AAD03040D Elevator Door Controller User Manual (4SW induction mode)
AAD03040D 4SW induction mode user manual
【!】Must refer to this manual. This controller only can be tested, repaired, and checked by the people certificated. Otherwise, it may course unexpected danger, such as hurts and destroy.
1. Setup and wiring (4SW induction mode) Before using AAD03040, please refer to the requirement, and connect the door controller to the right power supply and motor. At the same time, please make sure the controller connected correctly with input and output signals. Wiring figure:
COM Close speed change Open speed change (Reserve) Close arrival Open arrival Close command Open command COM
∽AC 200V
COM Close arrival Open arrival
★Notice: Among the open/close arrival status output relays, A1 is used for open arrival signal, and A2 is used for close arrival signal. A1 and A2 can work in exciting in ON status or Non-exciting in ON status, by setting the following parameters: P033=r10: The relay is turned ON when the coil is not excited. (Signal ON status = OFF between terminals A1 and C1) P033=10: The relay is turned ON when the coil is excited. (Signal ON status = ON between terminals A1 and C1) - 2 -
AAD03040D 4SW induction mode user manual
P034=r11: The relay is turned ON when the coil is not excited. (Signal ON status = OFF between terminals A2 and C2) P034=11: The relay is turned ON when the coil is excited. (Signal ON status = ON between terminals A2 and C2) Please refer to the main controller of the elevator, when setting the parameter.
2. Panel Users can operate the AAD03040 door controller with the panel. You can set parameter, and watch the monitor, and also open/close the door with the panel. Panel layout:
ay section
section
Mode switch flow:
Name
Function
MODE
To switch mode one by one(P,H,d,n)
SET
To comfirm parameter settings and enter a monitor
▲
To increase parameter number or setting data
▼
To decrease parameter number or setting data
RUN
To run the controller under panel control mode
STOP
To stop the controller or reset
Open/close with panel: Doors can be open and close with panel, as follows: Set P003 = 1; P004 =4; Press: ▲ + RUN : To open Press: ▼ + RUN: To close
3.Workmode and input/output settings (4SW induction mode) When the AAD03040 works in 4SW induction motor mode, please make sure the following settings: - 3 -
AAD03040D 4SW induction mode user manual
Control mode parameters: No.
Function name
Range 范围
Value
P003
Run Command Selection
0~2
2
Panel control: P003=1 External control:P003=2
P004
Control mode selection
0~5
4
4SW mode: P004=4
Remark
Signal input function parameters: Value
Input Signal Logic Setting
Rang e 范围 0~63
P027
SW1 Function Selection
0~16
1
=1:Open arrival signal(default)
P028
SW2 Function Selection
0~16
2
=2:Close arrival signal (default)
P029
SW3 Function Selection
0~16
0
=0:Null(reserve)
P030
SW4 Function Selection
0~16
3
=3:Open speed change signal(default)
P031
SW6 Function Selection
0~16
4
=4:Close speed change signal(default)
No.
Function name
P026
27
Remark 4 SW in close status:= 27(default) 4 SW in open status:= 0
Relay output function parameters: No.
Function name
Range
Value
Remark
P033
RY1 Function Selection(A1\C1)
0~17;r0~r1 7
r10
Non-exciting in ON status: =r10 Exciting in ON status: =10
P034
RY2 Function Selection (A2\C2)
0~17;r0~r1 7
r11
Non-exciting in ON status: =r11 Exciting in ON status: =11
P035
RY3 Function Selection (A3\B3\C3)
0~17;r0~r1 7
4
Alarm output signal: =4
Notice: Non-exciting in ON status (P033=r10; P034=r11) is default setting.
4. Open and close torque settings (4SW induction mode) When the door is very heavy and torque is not big enough to operate the door, please set the following parameters: No.
Function name
Range
Value
Remark
P044
Open torque boost
0~40%
15%
Default 15%
P059
Close torque boost
0~40%
10%
Default 10%
5. Open and close speed curve (4SW induction mode) Open speed curve and parameters - 4 -
AAD03040D 4SW induction mode user manual Close hold
Open hold
Open operation
Close arrival
Open arrival
hold current d095
d021
Frequency
d012 d013
d011
d020
hold current
d022 d023 d014
d094
d033
P002
d031
d015
P002 Door area
0
1
2
3
4
5
ON ON Open arrival
ON ON
Close arrival
ON
Open start timer
No.
Function name
Range
Value
d011
OPEN frequency 1
0.5-250.0 Hz
5.0Hz
d012
OPEN frequency 2
0.5-250.0 Hz
23.0Hz
d013
OPEN frequency 3
0.5-250.0 Hz
23.0Hz
d014
OPEN frequency 4
0.5-250.0 Hz
5.0Hz
d015
OPEN arrival hold frequency
0.5-250.0 Hz
3.0Hz
d020
OPEN acc/dec time1
0.1-999.9 s
0.5s
d021
OPEN acc/dec time2
0.1-999.9 s
0.5s
d022
OPEN acc/dec time3
0.1-999.9 s
0.8s
d023
OPEN acc/dec time4
0.1-999.9 s
0.5s
d031
OPEN arrival hold standby frequency
0.5-250.0 Hz
0.5Hz
d033
OPEN arrival hold standby time
0.00-10.00 s
0.0s
d035
Open start timer
0.00-10.00 s
0.3s
d092
Open speed change timer
0.00-10.00 s
0.0s
d094
Open hold current
0.1-100.0 A
150%
P002
The 1st deceleration time
0.1-999.9 s
0.5s
- 5 -
Remark
C lose spee d curv e and para mete rs
AAD03040D 4SW induction mode user manual Open hold
Close hold
Close operation
Open arrival
Close arrival
hold current d094
d025
Frequency d024
hold current
d026 d017 d018
d016
d027 d019
d095 d034 Hold operation P002
d032
d010
P002 Door area
5
Open command
6
7
9
0
ON
Close command Open arrival
8
ON ON
Close change
ON
Close arrival
ON
Close start timer Close speed change timer
No.
Function name
Range
Value
d016
CLOSE frequency 1
0.5-250.0 Hz
5.0Hz
d017
CLOSE frequency 2
0.5-250.0 Hz
19.0Hz
d018
CLOSE frequency 3
0.5-250.0 Hz
19.0Hz
d019
CLOSE frequency 4
0.5-250.0 Hz
4.0Hz
d010
CLOSE arrival hold frequency
0.5-250.0 Hz
2.0Hz
d024
CLOSE acc/dec time 1
0.1-999.9 s
0.5s
d025
CLOSE acc/dec time 2
0.1-999.9 s
0.5s
d026
CLOSE acc/dec time 3
0.1-999.9 s
1.0s
d027
CLOSE acc/dec time 4
0.1-999.9 s
1.0s
d032
CLOSE arrival hold standby frequency
0.5-250.0 Hz
0.5Hz
d034
CLOSE arrival hold standby time
0.00-10.00 s
0.0s
d036
Close start timer
0.00-10.00 s
0.0s
d093
Close speed change timer
0.00-10.00 s
0.0s
d095
Close arrival hold current
0.1-100.0 A
100%
P002
The 1st deceleration time
0.1-999.9 s
0.5s
Remark
6. Ob sta cle Det ect ion Op
eration In the 4SW induction mode, there are two methods for obstacle detection. - 6 -
AAD03040D 4SW induction mode user manual
Detection with time.: No.
Function name
d060
Detection time for forced CLOSE operation
Range
Value
0 • 1-9999 s
0s
Remark
Detection
related parameters with over-load: No.
Function name
d045
Close over-load detection frequency 1
Range
Value
0.5-250.0 Hz
10
Remark
Set detecti d046 Close over-load detection frequency 2 0.5-250.0 Hz 50 on d047 Close Over-load detection current 1 0.1-100.0 A 1.2 conditi d048 Close Over-load detection current 2 0.1-100.0 A 1.2 on of d049 Close Over-load detection time 0 • 1-9999 s 0 obstacl e detection with current during CLOSE operation. When obstacle detection with current is not performed, set the parameter d049 to “0”. Overload level can be switch to the detected level according to output frequency and SW current as shown in the below figure.
7. Default settings recover Parameter P037 can be used for default setting recover. If you want to recover all parameters into default settings, please set P037=2.
8.Setting procedure (4SW induction mode) Please set the controller follow the following procedure:
1. Please check the wiring. - 7 -
2. Turn on the power, and check the
AAD03040D 4SW induction mode user manual
9.Input signal monitor and input logic settings Input signals can be checked by monitor parameter n016. When you push the door passing each SW, make sure the status of each LED. Each LED refers to a SW. Here’s the check list. LED position
Referring input No.
Referring input signal
a1
No.2
Open command
b1
No.3
Close command
c1
No.4(SW1)
Open arrival
d1
No.5(SW2)
Close arrival
e1
No.6(SW3)
---
f1
No.7(SW4)
Open speed change
g1
No.8(SW5)
Close speed change
Door Position
4 SW status (Non-exciting in ON status)
Open
Open arrival: OFF
Open change: OFF
arrival
Close arrival : ON
Close change: ON
Middle position
Open arrival: ON
Open change: ON
Close arrival : ON
Close change: ON
Close
Open arrival: ON
change
Close arrival : ON
Close change: OFF
Close
Open arrival: ON
Open change: ON
arrival
Close arrival : OFF
Open
Open arrival: ON
Open change: OFF
change
Close arrival : ON
Close change: ON
When the door moves over a SW, the LED which the SW refers to gets on/off. For example:
All the input SW logic can be set by P026. n016
Open change: ON
Close change: OFF
When the 4 SW input signal is in OPEN status: P026 = 27(defaul t) When the 4 SW input signal is in CLOSE
status: P026 = 0 ■ Setting method ● Allocate the input signal logics of SW1 to SW6 to bit0 to bit5, multiply each SW logic by a corresponding addition value, sum up the products obtained to get the setting value, and conduct input with decimal numbers. ● The initial value is “0”, and all inputs are allocated to “contact a input”. ■ Each digit value ● Contact a input =“0”: When the input signal is in OPEN status (terminal levelis “L”), ON will be detected. ● Contact b input = “1”: When the input signal is in CLOSE status (terminal level is “H”), ON will be detected. ■ Operation example When SW1 and SW2 are “ contact b input ” and theother signals are “contact a input” Setting value = (0 × 32)+(0 × 16)+(0 × 8)+(0 × 4)+(1 × 2)+(1 × 1) = 3
- 8 -
AAD03040D 4SW induction mode user manual
10.Details and Remedies for Various Fault Trips The elevator door controller is equipped with a trip memory for storing incurred abnormalities. The trip memory can store the latest abnormal case and up to 3 previous ones, which can be checked in the monitoring mode n012 to n015. The stored contents can be kept safely even if the power supply is interrupted.
- 9 -
AAD03040D 4SW induction mode user manual