35 0 390KB
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 1 / 30 Date:
18-Jan-2002
MCS - TCBC List of Installation Parameters
Authorization Date D1:
18-Jan-02
Running on PCB:
GAA26800KA (TCBC)
Software Version:
GAA 30081 AAB
Document Revision :
V 1.1
Date 12-Oct-2001 18-Jan-0218Jan-02
SCN GAA 30081 AAA GAA 30081 AAB G15 30081 AAB
Author A. Gerwing A. Gerwing
Comment original document based on TCB/HCB software GAA 30084 AAF CNL=0 added; SDI-Dir
M. Hoinkis
SDI-Dir added
Copyright 2009, OTIS GmbH & Co. OHG Berlin. No part of this document may be copied or reproduced in any form or by any means without the prior written consent of OTIS.
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 2 / 30 Date:
18-Jan-2002
1 - SYSTEM No.
Symbol
Default
Purpose and Range
0.
TOP
2
Top position: 1 (1) 31
1.
LOBBY
0
Lobby position: Separate doortime LOB-NT can be used at the lobby. 0 (1) 31
2.
BOTTOM
0
Bottom position: 0 (1) 30
3.
CFT-P
255
Cafeteria Position: Separate doortime CFT-NT can be used at the cafeteria 0 (1) 31 > 31
Disabled
4.
OPERAT
1
Operation FCL / DCL / SAPB: 0 FCL (Full Collective) 1 DCL (Down Collective) 2 SAPB (Single Automatic Push Button) 3 SAPB with Car Coming Light 4 FCL, delete both calls on arrival 5 FCL with single button for both directions
5.
EN-BSM
0
Enable Basement mode for DCL (two Hall Calls at lobby (Up and Down): 0 1
Disabled Enabled
6.
PI
4
Type of serial Position Indicator: 0 7/16 Segment 1 Serial Multilight via RIB 2 7 Segment-PI and LM-PI via RIB 3 Brazilian 10-Segment 4 OTIS 2000: LCD and ELD 5 Australian Dot Matrix (uses also IO 975, 976) 6 Australian Dot Matrix and Direction Indicator (uses also IO 975, 976)
7.
PI-OPT
0
Vendor PI option 0 no option 1 returning to ground floor 2 overloaded 4 out of service 8 lift on firefighting service note: if more than one of the above options should be available then you must add the appropriate numbers (e.g. to select 1+4 you must program 5)
since
No.:
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 3 / 30
MCS - TCBC
Date:
List of Installation Parameters
18-Jan-2002
1 - SYSTEM No.
Symbol
Default
Purpose and Range
8.
ELD-fOPG
20
front door movement time: opening Time the front door needs to open
since
0 (0.1) 10.0 s 0 = automatic (not yet implemented) Note: 9.
ELD-fCLG
20
CPI-11 only (PI=4)
front door movement time: closing Time the front door needs to close 0 (0.1) 10.0 s 0 = automatic (not yet implemented) Note:
10.
ELD-rOPG
20
CPI-11 only (PI=4)
rear door movement time: opening Time the rear door needs to open 0 (0.1) 10.0 s 0 = automatic (not yet implemented) Note:
11.
ELD-rCLG
20
CPI-11 only (PI=4)
rear door movement time: closing Time the rear door needs to close 0 (0.1) 10.0 s 0 = automatic (not yet implemented) Note:
12.
ELD-LNG
5
Note: 13.
ELD-Sym1
0
14.
ELD-DOOR
0
CPI-11 only (PI=4)
set Language for ELD: 0 (1) 19 0=SwiGer, 1=SwiFra, 2=SwiIta, 4=Italy, 5=UK, 6=Spain, 8=Germany, 9=Austria, 10=Sweden, 12=Belgium, 13=Portugal, 14=Egypt, 16=SthAfrica, 17=Finland, 18=Arabia, 20=Moscow, 21=StPetrbrg, 22=not used, 24=Hungary, 25=Poland, 26=Czech,
3=France, 7=Netherlnd, 11=Luxem, 15=Denmark 19=Kuweit, 23=AGB, 27=UKB
CPI-11 only (PI=4)
Enable Non-Smoking symbol: 0 No Symbol on ELD 1 NoSmoking symbol is displayed Note:
CPI-11 only (PI=4)
Select Type of Door Display: 0: 1 COP for 1 door or 2 COPs for 2 doors (use dummy plug for rear ELD) 1: only 1 COP for 2 doors Note:
CPI-11 only (PI=4)
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 4 / 30 Date:
18-Jan-2002
1 - SYSTEM No.
Symbol
Default
Purpose and Range
15.
ELD-MSG
0
Enables Customer Messages on ELD: 0 no customer messages are displayed (existing customer messages will be deleted at the next PowerOn) 1 customer messages are enabled ELD must be reinitialized if the Position Indicator Setup is changed (use SETUP-ELD to define the texts) Note:
16.
EN-SFR
0
Enable SFR (signal flicker): Select that the outputs will blink (instead of being constantly illuminated) when activated: 0 1
17.
LR-T
20
CPI-11 only (PI=4)
Disabled single devices BUZ, EQL, ERL, FDL, FSL, HEL, INLC, NSLC, OLS, PFL, CRFL, EFOL, ARL, DUPL
Light Relay time (IO 0026, PX2:4): A parking car will switch off the car light after LR-T. The CPI-11 (ELD) is also switched off after this time. 0 (1) 255 s Note: LR-T is started after the car has become IDLE. As soon as LR-T has expired the LR output is activated and the ELD (CPI-11) is switched to Sleep-Mode.
18.
LR-MODE
0
Fan / Light Relay mode option (IO 0026, PX2:4): 0 LR pulls only when door closed (Light) 1 LR pulls even if door is opened (Fan)
19.
EN-HLC
0
Enable Hall Lanterns on car calls: 0 Hall lanterns will operate only on hall calls 1 Hall lanterns will operate on hall and car calls 2 like 0, but also during door closing 3 like 1, but also during door closing
20.
HDL-TYP
0
Hall Direction/Lantern Type for OTIS 2000 Hall Button Box (IOs 814ff, 846ff): 0 Direction Indicator 1 Hall Lantern
21.
HL-SET
0
Hall Lantern/Gong Setup: 0 Lantern and Gong at same pins 1 Lantern and Gong at different pins (RS4A) 2 NAO Chime board
22.
CR-DIR
0
Correction Fast Run Preferred Direction: 0 Down 1 Up
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 5 / 30 Date:
18-Jan-2002
1 - SYSTEM No.
Symbol
Default
Purpose and Range
23.
CR-DO
0
Door opening after Correction Run 0 no door opens 1 only front door opens 2 only rear door opens 3 both front and rear door will open note: After TCI/ERO the DO2000 needs a new initialization run. Normally the door is not opened after COR so that the init run is done upon the first demand which is usually a hall call. Therefore the passenger might wonder about the slow door movement. With this parameter you can select that the door opens immediately after completion of a correction run. The door movement for the first demand will then be done with a normal door profile.
24.
ERO-TYP
0
Define ERO type 0 without limit 1 car stops at terminal landings (same as TCI-limit)
25.
REM-TYP
0
Type of installed REM 0 REM-II, REM-III, REM-SL, REM-5 1 REM-G
26.
CPC-TYP
0
select use of CPC outputs: 0
1
2 3
27.
DFCR-DEL
0
car position contact The output at a landing is switched on if the car is at that landing (even if the car is moving) 'car here' light The output at a landing is switched on if the car is at that landing (only if the car has stopped) french SSM Arrival Hall Lantern (AHL-2) The output at a landing is switched on if the car is at that landing (only if this landing is the target landing)
Delay for DFC-Relay 0 disabled 1 (1) 255 s delay for which DFCR output is kept active after DFC input has been opened Note:
For Module BDC
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 6 / 30 Date:
18-Jan-2002
2 - OCSS No.
Symbol
Default
Purpose and Range
0.
CPR-T
20
Car Call Preference: This is the duration for which car calls have priority over hall calls after the doors are opened. Single Automatic Push Button (SAPB) and Down Collective operation (DCL). 0 (0.1) 25.5 s
1.
ARD-P
255
Automatic Return Device Position: If no further calls are pending, the car will return to this floor after ARD-T has expired. 0 (1) 31 > 31
Disabled
Note: Simplex only 2.
ARD-T
0
Set Delay for ARD (Automatic Return Device) mode: 0 (10) 2550 s
3.
ARBL-T
0
Delay for Automatic Return To Bottom Landing ARBL means that the car moves to the lowest landing after a selectable period of time. This Park Run is performed even for special OCSS modes as e.g. ISC or ATT. It also allows lobby parking (ARD-T) in presence of basement floors without defeating code requirements. 0 (10) 2540 s 255 disabled Note: This parameter must be larger than ARD-T to take effect.
4.
ARBL-PRK
0
ARBL park option 0 stay at bottom after ARBL has been performed 1 return to previous park landing after ARBL has been performed
5.
PKS-P
255
Parking Service Position: The car moves to this landing if PKS is operated. After opening and closing of the door the car is shut down with DOB enabled. 0 (1) 31 > 31
6.
PKS -TYP
0
Disabled
Parking Shutoff Type: 0 After serving all pending car calls, car will return to PKS position and shutdown after PKS-T seconds 1 Same as above, but after car arrived at PKS position it can be switched to ISC 2 Like 0, but car will shut down with door open
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 7 / 30 Date:
18-Jan-2002
2 - OCSS No.
Symbol
Default
Purpose and Range
7.
PKS-T
0
Parking Shutoff Time: Time after which the car is shut down at PKS-P 0 (1) 255 s
8.
PKS-DO
0
PKS default door: 0 Both doors will open at PKS-P 1 Only front door opens 2 Only rear door opens
9.
EN-SHB
0
Enable Separate Hall Buttons: 0 Normal HB-operation 1 Rear HB as Separate Riser Note:
10.
DCP-T
50
only available for elevators without any rear door
Time until DCP-mode (d When door is kept open longer than DCP-T, the car will be taken out of group operation. Hall calls assigned to this car will be re-dispatched. If enabled by EN-NDG, the door will start to nudge. 25 (1) 255 s
11.
CTL-DO
0
CTL default door (car to any landing): 0 Both doors will open at CTL-P 1 Only front door opens at CTL-P 2 Only rear door opens at CTL-P
12.
CTL-P
255
CTL (Car To Any Landing) position: The car moves to this landing if CTL input is activated. > 31
Disabled
13.
ANS
0
ANS (Anti Nuisance Service): 0 Disabled >0 Number of calls required to cancel all calls if car is loaded with ANS load (input: LWX)
14.
ATT
0
ATT (Attendant Service) type: 0 Press DCB or RDCB until the door is fully closed 1 Press ATTU or ATTD until the door is fully closed 2 Like 0, but the door may also be closed without any demand
15.
ISC
0
Independent Service: 0 Start on constant pressure of CCB 1 Start on constant pressure of DCB/RDCB 2 Start on ISD/ISU 3 as CHCS, Start on constant pressure of DCB/RDCB 4 Start on momentary pressure of CCB
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 8 / 30 Date:
18-Jan-2002
2 - OCSS No.
Symbol
Default
Purpose and Range
16.
ISPS-TYP
0
Independent Service Park Switch (IO 638) 0 car calls allowed when ISPS active 1 no car calls allowed when ISPS active
17.
ISC-T
0
Independent Service Close Timeout When Fire Proof Doors are installed it is not allowed to park with doors opened. This parameter sets a maximum duration after which the door is closed in ISC. 0 (1) 30 s
max door open time when FPD is installed
18.
SPEECH
0
Speech Mode: 0 Floor message on CC only 1 Floor message also on HC
19.
CPMT-D
0
Car Position Message Trigger for Vendor type PI 0 (0.1) 25.5 sec
20.
DCMT-A
0
Door Close Message Trigger for Vendor type PI 0 (0.1) 25.5 sec
21.
DOMT-O
0
Door Open Message Trigger Option for Vendor type PI 0 trigger on opening and reopen 1 trigger on opening only
22.
DOC
0
Door Reopen Count: Number of times the car will reopen the doors if a hall call is entered while the door is closing. If that limit is exceeded, the door will continue to close and the car starts 0 1 (1) 255
23.
DS-CCB
0
No limit Number of allowed door reopenings
Disable CCs behind moving car: The entry of car calls into the opposite direction can be disabled. 0 1
CCs behind allowed CCs behind not allowed
24.
DS-DOB
0
Disable DOB button: 0 DOB/RDOB always enabled 1 DOB disabled if door closed 2 RDOB disabled if door closed 3 Both disabled if door closed
25.
EN-RB
0
Enable car call Reset Button (IO 627, 725) 1 enabled in ATT mode 2 enabled in CHC mode 4 enabled in EFS mode 8 enabled in ISC mode note: if more than one of the above options should be available then you must add the appropriate numbers (e.g. to select 1+4 you must program 5)
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 9 / 30 Date:
18-Jan-2002
2 - OCSS No.
Symbol
Default
Purpose and Range
26.
DHB-TYP
0
Enable DoorHoldButton for CARGO 2000 (IOs 620,628) DHB doortime can be canceled by... 0 press DCB or any CCB (in this case the DHB-T is a 1-sec-timer 1 press DCB or any CCB, or press DHB again (in this case the DHB-T is a 10-sec-timer!)
27.
PARK-1
255
Park Clock Position 1: If PCLKx is operated, the car will park at PARK-x instead of ARD-D. PCLK1 has highest, PCLK8 has lowest priority. 0 (1) 31 > 31
Disabled
Note: Simplex only 28.
PARK-2
255
Park Clock Position 2: 0 (1) 31 > 31
Disabled
Note: Simplex only 29.
PARK-3
255
Park Clock Position 3: 0 (1) 31 > 31
Disabled
Note: Simplex only 30.
PARK-4
255
Park Clock Position 4: 0 (1) 31 > 31
Disabled
Note: Simplex only 31.
PARK-5
255
Park Clock Position 5: 0 (1) 31 > 31
Disabled
Note: Simplex only 32.
PARK-6
255
Park Clock Position 6: 0 (1) 31 > 31
Disabled
Note: Simplex only 33.
PARK-7
255
Park Clock Position 7: 0 (1) 31 > 31
Disabled
Note: Simplex only
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 10 / 30 Date:
18-Jan-2002
2 - OCSS No.
Symbol
Default
Purpose and Range
34.
PARK-8
255
Park Clock Position 8: 0 (1) 31 > 31
Disabled
Note: Simplex only
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 11 / 30 Date:
18-Jan-2002
3 - GROUP No.
Symbol
Default
Purpose and Range
0.
GRP-NO
1
Car identifier in group: 1 (1) 3
1.
GROUP
1
Number of cars in group: 1 (1) 3
2.
CNL
1
Cars parking in Lobby: 0 group parking disabled 1 (1) 3 number of cars parking in lobby Note:
3.
MIT-ST
0
Set CNL=0 to avoid parking at the lobby
MIT (Moderate incomming traffic) Start Time: If, within MIT-ST seconds, two cars leave the lobby with LNS load, then MIT is initiated. 0 (1) 255 s
4.
MIT-T
0
5.
MIT-VD
0
MIT Time-Out: If, within MIT-T seconds, no car leaves the lobby with LNS load, then MIT is suspended. 0 (1) 255 s MIT Variable Interval Dispatch: An assigned car at lobby will leave the lobby if calls are pending and MIT-VD is expired or if it becomes loaded. 0 (1) 255 s
6.
MIT-DOOR
0
MIT Default Door If car is waiting at the lobby for being selected…. 0 wait with opened door 1 wait with closed door
7.
MIT-NLB
0
MIT No Lobby Bypass 0 Answer hall calls while moving to the lobby 1 Don’t answer hall calls
8.
DUPK-P
255
Dual Up Peak Border Position: The elevator group is split into two subgroups if the DUPK input is operated. The selected landing DUPK-P divides the groups. 0 (1) 31 > 31
9.
DUPK-G
0
Disabled
Dual Up Peak Group: 0 Car belongs to subgroup 1. Car serves lobby landing and all landings below DUPK-P landing, but answers no hall calls. 1 Car belongs to subgroup 2 Car serves lobby landing and all landings above DUPK-P landing. This car responds to hall calls
since
AAB
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 12 / 30 Date:
18-Jan-2002
3 - GROUP No.
Symbol
Default
Purpose and Range
10.
MOT-T
0
MOT (Moderate Outgoing traffic) Time-Out: If, within MOT-T seconds, two cars with LNS load arrive at the lobby, then MOT is initiated. If then no car arrives at lobby with LNS load within the same time interval again, the MOT operation is suspended. 0 (1) 255 s
11.
EN-UCB
0
Enable Up Call Bypass during MOT: 0 Car responds to both up and down hall calls 1 Car responds only to down hall calls
12.
TFS-P
255
Transfer Floor Position: If a group is split into low and high rise subgroups, this is the position where passengers transfer between these subgroups. 0 (1) 31 > 31
Disabled
13.
EN-ZBS
0
Enable separate basement zone: 0 No free car parks in basement zone 1 A free car parks in basement zone
14.
SEL-COMP
0
Select MCS310 Compatible Communication 0 MCS120 / 220 / 220M (Triplex - Ring ICD 3.3) 1 MCS310 with G44 software (Duplex - Ring ICD 3.0) 2 MCS310 with G57 software (Duplex - Ring ICD 3.0)
15.
L-PARK
0
Lobby Park Option (only if SEL-COMP ≠ 0) A second car moves into lobby when the car which parks at
Note: This parameter takes effect after next Power-On
0 1 16.
PRKDST
0
receives a demand leaves the lobby
Minimum Distance to park target to do park run A park run is only performed if the distance to the destination floor is greater than the number given by this parame0 (1) 31
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 13 / 30 Date:
18-Jan-2002
3 - GROUP No.
Symbol
Default
Purpose and Range
17.
EN-GSS
0
Group Successive Starting If a building has limited emergency power supply it must be ensured that multiple cars do not start simultanously. Groups use the Ring Communication while simplex cars use remote I/Os to lock each other: If the GSSI input is active the car does not start. If the GSSI input is inactive the car sets its GSSO output (which is connected to the other car’s GSSI input) for the duration MGDEL and starts. 0 1 2
disabled GSS triggered by remote I/Os GSSI (972), GSSO (973) for multiple simplex cars GSS triggered by serial group communication
Note: during EPO only 18.
MG-DEL
0
Motor Generator Delay for GSS 0 (1) 255 s note: this delay depends on the duration of the acceleration phase Note: during EPO only
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 14 / 30 Date:
18-Jan-2002
4 - DRIVE No.
Symbol
Default
Purpose and Range
0.
DRV-TYP
0
Drive Type: 0
1.
EN-ADO
1
Enable Advanced Door Opening 0 disabled (XADO) 1 enabled (ADO)
2.
SPEED
100
Speed (fast run mode): 25 40 63 100 160 175 250 cm/s
3.
PDR-D
0
Delay for Power-Down 0 Drive is never switched off 15 (1) 42 min Delay until the drive package is powered down.
OVF-WW
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 15 / 30 Date:
18-Jan-2002
5 - DOORS No.
Symbol
Default
Purpose and Range
0.
DOOR
12
Type of Doors: 12 DCSS-5, AT120 13 DCSS-5, AT120 with DOBF (direct DOB)
1.
REAR
12
Type of Doors: 12 DCSS-5, AT120 13 DCSS-5, AT120 with DOBF (direct DOB)
2.
EN-DDO
0
Enable DDO (double door operation): Select that both front and rear door will open simultaneously 0 1 2
Disabled double door on car call and on hall call double door on car call, selected door on hall call
3.
EN-ADM
0
Alternating Door Mode 0 doors can open simultanously 1 ADM preference to front door 2 ADM preference to rear door
4.
LDR
0
Limited Door Reversal: 0 Full DOB, full EDP, full LRD 1 Full DOB, limited EDP, full LRD
5.
EN-PMO
0
Enable PMO (door time monitoring): If the actual door time is longer than 2 seconds and the LRD input is operated, door time will be decreased to 2 seconds. If the door time already is less than 2 seconds it will be decreased by 0.5 seconds 0 1
Disabled Enabled
6.
EN-NDG
0
Enable NDG (nudging): 0 Disabled 1 Enabled
7.
NDG-T
20
Nudging Time: 0 (1) 255 s
8.
EN-CK
0
Enable Cancel Doortime with CCB: 0 disabled 1 enable CK 2 enable CBC 3 enable CK and CBC note:
9.
DO-BEL
0
CK = cancel doortime with car button CBC = cancel registered car call with car button (press twice)
Open Door Bell Timer: 0 (0.1) 25.5 s
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 16 / 30 Date:
18-Jan-2002
5 - DOORS No.
Symbol
Default
Purpose and Range
10.
MIN-C
20
Min Doortime Car: The doortime for calls is automatically adjusted between MIN-C and MAX-C. If door time is expired and DOB is still operated, this will increase the door time by 0.2 s at the next stop, otherwise door time is decreased by 0.2 sec. 0 (0.1) 25.5 s
11.
MAX-C
40
Max Doortime Car: 0 (0.1) 25.5 s
12.
MIN-H
40
Min Doortime Hall: The doortime for calls is automatically adjusted between MIN-H and MAX-H. If door time is expired and DOB is still operated, this will increase the door time by 0.2 s at the next stop, otherwise door time is decreased by 0.2 sec. 0 (0.1) 25.5 s
13.
MAX-H
60
Max Doortime Hall: 0 (0.1) 25.5 s
14.
DOR-T
0
Door reverse time: 0 (0.004) 1 s
15.
RDOR-T
0
Rear door reverse time: 0 (0.004) 1 s
16.
DTC-T
20
Door Close Protection Time: If the door cannot fully close within DTC-T then the door will reopen and try to close again. After three unsuccessful tries the elevator is shut down. 10 (1) 254 s 255
17.
DTO-T
Door Open Protection Time: If the door cannot fully open within DTO-T then the door will close and tries to open at the next. After three unsuccessful tries the elevator is shut down 10 (1) 254 s 255
18.
LOB-NT
DTC-time Disabled
40
DTO-time Disabled
Lobby Door Time: This door time is used at LOBBY if it is longer than MIN-H 0 (0.1) 25.5 s
19.
CFT-NT
40
Cafeteria Door Time: This door time is used at CFT-P if it is longer than MIN-H. 0 (0.1) 25.5 s
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 17 / 30 Date:
18-Jan-2002
5 - DOORS No.
Symbol
Default
Purpose and Range
20.
SPB-NT
0
Special DOB Door Time: If the Special DOB (SDB/RSDB) is operated and it is enabled via the 3rd allowed mask for the current landing, the special door time SPB-NT will be used instead of the normal door time. 0 (0.1) 25.5 s
21.
DHB-T
120
DHB Doortime: Defines the doortime when DHB/RDHB is pressed. The used timer is either a 1-sec-timer or a 10-sec-timer depending on the parameter DHB-TYP. 0 (1) 255 s 0 (10) 2550s
for DHB-TYP=0 (see 2-OCSS) for DHB-TYP=1 (see 2-OCSS)
22.
WCO-T
0
23.
SHO-T
0
Shabat Door Time: 0 (0.1) 25.5 s
24.
SHO-LT
0
Shabat Lobby Door Time: 0 (0.1) 25.5 s
25.
DAR-T
60
Door Time for Drive-Fault with Automatic Return: In case of a fault the door is kept open for DAR-T and then
Wild Car Door Time: On wild car operation the car runs continously from floor to floor serving all landings. This door time has to be set to a value that ensures that the maximum number of runs per hour allowed for the drive can not be exceeded. 0 (0.1) 25.5 s
: Hydraulic only. Applies for OTS, PLS1, MCLS, MPD, 26.
DXT-T
0
DXT Time (extended door time): Extents the door dwell time for a hall call if the car is already parking at that landing. 0 (0.1) 25.5 s
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 18 / 30 Date:
18-Jan-2002
6 - POSITION REFERENCE No.
Symbol
Default
Purpose and Range
0.
DZ-TYP
0
DZ coding: 0 DZ = 1LV 1 DZ = 1LV and 2LV 2 POSY operation (if neither RLV nor ADO) to stop: DZ = 1LV and 2LV after stop: DZ = 1LV or 2LV
1.
EN-RLV
0
Enable RLV operation: 0 Disabled 1 Enabled
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 19 / 30 Date:
18-Jan-2002
7 – Service No.
Symbol
Default
Purpose and Range
0.
Encoder
13
Pulse Width of Speed Encoder for SPB 13 mm (fixed)
since
Distance between two rising edges of the tension device. 1.
SDI-Max
30
Maximum speed value of SDI 0 (0.01) 0.63 m/s Speed at which all 8 LEDs of the Speed/Direction-Indicator are switched on. If during manual rescue operation the measured car speed is higher than this value, the LEDs are blinking and the buzzer is turned on.
2.
SDI-Dir
0
Direction of Speed and Direction Indicator 0 machine mounted on left side of hoistway 1 machine mounted on right side of hoistway Use this parameter to invert the display of the SDI.
3.
BRE-Max
10
Maximum speed for Brake Release Electrical 0 (0.01) 0.30 m/s Manual rescue operation: SPB drops the brake if the measured car speed is higher than BRE-MAX.
4.
SPB-Temp
60
Temperature Limit for Service Panel Board 0 (1) 63 degrees celsius HTS is activated if the SPB detects a temperature which is
AAB Formatted: Bullets and numbers
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 20 / 30 Date:
18-Jan-2002
8 – EMERGENCY No.
Symbol
Default
Purpose and Range
0.
ES-TYP
0
Define ES-Type: 0 ESS car stops as long as input is activated door is deenergized 1 ESB / RSS car stops until a car call button is pressed. a door which was not closed will be opened
1.
ES-LRCU
0
LRCU selftest duration (IOs 964, 965, 966) 0-4 no selftest else delay for LRCU selftest
2.
EFO-P
255
EFO (emergency fireman operation) position: 0 (1) 31 > 31 Disabled note: This parameter is ignored for EFO-NC=1
3.
EFO-NC
0
EFO Next Commitable Position: 0 move to EFO1 stop at next commitable landing; parameter EFO-P is ignored
4.
EFO-DC
0
EFO with Doors Closed: 0 1 (1) 255 s
The doors will be kept open at EFO-P After this time the doors wil close at EFO-P
5.
EFO-DO
0
EFO default door: 0 Both doors will open at EFO position 1 Only front door opens 2 Only rear door opens
6.
EFO-OP
0
EFO override option: A defect EFO input (e.g. smoke sensor) may be ignored to enable normal function while EFO input is repaired. 0 1 2 3
No override possible XEFO input overrides EFO after arrival at return landing After EFS no EFO is permitted if EFO or AEFO are still active Functions 1 + 2 together
7.
EFONDG
0
Enable nudging speed for EFO 0 Door closes with full speed 1 Door closes with nudging speed
8.
EFO-REV
0
Allowed Reversal Devices during EFO 0 all devices disabled 1 only SGS/DOS allowed 2 DOB and SGS/DOS allowed
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 21 / 30 Date:
18-Jan-2002
8 – EMERGENCY No.
Symbol
Default
Purpose and Range
9.
EFO-MP
0
EFO mode priority 1 ISC has priority 2 ATT has priority 4 EHS has priority note: if more than one of the above options should be available then you must add the appropriate numbers (e.g. to select 1+4 you must program 5)
10.
EFO-MP-T
0
EFO mode priority time 0 (1) 60 s max duration before EFO is started
11.
EFO-SD
0
EFO signal devices 0 no buzzer operation 1 constantly on 2 always flickering 3 constantly without EPO, flickering with EPO
12.
ASL-P
255
ASL (Alternate Service Landing) position for EFO: If the ASL-input is activated, the car will move to ASL-P instead of EFO-P (e.g. fire at EFO-P) 0 (1) 31 > 31 Disabled
13.
EFS-TYP
0
Type of EFS (Emergency Fireman Service) (if EFK (ASL) connected):
1
2
3 4 5 6
7 8 9 10 14.
EFS-DO
0
Car will go to EFO landing and stays there with door open EFS 1 (Automatic) If car arrives at EFO landing, it will go automatically into ISC. EFS 2 (Manual) If car arrives at EFO landing, it can be switched to ISC with ISS switch ANSI (SES I / II) British Standard 5533 Swiss Standard Australia Same as EFS 2, but car can be switched to ISC with ESK switch only New Zealand EFS 2 (Manual with ESK) New Zealand with DCB GENERIC
EFS default door: 0 Both doors will open position 1 Only front door opens 2 Only rear door opens
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 22 / 30 Date:
18-Jan-2002
8 – EMERGENCY No.
Symbol
Default
Purpose and Range
15.
EFSINI
0
EFS initiation of Phase II 1 automatically 2 when ISS operated 4 when ESK operated 8 when CFS operated 16 when 1EFS operated note: if more than one of the above options should be available then you must add the appropriate numbers (e.g. to select 1+4 note:
16.
EFSCLD
0
only applicable if EFS-TYP=10
EFS close door type 1 car button (constant pressure) 2 door close button (constant pressure) 4 up/down start buttons 8 CS start button 16 ANSI style ISC 32 car call demand (momentary pressure) note: if more than one of the above options should be available then you must add the appropriate numbers (e.g. to select 1+4 you must program 5) note:
17.
EFSOPD
0
only applicable if EFS-TYP=10
EFS open door type 1 always automatically 2 when DOB constantly pressed 4 only on 1st arrival 8 Door Hold Function if door not fully opened or closed (I/Os DDM, RDDM) if more than one of the above options should be available then you must add the appropriate numbers (e.g. to select 2+4 you must program 6) valid values are 1, 2, 4 and 6 only applicable if EFS-TYP=10
18.
EFS-EX
0
19.
EFS-RT
0
EFS exit type 0 only if at EFO landing 1 if not moving and door is open 2 at any landing when door is closed 3 when door is opened or closed (option 1+2) note:
only applicable if EFS-TYP=10
EFS return time (diration for which EFK must be low to force car back to EFO landing if EFK is switched on again while in EFS): 0-39 Function disabled 40-255 Time (in 100 ms units) EFK must be low
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 23 / 30 Date:
18-Jan-2002
8 – EMERGENCY No.
Symbol
Default
Purpose and Range
20.
EFS-RC
0
EFS recall type 1 EFK off timeout 2 EFK off, moving 4 EFK off, not moving 8 EFK off, not moving, door closed 16 EFK off, not moving, door opened 32 EFS1 off note: if more than one of the above options should be available then you must add the appropriate numbers (e.g. to select 1+4 yo note:
21.
EF-I-LT
0
only applicable if EFS-TYP=10
EFO/EFS input latching 1 EFO input is latched 2 AEFO input is latched 4 EFK input is latched 8 ASL input is latched note: if more than one of the above options should be available then you must add the appropriate numbers (e.g. to select 1+4 yo note:
22.
EN-BAK
0
Enable E2P-backup of EFO/EFS: If enabled, the system keeps all necessary information during power-off to avoid a correction run after power-on if car was in any door zone. 0 1
Disable backup Enable backup
23.
HDWPOS
0
Hardware position reference: 0 Disabled 1 One contact per floor 2 Binary coded contacts 3 Signal at every odd floor
24.
EPO-P
255
EPO (emergency power operation) Position: 0 (1) 31 EPO A/C (position) EPO E (hydro: bottom) = 32 EPO B/D (next floor) EPO F (hydro: next floor down) >32 Disabled
25.
EPO-DC
0
EPO with doors closed: 0 Disabled 1 (1) 255 s After rescue operation and waiting for further run, the doors will close after EPO-DC
26.
EPO-DO
0
EPO default door: 0 Both doors will open at EPO position 1 Only front door opens 2 Only rear door opens
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 24 / 30 Date:
18-Jan-2002
8 – EMERGENCY No.
Symbol
Default
Purpose and Range
27.
EPO-PR
0
EPO priority if EFO or EFS active: 0 No priority for EPO 1 EPO has priority over EFO/EFS
28.
EQO
0
Earthquake Operation Version: 0 California 1 New Zealand
29.
EPS-TYP
0
Express Priority Service: After arriving at the floor where the EHS call was given: xx0 automatic ISC xx1 return to normal xx2 automatic CHCS Before arriving at the floor where the EHS call was given: x0x immediate return x1x stop at next commitable x2x serve car calls en route General: 1xx with Tale Tell Lights (EHS-2)
30.
EHS-T
0
EHS time-out: After the car has stopped for the EHS call, the car will return to normal operation after this time. 0 1 (1) 255 s
Disabled
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 25 / 30 Date:
18-Jan-2002
9 - SECURITY No.
Symbol
Default
Purpose and Range
0.
EN-FPD
0
Enable FPD (fireproof doors): 0 Disabled 1 Enabled
1.
EN-IST
0
Enable IST (intermittent stop): Stop at IST-P if the car passes this landing. 0 1 2 3 5 6 7
Disabled In up direction only In down direction only In both directions In up direction only, if ISTS active In down direction only, if ISTS active In both directions, if ISTS active
2.
IST-P
255
Intermittent Stop Position: 0 (1) 31 >31 Disabled
3.
EN-CRO
0
Enable Car Card Reader Operation: 0 Disabled 1 Single Contact Reader Use CRC contact and Card-Rd Mask, C bit = 1: car call always allowed C bit = 0: car calls only allowed if CRC operated 2 Multi Contact Reader Use CRSn contacts and Card-Rd Mask, C bit = 1: car call always allowed C bit = 0: car calls only allowed if corresponding CRSn contact operated 3 Single and Multi Contact Reader combination of 1 and 2, so both CRC and CRSn can be used at the same time 4 no card reader operation 5 like 1, but ISC will override any CRS security 6 like 2, but ISC will override any CRS security 7 like 3, but ISC will override any CRS security
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 26 / 30 Date:
18-Jan-2002
9 - SECURITY No.
Symbol
Default
Purpose and Range
4.
EN-HCRO
0
Enable Hall Call Card Reader Operation 0 no hall card reader 1 Accept normal hall calls normal hall calls only if SECn input is operated, EHC calls are always allowed 2 Accept EHC calls EHC calls if SECn input is operated, normal calls are always allowed 3 Accept all hall calls all hall call types only if SECn input is operated 4 no hall card reader 5 Delete and Disable normal hall calls if SECn input is operated, normal hall calls are disabled 6 Delete and Disable EHC calls if SECn input is operated, EHC calls are disabled 7 Delete and Disable all hall calls if SECn input is operated, all hall call types are disabled
5.
GCBTYP
0
General Control of 0 disabled 1 GCB-1 (car calls disabled; park run allowed) 2 GCB-2 (all calls disabled)
6.
RIOT-P
255
RIOT Operation Position: The car will run to the riot position and keep the doors open if the RIOT switch is operated. 0 (1) 31 >31 Disabled
7.
SACTYP
0
Secure Access Type: 0 SAC disabled 1 SAC enabled, without ISC override 3 SAC enabled, with ISC override 5 SAC enabled, without ISC override, clear only possible if security enabled 7 SAC enabled, with ISC override, clear only possible if security enabled else SAC disabled
8.
SAC-D1
0
Secure Access digit 1: First digit of Master Access Code 0 1 (1) 6
9.
SAC-D2
0
disabled use CSA1 - CSA6 as code input
Secure Access digit 2: Second digit of Master Access Code 0 1 (1) 6
disabled use CSA1 - CSA6 as code input
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 27 / 30 Date:
18-Jan-2002
9 - SECURITY No.
Symbol
Default
Purpose and Range
10.
SAC-D3
0
Secure Access digit 3: Third digit of Master Access Code 0 1 (1) 6
disabled use CSA1 - CSA6 as code input
since
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
MCS - TCBC List of Installation Parameters
No.:
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 28 / 30 Date:
18-Jan-2002
10 - TEST No.
Symbol
Default
Purpose and Range
0.
TPOS 1
255
Test position 1(automatic test run): If TPOS1≠TPOS2 and TDELAY>0, the car will move between TPOS1 and TPOS2, waiting at both floors for TDELAY seconds. 0 (1) 31 > 31
Disabled
1.
TPOS 2
255
Test position 2(automatic test run): 0 (1) 31 > 31 Disabled
2.
TDELAY
255
Test Delay for automatic test run: 0 (1) 255 s
3.
DEBUG
0
Debug parameter: 0 (1) 255
4.
DEBUG1
0
Debug parameter1: 0 (1) 255
5.
EN-EVT
0
Enable Storage of 10 events into E2PROM: 0 all events are lost after PowerOff 1 10 events are memorized in E2Prom during PowerOff
6.
EN-CRT
0
Enable contract handling: 0 1
up to 16 openings up to 32 openings (contract definition of RS addresses re-
quired) 7.
DISP-ALL
0
display of inputs in M-1-1-2 (System-Status-Inputs) 0 only those inputs are displayed which are used by the specific configuration 1 all inputs are displayed, even if not available for the specific configuration
since
No.:
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
GAA26800KA VIII a_FC1
SCN:
GAA30081AAB
Rev.:
V1.1
Page: 29 / 30
MCS - TCBC
Date:
List of Installation Parameters
18-Jan-2002
Index A ANS ARBL-PRK ARBL-T ARD-P ARD-T ASL-P ATT
7 6 6 6 6 21 7
B BOTTOM
2
C CFT-NT CFT-P CNL CPC-TYP CPMT-D CPR-T CR-DIR CR-DO CTL-DO CTL-P
16 2 11 5 8 6 4 5 7 7
D DAR-T DCMT-A DCP-T DEBUG DEBUG1 DFCR-DEL DHB-T DHB-TYP DISP-ALL DO-BEL DOC DOMT-O DOOR DOR-T DRV-TYPE DS-CCB DS-DOB DTC-T DTO-T DUPK-G DUPK-P DXT-T DZ-TYP
17 8 7 28 28 5 17 9 28 15 8 8 15 16 14 8 8 16 16 12 11 17 18
E EF-I-LT
23
EFO-DC EFO-DO EFO-MP EFO-MP-T EFO-NC EFONDG EFO-OP EFO-P EFO-REV EFO-SD EFSCLD EFS-DO EFS-EX EFSINI EFSOPD EFS-RC EFS-RT EFS-TY EHS-T ELD-DOOR ELD-fCLG ELD-fOPG ELD-LNG ELD-MSG ELD-rCLG ELD-rOPG ELD-Sym1 EN-ADM EN-ADO EN-BAK EN-BSM EN-CK Encoder EN-CRO EN-CRT EN-DDO EN-EVT EN-FPD EN-GSS EN-HCRO EN-HLC EN-IST EN-NDG EN-PMO EN-RB EN-RLV EN-SFR EN-SHB EN-UCB EN-ZBS EPO-DC EPO-DO EPO-P EPO-PR EPS-TYP EQO
20 20 21 21 20 20 20 20 20 21 22 21 22 22 22 23 22 21 24 3 3 3 3 4 3 3 3 15 14 23 2 15 19 25 28 15 28 25 13 26 4 25 15 15 9 18 4 7 12 12 23 24 23 24 24 24
ERO-TYP ES-LRCU ES-TYP
5 20 20
G GCBTYP GROUP GRP-NO
26 11 11
H HDL-TY HDWPOS HL-SET
4 23 4
I ISC ISC-T ISPS-TY IST-P
8 8 8 25
L LDR LOBBY LOB-NT L-PARK LR-MODE LR-T
15 2 16 12 4 4
M MAX-C MAX-H MG-DEL MIN-C MIN-H MIT-DOOR MIT-NLB MIT-ST MIT-T MIT-VD MOT-T
16 16 13 16 16 11 11 11 11 11 12
N NDG-T
15
O OPERAT
2
P PARK-1 PARK-2
9 9
No.:
Field Component Manual
OTIS
Software Data
Engineering Center Berlin
9 9 9 10 10 10 2 2 6 7 6 7 14 13
R RDOR-T REAR REM-TYP RIOT-P
16 15 5 26
GAA30081AAB V1.1
Date:
SPB-Con SPB-NT SPB-Temp SPEECH SPEED
18-Jan-2002
19 17 19 8 14
T
S SAC-D1 SAC-D2 SAC-D3 SACTYP SDI-Dir SEL-COMP SHO-LT SHO-T SPB-Buz
SCN: Rev.:
Page: 30 / 30
MCS - TCBC List of Installation Parameters
PARK-3 PARK-4 PARK-5 PARK-6 PARK-7 PARK-8 PI PI-OPT PKS -TY PKS-DO PKS-P PKS-T P-OFF-D PRKDST
GAA26800KA VIII a_FC1
26 26 27 26 19 12 17 17 19
TDELAY TFS-P TOP TPOS 1 TPOS 2
28 12 2 28 28
W WCO-T
17