binary input initiate breaker failure protection 1.
Phase-segregated breaker failure initiating (BFI) binary input When any phase-segregated BFI binary input is energized, if the current criterion of breaker failure protection is met, and the voltage blocking for breaker failure protection is released, the breaker failure protection will operates to re-trip the circuit breaker of the bay with the time delay of [Bayn.50BF.t_ReTrp], then it will trip all the breakers on the busbar that connected to the bay with the time delay of [Bayn.50BF.t_TrpBB], and transfer trip the breaker of the remote end of a line or inter-trip the breakers on other sides of a main-transformer. If the logic setting [Bayn.50BF.En_TrpBB_Ext] is set as “1”, when any phase-segregated BFI binary input is energized, and the voltage blocking for breaker failure protection is released, the breaker failure protection will operates to trip all the breakers on the busbar that connected to the bay with the time delay of [Bayn.50BF.t_TrpBB_Ext], and transfer trip the breaker of the remote end of a line or inter-trip the breakers on other sides of a main-transformer. When breaker failure protection is initiated, if the circuit breaker error binary input is “1” at the same time, breaker failure protection will operate to trip all the breakers on the busbar that connected to the bay with the time delay of [Bayn.50BF.t_TrpBB_CBErr], and transfer trip the breaker of the remote end of a line or inter-trip the breakers on other sides of a main-transformer.
2.
Three-phase breaker failure initiating (BFI) binary input When three-phase BFI binary input is energized, if the current criterion of breaker failure protection is met, and the voltage blocking for breaker failure protection is released, the breaker failure protection will operates to re-trip the circuit breaker of the bay with the time delay of [Bayn.50BF.t_ReTrp], then it will trip all the breakers on the busbar that connected to the bay with the time delay of [Bayn.50BF.t_TrpBB], and transfer trip the breaker of the remote end of a line or inter-trip the breakers on other sides of a main-transformer. If the logic setting [Bayn.50BF.En_TrpBB_Ext] is set as “1”, when three-phase BFI binary input is energized, and the voltage blocking for breaker failure protection is released, the breaker failure protection will operates to trip all the breakers on the busbar that
3-46
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
connected to the bay with the time delay of [Bayn.50BF.t_TrpBB_Ext], and transfer trip the breaker of the remote end of a line or inter-trip the breakers on other sides of a main-transformer. When breaker failure protection is initiated, if the circuit breaker error binary input is “1” at the same time, breaker failure protection will operate to trip all the breakers on the busbar that connected to the bay with the time delay of [Bayn.50BF.t_TrpBB_CBErr], and transfer trip the breaker of the remote end of a line or inter-trip the breakers on other sides of a main-transformer. 3.
Three-phase breaker failure initiating (BFI) binary input that is not controlled by current criterion When the three-phase BFI binary input that is not controlled by current criterion is energized, and the breaker of the bay is closed, the breaker failure protection will operates to re-trip the circuit breaker of the bay with the time delay of [Bayn.50BF.t_ReTrp], then it will trip all the breakers on the busbar that connected to the bay with the time delay of [Bayn.50BF.t_TrpBB], and transfer trip the breaker of the remote end of a line or inter-trip the breakers on other sides of a main-transformer. When breaker failure protection is initiated, if the circuit breaker error binary input is “1” at the same time, breaker failure protection will operate to trip all the breakers on the busbar that connected to the bay with the time delay of [Bayn.50BF.t_TrpBB_CBErr], and transfer trip the breaker of the remote end of a line or inter-trip the breakers on other sides of a main-transformer.
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-47
3
3 Protection Functions
3.7.2 Function Block Diagram Feeder 50BF Ia_Bayn, Ib_Bayn, Ic_Bayn
@Bayn.50BF.Op_ReTrp
Ua_BBx, Ub_BBx, Uc_BBx
@Bayn.50BF.Op_TrpBBx
@Bayn.BI_89b_@BBx
50BF.Op
@Bayn.50/51P.Op_Trp
3
50BF.Op_Trp@BBx
@Bayn.BI_89a_@BBx
@Bayn.50BF.Op_TrpBB
@Bayn.50/51G.Op_Trp
@Bayn.Op_TT
@BCy.50SOTF.Op_Trp
@Bayn.Alm_BI_BFI
87B.Op_Trp@BBx_Biased @Bayn.Alm_ExTrp_WOI_BFI 87B.Op_Trp@BBx_DPFC
50BF.Alm_BI_RlsVCE
@Bayn.BI_BFI
50BF.Alm_Pkp
@Bayn.BI_A_BFI
50BF.Alm_Off
@Bayn.BI_B_BFI @Bayn.BI_C_BFI @Bayn.BI_ExTrp_WOI_BFI
@Bayn.50BF.BI_CBErr 50BF.BI_RlsVCE @Bayn.BI_52a @Bayn.BI_52b @Bayn.50BF.Enable @Bayn.50BF.Block
3.7.3 I/O Signal Table 3.7-1 Input/Output signals of breaker failure protection No.
Input Signal
Description
1
@Bayn.50BF.Enable
Binary input of enabling breaker failure protection of bay n
2
@Bayn.50BF.Block
Binary input of disabling breaker failure protection of bay n
3
@Bayn.50/51P.Op_Trp
Phase overcurrent protection of bay n operates
4
@Bayn.50/51G.Op_Trp
Ground overcurrent protection of bay n operates
5
87B.Op_Trp@BBx_Biased
Steady-state busbar differential protection operates to trip BBx
6
87B.Op_Trp@BBx_DPFC
DPFC busbar differential protection operates to trip BBx
7
@BCy.50SOTF.Op_Trp
SOTF protection of BCy operates
8
@BSz.50SOTF.Op_Trp
SOTF protection of BSz operates
9
@Bayn.BI_BFI
Three-phase BFI binary input of bay n
10
@Bayn.BI_A_BFI
Phase-A BFI binary input of bay n
11
@Bayn.BI_B_BFI
Phase-B BFI binary input of bay n
12
@Bayn.BI_C_BFI
Phase-C BFI binary input of bay n
3-48
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions No.
Input Signal
13
@Bayn.BI_89a_@BBx
14
@Bayn.BI_89b_@BBx
15
@Bayn.BI_ExTrp_WOI_BFI
16
@Bayn.50BF.BI_CBErr
Description Normally open auxiliary contact of BBx disconnector of bay n Normally closed auxiliary contact of BBx disconnector of bay n, it is used if disconnector dual-position auxiliary contacts are adopted The external BFI binary input of bay n which is not controlled by the current criterion Circuit breaker error binary input of bay n, this binary input is generally used to connect the breaker control circuit failure binary input, or tripping pressure low binary input etc.
17
@Bayn.BI_52a
18
@Bayn.BI_52b
19
50BF.BI_RlsVCE
No.
Normally open auxiliary contact of the circuit breaker of bay n. The input signal is only configured if dual-position BI for circuit breaker is enabled. Normally closed auxiliary contact of the circuit breaker of bay n. Binary input of releasing voltage controlled element of breaker failure protection
Output Signal
Description
1
@Bayn.50BF.Op_ReTrp
BFP of bay n operates to re-trip the feeder breaker
2
50BF.Op_Trp@BBx
BFP operates to trip BBx
3
@Bayn.50BF.Op_Trp@BBx
BFP of bay n operates to trip BBx
4
@Bayn.50BF.Op_TrpBB
BFP of bay n operates to trip busbar zone
5
50BF.Op
BC/BS BFP or feeder BFP operates
6
@Bayn.Op_TT
DZP or BFP of bay n operates to initiate transfer trip to remote circuit breaker Binary input of initiating contact of BFP of bay n (@Bayn.BI_A_BFI,
7
@Bayn.Alm_BI_BFI
@Bayn.BI_B_BFI, @Bayn.BI_C_BFI or @Bayn.BI_BFI) is energized for over 10s.
8
@Bayn.Alm_ExTrp_WOI_BFI
9
50BF.Alm_BI_RlsVCE
10
50BF.Alm_Pkp
The external BFI binary input of bay n which is not controlled by the current criterion is energized for over 10s. Binary input of releasing voltage controlled element of breaker failure protection is energized for over 10s. Alarm signal indicating that FD element for BFP of any bay picks up for over 10s Alarm signal indicating feeder BFP is disabled. If the logic setting [50BF.En_Alm_Off] is set as “1”, once feeder BFP is disabled (feeder BFP
11
50BF.Alm_Off
can be disabled by the corresponding enabling binary input, function link or enabling logic setting), the alarm signal indicating feeder BFP is disabled will be issued
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-49
3
3 Protection Functions
3.7.4 Logic EN
[Bayn.50BF.En]
BI
50BF.BI_Blk
BI
50BF.BI_En
& Bayn.50BF is enabled
& >=1
SIG
@Bayn.Alm_BI_BFI
SIG
@Bayn.Alm_ExTrp_WOI_BFI
SIG
Fail_Device
Bayn.50BF is blocked
& Bayn.50BF.Valid
3
EN
[87B.En_Init50BF]
SIG
BBP operates to trip bay n
EN
[50/51.En_Init50BF]
SIG
@Bayn.50/51.Op_Trp
SIG
@BCy.50SOTF.Op_Trp
SET
Ia_Bayn>[Bayn.50BF.I_Set]
SET
Ib_Bayn>[Bayn.50BF.I_Set]
SET
Ic_Bayn>[Bayn.50BF.I_Set]
EN
[Bayn.50BF.En_3I0]
SET
3I0_Bayn>[Bayn.50BF.3I0_Set]
&
&
>=1
>=1
& &
>=1
& @Bayn.50BF.Op_Trp@BBx
&
@Bayn.Op_TT
& [Bayn.50BF.t_TrpBB ] 0
EN
[Bayn.50BF.En_I2]
SET
I2_Bayn>[Bayn.50BF.I2_Set]
SIG
@Bayn.50BF is enabled
SIG
VCE_BFP Rls BBx
SIG
VCE_BFP is disabled
&
50BF.Op_Trp@BBx
&
BI
50BF.BI_RlsVCE
EN
Bayn.50BF.En_BI_RlsVCE
SIG
[Bayn.50BF.t_ReTrp] 0
@Bayn.50BF.BI_CBErr
EN
[50BF.En_ReTrp]
@Bayn.50BF.Op_ReTrp
& &
@Bayn.50BF.Op_Trp@BBx
@Bayn.Op_TT
&
Disconnector position of BBx
BI
3-50
>=1
[Bayn.50BF.t_TrpBB_CBErr]
0
50BF.Op_Trp@BBx
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
BI
&
@Bayn.BI_BFI
>=1
SET
BI SET
BI SET
&
Ia_Bayn>[Bayn.50BF.I_Set]
@Bayn.BI_A_BFI
>=1
&
Ib_Bayn>[Bayn.50BF.I_Set]
@Bayn.BI_B_BFI
&
Ic_Bayn>[Bayn.50BF.I_Set]
BI
@Bayn.BI_C_BFI
EN
[Bayn.50BF.En_3I0_1P]
SET
3I0_Bayn>[Bayn.50BF.3I0_Set]
EN
[Bayn.50BF.En_I2_1P]
SET
I2_Bayn>[Bayn.50BF.I2_Set]
3
>=1 &
>=1 >=1
& >=1
BI
@Bayn.BI_BFI
BI
@Bayn.BI_A_BFI
BI
@Bayn.BI_B_BFI
BI
@Bayn.BI_C_BFI
EN
[Bayn.50BF.En_3I0]
& & @Bayn.50BF.Op_Trp@BBx
& >=1
@Bayn.Op_TT
&
&
[Bayn.50BF.t_TrpBB ] 0
&
50BF.Op_Trp@BBx
& >=1
@Bayn.50BF.Op_Trp@BBx
&
&
@Bayn.Op_TT
& [Bayn.50BF.t_TrpBB_Ext]
SET
3I0_Bayn>[Bayn.50BF.3I0_Set]
EN
[Bayn.50BF.En_I2]
SET
I2_Bayn>[Bayn.50BF.I2_Set]
EN
Bayn.50BF.En_TrpBB_Ext
SIG
@Bayn.Alm_BI_BFI
SIG
@Bayn.50BF is enabled
0
50BF.Op_Trp@BBx
&
& & [Bayn.50BF.t_ReTrp] 0
@Bayn.50BF.Op_Trp@BBx
>=1
@Bayn.Op_TT
& [Bayn.50BF.t_TrpBB_CBErr]
SIG
VCE_BFP Rls BBx
SIG
VCE_BFP is disabled
BI
50BF.BI_RlsVCE
EN
Bayn.50BF.En_BI_RlsVCE
SIG
Disconnect or position of BBx
EN
[50BF.En_ReTrp]
BI
@Bayn.50BF.BI_CBErr
BI
@Bayn.50BF.Op_ReTrp
>=1
0
50BF.Op_Trp@BBx
&
@Bayn.BI_ExTrp_WOI_BFI
&
& &
SIG
@Bayn.BI_52b=0
SIG
@Bayn.Alm_ExTrp_WOI_BFI
SIG
@Bayn.50BF is enabled
SIG
Disconnector position of BBx
@Bayn.50BF.Op_Trp@BBx
&
@Bayn.Op_TT
& [Bayn.50BF.t_TrpBB ] 0
50BF.Op_Trp@BBx @Bayn.50BF.Op_Trp@BBx @Bayn.Op_TT
& [Bayn.50BF.t_TrpBB_CBErr] BI
0
50BF.Op_Trp@BBx
@Bayn.50BF.BI_CBErr
& [Bayn.50BF.t_ReTrp] 0 EN
@Bayn.50BF.Op_ReTrp
[50BF.En_ReTrp]
Figure 3.7-1 Logic of breaker failure protection PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-51
3 Protection Functions
Where: @Bayn.50/51.Op_Trp: phase overcurrent protection or ground overcurrent protection of bay n operates. @Bayn.50BF is enabled: breaker failure protection is enabled (the corresponding enabling binary input “@Bayn.50BF.Enable” is energized, the corresponding disabling binary input “@Bayn.50BF.Block” is de-energized and the corresponding enabling logic setting [@Bayn.50BF.En] is set as “1”). VCE_BFP Rls BBx: Voltage controlled element for BFP of any connected BBx.
3
VCE_BFP is disabled: voltage concerned function is disabled or the logic setting [50BF.VCE.En] is set as “0”. Disconnector position of BBx: which busbar the bay is connected to (according to disconnector position of the bay). @Bayn.50BF.FD: FD element for feeder bay n BFP picks up. 3I0_Bayn: The residual current of bay n. I2_Bayn: The negative-sequence current of bay n. Ia_Bayn: The phase A current of bay n. Ib_Bayn: The phase B current of bay n. Ic_Bayn: The phase C current of bay n.
3.7.5 Settings
Breaker Failure Protection Setting
Access path: MainMenu Settings Protection Settings BFP Settings Table 3.7-2 Settings of breaker failure protection No.
1
Name
50BF.VCE.U_Set
Default
Range
value
Unit
Remark
Step Phase
0~100.000
40.000
V
V
0.001
voltage
50BF.VCE.3U0_Set
for
releasing the voltage blocking of breaker failure protection. Residual
2
setting
0~63.000V
6.000
V
0.001
voltage
setting
for
releasing the voltage blocking of breaker failure protection. Negative-sequence
3
50BF.VCE.U2_Set
0~63.000V
4.000
V
0.001
voltage
setting for releasing the voltage blocking
of
breaker
failure
protection. 4
3-52
Bayn.50BF.I_Set
0~20.00In
1.000
A
0.001
Phase current setting of breaker
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions No.
Name
Range
Default value
Unit
Remark
Step
failure protection of bay n.
5
6
Bayn.50BF.3I0_Set
Bayn.50BF.I2_Set
0.05In~20. 00In
0.05In~20. 00In
Residual 0.500
A
0.001
current
setting
of
breaker failure protection of bay n. Negative-sequence
0.500
A
0.001
setting
of
breaker
current failure
protection of bay n. Time delay for breaker failure
7
Bayn.50BF.t_ReTrp
0~10.000s
0.100
s
0.001
protection of bay n operates to re-trip breaker. Time delay for breaker failure protection of bay n operates to
8
Bayn.50BF.t_TrpBB
0~10.000s
0.250
s
0.001
trip all the breakers on the busbar that connected to the bay. Time delay for breaker failure protection of bay n operates to trip all the breakers on the busbar that connected to the bay
9
Bayn.50BF.t_TrpBB_Ext
0~10.000s
0.020
s
0.001
when the logic setting
[Bayn.50BF.En_TrpBB_Ext]
is
set as “1” and the breaker failure protection
is
initiated
phase-segregated three-phase
breaker
by or
failure
initiating binary input. Time delay for breaker failure protection of bay n operates to 10
Bayn.50BF.t_TrpBB_CBErr
0~10.000s
0.020
s
0.001
trip all the breakers on the busbar that connected to the bay in case of the bay breaker is abnormal. Logic setting for enable or
11
Bayn.50BF.En
Disabled Enabled
disable Enabled
breaker
failure
protection of bay n 1: Enable 0: Disable
12
50BF.En_ReTrp
Disabled Enabled
Logic setting for enable or Enabled
disable re-tripping function of breaker failure protection of bay
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-53
3
3 Protection Functions No.
Name
Range
Default value
Unit
Remark
Step n 1: Enable 0: Disable
Logic setting for enable or disable residual current criterion 13
Bayn.50BF.En_3I0
Disabled Enabled
Disabled
of breaker failure protection of bay n 1: Enable
3
0: Disable Logic setting for enable or disable 14
Bayn.50BF.En_I2
Disabled Enabled
Disabled
negative-sequence
current
criterion
of
breaker
failure protection of bay n 1: Enable 0: Disable 1: The phase current criterion will be blocked by residual
15
Bayn.50BF.En_3I0_1P
Disabled Enabled
Disabled
current criterion 0: The phase current criterion will not be blocked by residual current criterion 1: The phase current criterion will
be
blocked
negative-sequence 16
Bayn.50BF.En_I2_1P
Disabled Enabled
Disabled
by current
criterion 0: The phase current criterion will
not
be
blocked
negative-sequence
by
current
criterion Logic setting for enable or disable initiating the breaker failure
protection
of
bay
n
externally. If it is set as “1”, and the breaker failure protection is 17
Bayn.50BF.En_TrpBB_Ext
Disabled Enabled
Disabled
initiated by phase-segregated or three-phase
breaker
failure
initiating binary input, breaker failure
protection
of
bay
n
operates to trip all the breakers on the busbar that connected to the bay with the time delay of 3-54
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions No.
Name
Range
Default value
Unit
Remark
Step
[Bayn.50BF.t_TrpBB_Ext]. 1: the binary input for releasing voltage controlled element of breaker failure protection of bay 18
Bayn.50BF.En_BI_RlsVCE
Disabled Enabled
Disabled
n is enabled 0: the binary input for releasing voltage controlled element of breaker failure protection of bay n is disabled 1: breaker failure protection is controlled by voltage control
19
Disabled
50BF.VCE.En
Enabled
Enabled
element 0: breaker failure protection is not controlled by voltage control element Logic
setting
of
enabling/disabling the external BFI
binary
input
[@Bayn.BI_ExTrp_WOI_BFI]. 0: the external BFI binary input 20
Disabled
50BF.En_CB_Ctrl
Enabled
[@Bayn.BI_ExTrp_WOI_BFI] is Disabled
disabled; 1: the external BFI binary input [@Bayn.BI_ExTrp_WOI_BFI] is enabled, and it will be blocked by the normally closed contact, but not controlled by the current criterion. 1: Enabling the alarm function when breaker failure initiating binary input is energized for
21
Disabled
50BF.En_Alm_Init
Enabled
Disabled
over 10s. 0: Disabling the alarm function when breaker failure initiating binary input is energized for over 10s.
All the current settings in above table are converted according to the CT ratio of each bay. PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-55
3
3 Protection Functions
3.8 Phase Overcurrent Protection
The bay label of displayed alarm signals, tripping signals, binary input signals, settings and sampled values related with each bay will change with the corresponding label settings. In this section, “@Bayn” is used to refer to the label setting of corresponding bay.
3
Phase overcurrent protection is the most widely used type of protection element in power systems. It can be used as the main protection of the feeder, and can also be used as the backup protection for power equipment such as transformers, reactors, and motors. When a fault occurs in the system, a fault current will be generated and the phase overcurrent protection can reflect the increase of the fault current.
3.8.1 Function Description The device can provide two stages of phase overcurrent protection with independent logic. Each stage can be independently set as definite-time characteristics or inverse-time characteristics. The dropout characteristics can be set as immediate dropout, definite-time dropout or inverse-time dropout. The phase overcurrent protection picks up when the current exceeds the current threshold value, and operates after a certain time delay, once the fault disappears, the phase overcurrent protection will dropout. Phase overcurrent protection can be enabled or disabled via the settings or binary input signals, for some specific applications, overcurrent protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block overcurrent protection. The enabling and blocking logic of phase overcurrent protection is shown in the figure below: EN
@Bayn.50/51Px.En
SIG
@Bayn.50/51Px.Enable
SIG
@Bayn.50/51Px.Block
SIG
Fail_Device
& @Bayn.50/51Px.On
& @Bayn.50/51Px.Blocked
≥1
& @Bayn.50/51Px.Valid
Figure 3.8-1 The enabling and blocking logic of phase overcurrent protection
The logic diagram of the fault detector element of phase overcurrent protection is as follows:
3-56
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
SET
Ia>0.95*[@Bayn.50/51Px.I_Set]
SET
Ib>0.95*[@Bayn.50/51Px.I_Set]
SET
Ic>0.95*[@Bayn.50/51Px.I_Set]
SIG
@Bayn.50/51Px.On
SIG
@Bayn.50/51Px.Valid
≥1
& 0
500ms
& @Bayn.50/51Px.Pkp
Figure 3.8-2 Logic diagram of the fault detector element of phase overcurrent protection
3.8.1.1 Operating Characteristic Phase overcurrent protection can operate without time delay or operate with a definite-time limit, it can also operate with an inverse-time limit, the characteristic curve meets the IEC60255-3 and ANSI C37.112 standards. Phase overcurrent protection can support definite-time limit, IEC & ANSI standard reverse time limit and user-defined inverse-time limit, users can select the wanted operating curve by the setting [Bayn.50/51Px.Opt_Curve] (x=1~2), the relationship between the value of the setting and the curve is shown in the table below. Bayn.50/51Px.Opt_Curve
Time Characteristic
k
α
c
tr
ANSIE
ANSI Extremely Inverse
28.2
2.0
0.1217
29.1
ANSIV
ANSI Very inverse
19.61
2.0
0.491
21.6
ANSIN
ANSI Normal Inverse
0.0086
0.02
0.0185
0.46
ANSIM
ANSI Moderately Inverse
0.0515
0.02
0.114
4.85
ANSIDefTime
ANSI Definite Time
-
-
-
-
ANSILTE
ANSI Long Time Extremely Inverse
64.07
2.0
0.25
30
ANSILTV
ANSI Long Time Very Inverse
28.55
2.0
0.712
13.46
ANSILT
ANSI Long Time Inverse
0.086
0.02
0.185
4.6
IECN
IEC Normal Inverse
0.14
0.02
0
-
IECV
IEC Very inverse
13.5
1.0
0
-
IEC
IEC Inverse
0.14
0.02
0
-
IECE
IEC Extremely inverse
80.0
2.0
0
-
IECST
IEC Short-time inverse
0.05
0.04
0
-
IECLT
IEC Long-time inverse
120.0
1.0
0
-
IECDefTime
IEC Definite Time
-
-
-
-
Resv
Reserved
-
-
-
-
UserDefine
Programmable
Only when the setting [Bayn.50/51Px.Opt_Curve] is set as “UserDefine”, i.e. the user-defined inverse-time characteristic is selected, the settings [Bayn.50/51Px.K], [Bayn.50/51Px.C] and [Bayn.50/51Px.Alpha] are useful, the inverse-time operating curve is determined by the three settings.
Without time delay
When I > Ip , the protection operates immediately.
Definite-time characteristic
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-57
3
3 Protection Functions
When I > Ip , the protection operates with a time delay of top (i.e. the value of the setting [Bayn.50/51Px.t_Op]), and the operating characteristic curve is as shown in the following figure:
t
3
t op
IP
I
Figure 3.8-3 Definite-time operating characteristic curve of phase overcurrent protection
Inverse-time characteristic
When I > Ip , the inverse-time accumulator begins to accumulate, and the operating time is affected by the applied current I . The larger current is, the smaller the operating time is, but not unlimited. When the current is large enough to a certain threshold ( Ip ), the inverse-time operating time will not continue to decrease, then the operating characteristic becomes the definite-time characteristic, and the operating time is tmin , i.e. the setting [Bayn.50/51Px.tmin] (x=1~2). The inverse-time operating characteristic equation is: k t c TMS ( I / I ) 1 P
Where:
Ip is the current setting [Bayn.50/51Px.I_Set]; TMS is the inverse-time time multiplier, i.e. the setting [Bayn.50/51Px.TMS];
k is the inverse-time coefficient K, i.e. the setting [Bayn.50/51Px.K];
c is the inverse-time coefficient C, i.e. the setting [Bayn.50/51Px.C]; is the inverse-time coefficient Alpha, i.e. the setting [Bayn.50/51Px.Alpha];
I is the measured current. The inverse-time operating characteristic curve is as shown below:
3-58
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
t
3
t min
IP
ID
I
Figure 3.8-4 Inverse-time operating characteristic curve of phase overcurrent protection
When the applied current is not a fixed value, but changes with time, the operating behavior of the protection is shown in the following equation: T0
1
t ( I )dt
1
0
Where: T0 is the operating time of the protection element; t(I) is the theoretical operating time when the current is I. 3.8.1.2 Dropout Characteristic The supported dropout characteristics of the phase overcurrent protection include immediate dropout, definite-time dropout and ANSI inverse-time dropout. When the operating curve is selected as definite-time, IEC inverse-time or user-defined inverse-time characteristic, the dropout characteristic can only be selected as immediate dropout or definite-time dropout, if inverse-time dropout is selected, the alarm signal “Fail_Settings” will be issued and the device will be blocked. When the operating curve is selected as ANSI inverse-time characteristic, the dropout characteristic can be selected as immediate dropout, definite-time dropout and ANSI inverse-time dropout.
Immediate dropout
When I Ip , the inverse-time operating accumulator begins to accumulate, the accumulated value after tp (Assuming tp is less than the theoretical operating time) is calculated according to the following equation: tp
1 dt t(I ) 0
I tp
At this time, if I [@Bayn.50/51Px.I_Set]
SIG
@Bayn.50/51Px.Pkp
SIG
@Bayn.50/51Px.St_A
SIG
@Bayn.50/51Px.St_B
SIG
@Bayn.50/51Px.St_C
SIG
@Bayn.50/51Px.Op_A
SIG
@Bayn.50/51Px.Op_B
SIG
@Bayn.50/51Px.Op_C
Timer t
&
@Bayn.50/51Px.Op_A
t
>=1 @Bayn.50/51Px.St
>=1 @Bayn.50/51Px.Op
Figure 3.8-8 Logic diagram of phase overcurrent protection
3.8.5 Settings
Phase Overcurrent Protection Setting
Access path: MainMenu Settings Protection Settings OC Settings Table 3.8-2 Settings of phase overcurrent protection No.
Settings
Range
Default value
Unit
Step
Description The current setting of stage x
1
Bayn.50/51Px.I_Set
(0.05 ~40)In
15.000
A
0.001
of
phase
overcurrent
protection of bay n The operating time setting of 2
Bayn.50/51Px.t_Op
0 ~100.000
0.100
s
0.001
stage x of phase overcurrent protection of bay n
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-63
3 Protection Functions No.
Settings
Default
Range
value
Unit
Step
Description The dropout time setting of
3
Bayn.50/51Px.t_DropOut
0 ~100.000
0
s
0.001
stage x of phase overcurrent protection of bay n The
logic
setting
for
enabling/disabling the stage 4
Bayn.50/51Px.En
Disabled Enabled
Enabled
x
-
of
phase
overcurrent
protection of bay n 0: disabling
3
1: enabling ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime;
5
Bayn.50/51Px.Opt_Curve
ANSILTE;
The setting for selecting the
ANSILTV;
inverse-time
ANSILT;
characteristic curve of stage
IECN;
IECDefTime
-
x
of
phase
operating overcurrent
IECV;
protection of bay n. please
IEC;
refer to Section 3.8.1.1 for
IECE;
details.
IECST; IECLT; IECDefTime; Resv; UserDefine The setting for selecting the inverse-time
dropout
characteristic curve of stage 6
Bayn.50/51Px.Opt_Curve _DropOut
Inst; DefTime;
x Inst
-
of
phase
overcurrent
protection of bay n.
IDMT
Inst: instantaneous dropout DefTime:
definite-time
dropout IDMT: inverse-time dropout The time multiplier setting of 7
Bayn.50/51Px.TMS
0.040~20.000
1.000
0.001
stage x of phase overcurrent protection of bay n The minimum operating time
8
Bayn.50/51Px.tmin
0 ~10.000
0.020
s
0.001
setting of stage x of phase overcurrent protection of bay n
3-64
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions No.
Settings
Default
Range
value
Unit
Step
Description The
9
customized
0.0010~
Bayn.50/51Px.K
constant
0.1400
120.0000
0.0001
operating
“k”
of
the
inverse-time characteristic
of
stage x of phase overcurrent protection of bay n The constant “α” customized
10
Bayn.50/51Px.Alpha
0.0100~3.0000
0.0200
0.0001
operating
of
the
inverse-time characteristic
of
stage x of phase overcurrent protection of bay n The constant “C” of the customized 11
0 ~1.0000
Bayn.50/51Px.C
0
0.0001
operating
inverse-time characteristic
of
stage x of phase overcurrent protection of bay n
All the current settings in above table are converted according to the CT ratio of each bay.
3.9 Earth Fault Overcurrent Protection
The bay label of displayed alarm signals, tripping signals, binary input signals, settings and sampled values related with each bay will change with the corresponding label settings. In this section, “@Bayn” is used to refer to the label setting of corresponding bay. The normal operating power system is three-phase symmetrical, its zero-sequence current and voltage are theoretically zero. Most of the faults are three-phase asymmetrical, according to the asymmetry of the fault, various protections reflect sequence component principle can be constituted. Earth fault overcurrent protection has been widely used in power systems, it can be used for the fault conditions that zero-sequence fault current flows into the earth, including single-phase earth fault and phase-to-phase short-circuit earth fault etc..
3.9.1 Function Description The device can provide two stages of earth fault overcurrent protection with independent logic. Each stage can be independently set as definite-time characteristics or inverse-time characteristics. The dropout characteristics can be set as immediate dropout, definite-time PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-65
3
3 Protection Functions
dropout or inverse-time dropout. Earth fault overcurrent protection can be enabled or blocked by the external binary input. Earth fault overcurrent protection can be enabled or disabled via the settings or binary input signals, for some specific applications, the protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block earth fault overcurrent protection. The enabling and blocking logic of earth fault overcurrent protection is shown in the figure below:
&
EN
@Bayn.50/51Gx.En
SIG
@Bayn.50/51Gx.Enable
SIG
@Bayn.50/51Gx.Block
SIG
Fail_Device
@Bayn.50/51Gx.On
3
& @Bayn.50/51Gx.Blocked
≥1
& @Bayn.50/51Gx.Valid
Figure 3.9-1 The enabling and blocking logic of earth fault overcurrent protection
The logic diagram of the fault detector element of earth fault overcurrent protection is as follows: SET
&
3I0>0.95*[@Bayn.50/51Gx.3I0_Set]
0
SIG
@Bayn.50/51Gx.On
SIG
@Bayn.50/51Gx.Valid
500ms
& @Bayn.50/51Gx.Pkp
Figure 3.9-2 Logic diagram of the fault detector element of earth fault overcurrent protection
3.9.1.1 Operating Characteristic Earth fault overcurrent protection can operate without time delay or operate with a definite-time limit, it can also operate with an inverse-time limit, the characteristic curve meets the IEC60255-3 and ANSI C37.112 standards. Earth fault overcurrent protection can support definite-time limit, IEC & ANSI standard reverse time limit and user-defined inverse-time limit, users can select the wanted operating curve by the setting [Bayn.50/51Gx.Opt_Curve], the relationship between the value of the setting and the curve is shown in the table below. Bayn.50/51Gx.Opt_Curve
k
Time Characteristic
α
c
tr
ANSIE
ANSI Extremely Inverse
28.2
2.0
0.1217
29.1
ANSIV
ANSI Very inverse
19.61
2.0
0.491
21.6
ANSIN
ANSI Normal Inverse
0.0086
0.02
0.0185
0.46
ANSIM
ANSI Moderately Inverse
0.0515
0.02
0.114
4.85
ANSIDefTime
ANSI Definite Time
-
-
-
-
3-66
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions Bayn.50/51Gx.Opt_Curve
k
Time Characteristic
α
c
tr
ANSILTE
ANSI Long Time Extremely Inverse
64.07
2.0
0.25
30
ANSILTV
ANSI Long Time Very Inverse
28.55
2.0
0.712
13.46
ANSILT
ANSI Long Time Inverse
0.086
0.02
0.185
4.6
IECN
IEC Normal Inverse
0.14
0.02
0
-
IECV
IEC Very inverse
13.5
1.0
0
-
IEC
IEC Inverse
0.14
0.02
0
-
IECE
IEC Extremely inverse
80.0
2.0
0
-
IECST
IEC Short-time inverse
0.05
0.04
0
-
IECLT
IEC Long-time inverse
120.0
1.0
0
-
IECDefTime
IEC Definite Time
-
-
-
-
Resv
Reserved
-
-
-
-
UserDefine
Programmable
3
Only when the setting [Bayn.50/51Gx.Opt_Curve] is set as “UserDefine”, i.e. the user-defined inverse-time characteristic is selected, the settings [Bayn.50/51Gx.K], [Bayn.50/51Gx.C] and [Bayn.50/51Gx.Alpha] are useful, the inverse-time operating curve is determined by the three settings.
Without time delay
When I 0 > I 0 p , the protection operates immediately.
Definite-time characteristic
When I 0 > I 0 p , the protection operates with a time delay of top (i.e. the value of the setting [Bayn.50/51Gx.t_Op]), and the operating characteristic curve is as shown in the following figure:
t
t op
I0p
I
Figure 3.9-3 Definite-time operating characteristic curve of earth fault overcurrent protection
Inverse-time characteristic
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-67
3 Protection Functions
When I 0 > I 0 p , the inverse-time accumulator begins to accumulate, and the operating time is affected by the applied current I 0 . The larger current is, the smaller the operating time is, but not unlimited. When the current is large enough to a certain threshold ( I 0 p ), the inverse-time operating time will not continue to decrease, then the operating characteristic becomes the definite-time characteristic, and the operating time is tmin , i.e. the setting [Bayn.50/51Gx.tmin]. The inverse-time operating characteristic equation is:
k
t
(I 0 / I 0P ) 1
3
c TMS
Where:
I 0 p is the current setting [Bayn.50/51Gx.3I0_Set]; TMS is the inverse-time time multiplier, i.e. the setting [Bayn.50/51Gx.TMS];
k is the inverse-time coefficient K, i.e. the setting [Bayn.50/51Gx.K]; c is the inverse-time coefficient C, i.e. the setting [Bayn.50/51Gx.C];
is the inverse-time coefficient Alpha, i.e. the setting [Bayn.50/51Gx.Alpha];
I is the measured zero-sequence current.
The inverse-time operating characteristic curve is as shown below:
t
t min
ID
I0P
I
Figure 3.9-4 Inverse-time operating characteristic curve of earth fault overcurrent protection
When the applied zero-sequence current I 0 is not a fixed value, but changes with time, the operating behavior of the protection is shown in the following equation: T0
1
t ( I )dt 0
3-68
1
0
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
Where: T0 is the operating time of the protection element; t(I0) is the theoretical operating time when the current is I 0 . 3.9.1.2 Dropout Characteristic The supported dropout characteristics of the earth fault overcurrent protection include immediate dropout, definite-time dropout and ANSI inverse-time dropout. When the operating curve is selected as definite-time, IEC inverse-time or user-defined inverse-time characteristic, the dropout characteristic can only be selected as immediate dropout or definite-time dropout, if inverse-time dropout is selected, the alarm signal “Fail_Settings” will be issued and the device will be blocked. When the operating curve is selected as ANSI inverse-time characteristic, the dropout characteristic can be selected as immediate dropout, definite-time dropout and ANSI inverse-time dropout.
Immediate dropout
When I 0 I 0 p , the inverse-time operating accumulator begins to accumulate, the accumulated value after tp (Assuming tp is less than the theoretical operating time) is calculated according to the following equation: tp
Itp
1
t(I 0
dt
0
)
At this time, if I 0 [@Bayn.50/51GX.3I0_Set]
3
@Bayn.50/51Gx.Op
t
@Bayn.50/51Gx.Pkp
Figure 3.9-8 Logic diagram of earth fault overcurrent protection
3.9.5 Settings Earth Fault Overcurrent Protection Setting
Access path: MainMenu Settings Protection Settings ROC Settings Table 3.9-2 Settings of earth fault overcurrent protection No.
Settings
Default
Range
value
Unit
Step
Description The current setting of stage
1
Bayn.50/51Gx.3I0_Set
(0.05 ~40)In
15.000
A
0.001
x of earth fault overcurrent protection of bay n The operating time setting
2
Bayn.50/51Gx.t_Op
0 ~100.000
0.100
s
0.001
of stage x of earth fault overcurrent
protection
of
bay n The dropout time setting of 3
Bayn.50/51Gx.t_DropOut
0 ~100.000
0
s
0.001
stage
x
of
overcurrent
earth
fault
protection
of
setting
for
bay n The
logic
enabling/disabling the stage 4
Bayn.50/51Gx.En
Disabled Enabled
Enabled
-
x of earth fault overcurrent protection of bay n 0: disabling 1: enabling
ANSIE; 5
Bayn.50/51Gx.Opt_Curve
ANSIV; ANSIN;
The setting for selecting the IECDefTime
ANSIM;
-
inverse-time
operating
characteristic curve of stage x of earth fault overcurrent
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-73
3 Protection Functions No.
Settings
Default
Range
value
Unit
Step
Description
ANSIDefTime;
protection of bay n, please
ANSILTE;
refer to Section 3.9.1.1 for
ANSILTV;
details.
ANSILT; IECN; IECV; IEC; IECE;
3
IECST; IECLT; IECDefTime; Resv; UserDefine The setting for selecting the inverse-time
dropout
characteristic curve of stage 6
Bayn.50/51Gx.Opt_Curve _DropOut
Inst;
x of earth fault overcurrent
DefTime;
Inst
-
protection of bay n,
IDMT
Inst: instantaneous dropout DefTime:
definite-time
dropout IDMT: inverse-time dropout The time multiplier setting of 7
Bayn.50/51Gx.TMS
0.040~20.000
1.000
0.001
stage
x
of
overcurrent
earth protection
fault of
bay n The 8
Bayn.50/51Gx.tmin
0 ~10.000
0.02
s
0.001
minimum
operating
time setting of stage x of earth
fault
overcurrent
protection of bay n The constant “k” of the customized 9
Bayn.50/51Gx.K
0.0010~ 120.0000
0.1400
0.0001
inverse-time
operating characteristic of stage
x
of
overcurrent
earth protection
fault of
bay n The constant “α” of the customized 10
Bayn.50/51Gx.Alpha
0.0100~ 3.0000
0.0200
0.0001
inverse-time
operating characteristic of stage
x
overcurrent
of
earth protection
fault of
bay n
3-74
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions No.
Settings
Default
Range
value
Unit
Step
Description The constant “C” of the customized
11
0 ~1.0000
Bayn.50/51Gx.C
0
0.0001
inverse-time
operating characteristic of stage
x
overcurrent
of
earth protection
fault of
bay n
All the current settings in above table are converted according to the CT ratio of each bay.
3.10 CT Circuit Supervision
The bay label of displayed alarm signals, tripping signals, binary input signals, settings and sampled values related with each bay will change with the corresponding label settings. In this section, “@BBx” is used to refer to the label setting of corresponding busbar and “@Bayn” is used to refer to the label setting of corresponding bay. For a bus coupler bay, “@BCy” is also used to refer to the label setting of corresponding bus coupler. For a bus section bay, “@BSz” is also used to refer to the label setting of corresponding bus section.
3.10.1 Function Description CT circuit abnormality will affect the calculation result of the busbar differential current, and then affect the operation behavior of busbar differential protection. In order to prevent the protection from mal-operation due to CT circuit abnormality, CT circuit supervision function is provided by the device. 3.10.1.1 CT Circuit Failure 1. If the check zone differential current of one phase is larger than the setting [I_AlmH_CTS], CT circuit failure alarm of corresponding phase “AlmH_CTS_X” (X=A, B or C) will be issued. CT circuit failure alarm will affect the operation behavior of busbar differential protection, users can select the busbar differential protection blocking mode under CT circuit failure condition via the logic setting [87B.Opt_CTS_Blk], please refer to Section 3.3.1.9 for details. 2. For the BC/BS that only one CT is available, if the check zone differential current of one phase is smaller than the setting [I_AlmH_CTS] and both discriminating zone differential currents of the phase of the two connected busbars are larger than [I_AlmH_CTS], BC/BS CT circuit failure alarm signal of corresponding phase “@BCy.AlmH_CTS_X”/“@BSz.AlmH_CTS_X” PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-75
3
3 Protection Functions
will be issued with a time delay of 5s. BC/BS CT circuit failure alarm will affect the operation behavior of busbar differential protection, users can select the inter-linked mode under BC/BS CT circuit failure condition via the logic setting [87B.Opt_BC_CTS_IntLink], please refer to Section 3.3.1.5 for details. If [87B.Opt_BC_CTS_IntLink] is set as “None”, the busbar differential protection will be blocked according to the blocking mode that set via the logic setting [87B.Opt_CTS_Blk], please refer to Section 3.3.1.9 for details.
3
3. For the BC/BS that double CTs are available, if the check zone differential current of one phase is smaller than the setting [I_AlmH_CTS] and discriminating zone differential current of the phase of any connected busbar is larger than [I_AlmH_CTS], if the discriminating zone differential current equals to the difference of current between the two CTs, BC/BS CT circuit failure alarm signal of corresponding phase “@BCy.AlmH_CTS_X”/“@BSz.AlmH_CTS_X” will be issued with a time delay of 5s. BC/BS CT circuit failure alarm will affect the operation behavior of busbar differential protection, users can select the inter-linked mode under BC/BS CT circuit failure condition via the logic setting [87B.Opt_BC_CTS_IntLink], please refer to Section 3.3.1.5 for details. If [87B.Opt_BC_CTS_IntLink] is set as “None”, the busbar differential protection will be blocked according to the blocking mode that set via the logic setting [87B.Opt_CTS_Blk], please refer to Section 3.3.1.9 for details.
If the logic setting [En_AutoRecov_AlmH_CTS] is set as “1”, the CT circuit failure alarm can be reset automatically after the CT circuit returns to normal condition. If the logic setting [En_AutoRecov_AlmH_CTS] is set as “0”, the alarm should be reset manually after the CT circuit returns to normal condition, it can be reset by energizing the resetting binary input “BI_RstTarg” or pressing “ESC” first then “ENT” simultaneously (“ESC” and “ENT” are two keypads on the front of the device) after the CT circuit returns to normal condition. When voltage concerned function is enabled and VT circuit failure is not detected, CT circuit supervision will be blocked if voltage blocking element of any busbar is released. If VT circuit failure is detected, CT circuit supervision will not be blocked. If voltage concerned function is disabled, or the logic setting [87B.VCE.En] is set as “0”, CT circuit supervision logic will not be affected by voltage. If [87B.Opt_BC_CTS_IntLink] is set as “None”, and [87B.Opt_CTS_Blk] is set as “None”, “PhSeg_Blk87B” or “3-phase_Blk87B”, for BC/BS CT circuit failure will not affect the check zone differential element, so after BC/BS CT circuit failure occurs, the alarm signal will be issued, but the busbar differential protection will not be affected. 3.10.1.2 CT Circuit Abnormality 1.
3-76
If the check zone differential current of one phase is larger than the setting i.e. [I_AlmL_CTS],
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
CT circuit abnormality alarm of corresponding phase [AlmL_CTS_X] (X=A, B or C) will be issued with a time delay of 5s. 2.
For the BC/BS that only one CT is available, if the check zone differential current of one phase is smaller than the setting [I_AlmL_CTS] and both discriminating zone currents of the phase of the two connected busbars are larger than [I_AlmL_CTS], BC/BS CT circuit abnormality alarm of corresponding phase [@BCy.AlmL_CTS_X]/[@BSz.AlmL_CTS_X] will be issued with a time delay of 5s.
3.
For the BC/BS that double CTs are available, if the check zone differential current of one phase is smaller than the setting [I_AlmL_CTS] and discriminating zone differential current of the phase of any connected busbar is larger than [I_AlmL_CTS], if the discriminating zone differential current equals to the difference of current between the two CTs, BC/BS CT circuit abnormality alarm of corresponding phase [@BCy.AlmL_CTS_X]/[@BSz.AlmL_CTS_X] will be issued with a time delay of 5s.
If the logic setting [En_AutoRecov_AlmL_CTS] is set as “1”, the CT circuit abnormality alarm can be reset automatically after the CT circuit returns to normal condition. If the logic setting [En_AutoRecov_AlmL_CTS] is set as “0”, the alarm should be reset manually after the CT circuit returns to normal condition, it can be reset by energizing the resetting binary input [BI_RstTarg] or pressing “ESC” first then “ENT” simultaneously (“ESC” and “ENT” are two keypads on the front of the device) after the CT circuit returns to normal condition. Busbar differential protection will not be blocked when CT circuit abnormality occurs. 3.10.1.3 Discriminating Zone Differential Current High/Low Value Alarm 1.
If discriminating zone differential current of BBx is larger than [I_AlmL_CTS], BBx differential current low value alarm signal [@BBx.AlmL_Diff] will be issued with a time delay of 5s.
2.
If discriminating zone differential current of BBx is larger than [I_AlmH_CTS], BBx differential current high value alarm signal [@BBx.AlmH_Diff] will be issued with a time delay of 5s. BBx differential current high value alarm will affect the operation behavior of busbar differential protection, users can select the busbar differential protection blocking mode via the logic setting [87B.Opt_CTS_Blk], please refer to Section 3.3.1.9 for details.
If the logic setting [En_AutoRecov_AlmL_CTS] is set as “1”, the BBx differential current low value alarm can be reset automatically after the CT circuit returns to normal condition. If the logic setting [En_AutoRecov_AlmH_CTS] is set as “1”, the BBx differential current high
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-77
3
3 Protection Functions
value alarm can be reset automatically after the CT circuit returns to normal condition. Otherwise, the two alarm signals should be reset manually after the CT circuit returns to normal condition, it can be reset by energizing the resetting binary input [BI_RstTarg] or pressing “ESC” first then “ENT” simultaneously (“ESC” and “ENT” are two keypads on the front of the device) after the CT circuit returns to normal condition.
3.10.2 Function Block Diagram CTS
3
AlmH_CTS_X
Ia_Bayn, Ib_Bayn, Ic_Bayn
@BCy.AlmH_CTS_X
AlmL_CTS_X @BCy.AlmL_CTS_X @BBx.AlmH_Diff @BBx.AlmL_Diff
@BSz.AlmH_CTS_X @BSz.AlmL_CTS_X
X=A, B or C
3.10.3 I/O Signal Table 3.10-1 Output signal of CT circuit supervision No.
Output signal
Description
1
AlmH_CTS
CT circuit failure
2
AlmH_CTS_A
Phase-A CT circuit failure
3
AlmH_CTS_B
Phase-B CT circuit failure
4
AlmH_CTS_C
Phase-C CT circuit failure
5
@BCy.AlmH_CTS
BCy CT circuit failure
6
@BCy.AlmH_CTS_A
BCy phase-A CT circuit failure
7
@BCy.AlmH_CTS_B
BCy phase-B CT circuit failure
8
@BCy.AlmH_CTS_C
BCy phase-C CT circuit failure
9
@BSz.AlmH_CTS
BSz CT circuit failure
10
@BSz.AlmH_CTS_A
BSz phase-A CT circuit failure
11
@BSz.AlmH_CTS_B
BSz phase-B CT circuit failure
12
@BSz.AlmH_CTS_C
BSz phase-C CT circuit failure
13
AlmL_CTS
CT circuit abnormality
14
AlmL_CTS_A
Phase-A CT circuit abnormality
15
AlmL_CTS_B
Phase-B CT circuit abnormality
16
AlmL_CTS_C
Phase-C CT circuit abnormality
3-78
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions 17
@BCy.AlmL_CTS
BCy CT circuit abnormality
18
@BCy.AlmL_CTS_A
BCy phase-A CT circuit abnormality
19
@BCy.AlmL_CTS_B
BCy phase-B CT circuit abnormality
20
@BCy.AlmL_CTS_C
BCy phase-C CT circuit abnormality
21
@BSz.AlmL_CTS
BSz CT circuit abnormality
22
@BSz.AlmL_CTS_A
BSz phase-A CT circuit abnormality
23
@BSz.AlmL_CTS_B
BSz phase-B CT circuit abnormality
24
@BSz.AlmL_CTS_C
BSz phase-C CT circuit abnormality
25
@BBx.AlmH_Diff
BBx differential current high value alarm
26
@BBx.AlmL_Diff
BBx differential current low value alarm
3
3.10.4 Logic 3.10.4.1 CT Circuit Failure
SET
Ida_CZ>[I_AlmH_CTS]
5s
0
AlmH_CTS_A
SET
Idb_CZ>[I_AlmH_CTS]
5s
0
AlmH_CTS_B
SET
Idc_CZ>[I_AlmH_CTS]
5s
0
AlmH_CTS_C
Figure 3.10-1 Logic of CT circuit failure
Where: Ida_CZ: Phase-A check zone differential current Idb_CZ: Phase-B check zone differential current Idc_CZ: Phase-C check zone differential current I_AlmH_CTS: Current setting of CT circuit failure AlmH_CTS_A: Phase-A CT circuit failure alarm signal AlmH_CTS_B: Phase-B CT circuit failure alarm signal AlmH_CTS_C: Phase-C CT circuit failure alarm signal The logic of BC/BS CT circuit failure (for the BC/BS that only one CT is available) is shown as follows (Takes BC1 in Figure 3.2-6 as an example).
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-79
3 Protection Functions
SET
Ida_CZ[I_AlmH_CTS]
SET
Ida_BB2>[I_AlmH_CTS]
SET
Idb_CZ[I_AlmH_CTS]
SET
Idb_BB2>[I_AlmH_CTS]
SET
Idc_CZ[I_AlmH_CTS]
SET
Idc_BB2>[I_AlmH_CTS]
&
Figure 3.10-2 Logic of BC/BS CT circuit failure (for the BC/BS that only one CT is available)
Where: Ida_BB1: Phase-A discriminative differential current of BB1 Idb_BB1: Phase-B discriminative differential current of BB1 Idc_BB1: Phase-C discriminative differential current of BB1 Ida_BB2: Phase-A discriminative differential current of BB2 Idb_BB2: Phase-B discriminative differential current of BB2 Idc_BB2: Phase-C discriminative differential current of BB2 @BC1.AlmH_CTS_A: BC1 phase-A CT circuit failure @BC1.AlmH_CTS_B: BC1 phase-B CT circuit failure @BC1.AlmH_CTS_C: BC1 phase-C CT circuit failure The logic of BC/BS CT circuit failure (for the BC/BS that double CTs are available) is shown as follows (Takes BC1 in Figure 3.2-9 as an example).
3-80
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
SET
Idx_CZ[I_AlmH_CTS]
SIG
Idx_BB1=∣Ix_BC1_CT1-Ix_BC1_CT2∣
SET
Idx_CZ[I_AlmH_CTS]
SIG
Idx_BB2=∣Ix_BC1_CT1-Ix_BC1_CT2∣
& &
5s
0
@BC1.CT1.AlmH_CTS_X
5s
0
@BC1.CT2.AlmH_CTS_X
& &
3
Figure 3.10-3 Logic of BC/BS CT circuit failure (for the BC/BS that double CTs are available)
Where: Ix_BC1_CT1: Phase-X (A, B or C) current of CT1 of BC1 IX_BC1_CT2: Phase-X (A, B or C) current of CT2 of BC1 3.10.4.2 CT Circuit Abnormality
SET
Ida_CZ>[I_AlmL_CTS]
5s
0
AlmL_CTS_A
SET
Idb_CZ>[I_AlmL_CTS]
5s
0
AlmL_CTS_B
SET
Idc_CZ>[I_AlmL_CTS]
5s
0
AlmL_CTS_C
Figure 3.10-4 Logic of CT circuit abnormality
Where: Ida_CZ: Phase-A check zone differential current Idb_CZ: Phase-B check zone differential current Idc_CZ: Phase-C check zone differential current I_AlmL_CTS: Current setting of CT circuit abnormality AlmL_CTS_A: Phase-A CT circuit abnormality AlmL_CTS_B: Phase-B CT circuit abnormality AlmL_CTS_C: Phase-C CT circuit abnormality The logic of BC/BS CT circuit abnormality (for the BC/BS that only one CT is available) is shown PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-81
3 Protection Functions
as follows (Takes BC1 in Figure 3.2-6 as an example).
SET
Ida_CZ[I_AlmL_CTS]
SET
Ida_BB2>[I_AlmL_CTS]
SET
Idb_CZ[I_AlmL_CTS]
SET
Idb_BB2>[I_AlmL_CTS]
SET
Idc_CZ[I_AlmL_CTS]
SET
Idc_BB2>[I_AlmL_CTS]
& 5s
&
0
@BC1.AlmL_CTS_A
&
3
&
5s
0
@BC1.AlmL_CTS_B
5s
0
@BC1.AlmL_CTS_C
& &
Figure 3.10-5 Logic of BC/BS CT circuit abnormality (for the BC/BS that only one CT is available)
Where: Ida_BB1: Phase-A discriminative differential current of BB1 Idb_BB1: Phase-B discriminative differential current of BB1 Idc_BB1: Phase-C discriminative differential current of BB1 Ida_BB2: Phase-A discriminative differential current of BB2 Idb_BB2: Phase-B discriminative differential current of BB2 Idc_BB2: Phase-C discriminative differential current of BB2 @BC1.AlmL_CTS_A: BC1 phase-A CT circuit abnormality @BC1.AlmL_CTS_B: BC1 phase-B CT circuit abnormality @BC1.AlmL_CTS_C: BC1 phase-C CT circuit abnormality The logic of BC/BS CT circuit abnormality (for the BC/BS that double CTs are available) is shown as follows (Takes BC1 in Figure 3.2-9 as an example).
3-82
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions SET
Idx_CZ[I_AlmL_CTS]
SIG
Idx_BB1=∣Ix_BC1_CT1-Ix_BC1_CT2∣
SET
Idx_CZ[I_AlmL_CTS]
SIG
Idx_BB2=∣Ix_BC1_CT1-Ix_BC1_CT2∣
& &
5s
0
@BC1.CT1.AlmL_CTS_X
5s
0
@BC1.CT2.AlmL_CTS_X
& &
3
Figure 3.10-6 Logic of BC/BS CT circuit abnormality (for the BC/BS that double CTs are available)
Where: Ix_BC1_CT1: Phase-X (A, B or C) current of CT1 of BC1 IX_BC1_CT2: Phase-X (A, B or C) current of CT2 of BC1 3.10.4.3 Discriminating Zone Differential Current High/Low Value Alarm
SET
Ida_BBx>[I_AlmH_CTS]
SET
Idb_BBx>[I_AlmH_CTS]
SET
Idc_BBx>[I_AlmH_CTS]
>=1 5s
0
@BBx.AlmH_Diff
Figure 3.10-7 Logic of BBx differential current high value alarm
Where: Ida_BBx: Phase-A discriminative differential current of BBx Idb_BBx: Phase-B discriminative differential current of BBx Idc_BBx: Phase-C discriminative differential current of BBx @BBx.AlmH_Diff: BBx differential current high value alarm signal
SET
Ida_BBx>[I_AlmL_CTS]
SET
Idb_BBx>[I_AlmL_CTS]
SET
Idc_BBx>[I_AlmL_CTS]
>=1 5s
0
@BBx.AlmL_Diff
Figure 3.10-8 Logic of BBx differential current low value alarm
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-83
3 Protection Functions
Where: @BBx.AlmL_Diff: BBx differential current low value alarm signal
3.10.5 Settings Access path: MainMenuSettingsProt SettingsBBP Settings Table 3.10-2 CT circuit supervision function related settings 1
No.
Name
Default
Range
value
3
Unit
Step
Remark Logic setting for selecting the
differential
protection
blocking mode, please refer to Section 3.3.1.9 for details. None: Unblocking PhSeg_Blk87B: None
Phase-segregated blocking
PhSeg_Blk87B 1
87B.Opt_CTS_Blk
3-phase_Blk87B PhSeg_BlkDZ
PhSeg_B lkDZ
3-phase_BlkDZ
3-phase_Blk87B: Three-phase blocking PhSeg_BlkDZ: Phase-segregated blocking according to respective busbar zone 3-phase_BlkDZ: Three-phase according
blocking to
respective
busbar zone Logic setting for selecting the BC/BS CT circuit failure inter-linked
87B.Opt_BC_CTS_IntLink
PhSeg
please
refer to Section 3.3.1.5 for
None 2
mode,
PhSeg
3-phase
details. None: no inter-link PhSeg:
phase-segregated
inter-link; 3-phase:
three-phase
inter-link 1:
busbar
differential
protection is controlled by 3
87B.VCE.En
Disabled Enabled
Enabled
voltage control element 0:
busbar
differential
protection is not controlled by voltage control element
3-84
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
Access path:
MainMenu Settings Global Settings Superv Settings Table 3.10-3 CT circuit supervision function related settings 2 No.
Settings
Range
Default value
Unit
Step
1
I_AlmH_CTS
0.05In ~1.00In
0.100
A
0.001
2
I_AlmL_CTS
0.05In ~1.00In
0.080
A
0.001
Remark Current setting of CT circuit failure Current setting of CT circuit abnormality 1: the CT circuit failure alarm signal
can
be
reset
automatically after the CT circuit 3
En_AutoRecov_AlmH_CTS
Disabled Enabled
Enabled
returns
to
normal
condition 0: the CT circuit failure alarm signal
cannot
be
reset
automatically after the CT circuit
returns
to
normal
condition 1: the CT circuit abnormality alarm signal can be reset automatically after the CT circuit 4
En_AutoRecov_AlmL_CTS
Disabled Enabled
Enabled
returns
to
normal
condition 0: the CT circuit abnormality alarm signal cannot be reset automatically since the CT circuit
returns
to
normal
condition
All the current settings in above table are converted according to the referenced CT ratio.
3.11 VT Circuit Supervision 3.11.1 Function Description 1.
If BBx is in service and positive-sequence voltage (U1) of BBx is smaller than [VTS.U1_Set] and fault detector element does not pick up, the alarm signal “@BBx.Alm_VTS” will be issued with a time delay of [VTS.t_DPU].
2.
If BBx is in service and residual voltage (3U0) of BBx is larger than [VTS.3U0_Set] and fault
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-85
3
3 Protection Functions
detector element does not pick up, the alarm signal “@BBx.Alm_VTS” will be issued with a time delay of [VTS.t_DPU]. If VT circuit failure is detected, DPFC voltage FD element will be disabled. When the three phase-voltage returns to normal condition, the alarm “@BBx.Alm_VTS” will be reset automatically with a time delay of [VTS.t_DDO]. If the fault detector element picks up due to a disturbance in the system (DPFC current is detected), the VT circuit supervision will be disabled for 3s.
3.11.2 Function Block Diagram
3
VTS Ia_Bayn, Ib_Bayn, Ic_Bayn
@BBx.Alm_VTS
Ua_BBx, Ub_BBx, Uc_BBx
3.11.3 I/O Signal Table 3.11-1 Output signal of VT circuit supervision No. 1
Signal @BBx.Alm_VTS
Description BBx VT circuit failure
3.11.4 Logic SIG
Ua>0.7Un
SIG
Ub>0.7Un
SIG
Uc>0.7Un
SIG
IΨ_Bayn>0.04In
SET
3U0>[VTS.3U0_Set]
SET
U1=1 SIG
Bay n is conn ected to B B1
SIG
Bay n is conn ected to B B2
SIG
&
Bayn.Alm_DS
IΨ_Bayn>0.04In
3
Figure 3.12-2 Logic of disconnector position alarm
Where: Bayn DS position changes: Disconnector position of bay n changes (from open change to closed or from closed change to open). En_AutoRecov_DS: 1: Logic setting of busbar differential protection. When it is set as “1”, if any disconnector position alarm is issued, once the abnormality of disconnector position disappears, the alarm will be reset automatically. When it is set as “0”, if any disconnector position alarm is issued, the alarm cannot be reset unless energizing the disconnector position confirm binary input [BI_ConfirmDS]. Bay n is connected to BB1, Bay n is connected to BB2: Please refer to the inter-connection mode alarm logic. IΨ_Bayn: Any phase current of feeder bay n @Bayn.Alm_DS: Disconnector position of bay n is abnormal. 3.12.3.3 Disconnector Position Automatic Correction Logic Takes BB1 as an example
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-91
3 Protection Functions
SIG
3
Bay n is conn ected to B B1
SIG
Ida_CZ0.08In
SIG
Ida_BB2=1 BI
@Bayn.BI_89b_@BB1
BI
@Bayn.BI_89a_@BB1
BI
@Bayn.BI_89b_@BB1
SIG
Dual-position CB
BI
@Bayn.BI_52a
BI
@Bayn.BI_52b
BI
@Bayn.BI_52a
BI
@Bayn.BI_52b
BI
BI_Maintenan ce
0
@Bayn.Alm_89a/89b_@BB1
&
& >=1
3
& 5s
0
@Bayn.Alm_52a/52b
&
Figure 3.12-4 Logic of dual-position alarm
Where: Dual-position DS: Dual-position for disconnector status, it can be configured via PCS-Studio configuration tool. @Bayn.BI_89a_@BB1: Normally open auxiliary contact of BB1 disconnector of bay n @Bayn.BI_89b_@BB1: Normally closed auxiliary contact of BB1 disconnector of bay n Dual-position CB: Dual-position for circuit breaker status, it can be configured via PCS-Studio configuration tool. @Bayn.Alm_89a/89b_@BBx: Dual-position alarm for BB1 disconnector of bay n @Bayn.BI_52a: Normally open auxiliary contact of the circuit breaker of bay n @Bayn.BI_52b: Normally closed auxiliary contact of the circuit breaker of bay n BI_Maintenance: Binary input to indicate circuit breaker is in maintenance @Bayn.Alm_52a/52b: Dual-position alarm for circuit breaker of bay n
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-93
3 Protection Functions
3.12.3.5 Disconnector Position Alarm Blocking Busbar Differential Protection Logic
3
SIG
Bay n is connected to BB1
SIG
Bay n is connected to BB2
SIG
IΨ_Bayn>0.04In
SET
[En_Blk87B_DS_Open_WithCurr]
SET
[Opt_DS_DPS_BAD] = 2
SIG
Bayn.BI_89a_@BBx = 1
SIG
Bayn.BI_89b_@BBx = 1
SET
[Opt_DS_DPS_INT] = 2
SIG
Bayn.BI_89a_@BBx = 0
SIG
Bayn.BI_89b_@BBx = 0
SIG
Disconnector position of BBx
& &
&
>=1 &
DS Alarm Block 87B_BBx &
Figure 3.12-5 Logic of disconnector position alarm blocking busbar differential protection
Where: Bay n is connected to BB1, Bay n is connected to BB2: Please refer to the inter-connection mode alarm logic. IΨ_Bayn: Any phase current of feeder bay n. DS Alarm Block 87B_BBx: Bay n disconnector position alarm signal which will block busbar differential protection of BBx.
3.12.4 Settings Access path: MainMenuSettingsProt SettingsBBP Settings Table 3.12-4 Disconnector position related settings 1
No.
Settings
Range
Default value
Unit
Step
Remark 1: if current is detected for a bay, but the
corresponding
disconnector
position is missing, the last valid disconnector 1
En_Mem_DS_Open
Disabled
_WithCurr
Enabled
Enabled
position
will
be
memorized 0: if current is detected for a bay, but the
corresponding
disconnector
position is missing, the last valid disconnector position will not be memorized 2
3-94
En_Blk87B_DS_Open
Disabled
_WithCurr
Enabled
Disabled
1: busbar differential protection is blocked when current is detected for
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions a
bay
but
the
corresponding
disconnector position is missing 0: busbar differential protection is not blocked when current is detected for a
bay
but
the
corresponding
disconnector position is missing “0” is recommended for this logic setting. The treatment method when both of the normally open auxiliary contact and normally closed auxiliary contact of a disconnector are energized at the same time.
ForceCls 3
Opt_DS_DPS_BAD
Memorize
0: the disconnector position status is
Memorize
considered as closed;
BlkBBP
1: take the last valid memorized position; 2: take the last valid memorized position and block the corresponding busbar differential protection. The treatment method when both of the normally open auxiliary contact and normally closed auxiliary contact of a disconnector are de-energized at the same time.
ForceCls 4
Opt_DS_DPS_INT
Memorize
0: the disconnector position status is
Memorize
considered as closed;
BlkBBP
1: take the last valid memorized position; 2: take the last valid memorized position and block the corresponding busbar differential protection.
Access path:
MainMenu Settings Global Settings Superv Settings Table 3.12-5 Disconnector position related settings 2 No.
Settings
Range
Default value
Unit
Step
Remark Time
1
t_Alm_89a/89b
0~1000000.000
10.000
s
0.001
Date: 2019-03-11
for
disconnector
dual-position alarm (i.e. the normally closed and normally open auxiliary contact
PCS-915SC Centralized Busbar Relay
delay
of
a
disconnector
are
3-95
3
3 Protection Functions No.
Settings
Range
Default value
Unit
Step
Remark energized at the same time. Time delay for the alarm when the
2
t_Alm_Two_DS_Closed
0~1000000
10.000
s
0.001
disconnectors of two busbars of a bay are closed at the same time. 1: If any disconnector position alarm is issued, once the abnormality of disconnector position disappears,
3
3
En_AutoRecov_DS
Disabled Enabled
the alarm will be reset automatically. Enabled
0: If any disconnector position alarm is issued, the alarm cannot be reset unless energizing the disconnector position
confirm
binary
input
“BI_ConfirmDS”
3.13 Busbar Protection Operation Mode Identification Drawing the busbar arrangement on the page “Single Line Graph” via the auxiliary configuration tool PCS-Studio, and completing the type definition of each bay of the busbar arrangement, then PCS-915SC can be adapted to different busbar arrangement. The currently supported bay type including single-CT bus coupler (Tie), double-CTs bus coupler (Tie2CT), feeder (Feeder) and disconnector (SwitchTie). The currently supported busbar arrangement including single-busbar arrangement, single-busbar with bus section arrangement, double-busbars arrangement, double-busbars with one bus section arrangement, double-busbars with two bus sections arrangement, single-busbar with transfer bus arrangement, single-busbar with bus section and transfer bus arrangement, double-busbars with transfer bus arrangement etc..
3.13.1 Bay Type Description Following table lists the currently supported bay types of the device. The switch, TA, etc. in each bay symbol are not allowed to be deleted. The disconnector can be added according to the actual needs on site. It should be noted that the increased disconnector symbol must be guaranteed within the box of the bay symbol. If the disconnector symbol is outside the box of the bay symbol, the device does not consider that the added disconnector belongs to the bay. At present, the device only supports adding disconnector symbol in the bay symbol, and does not support adding other symbols such as switch and TA. For details, please refer to Section 3.13.2.
3-96
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
Bay type
Bay symbol
Description Single-CT bus coupler, it is used as the tie breaker for the busbar, the busbar can be connected to both the breaker side and the TA side. When only one busbar is connected to a certain side, the BC current will be counted into the discriminating zone differential
Tie
current of the connected busbar. When the number of the connected busbars on one side is greater than or equal to 2, the BC current will be counted into the discriminating zone differential current of the busbar of which the disconnector is closed. In addition, whether the BS current is counted into the discriminating zone differential current also needs to consider the dead zone fault protection function. Double-CTs bus coupler, it is used as the tie breaker for the busbar, the busbar can be connected to both the TA1 side and the TA2 side. Double-click the symbol, the cross attribute (Across, Non Across) can be selected. Across: TA1 and TA2 are cross-counted into the discriminating zone differential current of the connected busbars. Non Across: TA1 and TA2 are not cross-counted into the discriminating zone differential current of the connected busbars, if BC dead zone fault happens, the busbar differential protection will not operate. Currently BC dead zone fault busbar differential
Tie2CT
protection function is not available, so “Across” mode is recommended. When only one busbar is connected to a certain side, the BC current will be counted into the discriminating zone differential current of the connected busbar. When the number of the connected busbars on one side is greater than or equal to 2, the BC current will be counted into the discriminating zone differential current of the busbar of which the disconnector is closed. In addition, whether the BS current is counted into the discriminating zone differential current also needs to consider the dead zone fault protection function.
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-97
3
3 Protection Functions
The feeder TA is on the outside of the circuit breaker. The busbar can be connected to the QA1 side and the transfer bus can be connected to both sides of the TA1. The feeder current is fixedly counted into the check zone differential current, and it will be counted into the discriminating zone differential current according to the feeder disconnector position and the circuit breaker position (feeder dead zone fault protection is enabled). Feeder The feeder TA is on the inside of the circuit breaker. The busbar
3
can be connected to the TA1 side and the transfer bus can be connected to both sides of the QA1. The feeder current is fixedly counted into the check zone differential current, and it will be counted into the discriminating zone differential current according to the feeder disconnector position and the circuit breaker position (feeder dead zone fault protection is enabled).
It is used as the tie disconnector for the busbar, when it is closed, SwitchTie
the connected busbars of the tie disconnector will be considered as under the inter-linked operation mode automatically.
3.13.2 Typical Busbar Arrangement Description 1.
Single-busbar arrangement
The differential circuits include one check zone differential circuit and one discriminating zone differential circuit (Bus1), The current of each feeder is fixedly counted into the check zone differential current, and it will be counted into the discriminating zone differential current according to the disconnector position and the circuit breaker position of each bay (feeder dead zone fault protection is enabled). 2.
3-98
Single-busbar with transfer bus arrangement (the feeder TA is on the outside of the bypass disconnector)
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
3 The differential circuits include one check zone differential circuit and two discriminating zone differential circuits (Bus1 and Bus2), where Bus2 is the transfer bus. The current of each feeder is fixedly counted into the check zone differential current, and it will be counted into the discriminating zone differential current according to the disconnector position and the circuit breaker position of each bay (feeder dead zone fault protection is enabled). The BC current will be counted into the discriminating zone differential current of Bus1 and Bus2, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function. 3.
Single-busbar with transfer bus arrangement (the feeder TA is on the inside of the bypass disconnector)
The differential circuits include one check zone differential circuit and one discriminating zone differential circuit (Bus1), Bus2 is not within the protected zone of busbar differential protection. The current of each feeder is fixedly counted into the check zone differential current, and it will be counted into the discriminating zone differential current according to the disconnector position and the circuit breaker position of each bay (feeder dead zone fault protection is enabled). In the case of non-bypass operation, the BC current is 0. In the case of the bypass operation, the BC current is counted into the check zone differential current and discriminating zone differential current of Bus1, and it is decided whether to be excluded from discriminating zone differential PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-99
3 Protection Functions
current calculation according to BC dead zone fault protection function. 4.
Single-busbar with bus section arrangement
3 The differential circuits include one check zone differential circuit and two discriminating zone differential circuits (Bus1 and Bus2). The current of each feeder is fixedly counted into the check zone differential current, and it will be counted into the discriminating zone differential current according to the disconnector position and the circuit breaker position of each bay (feeder dead zone fault protection is enabled). The BS current will be counted into the discriminating zone differential current of Bus1 and Bus2, and it is decided whether to be excluded from discriminating zone differential current calculation according to BS dead zone fault protection function. 5.
Single-busbar with bus section arrangement (the feeder TA is on the outside of the bypass disconnector)
The differential circuits include one check zone differential circuit and three discriminating zone differential circuits (Bus1, Bus2 and Bus3), where Bus3 is the transfer bus. The current of each feeder is fixedly counted into the check zone differential current, and it will be counted into the discriminating zone differential current according to the disconnector position and the circuit breaker position of each bay (feeder dead zone fault protection is enabled). The BS current will be counted into the discriminating zone differential current of the busbar of which the disconnector is closed, and it is decided whether to be excluded from discriminating zone differential current calculation according to BS dead zone fault protection function. 6.
Single-busbar with bus section arrangement (the feeder TA is on the inside of the bypass disconnector)
3-100
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
The differential circuits include one check zone differential circuit and two discriminating zone differential circuits (Bus1 and Bus2), Bus3 is not within the protected zone of busbar differential protection. The current of each feeder is fixedly counted into the check zone differential current, and it will be counted into the discriminating zone differential current according to the disconnector position and the circuit breaker position of each bay (feeder dead zone fault protection is enabled). In the case of non-bypass operation, the BC current is 0. In the case of the bypass operation, the BC current is counted into the check zone differential current and discriminating zone differential current of Bus1, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function. 7.
Double-busbars arrangement
The differential circuits include one check zone differential circuit and two discriminating zone differential circuits (Bus1 and Bus2). The current of each feeder is fixedly counted into the check zone differential current, and it will be counted into the discriminating zone differential current according to the disconnector position and the circuit breaker position of each bay (feeder dead zone fault protection is enabled). The BC current will be counted into the discriminating zone differential current of Bus1 and Bus2, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function. 8.
Double-busbars arrangement (the feeder TA is on the outside of the bypass
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-101
3
3 Protection Functions
disconnector)
3 The differential circuits include one check zone differential circuit and three discriminating zone differential circuits (Bus1, Bus2 and Bus3), where Bus3 is the transfer bus. The current of each feeder is fixedly counted into the check zone differential current, and it will be counted into the discriminating zone differential current according to the disconnector position and the circuit breaker position of each bay (feeder dead zone fault protection is enabled). The current of the BC (Tie1) is counted into the discriminating zone differential current, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function. The current of the BC (Tie2) is counted into the discriminating zone differential current of which the disconnector is closed, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function. 9.
Double-busbars arrangement (the feeder TA is on the inside of the bypass disconnector)
The differential circuits include one check zone differential circuit and two discriminating zone differential circuits (Bus1 and Bus2), the transfer bus Bus3 is not within the protected zone of busbar differential protection. 3-102
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions
The current of each feeder is fixedly counted into the check zone differential current, and it will be counted into the discriminating zone differential current according to the disconnector position and the circuit breaker position of each bay (feeder dead zone fault protection is enabled). The current of the BC (Tie1) is counted into the discriminating zone differential current, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function. In the case of non-bypass operation, the current of the BC (Tie2) is 0. In the case of the bypass operation, the current of the BC (Tie2) is counted into the check zone differential current and discriminating zone differential current of Bus1, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function. 10. Double-busbars with one bus section arrangement
The differential circuits include one check zone differential circuit and three discriminating zone differential circuits (Bus1, Bus2 and Bus3). The current of each feeder is fixedly counted into the check zone differential current, and it will be counted into the discriminating zone differential current according to the disconnector position and the circuit breaker position of each bay (feeder dead zone fault protection is enabled). The current of the BC (Tie1) is counted into the discriminating zone differential current of Bus1 and Bus2, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function. The current of the BC (Tie2) is counted into the discriminating zone differential current of Bus2 and Bus3, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function. The current of the BC (Tie3) is counted into the discriminating zone differential current of Bus1 and Bus3, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function. 11. Double-busbars with two bus sections arrangement PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-103
3
3 Protection Functions
3
The differential circuits include one check zone differential circuit and four discriminating zone differential circuits (Bus1, Bus2, Bus3 and Bus4). The current of each feeder is fixedly counted into the check zone differential current, and it will be counted into the discriminating zone differential current according to the disconnector position and the circuit breaker position of each bay (feeder dead zone fault protection is enabled). The current of the BC (Tie1) is counted into the discriminating zone differential current of Bus1 and Bus2, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function. The current of the BC (Tie2) is counted into the discriminating zone differential current of Bus3 and Bus4, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function. The current of the BC (Tie3) is counted into the discriminating zone differential current of Bus1 and Bus3, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function. The current of the BC (Tie4) is counted into the discriminating zone differential current of Bus2 and Bus4, and it is decided whether to be excluded from discriminating zone differential current calculation according to BC dead zone fault protection function.
3.14 Device Configuration Description The differential circuits of PCS-915SC include one check zone differential circuit and up to six discriminating zone differential circuits, it can protect up to six busbars. If busbar voltage is not connected, the device can connect up to 36 bays (108 AC current inputs). If busbar voltage is connected, the device can connect up to 32 bays (96 AC current inputs) and the voltage of up to 4 busbars (12 AC voltage inputs). The busbar relay PCS-915SC includes one central unit (CU, 6U chassis) and up to two extended units (EU, 6U chassis). If busbar voltage is not connected, the central unit can connect up to 12 bays (36 AC current inputs). If busbar voltage is connected, the central unit can connect up to 8 bays (24 AC current inputs) and the voltage of up to 4 busbars (12 AC voltage inputs). Each extended unit can connect up to 12 bays (36 AC current inputs). Please refer to following table for details. 3-104
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3 Protection Functions PCS-915SC
Analog input Busbar voltage is not connected
CU
36 AC current inputs
1CU+1EU
72 AC current inputs
1CU+2EU
108 AC current inputs
Busbar voltage is connected 24 AC current inputs +12 AC voltage inputs 60 AC current inputs +12 AC voltage inputs 96 AC current inputs +12 AC voltage inputs
Binary
Binary
input
output
265
141
434
197
503
253
The extended unit is connected to the central unit via the optical fiber (ST type connector), the communication between the CU and the EU adopts CRC check, which has high reliability. The fiber connection rules are as follows: The fiber port TX1 of the DSP module located in slot No.1 of EU1 → The fiber port RX1 of the DSP module located in slot No.2 of the CU The fiber port RX1 of the DSP module located in slot No.1 of EU1 → The fiber port TX1 of the DSP module located in slot No.2 of the CU The fiber port TX1 of the DSP module located in slot No.1 of EU2 → The fiber port RX2 of the DSP module located in slot No.2 of the CU The fiber port RX1 of the DSP module located in slot No.1 of EU2 → The fiber port TX2 of the DSP module located in slot No.2 of the CU All the protection logic is completed in the CU, and the EU is responsible for bay current and binary quantity acquisition, and the EU also realizes the tripping of the connected bays. It should be noted that the analog quantity and the binary quantity configuration of the EU are all completed during the DEVS project configuration of the CU. The following parameters need to be set in the EU. 1.
System frequency The system frequency of the EU needs to be consistent with that of the CU. Otherwise, the analog sampling of the CU and the analog sampling of the EU are not synchronized, it will cause a differential current.
2.
Logic setting for enabling/disabling the communication between the EU and the CU (BU_RX.En) If the logic setting is set as “0”, the EU will no longer receive the information sent by the CU.
3.
Binary input module related parameters Binary input power supply voltage, operating voltage percentage, drop-off percentage, monitoring window of binary input jitter processing, blocking window of binary input status change due to jitter, time threshold to block binary input status change due to jitter, time threshold to initiate immediately another blocking window of binary input status change due to continuous jitter, logic setting to enable the jitter processing function in case of binary input
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
3-105
3
3 Protection Functions
voltage variation, and power supply mode of binary input module. 4.
Clock synchronization related parameters Set the clock synchronization related parameters if necessary. These parameters only affect the display time of the device and will not affect the sampling synchronization between the EU and the CU.
3
3-106
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
4 Measurement
4 Measurement Table of Contents 4.1 Overview ........................................................................................................... 4-1 4.2 Primary Values ................................................................................................. 4-1 4.2.1 General Values ..................................................................................................................... 4-1 4.2.2 Angle Values ......................................................................................................................... 4-1 4.2.3 Sequence Components Values ............................................................................................ 4-2
4.3 Secondary Values ............................................................................................ 4-3 4.3.1 General Values ..................................................................................................................... 4-3 4.3.2 Angle Values ......................................................................................................................... 4-3 4.3.3 Sequence Components Values ............................................................................................ 4-4
4.4 Function Values ............................................................................................... 4-4
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
4-a
4
4 Measurement
4
4-b
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
4 Measurement
4.1 Overview This device performs continuous measurement of the analogue input quantities. The current full scale of relay is 40 times of rated current, and there is no effect to the performance of IED due to overflowing of current full scale. The device samples 24 points per cycle and calculates the RMS value in each interval and updated the LCD display in every 0.5 second. The measurement data can be displayed on the LCD of the relay front panel or on the local/remote PC via software tool. Navigate the menu to view the sampling value through LCD screen.
4.2 Primary Values 4.2.1 General Values Access path: MainMenu “Measurements” “Primary Values” “General Values” No.
Symbol
Definition
Unit
1
Frequency
The system frequency
Hz
2
@BBx.Ua_Pri
Phase-A voltages of BBx
V
3
@BBx.Ub_Pri
Phase-B voltages of BBx
V
4
@BBx.Uc_Pri
Phase-C voltages of BBx
V
5
@Bayn.Ia_Pri
Phase-A currents of bay n
A
6
@Bayn.Ib_Pri
Phase-B currents of bay n
A
7
@Bayn.Ic_Pri
Phase-C currents of bay n
A
8
@Bayn.CT1.Ia_Pri
Phase-A currents of CT1 of bay n (for double-CT BC/BS)
A
9
@Bayn.CT1.Ib_Pri
Phase-B currents of CT1 of bay n (for double-CT BC/BS)
A
10
@Bayn.CT1.Ic_Pri
Phase-C currents of CT1 of bay n (for double-CT BC/BS)
A
11
@Bayn.CT2.Ia_Pri
Phase-A currents of CT2 of bay n (for double-CT BC/BS)
A
12
@Bayn.CT2.Ib_Pri
Phase-B currents of CT2 of bay n (for double-CT BC/BS)
A
13
@Bayn.CT2.Ic_Pri
Phase-C currents of CT2 of bay n (for double-CT BC/BS)
A
4.2.2 Angle Values Access path: MainMenu “Measurements” “Primary Values” “Angle Values” When voltage is sampled by the device and phase A voltage of BB1 is larger than a certain value, the phase A voltage of BB1 will be taken as a reference; if the phase A voltage of BB1 is smaller than the certain value and the phase A voltage of BB2 is larger than the certain value, the phase A voltage of BB2 will be taken as a reference; and so forth. When voltage is not sampled by the device, if the currents of some feeder are larger than a certain value, the phase A current of the feeder (takes the feeder whose number is minimal) will be taken as a reference.
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
4-1
4
4 Measurement No.
Symbol
Definition
Unit
If the phase A voltage of BBx is taken as a reference, the displayed value of “AngRef” is “x”, If phase A voltage of all busbars are all smaller than a 1
certain value, the displayed value of “AngRef” is “0”.
AngRef
If the phase A current of feeder m is taken as a reference, the displayed
°
value of “AngRef” is “m” (m=01, 02, 03, ……), if all the currents are smaller than a certain value, the displayed value of “AngRef” is “0”.
4
2
@BBx.Ang(Ua)
Phase-A angle of voltage of BBx
°
3
@BBx.Ang(Ub)
Phase-B angle of voltage of BBx
°
4
@BBx.Ang(Uc)
Phase-C angle of voltage of BBx
°
5
@Bayn.Ang(Ia)
Phase-A angle of current of bay n
°
6
@Bayn.Ang(Ib)
Phase-B angle of current of bay n
°
7
@Bayn.Ang(Ic)
Phase-C angle of current of bay n
°
8
@Bayn.CT1.Ang(Ia)
Phase-A angle of current of CT1 of bay n (for double-CT BC/BS)
°
9
@Bayn.CT1.Ang(Ib)
Phase-B angle of current of CT1 of bay n (for double-CT BC/BS)
°
10
@Bayn.CT1.Ang(Ic)
Phase-C angle of current of CT1 of bay n (for double-CT BC/BS)
°
11
@Bayn.CT2.Ang(Ia)
Phase-A phase angle of current of CT2 of bay n (for double-CT BC/BS)
°
12
@Bayn.CT2.Ang(Ib)
Phase-B phase angle of current of CT2 of bay n (for double-CT BC/BS)
°
13
@Bayn.CT2.Ang(Ic)
Phase-C phase angle of current of CT2 of bay n (for double-CT BC/BS)
°
4.2.3 Sequence Components Values Access path: MainMenu “Measurements” “Primary Values” “SeqComponent Values” No.
Symbol
Definition
Unit
1
@BBx.Uab_Pri
Phase-to-phase voltage (Uab) of BBx
kV
2
@BBx.Ubc_Pri
Phase-to-phase voltage (Ubc) of BBx
kV
3
@BBx.Uca_Pri
Phase-to-phase voltage (Uca) of BBx
kV
4
@BBx.U2_Pri
Negative-sequence voltage of BBx
kV
5
@BBx.3U0_Cal_Pri
The calculated residual voltage of BBx
kV
6
@Bayn.I2_Pri
Negative-sequence current of bay n
A
7
@Bayn.CT1.I2_Pri
Negative-sequence current of CT1 of bay n (for double-CT BC/BS)
A
8
@Bayn.CT2.I2_Pri
Negative-sequence current of CT2 of bay n (for double-CT BC/BS)
A
9
@Bayn.3I0_Cal_Pri
The calculated residual current of bay n
A
10
@Bayn.CT1.3I0_Cal_Pri
The calculated residual current of CT1 of bay n (for double-CT BC/BS)
A
11
@Bayn.CT2.3I0_Cal_Pri
The calculated residual current of CT2 of bay n (for double-CT BC/BS)
A
4-2
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
4 Measurement
4.3 Secondary Values 4.3.1 General Values Access path: MainMenu “Measurements” “Secondary Values” “General Values” No.
Symbol
Definition
Unit
1
Frequency
The system frequency
Hz
2
@BBx.Ua_Sec
Phase-A voltages of BBx
V
3
@BBx.Ub_Sec
Phase-B voltages of BBx
V
4
@BBx.Uc_Sec
Phase-C voltages of BBx
V
5
@Bayn.Ia_Sec
Phase-A currents of bay n
A
6
@Bayn.Ib_Sec
Phase-B currents of bay n
A
7
@Bayn.Ic_Sec
Phase-C currents of bay n
A
8
@Bayn.CT1.Ia_Sec
Phase-A currents of CT1 of bay n (for double-CT BC/BS)
A
9
@Bayn.CT1.Ib_Sec
Phase-B currents of CT1 of bay n (for double-CT BC/BS)
A
10
@Bayn.CT1.Ic_Sec
Phase-C currents of CT1 of bay n (for double-CT BC/BS)
A
11
@Bayn.CT2.Ia_Sec
Phase-A currents of CT2 of bay n (for double-CT BC/BS)
A
12
@Bayn.CT2.Ib_Sec
Phase-B currents of CT2 of bay n (for double-CT BC/BS)
A
13
@Bayn.CT2.Ic_Sec
Phase-C currents of CT2 of bay n (for double-CT BC/BS)
A
4.3.2 Angle Values Access path: MainMenu “Measurements” “Secondary Values” “Angle Values” No.
Symbol
Definition
Unit
If the phase A voltage of BBx is taken as a reference, the displayed value of “AngRef” is “x”, If phase A voltage of all busbars are all smaller than a 1
AngRef
certain value, the displayed value of “AngRef” is “0”. If the phase A current of feeder m is taken as a reference, the displayed
°
value of “AngRef” is “m” (m=01, 02, 03, ……), if all the currents are smaller than a certain value, the displayed value of “AngRef” is “0”. 2
@BBx.Ang(Ua)
Phase-A angle of voltage of BBx
°
3
@BBx.Ang(Ub)
Phase-B angle of voltage of BBx
°
4
@BBx.Ang(Uc)
Phase-C angle of voltage of BBx
°
5
@Bayn.Ang(Ia)
Phase-A angle of current of bay n
°
6
@Bayn.Ang(Ib)
Phase-B angle of current of bay n
°
7
@Bayn.Ang(Ic)
Phase-C angle of current of bay n
°
8
@Bayn.CT1.Ang(Ia)
Phase-A angle of current of CT1 of bay n (for double-CT BC/BS)
°
9
@Bayn.CT1.Ang(Ib)
Phase-B angle of current of CT1 of bay n (for double-CT BC/BS)
°
10
@Bayn.CT1.Ang(Ic)
Phase-C angle of current of CT1 of bay n (for double-CT BC/BS)
°
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
4-3
4
4 Measurement No.
Symbol
Definition
Unit
11
@Bayn.CT2.Ang(Ia)
Phase-A phase angle of current of CT2 of bay n (for double-CT BC/BS)
°
12
@Bayn.CT2.Ang(Ib)
Phase-B phase angle of current of CT2 of bay n (for double-CT BC/BS)
°
13
@Bayn.CT2.Ang(Ic)
Phase-C phase angle of current of CT2 of bay n (for double-CT BC/BS)
°
4.3.3 Sequence Components Values Access path: MainMenu “Measurements” “Secondary Values” “SeqComponent Values” No.
4
Symbol
Definition
Unit
1
@BBx.Uab
Phase-to-phase voltage (Uab) of BBx
V
2
@BBx.Ubc
Phase-to-phase voltage (Ubc) of BBx
V
3
@BBx.Uca
Phase-to-phase voltage (Uca) of BBx
V
4
@BBx.U2
Negative-sequence voltage of BBx
V
5
@BBx.3U0_Cal
The calculated residual voltage of BBx
V
6
@Bayn.I2
Negative-sequence current of bay n
A
7
@Bayn.CT1.I2
Negative-sequence current of CT1 of bay n (for double-CT BC/BS)
A
8
@Bayn.CT2.I2
Negative-sequence current of CT2 of bay n (for double-CT BC/BS)
A
9
@Bayn.3I0_Cal
The calculated residual current of bay n
A
10
@Bayn.CT1.3I0_Cal
The calculated residual current of CT1 of bay n (for double-CT BC/BS)
A
11
@Bayn.CT2.3I0_Cal
The calculated residual current of CT2 of bay n (for double-CT BC/BS)
A
4.4 Function Values Access path: MainMenu “Measurements” “Function Values” “DiffCurr Values” No.
Sign
Description
Unit
1
Ida_CZ
Phase-A check zone differential current
A
2
Idb_CZ
Phase-B check zone differential current
A
3
Idc_CZ
Phase-C check zone differential current
A
4
@BBx.Ida
Phase-A discriminating zone differential current of BBx
A
5
@BBx.Idb
Phase-B discriminating zone differential current of BBx
A
6
@BBx.Idc
Phase-C discriminating zone differential current of BBx
A
7
@BBx.Ira
Phase-A discriminating zone restraint current of BBx
A
8
@BBx.Irb
Phase-B discriminating zone restraint current of BBx
A
9
@BBx.Irc
Phase-C discriminating zone restraint current of BBx
A
10
@Bayn.Ia_Conv
Phase-A currents of bay n
the current
11
@Bayn.Ib_Conv
Phase-B currents of bay n
12
@Bayn.Ic_Conv
Phase-C currents of bay n
4-4
have
A
been
converted
A
according
to
A
that
the
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
4 Measurement No.
Sign
13
@Bayn.CT1.Ia_Conv
14
@Bayn.CT1.Ib_Conv
15
@Bayn.CT1.Ic_Conv
16
@Bayn.CT2.Ia_Conv
17
@Bayn.CT2.Ib_Conv
18
@Bayn.CT2.Ic_Conv
Description Phase-A currents of CT1 of bay n (for double-CT BC/BS) Phase-B currents of CT1 of bay n (for double-CT BC/BS) Phase-C currents of CT1 of bay n (for double-CT BC/BS) Phase-A currents of CT2 of bay n (for double-CT BC/BS) Phase-B currents of CT2 of bay n (for double-CT BC/BS) Phase-C currents of CT2 of bay n (for double-CT BC/BS)
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
Unit referenced CT ratio
A
A
A
A
A
A
4
4-5
4 Measurement
4
4-6
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
5 Supervision
5 Supervision Table of Contents 5.1 Overview ........................................................................................................... 5-1 5.2 Device Hardware Supervision ........................................................................ 5-1 5.2.1 Hardware Resource Consumption Supervision ................................................................... 5-1 5.2.2 Hardware Status Supervision ............................................................................................... 5-2 5.2.3 Hardware Configuration Supervision ................................................................................... 5-3 5.2.4 Device Firmware Supervision .............................................................................................. 5-3 5.2.5 CPU Process and Module Supervision ................................................................................ 5-3
5.3 Analog Input Supervision ............................................................................... 5-3 5.4 Secondary Circuit Supervision....................................................................... 5-4 5.5 Binary Input Supervision ................................................................................ 5-4 5.5.1 Debounce Time .................................................................................................................... 5-4 5.5.2 Jitter Processing ................................................................................................................... 5-6
5.6 Circuit Breaker Supervision ........................................................................... 5-8 5.7 Supervision Alarms and Handling Suggestion ............................................. 5-9
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
5-a
5
5 Supervision
5
5-b
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
5 Supervision
5.1 Overview Protection system is in quiescent state under normal conditions, and it is required to respond promptly for faults occurred on power system. When the device is in energizing process before the LED “HEALTHY” is on, the device need to be checked to ensure no abnormality. Therefore, the automatic supervision function, which checks the health of the protection system when startup and during normal operation, plays an important role. The numerical relay based on the microprocessor operations is suitable for implementing this automatic supervision function of the protection system. In case a defect is detected during initialization when DC power supply is provided to the device, the device will be blocked with indication and alarm of relay out of service. It is suggested a trial recovery of the device by re-energization. Please contact supplier if the device is still failure. When a failure is detected by the automatic supervision, it is followed by a LCD message, LED indication and alarm contact outputs. The failure alarm is also recorded in event recording report and can be printed if required.
5
5.2 Device Hardware Supervision All hardware has real-time monitoring functions, such as CPU module monitoring, communication interface status monitoring, power supply status monitoring. The monitoring function of CPU module also includes processor self-check, memory self-check and so on. The processor self-check is checked by designing execution instructions and data operations. Check whether the processor can execute all instructions correctly, and whether it can correctly calculate complex data operations to determine whether it works normally. For peripherals, it can monitor the status of the interface module, check the input and output data, send the communication interface and receive self-loop detection. Memory self-check is used to detect unexpected memory errors in the running process. It can effectively prevent program logic abnormality caused by memory errors. The status monitoring of communication interface also includes Ethernet communication interface monitoring and differential channel communication interface monitoring. By accessing the status register of the communication interface, the state of the corresponding interface is obtained, such as the state of connection, the number of sending frames, the number of frames received, and the number of wrong frames. According to the statistics of the acquired interface state, it is judged whether the interface work is abnormal. The hardware supervision also includes the power supply status monitoring. The voltage monitoring chip is used by all the power supplies. The reset voltage threshold is preset to the reset monitoring circuit. When the power supply is abnormal, the voltage monitoring chip will output the reset signal to control CPU to be in the reset state and avoid the wrong operation.
5.2.1 Hardware Resource Consumption Supervision 1.
Logic component total execution time monitoring
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
5-1
5 Supervision
In the process of operation, the safety allowance should always be kept and no overload phenomenon is allowed. When the user configures logic components with PCS-Studio, the PCS-Studio automatically calculates the time required for the theoretical execution of the configured components. When the security limit is exceeded, the PCS-Studio will indicate that the configuration error is not allowed to download the current configuration to the device. 2.
Module data exchange monitoring
During the operation of the device, there is a lot of data exchange between modules. The number of data exchanges is related to the number of logical components configured by the user. When the configuration is too large to cause the number of data exchange to exceed the upper limit supported by the device, the PCS-Studio prompts the configuration error. 3.
Configuration file size monitoring
The initialization of the device depends on the configuration files of each module. The user configured logical components will eventually be embodied in the configuration file, limited to the hardware memory space. When the configuration file size is more than the upper limit, the PCS-Studio prompts the configuration error.
5
5.2.2 Hardware Status Supervision 1.
Memory ECC and parity functions.
The DDR3 memory chip has the function of ECC (Error Checking and Correcting) to eliminate unexpected changes in memory caused by electromagnetic interference. The chip memory has parity function. When an error occurs, the system can detect anomalies immediately, and eliminate the logic abnormity caused by memory errors. 2.
Memory error monitoring in code area and constant data area
In addition to the above hardware memory reliability measures, the device software is also constantly checking the memory during operation, including code, constant data, and so on. Once the error detection, the system will automatically restart the restore operation. If they detect the error immediately after the restart, it may be the result of a permanent fault locking device hardware, only at the moment and not restart. 3.
Binary output relay drive monitoring
The reliability of the device is largely determined by the reliability of the export drive. By reading the driving state of the binary output relay, the alarm signal will be generated and the device is immediately blocked to prevent the relay from mal-operation when the device is not given a tripping order and the binary output relay driver is detected in the effective state. 4.
CPU temperature monitoring
The CPU chip needs to be able to ensure long-term stability under the permissible working temperature of the specification. Therefore, it is necessary to monitor the working temperature monitored by CPU.
5-2
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
5 Supervision
5.2.3 Hardware Configuration Supervision The device is blocked when the actual hardware configuration is not consistent with the hardware configuration file. Compared with pre configured modules, this device will be blocked if more modules are inserted, fewer modules are inserted, and wrong modules are inserted.
5.2.4 Device Firmware Supervision 1.
Each hardware module configuration check code needs to be consistent with CPU module.
The device CPU module stores the configuration check codes of other modules. In initialization procedure, it checks whether the configuration check code of each module is consistent with the stored code in CPU module, and if it is not consistent, this device is blocked. The hardware modules and process interface versions need to be consistent with the CPU module. 2.
If the system is incompatible with the upgrade, it will upgrade the internal interface version. At this moment, each hardware module and process will be upgraded synchronously, otherwise the version of the interface will be inconsistent. 3.
Configuration text is correct.
The configuration text formed by the device calibration visualization project includes checking whether the check code is wrong or not. 4.
Whether any setting is over the range, whether it needs to confirm the settings.
If the setting exceeds the configuration range, the device is blocked; if some settings are added, it is necessary to confirm the new values through the LCD.
5.2.5 CPU Process and Module Supervision 1.
Monitor the heartbeat of the module.
In the operation procedure, the CPU module sends a time synchronization command to other module, each module repeats heartbeat message to the CPU module, if it does not respond or the heartbeat is abnormal, then this device is blocked. 2.
Check whether the settings of other modules are consistent with the CPU module.
The actual values of all the settings in the CPU module are initialized to send to the corresponding slave modules. In the process of operation, the setting values stored in the CPU module and the setting values of other modules will be checked one by one. If they are not consistent, this device will issue the alarm signal [Fail_Settings].
5.3 Analog Input Supervision The sampling circuit of this device is designed as dual-design scheme. Each analog sampling channel is sampled by two groups of ADC. The sampling data is self checking and inter checking in real time. If any sampling circuit is abnormal, the device reports the alarm signal [Fail_Sample], PCS-915SC Centralized Busbar Relay Date: 2019-03-11
5-3
5
5 Supervision
and the protection function related to the sampling channel is disabled at the same time. When the sampling circuit returns to normal state, the related protection is not blocked after 10s.
5.4 Secondary Circuit Supervision The secondary circuit supervision function includes current transformer supervision (CTS), voltage transformer supervision (VTS), and binary inputs power supply supervision.
CTS function
The purpose of the CTS function is to detect whether the current transformer circuit is failed. In some cases, if the CT is failed (broken-conductor, short-circuit), related protective element should be blocked for preventing this device from mal-operation. Please refer to Chapter 3 about the details about the CTS function.
5
VTS function
The purpose of the VTS function is to detect whether the VT analog input is normal. Some voltage related function will be influenced by voltage input failure. The VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit fault, poor contact of VT circuit, VT maintenance and so on. The device can detect the failure, and then issue an alarm signal and block relevant function. Please refer to Chapter 3 about the details about the VTS function.
5.5 Binary Input Supervision 5.5.1 Debounce Time The well-designed debounce technique is adopted in this device, and the state change of binary input within “Debounce time” will be ignored. As shown in Figure 5.5-1. All binary inputs should setup necessary debounce time to prevent the device from undesired operation due to transient interference or mixed connection of AC system and DC system. When the duration of binary input is less than the debounce time, the state of the binary input will be ignored. When the duration of binary input is greater than the debounce time, the state of the binary input will be validated and wrote into SOE.
5-4
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
5 Supervision
Binary input state SOE report timestamps
SOE report timestamps Validated binary input state changes
1
Validated binary input state changes
0
Debounce time of delayed pickup
Debounce time of delayed dropout
Time
Figure 5.5-1 Sequence chart of debounce technique
All binary inputs should setup necessary debounce time to prevent the device from undesired operation due to transient interference or mixed connection of AC system and DC system. When the duration of binary input is less than the debounce time, the state of the binary input will be ignored. When the duration of binary input is greater than the debounce time, the state of the binary input will be validated and wrote into SOE. In order to meet flexible configurable requirement for different project field, all binary inputs provided by the device are configurable. Through the configuration tool, this device provides two parameters to setup debounce time of delayed pickup and dropout based on specific binary signal.
Figure 5.5-2 Debounce time configuration page
The configurable binary signals can be classified as follows: 1.
Type 1 This type of binary inputs includes enable/disable of protection functions, AR mode selection, “BI_RstTarg”, “BI_Maintenance”, disconnector position, settings group switch, open and close command of circuit breaker and disconnector, enable/disable of auxiliary functions (for example, manually trigger recording). They are on the premise of reliability, and the
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
5-5
5
5 Supervision
debounce time of delayed pickup and delayed dropout is recommended to set as 100ms at least. 2.
Type 2 This type of binary inputs include breaker failure initiating binary input and so on. Debounce time BI
t1
Input Signal.X1
t2
& Time delay
Output
SIG Operation condition
Time delay is equal to 0 The debounce time of delayed pickup and delayed dropout is recommended to set as 15ms, in order to prevent binary signals from mal-operation due to mixed connection of AC system and DC system.
5
Time delay is not equal to 0 The debounce time of delayed pickup and delayed dropout is recommended to set as (-t1+ t2+Time delay)≥15ms, in order to prevent binary signals from mal-operation due to mixed connection of AC system and DC system. Where, “t1” is the debounce time of delayed pickup, and “t2” is the debounce time of delayed dropout.
3.
Type 3 This type of binary inputs is usually used as auxiliary input condition, and the debounce time of delayed pickup and delayed dropout is recommended to set as 5ms.
When users have their own reasonable setting principles, they can set the debounce time related settings according to their own setting principles.
5.5.2 Jitter Processing This device can handle repetitive signal or so-called jitter via binary input module with the following settings: [Mon_Window_Jitter]
T, monitoring window of binary input jitter processing
[Num_Blk_Jitter]
N, times threshold to block binary input status change due to jitter
[Blk_Window_Jitter]
T', blocking window of binary input status change due to jitter
[Num_Reblk_Jitter]
N', times threshold to initiate immediately another blocking window of binary input status change due to continuous jitter
For a binary input voltage variation, if the jitter processing function is enabled, its handling 5-6
PCS-915SC Centralized Busbar Relay Date: 2019-03-11
5 Supervision
principle is: 1.
2.
During the T,
If the actual jitter times < N, the block will not be initiated and the status change of this binary input will be considered.
If the actual jitter times ≥ N, the T' is initiated, and the status change of binary input will be ignored during the T'.
During the T',
If the actual jitter times < N', the block window will expire. The final status of this binary input will be compared to the original one before T', so as to determine whether there is a change or not.
If the actual jitter times ≥ N', the T' will be initiated again immediately (i.e. restart the timer), and the status change of binary input will be ignored during the next T'.
An example of jitter processing is shown in the following sequence chart: Input voltage level
Debounce time (falling edge)
5
Debounce time (rising edge)
Jitter blocking flag n=N initiate jitter block
Signal after debounce & jitter processing
n=N Prolong blocking window
n=5