LV power air circuit-breakers and switch-disconnectors Masterpact Merlin Gerin

52387

Catalogue

■ Merlin Gerin ■ Modicon ■ Square D ■ Telemecanique

Sans titre-1

1

21/12/01, 9:26

0000 000 © 1996 Schneider Electric SA - All right reserved

Schneider Electric SA

5, rue Nadar 92506 Rueil-Malmaison Cedex France Tel: +33 (0)1 41 29 82 00 Fax:+33 (0)1 47 51 80 20

http://www.schneiderelectric.com

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

ce document a étéhas imprimé This document been printed on ecological paper. sur du papier écologique.

Created by: Photos: Schneider Printing by:

0000 000

Sans titre-1

12-96

2

21/12/01, 9:26

Masterpact: presentation

035928PC

Masterpact circuit breakers are used to protect and control low-voltage distribution systems. They may be installed in main LV switchboards (incoming units, main and secondary outgoers). Masterpact is a complete range offering a large selection of performance levels: c ratings from 800 to 6300 A AC, from 1000 to 8000 A DC; c breaking capacity from 40 to 150 kA rms; c operational voltages 690 V AC, 1000 V DC.

Many versions c 3 or 4 poles; c fixed or drawout versions; c current-limiting version up to 2500 A; c wide range of control units offering multiple functions. Circuit breakers designed for all applications c 1000 V AC version; c DC version; c anti-corrosion version; c source-changeover version; c merchant-marine and military versions. Masterpact circuit breakers comply with all major international standards and meet T2 tropicalisation criteria.

front face

2 5 1 6 12 13

4

E28760

7

c "charged"

charged

c "discharged"

discharged

13 main-contact position indicator c "OFF" (O);

8

9

10

11

c "ON" (I).

3

E28761

14

1 opening push-button (O) 2 closing push-button (I) 3 keylock for "connected", "disconnected" or "test" position 4 door interlock 5 stored-energy-mechanism charging handle 6 operations counter 7 "open" position keylock 8 racking handle storage 9 functional position indicator: "connected", "test" and "disconnected" 10 controls on fixed chassis (accessible with cubicle door closed) 11 padlocking facilities for "connected", "disconnected" or "test" position 12 stored-energy-mechanism status indicator

O

OFF

I

ON

E28791

14 fault-trip indicator/breaker reset button LV circuit-breaker: blue figures Enclosure: red figures

M63

M50

M40

M08 àtoM32 M32 M08

IG

LI

L

G off

LIG

I

reset V

push to reset

LG

MERLIN GERIN masterpact I

O

I3

I2

I1 90%

push OFF

I push ON

STR 58 UE

M32 H1 Ui

1000V

50/60Hz

Ue 380/440V

480/690V

Icu 100kA

85kA

Ics 100kA

85kA

Icw 75kA 1s

50%

IEC 947-2

discharged

20%

%Ir

.92 .95 60

.9

.88

0.8

0.63

90

.98 30

.85

1

.8

1

0.5

105

tr

Ir

Io

xIo

xIn Im

Ir :

t Ir fault

8

.2

.1 0 .1 2 on I t off

.2

10

xIo 12

8

17

6

22

4

Im :

480

off

2

xIn tr

th :

Ih

600 800

500

Ih

400

Im fault tm

fault th

T

th .4

.4 .3

.3

.2 .1 .1 2 on I t off

1000 .2 320 250

I

i +S–

1200

A

Ic1 .9

.8

–T+

R

Ic2.8

.93 .95

.7

.98

.6

.85 .9

.86 .85

test

F

00000

.3

6 .3

3 2 1.5

I

O OFF

240

15 at 1,5Ir

tm.4

5

4

120

Reduced dimensions c AC circuit breakers: v a single frame size from 800 to 3200 A, v common height and depth from 800 to 6300 A; c DC circuit breakers: v common height and length from 1000 to 8000 A for operational voltages of up to 500 V DC, v common height and length from 1000 to 4000 A for operational voltages greater than 500 V DC.

1 xIr

.95 1

.5 xIr

test

connected test disconnected

2 BTP207E-1.010-presentation

Merlin Gerin

2

21/12/01, 9:34

015159

1

2

3 4

6 7 8

5

10 9

drawout version 1 2 3 4 5 6 7 8 9 10

arc chute cover auxiliary terminal shield auxiliaries connection block fixed chassis safety shutters arc chute remote control voltage release motor for electrical charging of stored energy mechanism control unit (AC system) front cover

3

Merlin Gerin

BTP207E-1.010-presentation

3

21/12/01, 9:34

E29490

Masterpact: presentation

safety and reliability c reduced, simple maintenance (main contacts easily accessible, with wear indication feature); c double insulation from the front face; c positive contact indication; c auxiliary devices can be fitted on site without adjustment; c fewer parts than conventional ranges (by a factor of 5-10); c a trip interlock ensures that the circuit breaker is open during connection and disconnection; c connection to top or bottom terminals; c fully tropicalised as standard. STR 58 U

stored energy operating mechanism

50%

20% Io 0.8

0.63

90

.9

xIo

tm

Im

τ tr

3

6 .3

.2

2 1.5

8

.2

.1

I Ir : Ir fault

14

12

19 22 Max.

4 2

Ih

xIn Ih 1200A Max th

th :

th

600 800

500 400

Im fault tm

fault

0 .1 on I2t off

10

xIr

8

Im :

tr

320 250

I

i overcurrent

+





+

test

A

Ic2

Ic1

.9

.86

.8

.93 .95

.7

.98

.6

1

xIr

T

.4

.4

.3

.3

.2 1000 .2 .1 .1 1200 on I2t off

.85

ground

.3

.4

5

4

Masterpact circuit breakers are operated via a stored energy mechanism for instantaneous opening and closing. The mechanism is charged either manually or electrically. Closing and opening operations can be initiated either from the local pushbuttons on the circuit breaker front face, or by remote control.

15 at 1.5Ir

1

.8

xIn

norm min.

480

.98 30

.85

1

0.5

240

120 .92 .95 60

.88

%Ir 105

tr

Ir

R .85 .9

.8

.95 .5

1

xIr

test

isolation renforcée

séparation totale

classe II insulation double

entre phase chaque phase total separation

déclencheurs voltmétriques accessibles à l'avant voltage releases accessible from the front

c Fixed circuit breaker The fixed circuit breaker is derived from the moving part of the drawout circuit breaker by adding a fixing bracket on each side.

035929

other possibilities

c Switch version The switch (unprotected) version is derived directly from the standard circuit breaker, but does not implement a control unit (or the magnetic trip units used with the DC circuit breakers). Available models are: v standard: type HI and NI; v high performance: type HF, equipped with a protection system that instantaneously opens the circuit breaker in the event of closure under fault conditions.

Fixed circuit breaker

053060

c Earthing switch A special short-circuit and earthing switch is available on request for the M08 to M32H drawout types, 3 or 4 poles. Please consult us.

common auxiliaries from 800 A to 6300 A Auxiliaries c accessible from the front, mounted in a separate compartment insulated from power circuits; c secured by a single screw; c adjustment-free; c can be fitted on site. c Source changeover system Four solutions are available: v mechanical interlocking for 2 or 3 circuit breakers, adaptable to various sourcechangeover configurations; v automatic source-changeover controller, easy to implement on any two suitably equipped circuit breakers (electrically charged operating mechanism, etc.) (for 3 circuit breakers, consult us); v complete assembly including 2 or 3 mechanically (rod assembly) interlocked circuit breakers, adaptable to various source-changeover configurations; v complete assembly including 2 mechanically (rod assembly) interlocked circuit breakers and an automatic sourcechangeover controller, adaptable to various source-changeover configurations. Ready for connection.

053061

053058

c 1000 V AC circuit breakers

Automatic source-changeover controller

4 BTP207E-1.015-presentation

Merlin Gerin

4

21/12/01, 9:35

86094

DC circuit breakers

86096

Fixed Masterpact DC circuit breaker

Masterpact DC circuit breakers are available in fixed and drawout versions. They benefit from the AC range technology and advantages. c 5 available ratings from 1000 to 8000 A; c 2 breaking capacities, 100 kA at 500 V, 50 kA at 750 and 1000 V; c a circuit-breaker version offering instantaneous short-circuit protection with an adjustable, magnetic trip unit (DINA); c a switch (unprotected) version. note: up to 125 V DC, the devices in the AC range (M08 to M63) may be used only in the switch version, in which case a three-pole, type HI device should be used, with: c 1 pole for the positive polarity; c 1 pole for the negative polarity; c 1 pole not used.

Auxiliaries All the auxiliaries designed for the Masterpact AC circuit breakers may be used on the DC versions, with the exception of the position switches, indicating the connected (CE), disconnected (CD) and test (CT) positions. Auxiliary connections are made via one or two manually disconnectable plugs that remain accessible from the front. Accessories Standard Masterpact DC range equipment includes an arc-chute cover (CC) and, on drawout versions, safety shutters (VO). Interphase barriers (EIP) are not available for the DC range.

Drawout Masterpact DC circuit breaker

device identification M 20 H1 breaking capacity; c N1: standard; c H1: H2: high performance; c L1: current limiting; c DC: direct current. rating c rated current / 100. family c Masterpact: LV power air circuit breaker.

5

Merlin Gerin

BTP207E-1.015-presentation

5

21/12/01, 9:35

Masterpact circuit breakers are the product of Merlin Gerin’s vast experience in the field of power circuit breakers. They incorporate all the qualities of traditional air circuit breakers while drawing on certain of the advantages specific to moulded-case circuit breakers. In particular, they require no preventive maintenance.

ease of installation Masterpact is a complete and rationally designed range. c 10 ratings; c 4 breaking-capacity levels; c 6 control units; c a complete range of auxiliaries and accessories; c numerous versions (three and four-pole devices, fixed and drawout versions, etc.).

025179

2500 A Masterpact circuit breaker

Masterpact circuit breakers are easy to incorporate in switchboards. c a single frame size from 800 to 3200 A, thus making for standardised columns; c an upper safety clearance equal to zero due to the arc-chute cover, on both the fixed and drawout versions; c built-in measurement functions in the control units; c auxiliaries are the same for the entire range and may be easily implemented (only a screwdriver is required).

Top: front connection Bottom: rear vertical connection

Masterpact circuit breakers are easy to connect to the main distribution system. c all types of connections are available (horizontal and vertical terminals, front and mixed connections); c connections are possible with bars of any thickness; c connection to the input power source is possible on the upper or lower terminals of the circuit breakers. Due to their small size, Masterpact circuit breakers can replace most existing circuit breakers.

continuity of service Masterpact circuit breakers are designed with continuity of service in mind. The result is: c total time discrimination on the N1 and H1 circuit breakers and maximum discrimination on H2 circuit breakers; c factory pre-setting of Masterpact circuit breakers which never require any periodic maintenance; c high electrical endurance: 10 000 cycles at 1600 A and 30 cycles at 50 kA, without maintenance; c preventive indications: load-shedding indication switch, long-time threshold overrun alarm, etc.; c easy access to the main contacts fitted with mechanical wear indicators. An optional function on the STR68 control unit is the remote indication of contact wear, thus making possible continuous monitoring of circuit breakers during their service life. ,

036634

Masterpact: presentation

operating safety The insulating casing of Masterpact circuit breakers provides for: c user safety: v double insulation on the front face (class II), v auxiliary circuits in a compartment insulated from the power circuits; c switchboard safety when the circuit breaker is in the open position: v each pole is effectively isolated in its own housing, v limitation of external disturbances. Positive contact indication The position indicator cannot indicate «open» unless the poles are effectively separated by the required distance. The circuit breakers automatically open during racking in and out.

reliability c Masterpact circuit breakers comprise ten times fewer parts than traditional devices. They are easier to produce and more reliable. c the Masterpact circuit-breaker factory is certified ISO 9002; c the design of Masterpact circuit breakers is modular with delayed differentiation (highest possible number of common parts on all models). The result is shorter delivery times and enhanced reliability.

6 BTP207E-1.020-contents

Merlin Gerin

6

21/12/01, 9:38

LV power air circuit breakers and switch-disconnectors

Masterpact 2/ functions and characteristics page generales characteristics circuit breaker selection switch-disconnectors dimensions an weights control unit selection control unit accessories electrical auxiliaries mechanical accessories source changeover systems

0 0 0 0 0 0 0 0 0

7

BTP207E-2.001-content

7

21/12/01, 9:39

Masterpact: functions and characteristics

general characteristics

E29049

conformity with standards

MERLIN GERIN masterpact M32 H2 Ui

1000V

50/60Hz

Ue 380/440V 480/690V Icu 100kA

85kA

Ics 100kA

85kA

Icw 75kA 1s IEC 947-2

Masterpact circuit breakers comply with all the major international standards: c International standard IEC 947-2; c North American standards (please consult us): UL 489, ANSI C37-50, CSA C22-2, NEMA AB1 et SG3; c Japanese standards: JIS 160 and C 8372. They also comply with the following national standards: c France NF C 63-120; c Germany VDE 0660; c United Kingdom BS 4752; c Australia AS ; c Italy CEI. Masterpact circuit breakers comply with the specifications of the marine classification companies (Veritas, Lloyd's Register of Shipping, Det Norske Veritas, etc.).

Standardised characteristics indicated on the rating plate: Ui: rated insulation voltage Ue: rated operational voltage Icu: ultimate breaking capacity, for various values of the rated operational voltage Ue Ics: service breaking capacity Icw: short-time withstand current : suitable for isolation

IEC 947-2 This standard replaces IEC 157-1, applicable since 1973. The circuit breaker selection criteria are unchanged, but the new standard provides the user with a better guarantee concerning quality and performance. Circuit breakers are subjected to tests that are more representative of real operating conditions. IEC 947-2 also clarifies the notion of breaking capacity. c Icu : the ultimate breaking capacity, which must be greater than or equal to the 3-phase short-circuit current at the point of installation of the circuit breaker, a value unlikely to be reached under real conditions; c Ics : the service breaking capacity, generally expressed as a percentage of the ultimate breaking capacity (25, 50, 75 or 100 % of Icu). It corresponds to a shortcircuit current that is more likely to be reached under real conditions. The circuit breaker must continue to operate normally after having interrupted a current equal to Ics several times; c Icw : short-time withstand current for circuit breakers belonging to category B (category B refers to circuit breakers with time discrimination and category A to those without time discrimination). Furthermore, IEC 947-2 takes into account recent technological advances: c suitability for isolation recognised for circuit breakers having passed special electrical and mechanical tests; c industrial earth-fault circuit breakers covered by an appendix; c definition of tests designed to ensure coordination between two circuit breakers.

tropicalisation As standard, Masterpact circuit breakers comply with NF C 63-100 standard level 2 conditions (95 % relative humidity at 45 °C or 80 % at 55 °C, hot and humid climate conditions). They also comply with the following standards: c IEC 68-2-30 damp heat; c IEC 68-2-2 dry heat; c IEC 68-2-11 salt spray; c IEC 68-2-1 low temperatures during storage. Corrosive atmospheres: Special grease or other surface coatings available (please consult us).

pollution degree Masterpact circuit breakers are certified for operation in pollution degree IV environments as defined by IEC standard 947 (industrial environments).

8 BTP207E-2.020-gen. charact..

Merlin Gerin

8

21/12/01, 9:40

positive contact indication

All Masterpact circuit breakers are also disconnectors (suitable for isolation) as specified by IEC 947-2. They bear the corresponding symbol on the front cover:

All Masterpact circuit breakers offer positive contact indication. The toggle position rigorously reflects the position of the main contacts. It can indicate the "OFF" position only if the contacts are effectively open and a suitable distance apart.

E18569

035932RC

maximum dependability

This characteristic considerably increases the dependability of the circuit breaker. The conditions specified by IEC 947-2 for this function are: c positive contact indication; c impulse withstand: 8 kV at sea level; c very low leakage current, checked on new circuit breakers and on circuit breakers subjected to tests representative of the end of service life. Moreover Masterpact circuit breakers have a double-insulation front face (i.e. a class II device) allowing control from the outside.

installation Masterpact circuit breakers may be installed on horizontal metal surfaces or on rails. They are secured by four points accessible at the bottom of the chassis (drawout versions) or on either side of the circuit breaker (fixed versions). A single door cut-out is required for the entire range and provides access to Masterpact controls (see the description on page 2). .

degree of protection E28757

IP 30-5

circuit breaker installed in a cabinet with access to controls through a door cut-out

IP 40-5

circuit breaker installed in a cabinet behind a door with a cut-out fitted with a sealed, transparent cover

IP 54-9

E28763

circuit breaker installed free standing

E28758

(as defined by IEC 529)

9

Merlin Gerin

BTP207E-2.020-gen. charact..

9

21/12/01, 9:40

Masterpact: functions and characteristics

035928

circuit breaker selection

Masterpact circuit breakers number of poles

electrical characteristics as per IEC 947-2 and EN 60947-2 In

40 °C

Ui Uimp Ue

AC 50/60 Hz

ultimate breaking capacity (1) (kA rms)

Icu

AC 50/60 Hz

service breaking capacity short-time withstand current (kA rms)

Ics Icw

(% Icu) AC 50/60 Hz

making capacity (kA peak)

Icm

AC 50/60 Hz

electrodynamic withstand (kA peak) utilisation category suitability for isolation break time closing time endurance (C-O cycles) x 1000

mechanical

with maintenance no maintenance no maintenance

rated current (A) rating of 4th pole (A) rated insulation voltage (V) rated impulse withstand voltage (V) rated operational voltage (V)

type of circuit breaker Masterpact M16 H1

electrical

motor control (AC3-947-4) (2)

220/415 V 440 V 500/690 V 0.5 s 1s 3s 220/415 V 440 V 500/690 V

440 V - In 690 V - In 690 V

electrical characteristics as per standard Nema AB1 breaking capacity (kA)

480 V 600 V

protection (see following pages) sensor ratings (A) (see page 12) control unit protection type

instantaneous distribution selective universal

STR 18 M STR 28 D STR 38 S STR 58 U STR 68 U

installation and connections connection version

drawout fixed

indication and measurement auxiliaries auxiliary switches electronic trip unit related functions

control auxiliaries auxiliary releases (MN, MNR, MX, XF) motor mechanism (MCH) operation counter (CDM)

installation and connection accessories locking by padlock or keylock/mismatch protection

(1) Defined for a power factor of 0.25 if 20 < kA rms ≤ 50 or 0.20 of kA rms > 50. (2) Closing at 6 x Ie and opening at 0.17 x Un. (3) For control unit STR 68 U, the minimum rating In is 400 A.

safety shutters (VO) interphase barriers (EIP) partitioning fixture (AC) arc-chute cover (CC) terminal-block cover (CB) door frame (CDP) transparent cover (CCP) Merlin Gerin

6 BTP207E-2.060-M08...16

6

21/12/01, 9:41

M08

M10

M12

M16

3, 4

3, 4

3, 4

3, 4

800 800 1000 8000 690

1000 1000 1000 8000 690

1250 1250 1000 8000 690

1600 1600 1000 8000 690

N1

N1

H1

H2

L1

N1

H1

H2

L1

40 65 100 130 40 65 100 130 40 65 100 110 40 65 100 110 40 65 85 65 40 65 85 65 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 40 65 65 12 40 65 65 12 30 50 50 12 30 50 50 12 22 32 32 12 22 32 32 12 84 143 220 286 84 143 220 286 84 143 220 242 84 143 220 242 84 143 187 143 84 143 187 143 84 143 143 24 84 143 143 24 B B B B B B B B c c 25 to 30 ms without intentional time delay and 9 ms for type L1 70 ms 20 20 20 20 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 3 10 10 10 2.7 10 10 10 3 10 10 10 2.7 10 10 10 10 10 10 -

H1

40 40 40 100 % 40 30 22 84 84 84 84 B c

65 65 65 100 % 65 50 32 143 143 143 143 B

100 100 85 100 % 65 50 32 220 220 187 143 B

130 110 65 100 % 12 12 12 286 242 143 24 B

40 40 40 100 % 40 40 22 84 84 84 84 B c

65 65 65 100 % 65 50 32 143 143 143 143 B

100 100 85 100 % 65 50 32 220 220 187 143 B

130 110 65 100 % 17 17 12 286 242 143 34 B

20 10 10 10 10

20 10 10 10 10

20 10 10 10 10

15 10 2.5 2.5 -

20 10 10 10 10

20 10 10 10 10

20 10 10 10 10

15 10 2.2 2.2 -

40 40

-

40 40

65 65

100 65

-

40 40

65 65

100 65

-

c c c

200 to 1250 (3) c c c c c c c c c c

c c c

200 to 1600 (3) c c c c c c c c c c

c c c c c

c c c

65 65

200 to 800 (3) c c c c c c c c c c

H2

100 65

c c c c c

L1

N1

H1

-

40 40

65 65

c c c

200 to 1000 (3) c c c c c c c c c c

H2

100 65

c c c c c

L1

c c c c c

front and rear connections c c

c c

c c

c c

c c

c c

c c

c c

c c c

c c c

c c c

c c c

c

c

c

c

c c c c c c c

c c c c c c c

c c c c c c c

c c c c c c c 7

Merlin Gerin

BTP207E-2.060-M08...16

7

21/12/01, 9:41

Masterpact: functions and characteristics

036635

circuit breaker selection (cont.)

Masterpact circuit breakers number of poles

electrical characteristics as per IEC 947-2 and EN 60947-2 In

40 °C

Ui Uimp Ue

AC 50/60 Hz

ultimate breaking capacity (1) (kA rms)

Icu

AC 50/60 Hz

service breaking capacity short-time withstand current (kA rms)

Ics Icw

(% Icu) AC 50/60 Hz

making capacity (kA peak)

Icm

AC 50/60 Hz

electrodynamic withstand (kA peak) utilisation category suitability for isolation break time closing time endurance (C-O cycles) x 1000

mechanical

with maintenance no maintenance no maintenance

rated current (A) rating of 4th pole (A) rated insulation voltage (V) rated impulse withstand voltage (V) rated operational voltage (V)

type of circuit breaker Masterpact M50 H1

electrical

motor control (AC3-947-4) (2)

220/415 V 440 V 500/690 V 0.5 s 1s 3s 220/415 V 440 V 500/690 V

440 V - In 690 V - In 690 V

electrical characteristics as per standard Nema AB1 breaking capacity (kA)

480 V 600 V

protection (see following pages) sensor ratings (A) (see page 12) control unit protection type

instantaneous distribution selective universal

STR 18 M STR 28 D STR 38 S STR 58 U STR 68 U

installation and connections connection version

drawout fixed

indication and measurement auxiliaries auxiliary switches electronic trip unit related functions

control auxiliaries auxiliary releases (MN, MNR, MX, XF) motor mechanism (MCH) operation counter (CDM)

installation and connection accessories locking by padlock or keylock/mismatch protection

(1) Defined for a power factor of 0.25 if 20 < kA rms ≤ 50 or 0.20 of kA rms > 50. (2) Closing at 6 x Ie and opening at 0.17 x Un. (3) For control unit STR 68 U, the minimum rating In is 400 A. (4) 83% if Ue i 440 V. (5) Consult us for full rated neutral.

safety shutters (VO) interphase barriers (EIP) partitioning fixture (AC) arc-chute cover (CC) terminal-block cover (CB) door frame (CDP) transparent cover (CCP) Merlin Gerin

8 BTP207E-2.070-M20...63

8

21/12/01, 9:42

M20

M25

M32

M40

M50

M63

3, 4

3, 4

3, 4

3, 4

3, 4

3, 4

2000 2000 1000 8000 690

2500 2500 1000 8000 690

3200 3200 1000 8000 690

4000 4000 1000 8000 690

5000 2500 (5) 1000 8000 690

6300

N1

H1

H2

H1

H2

H1

H2

H1

H2

55 75 100 130 55 75 100 130 75 55 75 100 110 55 75 100 110 75 55 75 85 65 55 75 85 65 75 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 55 75 75 17 55 75 75 17 75 55 75 75 17 55 75 75 17 75 50 57 57 17 50 75 75 17 75 121 165 220 286 121 165 220 286 165 121 165 220 242 121 165 220 242 165 121 165 187 143 121 165 187 143 165 121 165 165 34 121 165 165 34 165 B B B B B B B B B c c c 25 to 30 ms without intentional time delay and 9 ms for type L1 70 ms 15 15 15 15 15 15 15 15 15 10 10 10 10 10 10 10 10 10 9 9 9 2 8 8 8 1.8 4 7 7 7 2 6 6 6 1.8 2.6 7 7 7 6 6 6 2.6

100 100 85 100 % 75 75 75 220 220 187 165 B

75 75 75 100 % 75 75 75 165 165 165 165 B c

100 100 85 100 % 75 75 75 220 220 187 165 B

100 100 85 100 % 100 100 100 220 220 187 220 B c

150 150 85 100 % (4) 100 100 100 330 330 187 220 B

100 100 85 100 % 100 100 100 220 220 187 220 B c

150 150 85 100 % (4) 100 100 100 330 330 187 220 B

15 10 4 2.6 2.6

80 ms 10 5 3 2.5 2.5

10 5 3 2.5 2.5

10 5 3 2.5 2.5

10 5 3 2.5 2.5

10 5 2 1.5 1.5

10 5 2 1.5 1.5

55 55

100 75

75 75

100 75

100 100

125 100

100 100

150 100

75 75

H2

100 75

200 to 2000 (3) c c c c c c c c c c c c c c c

L1

N1

H1

75 75

H2

-

55 55

100 75

c c c

300 to 2500 (3) c c c c c c c c c c c c c c c

L1

H1

3200 1000 8000 690

-

75 75

c c c

600 to 3200 c c c c c c c c c c

2000 to 4000 c c c c c c c c c c

2000 to 5000 c c c c c c c c c c

2000 to 6300 c c c c c c c c c c

front and rear connections c c

c c

c c

rear connections c c

c c (3P only)

c

c c

c c

c c

c c

c c

c c

c c c

c c c

c c c

c c c

c c c

c c c

c

c

c

c

c

c

c c c c c c c

c c c c c c c

c c c c c c c

c c (3P only) c c c c c

c

c

c c c c c

c c c c c 9

Merlin Gerin

BTP207E-2.070-M20...63

9

21/12/01, 9:42

Masterpact: functions and characteristics

052380

circuit breaker selection (cont.) Masterpact 1000 V AC Masterpact 1000 V AC circuit breakers number of poles

electrical characteristics as per IEC 947-2 and EN 60947-2 In

40 °C

Ui Uimp Ue

AC 50/60 Hz

ultimate breaking capacity (1) (kA rms)

Icu

AC 50/60 Hz

service breaking capacity short-time withstand current (kA rms)

Ics Icw

(% Icu) AC 50/60 Hz

making capacity (kA peak)

Icm

AC 50/60 Hz

electrodynamic withstand (kA peak) utilisation category suitability for isolation break time closing time endurance (C-O cycles) x 1000

mechanical

with maintenance no maintenance no maintenance

rated current (A) rating of 4th pole (A) rated insulation voltage (V) rated impulse withstand voltage (V) rated operational voltage (V)

type of circuit breaker Masterpact M20 H1 1000 V

electrical

motor control (AC3-947-4) (2)

220/415 V 440 V 500/690 V 1000 V 0.5 s 1s 3s 220/415 V 440 V 500/690 V 1000 V

440 V - In 690 V - In 690 V

protection (see following pages) sensor ratings (A) (see page 12) control unit protection type

instantaneous distribution selective universal

STR 18 M STR 28 D STR 38 S STR 58 U STR 68 U

installation and connections connection version

drawout fixed

indication and measurement auxiliaries auxiliary switches electronic trip unit related functions

control auxiliaries auxiliary releases (MN, MNR, MX, XF) motor mechanism (MCH) operation counter (CDM)

installation and connection accessories

(1) Defined for a power factor of 0.25 if 20 < kA rms ≤ 50 or 0.20 of kA rms > 50. (2) Closing at 6 x Ie and opening at 0.17 x Un. (3) For control unit STR 68 U, the minimum rating In is 400 A.

locking by padlock or keylock/mismatch protection safety shutters (VO) interphase barriers (EIP) partitioning fixture (AC) arc-chute cover (CC) (as standard on the 1000 V version) terminal-block cover (CB) door frame (CDP) transparent cover (CCP)

Merlin Gerin

10 BTP207E-2.080-M08...32

10

21/12/01, 9:42

M08

M10

M12

M16

M20

M25

M32

3, 4

3, 4

3, 4

3, 4

3, 4

3, 4

3, 4

800 800 1000 8000 1000

1000 1000 1000 8000 1000

1250 1250 1000 8000 1000

1600 1600 1000 8000 1000

2000 2000 1000 8000 1000

2500 2500 1000 8000 1000

3200 3200 1000 8000 1000

H1

H1

H1

H1

H1

H1

H1

65 65 65 65 65 65 65 65 65 65 65 65 45 45 45 45 100 % 100 % 100 % 100 % 45 45 45 45 45 45 45 45 32 32 32 32 95 95 95 95 143 143 143 143 143 143 143 143 143 143 143 143 143 143 143 143 B B B B c c c c 25 to 30 ms without intentional time delay and 9 ms for type L1 70 ms 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

75 75 75 45 100 % 45 45 45 95 165 165 165 165 B c

75 75 75 45 100 % 45 45 45 95 165 165 165 165 B c

75 75 75 45 100 % 45 45 45 95 165 165 165 165 B c

15 10 9 7 7

15 10 8 6 6

15 10 4 2.6 2.6

200 to 800 (3) c c c c c

200 to 2000 (3) c c c c c

300 to 2500 (3) c c c c c

600 to 3200 c c c c c

rear connections only / supply by upstream terminals mandatory c c c c

c

c

c

c c

c c

c c

c c

c c

c c

c c

c c c

c c c

c c c

c c c

c c c

c c c

c c c

c c c c c c c c

c c c c c c c c

c c c c c c c c

c c c c c c c c

c c c c c c c c

c c c c c c c c

c c c c c c c c

200 to 1000 (3) c c c c c

200 to 1250 (3) c c c c c

200 to 1600 (3) c c c c c

11

Merlin Gerin

BTP207E-2.080-M08...32

11

21/12/01, 9:42

Masterpact: functions and characteristics

052384

switch-disconnectors

Masterpact switch-disconnectors number of poles

electrical characteristics as per IEC 947-2 and EN 60947-2 rated current (A) rating of 4th pole (A) rated insulation voltage (V) rated impulse withstand voltage (V) rated operational voltage (V)

In

40 °C

Ui Uimp Ue

AC 50/60 Hz

type of switch-disconnector short-time withstand current (kA rms)

Icw

AC 50/60 Hz

making capacity (kA peak)

Icm

AC 50/60 Hz

electrodynamic withstand (kA peak) suitability for isolation closing time endurance (C-O cycles) x 1000

mechanical

with maintenance no maintenance no maintenance

Masterpact M10 NI

electrical

motor control (AC3-947-4) (1)

0.5 s 1s 3s 440 V 500/690 V

440 V - In 690 V - In 690 V

protection STR 08 dummy unit (no protection) STR 18I (protection against short-circuits when closing)

installation and connections connection version

drawout fixed

indication and measurement auxiliaries auxiliary switches

control auxiliaries auxiliary releases (MN, MNR, MX, XF) motor mechanism (MCH) operation counter (CDM)

installation and connection accessories locking by padlock or keylock/mismatch protection safety shutters (VO) interphase barriers (EIP) partitioning fixture (AC) arc-chute cover (CC) terminal-block cover (CB) door frame (CDP) transparent cover (CCP)

(1) Closing at 6 x Ie and opening at 0.17 x Un. Merlin Gerin

12 BTP207E-2.082-inter M08

12

21/12/01, 9:42

M08

M10

M12

M16

3, 4

3, 4

3, 4

3, 4

800 800 1000 8000 690

1000 1000 1000 8000 690

1250 1250 1000 8000 690

1600 1600 1000 8000 690

NI

HI

HF

NI

HI

HF

NI

HI

HF

NI

HI

HF

40 30 22 84 84 84 c 70 ms 20 10 10 10 10

65 50 32 105 105 143

65 50 32 143 143 143

40 30 22 84 84 84 c

65 50 32 105 105 143

65 50 32 143 143 143

40 30 22 84 84 84 c

65 50 32 105 105 143

65 50 32 143 143 143

40 30 22 84 84 84 c

65 50 32 105 105 143

65 50 32 143 143 143

20 10 10 10 10

20 10 10 10 10

20 10 10 10 10

20 10 10 10 10

20 10 10 10 10

20 10 10 10 10

20 10 10 10 10

20 10 10 10 10

20 10 10 10 10

20 10 10 10 10

20 10 10 10 10

c

c

c

c

c

c

c

c

c

c

c

c

front and rear connections c c

c c

c c

c c

c

c

c

c

c c c

c c c

c c c

c c c

c c c c c c c c

c c c c c c c c

c c c c c c c c

c c c c c c c c

13

Merlin Gerin

BTP207E-2.082-inter M08

13

21/12/01, 9:42

Masterpact: functions and characteristics

052388

switch-disconnectors (cont.)

Masterpact switch-disconnectors number of poles

electrical characteristics as per IEC 947-2 and EN 60947-2 rated current (A) rating of 4th pole (A) rated insulation voltage (V) rated impulse withstand voltage (V) rated operational voltage (V)

In

40 °C

Ui Uimp Ue

AC 50/60 Hz

type of switch-disconnector

Masterpact M50 HI

short-time withstand current (kA rms)

Icw

AC 50/60 Hz

making capacity (kA peak)

Icm

AC 50/60 Hz

electrodynamic withstand (kA peak) suitability for isolation closing time endurance (C-O cycles) x 1000

mechanical

with maintenance no maintenance no maintenance

electrical

motor control (AC3-947-4) (1)

0.5 s 1s 3s 440 V 500/690 V

440 V - In 690 V - In 690 V

protection STR 08 dummy unit (no protection) STR 18 I (protection against short-circuits when closing)

installation and connections connection version

drawout fixed

indication and measurement auxiliaries auxiliary switches

control auxiliaries auxiliary releases (MN, MNR, MX, XF) motor mechanism (MCH) operation counter (CDM)

installation and connection accessories locking by padlock or keylock/mismatch protection safety shutters (VO) interphase barriers (EIP) partitioning fixture (AC) arc-chute cover (CC) terminal-block cover (CB) door frame (CDP) transparent cover (CCP)

(1) Closing at 6 x Ie and opening at 0.17 x Un. Merlin Gerin

12 BTP207E-2.084-inter M20

12

21/12/01, 9:43

M20

M25

M32

M40

M50

M63

3, 4

3, 4

3, 4

3, 4

3, 4

3, 4

2000 2000 1000 8000 690

2500 2500 1000 8000 690

3200 3200 1000 8000 690

4000 4000 1000 8000 690

5000 2500 1000 8000 690

6300 3200 1000 8000 690

NI

HI

HF

NI

HI

HF

HI

HF

HI

HF

HI

HF

HI

HF

55 55 50 84 84 121 c 70 ms 15 10 9 7 7

75 75 57 105 105 165

75 75 57 165 165 165

55 55 50 84 84 121 c

75 75 75 105 105 165

75 75 75 165 165 165

75 75 75 105 105 165 c

75 75 75 165 165 165

75 75 75 165 165 165

100 100 100 187 187 220 c

100 100 100 220 220 220

100 100 100 187 187 220 c

100 100 100 220 220 220

15 10 9 7 7

15 10 9 7 7

15 10 8 6 6

15 10 8 6 6

15 10 8 6 6

15 10 4 2.6 2.6

15 10 4 2.6 2.6

75 75 75 105 105 165 c 80 ms 10 5 3 2.5 2.5

10 5 3 2.5 2.5

10 5 3 2.5 2.5

10 5 3 2.5 2.5

10 5 2 1.5 1.5

10 5 2 1.5 1.5

c

c

c

c

c

c c

c c

c c

c c

c

front and rear connections c c

c c

c c

rear connections c c

c c (3P only)

c

c

c

c

c

c

c

c c c

c c c

c c c

c c c

c c c

c c c

c c c c c c c c

c c c c c c c c

c c c c c c c c

c c c (3P only) c c c c c

c c

c c

c c c c c

c c c c c

13

Merlin Gerin

BTP207E-2.084-inter M20

13

21/12/01, 9:43

Masterpact: functions and characteristics

dimensions and weights

Masterpact circuit breakers and switch-disconnectors type dimensions and weights dimensions W x H x D (mm)

drawout

3P 4P 3P 4P 3P 4P 3P 4P

fixed maximum weight (kg)

drawout fixed

Masterpact circuit breakers and switch-disconnectors type dimensions and weights dimensions W x H x D (mm)

drawout

3P 4P 3P 4P 3P 4P 3P 4P

fixed maximum weight (kg)

drawout fixed

Masterpact 1000 V circuit breakers type dimensions and weights dimensions W x H x D (mm)

drawout

maximum weight (kg)

drawout

3P 4P 3P 4P

sensor selection In (A) Ir threshold settings (A) In (A) Ir threshold settings (A)

200 80 to 200 1250 500 to 1250

250 100 to 250 1600 640 to 1600

320 125 to 320 2000 800 to 2000

400 160 to 400 2500 1000 to 2500

500 200 to 500 3000 1200 to 3000

600 240 to 600 3200 1280 to 3200

630 250 to 630 4000 1600 to 4000

800 320 to 800 5000 2000 to 5000

1000 400 to 1000 6000 2400 to 6000

1200 480 to 1200 6300 2500 to 6300

The table above indicates: c all the available sensor ratings In; c the limits of the long time Ir settings.

Merlin Gerin

12 BTP207E-2.090-M08...63

12

21/12/01, 9:47

M08

M10

M12

M16

M20

M25

M32

N1/H1/H2/L1 NI/HI/HF

N1/H1/H2/L1 NI/HI/HF

N1/H1/H2/L1 NI/HI/HF

N1/H1/H2 L1 NI/HI/HF

N1/H1/H2 L1 NI/HI/HF

N1/H1/H2 L1 NI/HI/HF

H1/H2 HI/HF

435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 65 80 43 54

435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 65 80 43 54

435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 65 80 43 54

435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 69 82 85 102 46 55 58 69

435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 82 130 102 150 55 80 69 90

435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 82 130 102 150 55 80 69 90

435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 130 150 80 90

M40

M50

M63

H1/H2 HI/HF

H1/H2 HI/HF

H1/H2 HI/HF

550 x 439 x 367 815 x 484 x 367 537 x 356 x 290 801 x 356 x 290 150 200 90 110

815 x 484 x 367 1045 x 484 x 367 802 x 356 x 290

1045 x 484 x 367 1045 x 484 x 367

215 230 110

245 265

M08

M10

M12

M16

M20

M25

M32

H1

H1

H1

H1

H1

H1

H1

435 x 439 x 367 550 x 439 x 367 65 80

435 x 439 x 367 550 x 439 x 367 65 80

435 x 439 x 367 550 x 439 x 367 65 80

435 x 439 x 367 550 x 439 x 367 69 85

435 x 439 x 367 550 x 439 x 367 82 102

435 x 439 x 367 550 x 439 x 367 82 102

435 x 439 x 367 550 x 439 x 367 130 150

13

Merlin Gerin

BTP207E-2.090-M08...63

13

21/12/01, 9:47

Masterpact: functions and characteristics

control unit selection

current settings (A)

Masterpact M08 to M63 circuit breakers are equipped with microprocessor-based electronic control units.

80

160

400

E31218

All the protection functions are powered by the AC system and no auxiliary power supply is required. The same is true for most of the complementary functions.

1250

1600

2000

2500

3200

4000

5000

6300

STR 18 M STR 28 D STR 38 S

Each control unit of the Masterpact range corresponds to a certain type of application (instantaneous, distribution, selective, universal). All the STR control units measure the true rms value of the current and are therefore not affected by harmonics that may be present on the system.

STR 58 U STR 68 U

instantaneous protection distribution protection selective protection universal protection

protection

push to reset

1

E31219

E30703

STR 18 M

t

Key:

3

1

reset button: pops out when the circuit breaker has tripped on a fault and must be pressed (reset) before the circuit breaker can be closed again.

2

maximum protection rating.

3

instantaneous pick-up.

4

test connector.

5

holes for sealable cover plate screws.

STR 18 M

2 5 0

I

I

other functions c fault indication. I 12 14 8

19 2

+

3

22 max

4 xIn



4

test

5

Merlin Gerin

14 BTP207E-2.110-unité cont.

14

21/12/01, 9:47

protection 1

push to reset

E31220

E30704

STR 28 D

t

Key:

6

2 I1

I2

I

I3

3 STR 28 D

4

50%

20%

90

8

Ir 0.8

%Ir 105

7

11 Io 0.63

1

0.5

.88

.9 .92 .95

.85

.98 .8

xIn

xIo

0

6

1

4 5 6 2 8 1.5 xIr 10 3

c c c c

7

Ir :

Ir

2

ammeter digital display.

3

bar graph indicating load level (% Ir).

4

maximum protection rating.

Im :

Ir

I

I

8

overcurrent indicator LED.

9

noted settings.

10 test connector. 11 holes for sealable cover plate screws.

other functions

Im

t

reset button: pops out when the circuit breaker has tripped on a fault and must be pressed (reset) before the circuit breaker can be closed again.

5-6 long-time current setting as a function of: Io x Ir x In. 7 instantaneous pick-up.

90%

5

1

9

fault indication; indication of LT overrun; ammeter; self-monitoring (internal overheating).

Im

i +



10

test

11

protection

E33950

E31221

STR 38 S

t

Key: I2t ON

1

push to reset

1

reset button: pops out when the circuit breaker has tripped on a fault and must be pressed (reset) before the circuit breaker can be closed again.

2

ammeter digital display.

3

bar graph indicating load level (% Ir).

4

maximum protection rating.

5

overcurrent indicator LED.

7 I2t OFF

2 I1

I2

I

I3

90%

12

3 50%

4

20%

16 Ir 0.8

%Ir 1

0.5

.88

.9 .92 .95

.85

.98 .8

xIn

6

Im

8

tm

4 5

2 1.5

6

.3

8 10

.2

xIr t

0

.2

.1 0 .1 on I2t off

9 11

Im :

Ih fault th

14 16

max. off xIn th : Ih T th 500 600 .4 .4 Im fault 400 tm 800 .3 .3 I 320 1000 .2 .2 .1 250 1200 .1 i A on I2t off overcurrent +





+

12 13

I

c c c c c

short-time delay.

10 noted settings. 11 instantaneous pick-up. 12 earth fault pick-up.

fault indication; indication of LT overrun; ammeter; self-monitoring (internal overheating); indication of type of fault (F).

13 earth fault delay. 14 LEDs indicating tripping on long-time, short-time or earth fault. 15 test connector. 16 holes for sealable cover plate screws. 17 battery supplying backup power for fault indication. 18 fault indication reset and/or battery test.

15

test

I

.4 .3

I

Ir :

Im

other functions

Ir fault tr

Ir

7

1 xIo

3

10

9

11 Io 0.63

90 105

6-7 long-time current setting as a function of: Io x Ir x In. 8 short-time pick-up.

9

13

STR 38 S

5

8

ground

19 re-indication of last fault.

F test

17

19 18 15

Merlin Gerin

BTP207E-2.110-unité cont.

15

21/12/01, 9:47

Masterpact: functions and characteristics

control unit selection (cont.)

protection E31222

E30705

STR 58 U V

1 push to reset

reset V

I+T L+I L+I+T L+T T L off I

Key:

t I2t ON

2

1

8 I2t OFF

9 3 I1

I2

I

I3

10

90%

14

4 STR 58 U

11

15

5

50%

21 20%

6

Ir

Io 0.63

120 240 .9 .92 .95 60 480 .98 30 1 15 .8 xIn at 1.5Ir xIo Max. Im tm 4 5 .4 .3 τ tr 3 .3 6 .2 2 .2 norm 8 .1 0 1.5 10 .1 on I2t off xIr I 12 14 Ir : 8 19 Ir fault 4 22 Im : 2 off tr xIn th : Ih 1200A Max th T Ih 500 600 .4 .4 fault Im fault 400 800 .3 .3 tm th 320 1000 .2 .2 I .1 250 1200 .1 i A on I2t off overcurrent Ic1 Ic2 R + – .9 .93 .8 .85 test .86 .95 .7 .9 .85 – + .98 .6 .95 ground 1 8 1 .5 xIr xIr

90

0.8

%Ir

105

7 12 10

t

16

19 21 24 F

.88

.85

1

0.5

13

8

tr

test

0

9

Ir

Im

I

I

other functions c c c c c c

fault indication; indication of LT overrun; ammeter; self-monitoring (internal overheating); fault type indication (F); segregated alarm switch for selected fault type (V); c zone selective interlocking (Z); c load monitoring (R); c communication (COM).

11 13 14 15 17 18 20

23

22

protection 1

reset

E31223

E33949

STR 68 U

I2t ON

t

Key: 1

V N

1

2

3

LT setting (Ir)

2

Hz

I2t OFF

Cos ϕ

LT time delay (tr)

kW

2

MWh

ST pick-up (Im) ST time delay (tm)

STR 68 U

earth fault pick-up (Ih) 685812 A KA

3

S test

1

2

3

earth fault time delay (th)

0

instantaneous pick-up (I)

Ir

Im

I

max

other functions fault

s

4

tr

tm th Ih

Ir

Im

I

2

11

5

1

6

load monitoring

10 8

A

% maintenance

– trip

reset button: pops out when the circuit breaker has tripped on a fault and must be pressed (reset) before the circuit breaker can be closed again. 2 selection of fault type for segregated alarm: Ir and/or Im and/or Ih L: long-time fault (Ir) I: short-time fault (Im/l) T: earth fault (Ih) 3 ammeter digital display. 4 bar graph indicating load level (% Ir). 5 maximum protection rating. 6 overcurrent indicator LED. 7-8 long-time current setting as a function of: Io x Ir x In. 9 long-time trip delay 10 short-time pick-up. 11 short-time delay. 12 adjustment of thermal memory after tripping. 13 instantaneous pick-up. 14 earth fault pick-up. 15 earth fault delay. 16 noted settings. 17-18 load monitoring settings. 19 test connector. 20 battery supplying backup power for fault indication. 21 holes for sealable cover plate screws. 22 fault indication reset and/or battery test. 23 re-indication of last fault. 24 LEDs indicating tripping on long-time, short-time or earth fault.

no trip test

MEM

c c c c c c c

fault indications and memorisation; maintenance indicator; ammeter; integrated test; power measurement; load monitoring (R); self-monitoring (internal overheating, malfunction of the microprocessor); c zone selective interlocking for earth faults.

I

reset button: pops out when the circuit breaker has tripped on a fault and must be pressed (reset) before the circuit breaker can be closed again. 2 selection of displayed value (voltage, power, energy, power factor, frequency). 3 display of current or interrupted current (when flashing). 4 local fault indication and indication reset. 5 selection and indication of protection parameter to be set. 6 selection and indication of load monitoring parameters. 7 adjustment and saving of parameter settings. 8 holes for sealable cover plate screws. 9 test connector. 10 test. 11 maintenance indicator.

7

+ 24 V DC

9

adjustments

8 Merlin Gerin

16 BTP207E-2.120-unité cont.

16

21/12/01, 9:50

options for STR control units

"earth fault" protection (T or W)

E31225

zone selective interlocking (Z)

A number of circuit breakers are interconnected one after another by a pilotwire. In the event of a short-time or earth fault, the control unit applies the set time delay only if it receives a signal from a downstream circuit breaker. If not, it trips instantaneously (tripping time as 0.1 shorttime setting). In this way, the fault is cleared rapidly by the nearest circuit breaker. The thermal stresses in the installation are minimised while maintaining time discrimination throughout the entire

installation. Opto-electronic outputs The use of opto-transistors ensures total isolation between the internal circuits of the control unit and the circuits wired by the user.

t

This earth fault protection is designed to protect the installation against the risks of fire due to high earth faults (not to be confused with schemes designed for the protection of persons against electrical shock). Two types of earth protection are available for Masterpact: c residual current type (T): the control unit calculates the vector sum of the phase and neutral (if distributed) currents; c source ground return type (W): the control unit acts directly on the signal received from an external current transformer installed on the source earthing circuit.

I2t ON

I2t OFF

Ih Th

0

I

load monitoring (R)

E26037

earth fault curves for the STR 58

Remote indication of threshold overrun for load-shedding or load-reconnection purposes.

t

Ic2 Ic1

0

I

load monitoring curves for the STR 58

communication: STR 58 U transmission: STR 68 U

Transmission of the control unit settings, circuit breaker position and current, voltage and power measurements.

Other information that can be transmitted includes the value of the interrupted current, the state of the thermal memory and the maintenance indications

indication and measurement

c ammeter (I): a digital display continuously indicates the current of the phase with the greatest load (Imax). By pressing a scroll button, it is also possible to display successively the readings of I1, I2, I3, Ineutral and Ih. In addition, three bargraphs provide an immediate visual indication of the load on each of the three phases.

c indication of type of fault (F); c segregated alarm switch for selected fault type (V), wired in parallel with the opening button (MX), it disables circuit breaker closing for the selected type of fault.

17

Merlin Gerin

BTP207E-2.120-unité cont.

17

21/12/01, 9:50

Masterpact: functions and characteristics

048449

control unit selection (cont.) STR 18 M to STR 58 U control unit type of circuit breaker

basic protection long time protection LT current setting (Ir) as a function of Io and Ir settings tripping between 1.05 and 1.20 x Ir time delay (tr) accuracy: + 0 - 20 %

short-time protection ST pick-up (Im) adjustable by Im setting time delay (tm)

Io = In x ... Ir = Io x ... tr at 1.5 Ir (s) tr at 6 Ir (s) tr at 7.2 Ir (s) Im = Ir x ... tm setting with I2t OFF tm setting with I2t ON max. overcurrent time before tripping (ms) max. break time (ms)

instantaneous protection I pick-up setting setting range accuracy OFF switch on front face

STR 58 U

basic functions fault indication for tripping on a fault for LT setting overrun

self-monitoring

indicator button on front face fault trip alarm contact (SDE) LED (lights up at 0.9 Ir and flashes at 1.05 Ir) LT overrun alarm contact (optional) self-powered internal overheating

optional functions

(1) Plus the uncertainty of the built-in transformers: ± 3 %. (2) Max = In x ... 630 A 800 - 1000 A 1200 - 1600 A 2000 A 2500 A 3000 - 3200 A 4000 - 6300 A

N1/H1 22 22 22 17 12 10 8

H2 28 28 24 20 14 12 10

L1 14 10 8 6 6 – –

(3) Continuous display for the phase with the greatest load. (4) 0.2 x In to 1200 A without external power supply or 0.1 x In with external power supply. (5) Accuracy with respect to the long time LT protection.

ammeter (I) display between 0.2 and 1.20 In current readings with an accuracy of ± 1.5 % (1) (3) bargraph indication of current levels with a resolution of 10 % self-powered earth fault protection: residual current (T) or source ground return (W) type on request pick-up adjustable by Ih setting Ih = In x ... time delay (th) th setting with I2t ON and I2t OFF max. overcurrent time before tripping (ms) max. break time (ms) indication of type of fault (F) (LT - CT/Inst. - Earth) by LEDs on front face power supply with battery module with external power supply by AD module segregated alarm switch for selected fault type (V) (LT - CT/Inst. - Earth) output via relay contact power supply by AD module zone selective interlocking (Z) by opto-electronic contact on ST and earth (T/W) fault load monitoring (R) adjustment of load limit thresholds by Ic1 and Ic2 settings Ic1 = Ir x ... / Ic2 = Ir x ... time delay tr1 at 1.5 Ic1 time delay tr2 at 1.5 Ic2 output via opto-electronic contact 0.1 A / 240 V time delay for load reconnection communication (COM) 2 outputs for data transmission to Dialpact module transmitted values all control unit settings alarms: Ir warning, fault type, self-monitoring load monitoring thresholds current values I1, I2, I3, IN power supply by AD module

(6) Resettable maximum ammeter. Merlin Gerin

18 BTP207E-2.130-STR18…58

18

21/12/01, 9:51

STR 18 M

STR 28 D

STR 38 S

STR 58 U

N1, H1, H2

N1, H1, H2

N1, H1, H2, L1

N1, H1, H2, L1

c 0.5 to 1 (4 settings) 0.8 to 1 (8 settings) fixed 120 7.5 5.2

c 0.5 to 1 (4 settings) 0.8 to 1 (8 settings) fixed 120 7.5 5.2 c 1.5 to 10 ± 15 % 0 0.1 0.2 0.3 0.1 0.2 0.3 0 80 140 230 80 140 230 350 c I = In x ... fixed at high set (Max) (2) ± 20 % on types N1 and H1

c 0.5 to 1 (4 settings) 0.8 to 1 (8 settings) adjustable 15 30 60 120 0.94 1.88 3.75 7.50 0.65 1.30 2.60 5.20 c 1.5 to 10 ± 15 % 0 0.1 0.2 0.3 0.1 0.2 0.3 0 80 140 230 80 140 230 350 c I = In x ... 2 x In to Max (2) ± 15 % on types N1 and H1

0.4 350 500

240 15 10

480 30 21

0.4 350 500

c Im = In x ... 2 x In to Max (2) ± 15 % on types N1 and H1

c Im = Ir x ... 1.5 to 10 x Ir ± 15 %

c c

c c c c c c

c c c c c c

c c c c c c

c I1, I2, I3, IN, Imax (6) I1, I2, I3 c

c I1, I2, I3, IN, Ih, Imax (6) I1, I2, I3 c c 0.1 at 1 (max 1200 A) (4) ± 15 % 0.1 0.2 0.3 0.4 60 140 230 350 140 230 350 500 c c c

c I1, I2, I3, IN, Ih, Imax (6) I1, I2, I3 c c 0.1 at 1 (max 1200 A) (4) ± 15 % 0.1 0.2 0.3 0.4 60 140 230 350 140 230 350 500 c c c c c c 0.8 to 1 (8 settings) ± 1 % (5) 0.5 x tr 0.25 x tr c fixed at 10 s c c c c c c 19

Merlin Gerin

BTP207E-2.130-STR18…58

19

21/12/01, 9:51

Masterpact: functions and characteristics

036630

control unit selection (cont.) STR 68 U presentation The STR 68 U control unit offers measurement, supervision and energy management functions. Microprocessor technology, liquid crystal display and function keys ensure high accuracy and easy adjustment. The standard STR 68 U control unit provides the following: c universal protection; c ammeter function; c indication of fault type; c values of interrupted currents; c maintenance indicator; c integrated test. The following options can be added: c power measurement module (P); c "earth fault" protection module; c control and indication modules (M) with or without transmission to a supervisor. Certain M modules can provide load monitoring or zone selective interlocking for earth fault protection.

protection

The STR 68 control unit provides: c overload protection, with long time protection LT including: v adjustable time delay and thermal memory possibility; c short-circuit protection: v delayed, with short time function ST, for which the I2t curve can be disabled by the user, v instantaneous, with the INST function that can be disabled by the user;

basic functions

c ammeter; c maintenance indicator; c fault indications and values of the interrupted currents; c self-monitoring: in the event of overheating of the control unit or a malfunction of the microprocessor, an alarm signal is transmitted. Unless the "service continuity" option was ordered, the circuit breaker will trip ; c test.

c "earth" protection with time discrimination or zone selective interlocking. The protection is of the residual current type (or source ground return type on request).

Merlin Gerin

20 BTP207E-2.140-unité cont.

20

21/12/01, 9:51

optional functions

c power measurement (P); c indication and control (M) Thirty-one different modules offer various combinations of functions including: v load monitoring, v trip indication, v self-monitoring, v zone selective interlocking for "earth fault" protection, v transmission of data to a supervisor (modules M17 to M31 only). Each STR 68 U control unit can be equipped with only one M module. For the function offered by each M module, (see page xxx).

c "earth fault" protection (T) Of the residual current type (or source ground return type on request), it is possible to obtain zone selective interlocking by combining the T option with the appropriate M option.

21

Merlin Gerin

BTP207E-2.140-unité cont.

21

21/12/01, 9:51

Masterpact: functions and characteristics

control unit selection (cont.) STR 68 U control unit

STR 68 U

type of circuit breaker

N1. H1. H2. L1

basic protection long time protection LT current setting (Ir) adjustable in 2 % steps tripping time delay (tr) accuracy: + 0 - 20 %

thermal memory (30 mn) short time protection ST pick-up (Im) adjustable in 4 % steps time delay (tr)

Ir = In x ...

tr at 1.5 Ir (s) tr at 6 Ir (s) tr at 7.2 Ir (s)

Im = Ir x ... tm setting with I2t OFF tm setting with I2t ON max. overcurrent time before tripping (ms) max. break time (ms)

thermal memory (10 mn) instantaneous protection I fixed pick-up I (kA) pick-up (I) adjustable in 8 % steps accuracy OFF switch on front face

c 0.4 to 1 (mini 160 A) between 1.05 and 1.20 x Ir adjustable 15 30 60 120 240 480 0.94 1.88 3.75 7.50 15 30 0.65 1.30 2.60 5.20 10 21 standard + OFF position c 0.4 to 15 ± 10 % 0.1 0.2 0.3 0.4 0.1 0.2 0.3 0.4 60 140 230 350 140 230 350 500 standard c M08 to M16 : 65. M20 to M63: 75. from In to fixed pick-up (mini at 1.6 kA) ± 15 % on types N1 and H1

basic functions fault indication for tripping on a fault for Ir setting overrun indication of fault type and value of interrupted current self-monitoring maintenance indicator displays degree of wear of main contacts ammeter current readings with an accuracy of ± 3 % self-powered integrated test

button on front face fault trip alarm contact (SDE) LED on front face self powered LEDs on front face display on ammeter power supply internal overheating and microprocessor errors

c c c c c c 110 V - 220 V - 380 V AC 50/60 Hz c c between 0 and 655 c I1. I2. I3. Imax (1) c c

(1) Current of the phase carrying the highest load. Merlin Gerin

22 BTP207E-2.160-STR68U

22

21/12/01, 9:52

optional functions earth fault protection: residual current (T) or source ground return (W) type on request pick-up (Ih) adjustable in 2 % steps Ih = In x ... time delay (th) th setting max. overcurrent time before tripping (ms) max. break time (ms) thermal memory (10 mn) power measurement (P) (see opposite page for details) output characteristics integrated power supply voltage measurements U12. U23. U31 V1N. V2N. V3N frequency measurement: f power factor measurement: cos ϕ instantaneous active power measurement: P instantaneous active energy measurement: EP indication and control (M): 31 modules (1 per control unit) providing the following combinations: load monitoring option 1: 2 load limit pick-ups Ic1 and Ic2 Ic1 = In x ... delay tr1 = Ic2 = In x ... delay tr2 = option 2: 1 load limit pick-up Ic1 Ic1 = In x ... 1 load reconnection pick-up Ic2 delay tr1 = Ic2 = In x ... delay tr2 = zone selective interlocking trip indications for type of fault for self-monitoring (1) transmission characteristics type protocol speed max. number of addresses values transmitted: type of fault circuit breaker status self-monitoring settings circuit breaker status values transmitted: ammeter power system status voltmeter power factor, frequency instantaneous active power and energy: P. EP instantaneous reactive power and energy: Q. EQ power supply

c (zone selective interlocking with option M) 0.2 to 1 (maxi 1200 A. mini 160 A ) ± 15 % 0.1 0.2 0.3 0.4 60 140 230 350 140 230 350 500 c c opto-decoupled 0.2 A - 24 V DC c 160 to 690 ± 1 % 90 to 400 V ± 1 % 45 to 65 Hz ± 0.5 % - 1 to + 1 ± 2.5 % - 9000 to 9000 kW ± 5 % 0 to 9999 MWh ± 5 % c 2 possible options 0.2 to 1 In 2 % steps 0.5 x tr ± 5 % 0.2 to 1 In 2 % steps 0.25 x tr ± 5 % 0.2 to 1 In 2 % steps 0.5 x tr ± 5 % 0.2 to 1 In 2 % steps 60 s fixed ± 5 % for earth fault protection long-time, short-time, earth alarm RS 485 JBus 9600 bauds 255 tripping on Im, Ir, Ih alarm all pick-ups and delays open or closed currents I1, I2, I3 max voltages U12, U23, U31 voltages V1N, V2N, V3N cos ϕ, f - 9000 to 9000 kW. 0 to 9999 MWh ± 5 % - 9000 to 9000 kVar. 0 to 9999 MVahr ± 5 % 24, 48, 125 V DC or 100, 240 V AC

(1) Depending on the equipment, the "self-monitoring" alarm signal may or may not trip the circuit breaker, see "service continuity" option on the order form.

23

Merlin Gerin

BTP207E-2.160-STR68U

23

21/12/01, 9:52

Masterpact: functions and characteristics

control unit selection STR 68 U (cont.) option m selection

The following table indicates the functions of the different versions, designated m01 to m31. For terminal wiring see page xxxx.

Option M can be incorporated in control unit STR68U to provide the following functions: c RS485 data transmission at 9600 bauds to JBUS protocol; c remote signal via opto-electronic output; c zone selective interlocking for earth fault protection.

without data transmission option remoting load monitoring and control pick-up Ic1 indication load shedding pick-up Ic2 indication load shedding load reconnection fault indications Ir Im/I Ih self-monitoring zone selective interlocking on the earth fault protection

m01

m02

m03

m04

m05

m06

m07

m08

c c c c

c c c

c c

c c c c

c c

c c

c

c c

c c

c c

c c

c

c

m09

m10

c

c

c

c

m11

c c c c

c c c

c

c c

c

c

c

m12

m13

m14

m15

c

c c

c c

c

c

c

c c c c

c c c c

c c c c

c

c c c

c c

c

c c c

m16

c

c c c

c

c c

c c c

c

c

c c (1) c c

with data transmission option data transmission all parameters (see page xxxx) remoting load monitoring and control pick-up Ic1 indication load shedding pick-up Ic2 indication load shedding load reconnection fault indications Ir Im/I Ih self-monitoring zone selective interlocking on the earth fault protection

m17

m18

m19

m20

m21

m22

m23

m24

m25

m26

m27

m28

m29

m30

m31

c

c

c

c

c

c

c

c

c

c

c

c

c

c

c

c

c

c

c

c

c

c

c c c c c

c c

c c

c c

c c c

c

c

c c

c

c

c c

c

(1) Two separate outputs for Im and I. Merlin Gerin

24 BTP207E-2.170-STR68U

24

21/12/01, 9:52

Basic functions: long time LT, short time ST, instantaneous INST

Earth fault protection (option T)

t

t

Factory adjustments The STR68U control unit is factory adjusted as follows: LT

E26042

E26039

operating zones

I2t ON

ST

I2t ON

1 I2t OFF

INST T

I2t OFF

2

setting Ir time delay tr pick-up Im time delay tm pick-up I earth fault pick-up Ih time delay th load monitor Ic1 Ic2

In 480 s 4 In 0,2 s maxi 0,2 In 0,1 s In In

T1

3

T2

4 5 0

Ir

Im

I

0

I

earth fault protection settings T1 : earth fault pick-up Ih T2 : earth fault time delay th

overcurrent settings 1 : LT setting Ir (long time) 2 : LT time delay tr (long time) 3 : ST pick-up Im ( short time) 4 : ST time delay tm ( short time) 5 : INST pick-up I (instantaneous)

load monitoring and control (option M) Operation with 2 load limit pick-ups

Operation with 1 load limit and 1 load reconnection pick-up

t

t

E26038

E26037

I

Ic2

Ic2

Ic1

Ic1

0

I

load monitoring and control settings Ic1 pick-up (load limit) Ic2 pick-up (load limit)

0

I

load monitoring and control settings Ic1 pick-up (load limit) Ic2 pick-up (load reconnection)

Merlin Gerin

BTP207E-2.170-STR68U

25

25

21/12/01, 9:52

Masterpact: functions and characteristics

control unit accessories

048327

battery module (PIL) Complementary to the local indication of the faults (F option for STR 38 and STR 58 trip units), the battery module avoids the need for any external power supply to save front face indications.

048321

interface module ET44 Compulsory with the data transmission option on the STR 68 trip unit, the ET44 interface module allows: c setting of the transmission speed; c definition of the address of the breaker (which will not be affected by any drawout breaker manipulation);

025172

relay module (MR6) For relaying of information from outputs of modules m01 to m32 of control unit STR 68 via output changeover contacts 10 A/220 V AC or 3 A/24 V DC.

025173

power supply module (AD) These modules can be used to power control unit complementary functions which cannot be self-powered by the built-in current transformers: c STR 38 and STR 58: fault type indication (F); c STR 58: segregated alarm switch (V); c STR 58: communication option (COM); c STR 28, STR 38, STR 58: ammeter (I) for load less than 20% of In. c STR 68: indication and saving of

025171

battery module (BAT) Providing a complement to the AD module, the battery module provides backup power for display indications and maintenance indicator data in the event of a power failure. Float connected between the power supply and the control unit, it ensures a backup time of approximately:

047035

mini test kit (BU) This self-contained portable unit is used to check STR 18 M to STR 58 U control units operations and breaker tripping. Power supply: five 9 V alkaline batteries (not supplied).

052172

portable test kit for STR 18 to STR 58 The portable test kit is used: c for control unit STR 68, to power, check and carry out adjustments and tests on the breaker/control unit assembly (control unit without auxiliary power supply connected);

This module is equipped with a button for reactivation, of fault indications that have been de-activated by the battery power-saving feature. A test button is used to check the battery status.

c the direct remote control of the breaker, thanks to two outputs directly controlled through the data transmission. Installation: on vertical plate or symmetrical rail. Power supply: 24 V DC with galvanic isolation, or AD type power module. Installation : on vertical plate or symmetrical rail. Power supply module (AD) is required.

measurements, alarms, maintenance indicator…; c MR6 module. Moreover, these modules protect the trip unit from transient overvoltages thanks to galvanic isolation. Available voltages: c AC 50/60 Hz: 110 V, 220 V or 380 V (–20 %; +15 %) (consumption 10 VA); c DC : 24/30 V, 48/60 V, 125 V (±20 %) (consumption 10 W). Installation: on vertical plate or symmetrical rail. c 12 h with STR 38 and STR 58 control units; c 1.5 h with STR 68 control unit. Installation: on vertical plate or symmetrical rail. (ambient temperature from: 0 °C to +50 °C).

This test kit is common to the Masterpact, Compact NS, C, CM ranges.

c for other control units, to check the operation of the trip unit by measuring the actual trip time: v long-time protection, v short-time protection, v instantaneous protection, v earth-fault protection. Power supply: 110, 220 V AC 50/60 Hz. This test kit is common to the Masterpact, Compact NS, C, CM ranges.

Merlin Gerin

26 BTP207E-2.180-unité cont

26

21/12/01, 9:56

Masterpact: functions and characteristics

auxiliary power supplies

The protection functions and most of the options available for the STR control units are self-powered. An auxiliary power supply is nevertheless required for certain uses.

self-powered

auxiliary power supply direct AD + BAT connection modules

terminals

battery

no (1)

yes (2)

F1/F2

no

no (1) no (1)

yes yes

F1/F2 F1/F2

yes no

no (1)

yes

F1/F2

no

STR 28 / 58 protection : LT, ST, INST option I if I u 20% In if I < 20% In or single phase load option F option FV option ALR option R option T/W if Ih u 0.2 x In if Ih < 0.2 x In

yes yes no no no yes yes yes no (3)

STR 68 protection : LT, ST, INST, T, W

yes

other functions : see drawings page 71 (1) Not recommended: possible with a 24 V DC source, class 2, 5 Watt, ripple factor < 10%. (2) Display will in this case be "❊❊❊❊". Auxiliary supply allows to save maximeter information. (3) Ih pick-ups for which protection is not self-powered are printed in red on the trip unit front face.

27

Merlin Gerin

BTP207E-2.180-unité cont

27

21/12/01, 9:56

Masterpact: functions and characteristics

013282

auxiliaries

electrical operating mechanism Added to the manual charging mechanism, a motor charges and automatically recharges the stored-energy spring upon breaker closing making possible fast O-C-O cycles. Opening and closing operations are instantaneous. The manual mechanism remains available for emergency use. characteristics power supply 50/60 Hz (V) consumption (VA) DC (V) consumption (W) motor start-up surge charging time

The electrical operating mechanism includes: c the gear motor(MCH); c a closing release (XF); c a shunt release (MX) or an undervoltage release (MN) for opening; c "springs charged" limit switch changeover contact (CH). The addition of the electrical operating mechanism does not alter circuit breaker dimensions.

geared motor MCH 100/127 - 200/240 - 250/277 - 380 - 415 - 440 - 480 180 24/30 - 48/60 - 100/125 - 200/250 180 2 to 3 In for 0.1 s 3 to 4 s

14 BTP207E-2.202-circuit-breaker

Merlin Gerin

14

21/12/01, 9:58

035932

operation counter (CDM) With gear-motor option only. The operation counter is read from the front and gives the total number of breaker operating cycles.

15

Merlin Gerin

BTP207E-2.202-circuit-breaker

15

21/12/01, 9:58

Masterpact: functions and characteristics

016813

auxiliaries (cont.)

releases Two types of voltage releases can be used for remote opening of Masterpact circuit breakers. Undervoltage releases c instantaneous (MN) This release instantaneously opens the breaker when its supply voltage drops below a value between 35 % and 70 % of its rated voltage. If the release is not energised, the breaker cannot be closed (either manually of electrically). Any attempt to close will have no effect on the main contacts. Closing is possible when the release voltage reaches 85 % of its rated value. c time delayed (MNR) To prevent the breaker tripping in the event of transient voltage dips, this release has a built-in time delay. A special version, available on request, allows instantaneous tripping (from a mushroom-head emergency off button) by the wiring of an external contact.

closing release (XF) This device releases the breaker closing mechanism when the spring is charged. Energisation can be maintained, as the closing release provides an antipumping function.

characteristics breaker response time at Un operating thresholds opening closing power supply AC 50/60 Hz (V)

036051

consumption (VA) DC (V) (2) consumption (W)

Shunt release (MX) This release instantaneously opens the breaker when energised. The supply can be maintained or automatically disconnected. In the latter case, the user can series connect an internal auxiliary contact (OF).

Note: anti-pumping function: After the breaker has been opened, either by fault trip or by manual or electrical operation, anti-pumping is provided by requiring cancellation of the initial closing command before reclosure of the breaker is possible. The closing release is supplied on request with the manual operating mechanism

undervoltage and shunt releases MN MNR MX 90 ms ± 5 0.5 s-0.9 s 50 ms ± 10 1.5 s-3 s

from 0.35 to 0.7 Un 0.85 Un

closing release XF 70 ms + 10, – 15 i 3 200 A 80 ms ±10 > 3 200 A

0.7 to 1.1 Un 0.85 to 1.1 Un

100 - 110/127 - 200 - 220/250 - 277 - 380/415 - 440/480 500/525(1) 20 24 - 30 - 48 - 60 - 100/110 - 125 - 200/220 - 250 15

Release combinations Each Masterpact circuit breaker can be equipped with: 1 MX + 1 MN + 1 XF, or 2 MX + 1 XF

(1) 500/525 V AC not available for MNR. (2) MNR: DC, 125 V only.

16 BTP207E-2.204-auxiliaries

Merlin Gerin

16

21/12/01, 10:08

016814

"spring charged" contact (CH)

auxiliary switches

018242

Double break changeover switches "OF"

Additional changeover switches ("OFSUP" block)

In addition to the main contact position indication on the front, 3 auxiliary switch blocks are available to indicate the open and closed breaker positions. c standard: 4 contacts (O) (2 normally open 2 normally closed); c optional: 4 directly-operated double break changeover switches (OF) which operate only when the minimum isolating distance between the main contacts is reached; c optional: 24 additional changeover switches (OFSUP block). These microswitches can be parallel connected in pairs to increase the rated current and breaking capacity (in drawout version only).

In addition to the local mechanical indicator and the "ready to close" contact, the gearmotor limit switch changeover contact can indicate that the operating mechanism is ready (spring charged). This contact is supplied as standard with the gear motor.

fault-trip indication (SDE) As standard and independent from the differentiated fault indications on the control unit, any fault-trip is indicated by: c 1 fault-trip indicator/reset button; c 1 changeover contact (SDE). The reset button must always be pressed after a fault-trip to enable breaker closing. Optional: automatic reset, allowing remote breaker closing without local resetting (the SDE contact operates up to the reset).

"ready to close" contact (PF)

016524

Optional: This contact simultaneously indicates the following: c the breaker is open; c the stored-energy mechanism is charged; c the mechanism is correctly reset; c the breaker opening pushbutton is not locked; c no opening order is present. This contact can be series connected to the closing release (XF) to disable the antipumping function.

connected/disconnected position carriage switches Changeover switches to indicate "connected" position "CE"

In addition to the local "connected/test/ disconnected" position indicator, two series of optional carriage switches are available for the fixed chassis (of drawout circuit breaker). c a block of 4 changeover switches to indicate "connected" position (CE); c a block of 2 changeover switches to indicate "disconnected" position (CD). The disconnected position is indicated only when the minimum isolating distance between main and auxiliary circuits has been reached. By series connection of these contacts the test position can be indicated. c 1 changeover switch to indicate "test" position (CT).

contact characteristics auxiliary contacts quantity

current rating (A) breaking capacity AC 50/60 Hz (A rms.) pf u 0.3

DC (A) L/R i 0.01 s

type O changeover NO 2 NO NC 2 NC 10 110 V 240 V 10 380 V 6 480 V 6 600 V 3 48 V 3 125 V 0.5 250 V 0.25 500 V

OF 4

OFSUP SDE PF 24 1 1

CE 4

CD 2

CT 1

CH 1

10 15 10 10 10 6 5 3 3 0.5

10

10

10

10

10

10

10

10 6 6 3 3 0.5 0.25

10 5

10 5

10 6 6 3 3 0.5 0.25

10 6 6 3 3 0.5 0.25

10 6 6 3 3 0.5 0.25

17

Merlin Gerin

BTP207E-2.204-auxiliaries

10 6 6 3 3 3 3 0.3 0,3 0.5 0.15 0.15 0.25

17

21/12/01, 10:08

Masterpact: functions and characteristics

013280

accessories

safety shutters (VO)

shutter lock (VVC)

Optional: mounted on the fixed portion of drawout breakers, the safety shutters automatically block access to the disconnection contacts when the breaker is in the disconnected or test position (degree of protection IP 20).

Optional: mounted on the fixed portion of drawout breakers, a mobile and lockable slide (padlocks not supplied) is used to: c lock the shutters in the closed position;, c hold the shutters in the open position. A support is provided at the back of the frame to hold the slide when not in use. A second slide is supplied: c on request for Masterpact i 3200 A ; c in standard for Masterpact 4000 A to 6300 A.

arc chute cover (CC)

terminal shield (CB)

Optional: attached to the fixed portion of drawout circuit breakers or on the fixed circuit breaker, this cover eliminates the safety clearance requirement above the breaker (this option is incompatible with front connection on top).

Optional: attached to the fixed portion of drawout circuit breakers, this cover prevents access to the electrical auxiliary connection terminals.

interphase barrier (EIP)

partitioning fixture (AC)

035928

Fixed portion of drawout circuit breakers with safety shutters

016818

Fixed portion of drawout circuit breakers with arc chute and terminal shield

Optional: attached to the fixed portion of drawout breakers (except when equipped with front connections), this fixture provides IP30 partitioning between the breaker compartment (accessible from the front) and the connection zone (located in the rear). It simplifies partition cut-outs. Example of partition cut-out for Masterpact M08 to M32. 445 (3 445 (3pole) pôles)

560 pole) etand 560 (4(4 pôles)

28518

Optional: attached to the fixed portion of drawout breaker (Masterpact i M40 3P), the insulated partitions for vertical installation between connection pads to: c reinforce insulation at connection points in insulated busbar installation; c prevent arc propagation to the breaker in the event of a line side fault on the main busbars.

360

datum référence a

plan de fixation chassis châssis fixing 60

b

a: partitioning fixture (AC) b: interphase barrier (EIP)

18 BTP207E-2.206-accessories

Merlin Gerin

18

21/12/01, 10:09

016819 016814

door frame (CDP)

transparent cover (CCP)

Optional: fixed to the cublicle door, this frame provides an equipment seal function (degree of protection IP 405). Suitable for fixed and drawout patterns.

Optional: hinge-mounted and equipped with a screw-closure, this cover is designed for the door frame (CDP). It provides a degree of protection of IP549. Suitable for fixed and drawout patterns.

auxiliaries connection

"Connected/disconnect/test" position contacts Installed on the fixed chassis, these contacts are directly connected by 6.35 mm connectors.

Fixed version Connection by one or two plugs, disconnectable and accessible from the front (screwless tunnel terminals for flex cable up to 2.5 mm2). Drawout version c standard: connection to a terminal block in the front of the fixed frame (screwless tunnel terminals for flex cable up to 2.5 mm2). The breaker auxiliary circuits are connected by connection blocks that operate automatically to isolate the auxiliaries when the breaker is in "disconnected" position. On request, an additional 5-way terminal block (BS) is available to provide five common points. c optional: by one or two plugs, disconnectable and accessible from the front, installed on the mobile part of the assembly.

015561

Auxiliaries for fixed version

Auxiliaries for drawout version

035940

breaker mismatch protection Optional: for drawout version only, this systems allows only correctly matched breakers (rating, type wiring, etc.) to be inserted in a given fixed frame. Two matching parts (1 for the fixed chassis and 1 for the mobile assembly) can be used to create 20 different user selected combinations.

Earth connection The earth connection terminal (drawout pattern) is on the left hand side of the chassis. It is marked with the symbol t

19

Merlin Gerin

BTP207E-2.206-accessories

19

21/12/01, 10:09

Masterpact: functions and characteristics

035932

accessories (cont.)

pushbutton locking device Optional: this padlockable device (padlocks not supplied) prevents direct operation of the circuit breaker by covering the "on" and "off" pushbuttons. This locking device can also be used for lead sealing.

"off" position locking device Optional: a Profalux key lock locks the breaker in "off" position by holding the pushbutton in its depressed position.

pushbutton locking device by padlocks (not supplied)

VBP

"off " position locking device (1)

035931

1 Profalux key lock 2 Profalux key locks, identical profiles adaptation fixture for 1 Profalux key lock, lock not supplied On request 1 Ronis key lock 2 Ronis key locks, identical profiles adaptation for 1 Castell key lock, lock not supplied adaptation for 1 Kirk key lock, lock not supplied

"disconnected", "connected" and "test" position locking (1) Mounted on the frame and accessible with the cubicle door locked, this system is available in two versions: c "disconnected" position locking; v as standard by 1 padlocking device (1 to 3 padlocks not supplied), v optional: by a locking device with 1 or 2 Profalux key locks; c "disconnected", "connected" and "test" position locking (optional); v by 1 padlocking device, with 1 to 3 padlocks not supplied (VEC), v by 1 locking device, with 1 or 2 Profalux key locks (VSPEC), padlocks "disconnected" standard "disconnected" standard "disconnected" standard "disconnected, connected" "disconnected, connected" "disconnected, connected"

1 keylock

VSPA1 VSPA2 VSPRAC VSRA1 VSRA2 VSCA VSKA

Remarks c the keylocks are of the captive key type, i.e. key free when locked; c Profalux and Ronis keylocks can be used together; c a second Profalux or Ronis lock, identical to the one mounted on the chassis, can be supplied separately.

2 keylocks

"disconnected" optional "disconnected" "disconnected" optional optional

"disconnected, connected" "disconnected, "disconnected, connected" connected"

(1) keylock types Profalux B24 D4Z Ronis 1351 B Kirk CN22-12 Castell SK7113/1 Trayvou L1P1E

20 BTP207E-2.208-accessories

Merlin Gerin

20

21/12/01, 10:09

"disconnected" position locking by padlocks (not supplied) 1 Profalux key lock 2 Profalux key locks, identical profiles 2 Profalux key locks, different profiles adaptation fixture for Profalux key lock (lock not supplied)

as standard VSPC1 VSPC2 2 VSPC1 VSPRCC

On request 1 Ronis key lock 2 Ronis key locks, identical profiles 2 Ronis key locks, different profiles adaptation fixture for Castell key lock (lock not supplied) adaptation fixture for Kirk key lock (lock not supplied) adaptation fixture for Trayvou key lock (lock not supplied)

VSRC1 VSRC2 2 VSRC1 VSCC VSKC VSTC

"disconnected", "connected" and "test" position locking by padlocks (not supplied) 1 Profalux key lock 2 Profalux key lock, different profiles

VEC VSEPC 2 VSEPC

On request 1 Ronis key lock 2 Ronis key locks, differents profiles adaptation fixture for Castell key lock (lock not supplied) adaptation fixture for Kirk key lock (lock not supplied)

VSERC 2 VSERC VSECC VSEKC

016817

door interlock Optional: mounted on the chassis, this lock prevents the cubicle door from being opened when the breaker is in the "connected" position. If the breaker is put into the "connected" position with the door open, the latter can be closed without disconnecting the breaker.

withdrawal/spring charged interlock Optional: this lock prevents withdrawal of the breaker from the chassis when the springs are charged. Incompatible with MN or MNR release.

racking interlock

a

Optional: this lock prevents insertion of the breaker racking handle when the cubicle door is open. It can be defeated by pressing on the unlocking mechanism.

b

door interlock right-hand side left-hand side racking interlock withdrawal/spring charged interlock

a: racking interlock b: door latch

VPECD VPECG VPOC VEAA

21

Merlin Gerin

BTP207E-2.208-accessories

21

21/12/01, 10:09

Masterpact: functions and characteristics

automatic source-changeover systems

053060

025186

Masterpact source-changeover systems can be used to implement various configurations involving several incoming feeders. The two or three Masterpact circuit breakers or switch-disconnectors used are mechanically interlocked to prevent certain combinations of operations. All types of Masterpact devices may be fitted (fixed and drawout versions, three-pole and four-pole, different ratings). The devices may be arranged: c vertically, i.e. stack-mounted and interconnected by a set of rods; c horizontally (two only), i.e. side-by-side and interconnected by a set of cables. An electrical interlock must be used when the source changeover is part of an automatic system.

053061

053058

Masterpact automatic source-changeover system

Controller

automatic source-changeover system with 2 devices without controller

In this case, the automatic control system to initiate changeovers between the «Normal» and «Replacement» sources under predefined conditions must be provided by the customer. Note that we can provide diagrams for the design of various automatic control systems for different sources.

E33079

A Masterpact automatic sourcechangeover system with 2 devices is made up of: 1 - circuit breaker QN connected to the "Normal" source; 2 - circuit breaker QR connected to the "Replacement" source; 3 - mechanical interlocking system by rods or cables;

1

automatic control of the system can be provided by adding: 4 - electrical interlocking unit IVE; 5 - auxiliaries control plate ACP; 6 - controller BA or UA.

E33078

3 2

Each Masterpact circuit breaker is equipped with: c a motor mechanism; c a shunt release (MX); c a «ready to close» contact (PF); c a block of 4 changeover switches (OF); c an additional terminal block (BS) and a block of 4 «connected» position switches (CE) for source-changeover systems made up of drawout breakers.

1

2

3

3

with controller E33082

In this case, conditional changeovers between the «Normal» and «Replacement» sources are initiated by a Merlin Gerin controller. IN GER

MERLIN

N R N

UN =

O

UN =

1

UR

0,5s

UN ON / ON / OFF

I

OFF

I

0,5s

/O

/O

R

fault

fault stop

test

manu

R N

4 6 GERIN MERLIN multi

9

0 . OFF

P25M

GERIN MERLIN multi

9

0 . OFF

660V 2-1 AC3-IEC29

P25M 660V 2-1 AC3-IEC29

Test

B US

Test

MERLIN

IN GER

N R

N

UN =

O

UN =

1

generat

or

UR

UN ON / ON / OFF

I

OFF

I /O

R

/O fault

fault auto stop

manu

test STOP

R N

5 Merlin Gerin

36 BTP207E-2.220-invers source

36

21/12/01, 10:10

automatic source-changeover system with 3 devices without controller

In this case, the automatic control system to initiate changeovers between the «Normal» and «Replacement» sources under predefined conditions must be provided by the customer. Note that we can provide diagrams for the design of various automatic control systems for different sources.

E33080

A Masterpact automatic sourcechangeover system with 3 devices is made up of: 1 - 2 circuit breakers QN1 and QN2 connected to the "Normal" source; 2 - circuit breaker QR connected to the "Replacement" source; 3 - mechanical interlocking system by rods;

1

for such applications (consult us) automatic control of the system can be provided by adding: 4 - 2 electrical interlocking unit IVE; 5 - auxiliaries control plate ACP; 6 - controller BA or UA.

3

Each Masterpact circuit breaker is equipped with: c a motor mechanism; c a shunt release (MX); c a "ready to close" contact (PF); c a block of 4 changeover switches (OF); c an additional terminal block (BS) and a block of 4 "connected" position switches (CE) for source-changeover systems made up of drawout breakers.

1

3 2

3

E33383

with controller (consult us)

GERIN MERLIN multi

9

0 . OFF

P25M

GERIN MERLIN multi

9

0 . OFF

660V 2-1 AC3-IEC29

P25M 660V 2-1 AC3-IEC29

MERLIN

IN GER

N

Test

R

UN =

O

UN =

1

UR

0,5s

Test

N

UN ON / I ON / OFF

OFF

I

0,5s

/O

/O

R

fault

fault stop

test

manu

R N

4

B US

6

5 MERLIN

IN GER

N R

N

UN =

O

UN =

1

UR

UN ON / ON / OFF

I

OFF

I /O

R

/O fault

fault auto stop

manu

test STOP

gen

erator

R N

In this case, conditional changeovers between the "Normal" and "Replacement" sources are initiated by a Merlin Gerin controller.

37

Merlin Gerin

BTP207E-2.220-invers source

37

21/12/01, 10:10

Masterpact: functions and characteristics

automatic source-changeover systems (cont.) mechanical interlock selection 025184

mechanical interlocking by connecting rods for 2 or 3 stack-mounted breakers This involves: c 2 or 3 Masterpact circuit breakers and/or switch-disconnectors; c an adaptation fixture on the right side of each breaker; c 1 or 2 sets of connecting rods with no-slip adjustments; The various parts are mounted by the user. The changeover system with interlocking by connecting rods is also available in a version which is factory mounted on a steel frame. Maximum distance between fixing planes: 900 mm.

025186

mechanical interlocking by cables for 2 side-by-side breakers This involves: c 2 Masterpact circuit breakers and/or switch-disconnectors; c an adaptation fixture on the right side of each breaker; c a set of cables with no-slip adjustments; The various parts are mounted by the user. Distance between fixing planes: c maximum: 2 000 mm; c minimum: breaker height with arc chute cover (see pages ????).

device combinations

assembly and installation

All combinations are possible: fixed and drawout versions, three-pole and four-pole, different ratings, circuit breakers or switchdisconnectors. All control units can be used on the circuit breakers.

The various parts of the Masterpact automatic source-changeover system are mounted and connected by the user. No circuit breaker modifications are required. The wiring diagrams are shown on pages ??? to ???. The Masterpact automatic sourcechangeover system may also be supplied factory-wired and mounted on a metal frame.

Merlin Gerin

38 BTP207E-2.230-invers source

38

21/12/01, 10:11

Masterpact: functions and characteristics

automatic source-changeover systems (cont.) automatic control: typical configurations c a motor mechanism (MCH); c a shunt release (MX); c a "ready to close" contact (PF); c a block of 4 changeover switches (OF); c an additional terminal block (BS) and a block of 4 "connected" position switches (CE) for changeover systems including drawout breakers.

Necessary auxiliaries and accessories To implement the configurations below, each Masterpact circuit breaker must be equipped with:

Option with "lockout after fault" With this option, the circuit breaker must be reset manually after a fault trip.

power circuit

possible combinations

configuration type

cat. No.

interlocking with 2 breakers

Q1 0 0 1

Q2 0 1 0

electrical interlocking automatic control with generator set with permanent "Replacement" source

685363

Q1 0 1 0 1 0

Q2 0 0 0 1 1

Q3 0 0 1 0 0

automatic control with permanent "Replacement" source with lockout after fault 685366 without lockout after fault 688183 automatic control with generator set with lockout after fault 689642 without lockout after fault 689644

Q1 0 1 0 0

Q2 0 0 1 0

Q3 0 0 0 1

electrical interlocking with lockout after fault without lockout after fault

688188 688187

Q1 0 1 0 0 1 0 1

Q2 0 0 1 0 1 1 0

Q3 0 0 0 1 0 1 1

electrical interlocking with lockout after fault without lockout after fault automatic control

688189 688190 689651

E30736

The electrical interlocking system and automatic control system for multiple sources must be wired by the user. It must be used in conjunction with the mechanical interlocking system. Typical wiring configurations are available on request. See examples below. For other configurations, consult us.

Q1

Q2

E30737

interlocking with 3 breakers 2 "Normal" sources + 1 "Replacement" source

Q1

Q2

Q3

E30738

interlocking with 3 breakers 3 sources, only one breaker closed

Q1

Q2

Q3

E30739

interlocking with 3 breakers 2 sources + 1 coupling

Q1

Q2

Q3

39

Merlin Gerin

BTP207E-2.230-invers source

688784 688942

39

21/12/01, 10:11

Masterpact: functions and characteristics

automatic source-changeover systems (cont.) controller option selection Used together with the auxiliaries control plate ACP, controllers BA and UA initiate the automatic changeover operations according to the status of the "Normal" and "Replacement" sources. c mounted on the front of the switchboard. The distance between the controller and the auxiliaries control plate must not exceed 2 metres. The interconnection wiring must be done by the customer.

E32704

E32705

Installation Two possibilities: c mounted directly on the auxiliaries control plate ACP.

MERLI multi

0 . OFF

N GERIN

9

MERLI multi

N GERIN

9

660V 292-1 AC3-IEC

0 . OFF

N GERIN

MERLI multi

9

0 . OFF

N GERIN

0 . OFF

660V 292-1 AC3-IEC

P25M 660V 292-1 AC3-IEC

660V 292-1 AC3-IEC

Test

Test

Test

Test

B US

multi

9

P25M

P25M

MERLI P25M

RIN IN GE MERL

N R

B US

N

RIN IN GE MERL

N R

N

UN =

O

/O

ON /

I

OFF

/O

I

OFF

/O

I

O

OFF

/O

UN =

1

R

fault

auto stop

I

OFF

ON /

ON /

fault

UR

UN

ON /

UN =

UR

UN

manu UN =

1

test

R

P

STO

genera

tor

R N

fault

fault auto stop

manu

test tor

P STO

genera

R N

customer connection

terminal block and electrical interlocking unit: IVE E32703

The terminal block and electrical interlocking unit IVE is used to connect the operating mechanism. Control voltage: c 48 to 415 V, 50/60 Hz - 440 V 60 Hz. The IVE control voltage must be the same as the motor mechanism voltage.

auxiliaries control plate: ACP 053060

The auxiliaries control plate ACP includes: c two P25M circuit breakers supplying and protecting the automatic control circuits for the "Normal" and "Replacement" sources. These circuit breakers have an infinite breaking capacity; c two relay contactors for the BA or UA controller; c the terminal block for connection to the controller.

Power supply: Power is supplied by the "Normal" and "Replacement" sources. The control voltage for the auxiliaries control plate must be the same as for the IVE unit and the motor mechanisms. Control voltages c 220 to 240 V 50/60 Hz; c 380 to 415 V 50/60 Hz - 440 V 60 Hz. Installation: The auxiliaries control plate ACP must be wired to the IVE unit by the customer.

Merlin Gerin

40 BTP207E-2.240-invers source

40

21/12/01, 10:12

053058

controller

Controller UA

controller

BA

compatible circuit breakers

All Masterpact circuit breakers

UA

4-position switch automatic operation forced operation on "Normal" source forced operation on "Replacement" source stop (both "Normal" and "Replacement" sources off)

c c c c

c c c c

c

c c c

automatic operation monitoring of the "Normal" source and automatic changeover generator set control load shedding and reconnection of non-priority circuits changeover to the "Replacement" source if one of the phases of the "Normal" phase is absent

c

test by opening the P25M circuit breaker supplying the controller by pressing the test button on the front of the controller

c c

indications circuit breaker status indication on the front of the controller: on, off, fault trip, automatic mode indicating contact automatic mode indicating contract

c c

c c

c

c c

other functions selection of type of "Normal" source (single-phase or three-phase) voluntary transfer to "Replacement" source (e.g. energy management commands) during peak-tariff periods (energy management commands), forced operation on "Normal" if "Replacement" source not operational supplementary control contact (not carried out by the controller). Transfer to "Replacement" source only if contact closed. (ex: UR frequency control) setting of maximum startup time for the replacement source

c c

c c

power supply control voltages (1)

220 to 240 V 50/60 Hz 380 to 415 V 50/60 Hz - 440 V 60 Hz

options c

communication option

(1) The same voltage must be used for the ACP plate, the IVE unit and the circuit breaker motor mechanisms. If this voltage is the same as the source voltage, then the “Normal” and “Replacement” sources can be used directly for the power supply. If not, a BC type or equivalent isolation transformer must be used.

Merlin Gerin

BTP207E-2.240-invers source

41 41

21/12/01, 10:12

Masterpact: functions and characteristics

automatic source-changeover systems controller option selection (cont.)

E30184

controller BA

Controller BA can be used with Masterpact circuit breakers to implement a straightforward automatic source-changeover system (switching from one source to another depending on the presence of voltage UN on the "Normal" source).

MERLIN GERIN compact / masterpact

BA automatism 220/240 V 50/60 Hz

N

R

UN

N

UR

ON/I

ON/I

OFF/O

OFF/O

fault

fault

UN = 0

2 4 t1 1 8 s 15 0.5 0.1 30

0.5s

0.5s

t2 s

stop manu

reset

N

15 30 8 60 120 4 0.1 240

UN = I

R

auto

Electrical characteristics Power is supplied from the auxiliaries control plate ACP. The same voltage must be used to supply the ACP plate, the IVE unit and the circuit breaker motor mechanisms. If this voltage is the same as the source voltage, the "Normal" and "Replacement" sources can be used directly for the power supply. If not, a BC type or equivalent isolation transformer must be used.

Control voltages c 220 to 240 V 50/60 Hz; c 380 to 415 V 50/60 Hz - 440 V 60 Hz.

Operation c a four-position switch can be used to select: v automatic operation; v forced operation on source N; v forced operation on source R; v stop (both "Normal" and "Replacement" sources off); c adjustment of time delays in front: v t1 from 0.1 to 30 seconds; v t2 from 0.1 to 240 seconds; c circuit breaker status indication on the front of the controller: on, off, fault trip;

c integrated terminal block for connection of the following signals: v inputs: – order for voluntary transfer to source R (e.g. energy management commands), – supplementary control contact: (not carried out by the controller). Transfer to "Replacement" source only if contact closed (ex: UR frequency control), v outputs: – indication of operation in automatic mode. Connection to the terminal block: see p.XXX. c controller BA can be tested by opening the P25M circuit breaker on the N circuit, thus simulating a failure of UN. See detailed transfer steps on page XXX.

R

Front face of controller BA

Time delay settings: QN: Masterpact circuit breaker with motor mechanism on “Normal” source, QR: Masterpact circuit breaker with motor mechanism on “Replacement” source, t1: time delay before QN opens when the voltage UN of the “Normal” source disappears, t2: time delay before QR opens when the voltage UN of the “Normal” source is restored.

Merlin Gerin

42 BTP207E-2.250-BA

42

21/12/01, 10:12

c 4-position switch in "auto" position (automatic operation)

QN et QR open

off

N I

operat. on source N

R O

4-position switch N et UN présente

UN fail (duration > t1) or voluntary switching order received UR present and supplementary control contact N➡R closed

"auto"

reset

c 4-position switch in "N " position (forced operation on "Normal" source) E30187

E27107

E21108

c 4-position switch in "stop" position

duration a 1 s

QR opens

QN opens

t > 0,5 s

end of reset t > 0,5 s

QN closes

QR closes

QN fermé

"stop" operat. on source N

QR closed

N O

operat. on source R

R I

N I

R O

action on 4-position switch

UN present for t > t2 or voluntary switching order stopped

c 4-position switch in "R" position (forced operation on "Replacement" source) E32708

QR opens

t > 0,5 s

4-position switch in "R" position UR present and supplementary control contact N➡R closed QN closes QN opens

QN closed t > 0,5 s

QR closes

QR closed

operat. on source R

N O

R I

action on 4-position switch

Merlin Gerin

BTP207E-2.250-BA

43 43

21/12/01, 10:12

Masterpact: functions and characteristics

automatic source-changeover systems controller option selection (cont.) controller UA

E30183

053059

Controller UA can be used with Masterpact circuit breakers to implement a sourcechangeover system offering the following automatic functions: c switching from one source to another depending on the presence of voltage UN on the "Normal" source; c control of an engine generating set; c shedding and reconnection of non-priority circuits; c switching to the "Replacement" source in the event of a failure on one of the phases of the "Normal" source. Electrical characteristics Power is supplied from the auxiliaries control plate ACP. The same voltage must be used to supply the ACP plate, the IVE unit and the circuit breaker motor mechanisms. If this voltage is the same as the source voltage, the "Normal" and "Replacement" sources can be used directly for the power supply. If not, a BC type or equivalent isolation transformer must be used.

Control voltages c 220 to 240 V 50/60 Hz; c 380 to 415 V 50/60 Hz - 440 V 60 Hz.

Operation c a four-position switch can be used to select: v automatic operation; v forced operation on source N; v forced operation on source R; v stop (circuit breakers open and manual operation); c adjustment of time delays in front: v t1 from 0.1 to 30 seconds; v t2 from 0.1 to 240 seconds; v t3 from 0.5 to 30 seconds; v t4 from 0.5 to 30 seconds; v t5 from 60 to 600 seconds; c circuit breaker status indication on the front of the controller: on, off, fault trip; c test button on the front of the controller to check the transfer from the “Normal” source to the "Replacement" source and the return to the "Normal" source;

c integrated terminal block for connection of the following signals: v inputs: – order for voluntary transfer to source R (e.g. energy management commands), – supplementary control contact: (not carried out by the controller). Transfer to "Replacement" source only if contact closed (ex: UR frequency control), v outputs: – control of engine generator set, – load shedding of non-priority circuits, – indication of operation in automatic mode; c 3 switches provide the following functions: v selection of the type of "Normal" source, i.e. single-phase or three-phase; v enable or disable voluntary energy management transfer if the "Replacement" source is not operational; v selection of the maximum tolerated starting time for the engine generator set ("Replacement" source): 120 s or 180 s.

Batibus option for controller UA A communication function can be used to check the following from a remote location: c status of the circuit breakers (open, closed or fault trip); c voltage presence on the “Normal” and “Replacement” sources; c presence of an order forcing operation on the “Replacement” source (e.g. for energy management purposes); c values of settings and configurations, c status of the non-priority circuits (whether subject to load shedding or not).

In automatic mode, this communications option also offers the possibility of remote forced operation on the “Replacement” source.

MERLIN GERIN compact / masterpact

UA automatism 220/240 V 50/60 Hz

N

R

UN ON/I

ON/I

OFF/O

OFF/O

fault

fault

stop manu

reset

auto test

N

N

UR

UN = 0

t4 s

5 10 2 15 20 1 0.5 30

t2 s

15 30 8 60 120 4 0.1 240

240 300 160 360 480 120 60 600

2 4 t1 1 8 s 15 0.5 0.1 30 5 10 t3 2 15 s 20 1 0.5 30

UN = I

R

t5 s

R STOP

generator

Front face of controller UA

Time delay settings: QN: Masterpact circuit breaker with motor mechanism on “Normal” source, QR: Masterpact circuit breaker with motor mechanism on “Replacement” source, t1: time delay before QN opens when the voltage UN of the “Normal” source disappears, t2: time delay before QR opens when the voltage UN of the “Normal” source is restored, t3: time delay before QR closes once QN has opened and the load has been shed, t4: time delay before QN closes once QR has opened and the load has been reconnected, t5: time delay for confirmation of presence of UN before stopping the generator set.

44 BTP207E-2.260-UA

Merlin Gerin

44

21/12/01, 10:12

E30185

E27107

QN and QR open

stop

"auto"

reset

c 4-position switch in "N" position (forced operation on "Normal" source) E30187

c 4-position switch in "auto" position (automatic operation)

c 4-position switch in "stop" position

N I

operat. on source N

R genset off O

4-position switch in "N" and UN present

UN fails (duration > t1) or voluntary switching order received duration a 1 s

end of reset

QR opens and load shedding

genset startup

t > t4

UR present for t < 120 s or 180 s and supplementary control contact N➡R closed

QN closes

QN opens and load shedding

QN closed

"stop"

operat. on source N

t > t3

QR closes

N I

R genset off O

action on 4-position switch

QR closed

R genset on I

UN present for t > t2 or voluntary switching order stopped

c 4-position switch in "R" position (forced operation on "Replacement" source) E30186

N O

operat. on source R

4-position switch in "R" and UN present

QR opens and load reconnection genset startup t > t4

UR present for t < 120 s or 180 s and supplementary control contact N➡R closed QN closes QN opens and load shedding

QN closed t > t3 genset remains on QR closes UN present for t > t5 and no voluntary switching order received QR closed genset off operat. on source R

N O

R genset on I

UR absent action on 4-position switch

45

Merlin Gerin

BTP207E-2.260-UA

45

21/12/01, 10:12

Merlin Gerin

40 BTP207E-3.001-sommaire

40

21/12/01, 10:13

LV power air circuit breakers and switch-disconnectors

Masterpact 3/ installation and connection page installation general safety clearance fixed circuit breakers M08 to M32 drawout circuit breakers M08 to M32 fixed circuit breaker M40 drawout circuit breaker M40 fixed circuit breaker M50 drawout circuit breaker M50 drawout circuit breaker M63 manual source changeover systems manual and automatic source changeover systems connection fixed and drawout circuit breakers M08N/M10N/M12N fixed and drawout circuit breakers M08H,L/M10H,L/M12H,L/M16N,H,L fixed and drawout circuit breakers M20N,H/M25N,H fixed and drawout circuit breakers M20L/M25L/M32H fixed and drawout circuit breaker M40 fixed and drawout circuit breaker M08 to M16 fixed and drawout circuit breaker M50 to M63 wiring diagrams: c STR 18 M / 28 D / 38 S / 58 U c STR 28 D / 38 S / 58 U avec options c STR 68 U avec options m01 à m31 c automatic source changeover c manual source changeover

0 0 0 0 0 0 0 0 0

0

0 0 0 0 0 0 0 0 0 0 0 0

41

BTP207E-3.001-sommaire

41

21/12/01, 10:13

Masterpact: installation and connection

general

installation

Masterpact circuit breakers must be installed in the vertical position on a base plate or on rails.

drawout circuit breaker (M08 to M63)

The drawout version makes it possible to: c rapidly remove and/or replace the circuit breaker without having to deal with connections; c install stand-by outgoers in a switchboard that will receive the necessary circuit breakers later in time

E31256

E31254

"Connected" position

26

"Test" position ample clearance between contacts

E31255

Installation on a metal base plate

018241

Installation on rails

45

"Disconnected" position easy withdrawal, short travel

E31257

E29026

E28811

fixed circuit breaker (M08 to M50)

305

"Withdrawn" position compact dimensions

Merlin Gerin

42 BTP207E-3.200-généralité

42

21/12/01, 10:14

Masterpact: installation and connection

safety clearance

Certain distances must be maintained between a circuit breaker and other elements such as panels, bars and other circuit breakers. Taken together, these distances form the safety clearance for the circuit breaker. The diagrams and the table below indicate the required distances when installing Masterpact circuit breakers.

These distances are the results of tests carried out in accordance with standard IEC 947-2 and are in part determined by the ultimate breaking capacities.

C

100

A

D

D

C A

E31230

100

E31233

E31232

fixed circuit breaker

A

A B

B

B

Masterpact M08 to M50 type of connection

to insulated barrier A B C front connection without cover (1) 360 30 0 rear connection without cover 150 30 20 rear connection with cover 0 0 20

to metal parts A B 360 70 250 70 0 0

D (2) 0 0 0

C – 95 95

D (2) 0 0 –

B

to live bars A B 1085 420 1085 420 145 105

C – 495 125

D (2) 0 0 0

100

C E31231

E31229

drawout circuit breaker

A

A

B

213

B

Masterpact M08 to M63 type of connection

to insulated barrier A B front connection without cover (1) 300 15 rear connection without cover 150 15 rear connection with cover 0 0

(1) Shield necessary. (2) D is the clearance required for connection of auxiliaries. D = 0 for fixed circuit breakers (required clearance included in the height of the connection plugs). D = 0 for drawout circuit breakers as well.

C 0 45 45

to metal parts A B 300 50 150 50 0 0

C – 45 45

C – 445 75

Note: For the fixed circuit breakers, a clearance of 130 mm is required on top for removal of the arc chutes.

43

Merlin Gerin

BTP207E-3.200-généralité

to live bars A B 1000 400 1000 400 60 85

43

21/12/01, 10:14

Masterpact: connection

general

Conductor materials The terminals of Masterpact circuit breakers can be used to connect bare copper, tinned copper or tinned aluminium conductors without any special surface treatment.

016807

016806

Four types of connection are possible: c rear horizontal; c rear vertical; c front; c mixed. The terminals are sized to allow circuit breaker connection with bars up to 20 mm thick (except for the M40, M50 and M63).

Rear vertical connection

016808

025179

Front connection

electrodynamic forces

Rear horizontal connection

Mixed connection. Upper terminals: front connection. Bottom terminals: vertical connection.

c the first bar spacers must be located at less than a certain distance from the circuit breaker connection point;

c this maximum distance must be respected to withstand the electrodynamic forces that are applied between the bars during a short-circuit.

Maximum distance between circuit breaker connection point and the first bar spacers for various short-circuit currents Isc (kA) distance (mm)

30 350

50 300

65 250

80 150

150 150

Merlin Gerin

44 BTP207E-3.210-généralité

100 150

44

21/12/01, 10:16

Note: The indicated values come from tests and theoretical calculations made for the parameters given below. These tables are intended to serve as a general guide for connection design and not to replace experience acquired for a certain type of connection or the need for subsequent tests.

parameters used in establishing the tables

c maximum admissible bar temperature: 100 °C; c temperature in the switchboard around the circuit breaker and its connections: Ta; c copper busbars.

drawout circuit breakers

E31258

connection selection table

drawout circuit breakers, edgewise bars maximum current

Ta = 40 °C

800 1000 1250 1400 1600 1800 2000 2200 2500 2800 3000 3200 3600 4000 4700 5000 5100 5700 6300

M08 M10 M12 M16 M16 M20 M20 M25 M25 M32 M32 M32 M40 M40 M50 M50 M63 M63 M63

Masterpact

Ta = 50 °C number of bars 5 thick bars 10 thick bars 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.63 x 5 1b.63 x 10 2b.63 x 5 1b.63 x 10 2b.80 x 5 1b.80 x 10 2b.80 x 5 1b.80 x 10 2b.100 x 5 2b.63 x 10 2b.100 x 5 2b.63 x 10 4b.80 x 5 2b.80 x 10 4b.100 x 5 2b.100 x 10 5b.100 x 5 3b.80 x 10 6b.100 x 5 3b.100 x 10 4b.100 x 10 4b.100 x 10 5b.100 x 10 5b.100 x 10 5b.100 x 10 6b.100 x 10 6b.100 x 10

Masterpact M08 M10 M12 M16 M16 M20 M20 M25 M25 M32 M32 M40 M40 M50 M50 M50 M63 M63

Ta = 60°C number of bars 5 thick bars 10 thick bars 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.63 x 5 1b.63 x 10 2b.63 x 5 1b.63 x 10 2b.80 x 5 1b.80 x 10 2b.80 x 5 2b.50 x 10 2b.100 x 5 2b.63 x 10 2b.100 x 5 2b.63 x 10 4b.80 x 5 2b.80 x 10 4b.100 x 5 2b.100 x 10 6b.100 x 5 3b.100 x 10 3b.100 x 10 4b.100 x 10 4b.100 x 10 5b.100 x 10 5b.100 x 10 6b.100 x 10 6b.100 x 10

Masterpact M08 M10 M12 M16 M20 M20 M25 M25 M32 M32 M40 M40 M50 M50 M50 M63 M63

Merlin Gerin

BTP207E-3.210-généralité

number of bars 5 thick bars 10 thick bars 2b.50 x 5 1b.50 x 10 2b.63 x 5 1b.63 x 10 3b.50 x 5 2b.50 x 10 3b.50 x 5 2b.50 x 10 3b.63 x 5 2b.50 x 10 3b.80 x 5 2b.63 x 10 3b.100 x 5 2b.80 x 10 3b.100 x 5 2b.80 x 10 4b.100 x 5 3b.80 x 10 4b.100 x 5 3b.80 x 10 3b.100 x 10 4b.100 x 10 4b.100 x 10 5b.100 x 10 5b.100 x 10 6b.100 x 10 6b.100 x 10

45 45

21/12/01, 10:16

Masterpact: installation

fixed circuit breakers M08 to M32

dimensions E30742

553

E30749

necessary space for removing the arc chutes (with or without arc chute cover)

E30748

3 or 4 poles

438 493 378

90 130

45

311 (*) (*)

30 mini 60 maxi

150

400

11

68

11

422 (3p)

290

515

11

11

537 (4p)

(*) Datum

mounting on a base plate

mounting detail Ø14

E30775

E30766

E30765

on rails

B

Ø11

150

150

30 mini 60 maxi

A B

30 mini 60 maxi

A

3 poles 150 400

2 Ø11 x 6

4 poles 150 515

cut-outs holes for escutcheon

E30764

E30763

cut-outs de porte

152,5

270 14,5 148,5

(*) 71,5

69

27 37,5

80 mini

80 mini

325

11 Ø5

180

180

17,5

(*)

(*) Datum Merlin Gerin

48 BTP207E-3.230-M08…32

48

21/12/01, 10:17

Masterpact: installation

a

drawout circuit breaker M08 to M32

E30746

3 or 4 poles

"disconnected" position

E30747

dimensions E30741

45

a 439

800 mini

(*)

60

101

175

55

325

55

128

435 (3p)

85

367

55

425

70

550 (4p)

(*)

(*) Datum

mounting

mounting detail

E30768

E30767

E30775

on rails

on a base plate

Ø14

B

Ø11

101

175

101

cut-outs

E30761

front panel cut-out

A B

175

A

3 poles 175 325

2 Ø11 x 6

4 poles 175 425

holes for escutcheon

E30760

ACB's side

152,5

270

148,5

71,5

47

55

100 mini ACB's basis

100 mini

325

Merlin Gerin

BTP207E-3.230-M08…32

19

69

18,5

11 Ø5

180

180

17,5

49

49

21/12/01, 10:17

Masterpact: installation

fixed circuit breaker M40

dimensions E31226

E30752

necessary space for removing the arc chutes (with or without arc chute cover) 90

45

819

E30753

3 or 4 poles

553 759 493

130

311 (*) (*)

30 mini 60 maxi

150 290

11

515

11

68

537 (3p)

11

780 11

802 (4p) (*) Datum

mounting on a base plate

mounting detail E30775

E30772

E30771

on rails

Ø14

B

Ø11

150

50 maxi

150

50 maxi

A B

30 mini 60 maxi

30 mini 60 maxi

A

3 poles 150 515

2 Ø11 x 6

4 poles 150 780

cut-outs holes for escutcheon

E30764

E30763

front panel cut-out

152,5

270 14,5 148,5

(*) 71,5

69

27 37,5

80 mini

80 mini

325

11 Ø5

180

180

17,5

(*)

(*) Datum Merlin Gerin

50 BTP207E-3.240-M40

50

21/12/01, 10:17

Masterpact: installation

a

drawout circuit breaker M40

E30743

E30750

3 or 4 poles

"disconnected" position

E30751

dimensions

45

a 439 484

(*)

800 mini

128

(1)

60

101

55

425

70

85

175

550 (3p)

367

60

55

350

350

815 (4p)

(*)

(*) Datum (1) 4-pole version only.

mounting

on a base plate

mounting detail

E30777

E30773

E30774

on rails

40

40

30

350

150

350

101

101

175

(1) 4-pole version only.

cut-outs

front panel cut-out

2 Ø11 x 6 (3p) 6 Ø11 x 22 (4p)

175

holes for escutcheon

ACB's side

E30760

E30762

175

(1)

(1)

152,5

270

47

19

45 (1)

55

100 mini

325

ACB's basis

(1) 4-pole version only.

69

18,5

11 Ø5

180

180

17,5

51

Merlin Gerin

BTP207E-3.240-M40

148,5

71,5

51

21/12/01, 10:17

Masterpact: installation

fixed circuit breaker M40

dimensions E31226

E30752

necessary space for removing the arc chutes (with or without arc chute cover) 90

45

819

E30753

3 or 4 poles

553 759 493

130

311 (*) (*)

30 mini 60 maxi

150 290

11

515

11

68

537 (3p)

11

780 11

802 (4p) (*) Datum

mounting on a base plate

mounting detail E30775

E30772

E30771

on rails

Ø14

B

Ø11

150

50 maxi

150

50 maxi

A B

30 mini 60 maxi

30 mini 60 maxi

A

3 poles 150 515

2 Ø11 x 6

4 poles 150 780

cut-outs holes for escutcheon

E30764

E30763

front panel cut-out

152,5

270 14,5 148,5

(*) 71,5

69

27 37,5

80 mini

80 mini

325

11 Ø5

180

180

17,5

(*)

(*) Datum Merlin Gerin

50 BTP207E-3.240-M40

50

21/12/01, 10:17

Masterpact: installation

a

drawout circuit breaker M40

E30743

E30750

3 or 4 poles

"disconnected" position

E30751

dimensions

45

a 439 484

(*)

800 mini

128

(1)

60

101

55

425

70

85

175

550 (3p)

367

60

55

350

350

815 (4p)

(*)

(*) Datum (1) 4-pole version only.

mounting

on a base plate

mounting detail

E30777

E30773

E30774

on rails

40

40

30

350

150

350

101

101

175

(1) 4-pole version only.

cut-outs

front panel cut-out

2 Ø11 x 6 (3p) 6 Ø11 x 22 (4p)

175

holes for escutcheon

ACB's side

E30760

E30762

175

(1)

(1)

152,5

270

47

19

45 (1)

55

100 mini

325

ACB's basis

(1) 4-pole version only.

69

18,5

11 Ø5

180

180

17,5

51

Merlin Gerin

BTP207E-3.240-M40

148,5

71,5

51

21/12/01, 10:17

Masterpact: installation

fixed circuit breaker M50

dimensions

90

45

E30757

E30756

necessary space for removing the arc chutes (with or without arc chute cover)

E31227

3 poles

819 759

130

311

(*) (*) 30 mini 60 maxi

150

780

11

68

11

802

290

(*) Datum

mounting on a base plate

mounting detail E30775

E30772

E30771

on rails

Ø14

B

Ø11

150

50 maxi

150

50 maxi

A B

30 mini 60 maxi

30 mini 60 maxi

A

2 Ø11 x 6

3 poles 150 780

cut-outs holes for escutcheon

E30764

E30763

front panel cut-out

152,5 270

14,5 148,5

(*)

71,5

69

27 37,5

80 mini

80 mini

325

11 Ø5

180

180

17,5

(*)

(*) Datum Merlin Gerin

52 BTP207E-3.250-M50

52

21/12/01, 10:18

Masterpact: installation

a

drawout circuit breaker M50

E30744

3 or 4 poles

"disconnected" position

E30755

E30754

dimensions

45

45

a 484

800 mini

(*)

128 60

101

175

60

85

55

350

350

815 (3p)

367

40

475

55

475

1045 (4p)

(*)

(*) Datum

mounting

on a base plate

mounting detail

E31228

E30770

E30769

on rails

40

40

30

350

150

350

175

101

101

175

cut-outs

175

holes for escutcheon

front panel cut-out

E30762

6 Ø11 x 22 (3p) 6 Ø11 x 33 (4p)

E30760

ACB's side

152,5

270

47

19

45 (1)

55

100 mini

325

ACB's basis

(1) 4-pole version only. Merlin Gerin

BTP207E-3.250-M50

148,5

71,5

69

18,5

11 Ø5

180

180

17,5

53

53

21/12/01, 10:18

Masterpact: installation

a

drawout circuit breaker M63

E30745

3 poles or 4 poles

"disconnected" position

E30759

E30758

dimensions

45

45

a 484

800 mini

(*)

128 60

101

175

40

85

55

475

475

1045

367

(*)

(*) Datum

mounting on a plate

mounting detail

E30778

E30770

E30769

on rails

40

40

30

475

150

475

175

101

101

175

cut-outs

175

holes for escutcheon

front panel cut-out

side of c.b.

E30760

E30762

6 Ø11 x 33

152,5

270

47

148,5

71,5

19

55

325

45 (1)

18,5

100 mini

11 Ø5

base of c.b.

(1) 4-pole version only.

180

180

17,5

Merlin Gerin

54

BTP207E-3.260-M63+inv sour

69

54

21/12/01, 10:18

Masterpact: installation

source-changeover system

Interlocking by connecting rods for 2 stack-mounted breakers drawout pattern, 3 or 4 poles E30780

E30779

fixed pattern, 3 or 4 poles

50 50 5 52

40

30

14

30

125

125

900 max.

900 max. 900 max.

175

153

105

(*)

163

30 base of c.b. 180 30 mini 60 maxi

45 65 166

base of c.b. for ratings : M08 to M40 (3p)

base of c.b. for ratings : M40 (4p) to M63

(*)

82 (*)

44 (*)

Interlocking by connecting rods for 3 stack-mounted breakers fixed pattern, 3 or 4 poles E30782

E30781

drawout pattern, 3 or 4 poles

50 5

40

52

180

60

14

60

14

60

180 900 max.

900 max.

50

50 5

40

52

180

60

180 900 max.

900 max.

153

175

900 max.

105

(*)

163

45 65 166

base of c.b. for ratings : M08 to M40 (3p)

base of c.b. for ratings : M40 (4p) to M63

100

(*)

30 base of c.b. 180 30 mini 60 maxi

62 (*)

(*) Datum Merlin Gerin

BTP207E-3.260-M63+inv sour

55 55

21/12/01, 10:18

Masterpact: installation

source-changeover system

Interlocking by cables for 2 side-by-side breakers E30783

fixed or drawout patterns, 3 or 4 poles 2m maxi

200 mini r= 120 mini

r= 120 mini

automatic source-changeover system

7

8

9

10

11 1 2 1 3 1 4 1 5 1 6

E33352

6

H48

5

E30784

E33353

electrical interlocking IVE

mounted on a frame

1

2

3

4

H47 H43

H49 R

N

controller P58

L33

P62

L34 L35

M32(4p) M40(3p) M32(3p)

E33354

E33355

auxiliaries control plate ACP and controller UA/BA

2100

P60

1940 H51

1640

H50

H52

940

P61 P59 P63

L36 L37

panel cut-out for controller UA/BA

56

56

56

E33364

E33363

150 56

600

750 C34

C34

Dimensions (mm) type C34 H43 140 120

H47 151

H48 137

H49 160

H50 200

H51 255

H52 22

L33 6

L34 48

L35 84

L36 138

L37 150

P58 61,5

P59 170

P61 90

P62 P63 150(min) 187 Merlin Gerin

56 BTP207E-3.270-inv sour+M08N

P60 95

56

21/12/01, 10:19

Masterpact: connection

fixed and drawout circuit breakers M08N/M10N/M12N fixed circuit breaker front connection

rear connection

front connection E30786

E30785

horizontal terminals vertical terminals

115

115

85 45

12,5

front connectors screen

115 25

10

N (1)

10

25

112

horizontal terminals

15

17

115

E30787

12,5 107

115

85

115 45

23

17,5

(*)

rear connection

132

53

175 (**)

2 Ø12

50

335

25

10

(*) 12,5

221

2 Ø12

10 233

(*) 12,5

vertical terminals E30788

278

115

115

85

115

10

2 Ø12

(*) Datum.

(*)

(**) Hole for securing front connection support bracket. (1) On request, neutral on the right.

drawout circuit breaker front connection

rear connection

front connection

E30789

E30790

horizontal terminals vertical terminals

115

115

115

47,5 80 25 25

front connectors screen

12,5

15

N (1)

3 Ø12

10

(*) 45

rear connection 112

25

92

10

horizontal terminals

112

74,5

115

E30791

306

115

25 12,5

273 300,5

12,5

47,5 45

25

30 175

115

10

15 12,5

2 Ø12

10

(*)

306

vertical terminals E30792

(*)

115

115

47,5

8

2 Ø12

(*) Datum.

(*)

(1) On request, neutral on the right. Merlin Gerin

BTP207E-3.270-inv sour+M08N

115

57

57

21/12/01, 10:19

Masterpact: connection

fixed and drawout circuit breaker M50 to M63 fixed circuit breaker M50 rear connection 3 poles vertical terminals

E30819

horizontal terminals

100

30 200

112

53 (*)

25

25 25 25 52

15

246

55 306

12,5 15

drawout circuit breaker M50 rear connection 3 or 4 poles vertical terminals

E30810

horizontal terminals

100 30 112 25 157 25 25

92 137

79,5 12,5 43

25 15

345

363

15

(*)

drawout circuit breaker M63 rear connection 3 or 4 poles vertical terminals

E30820

horizontal terminals

100 30 112 25 157 25 25

92 137

79,5 12,5 25

43

15

345

363

15

(*) (*) Datum. Merlin Gerin

64 BTP207E-3.310-raccord M50-M63

64

21/12/01, 10:22

fixed circuit breaker M50 rear connection 3 poles vertical terminals 248

E30826

E30827

horizontal terminals

248

248

213

248

226

142,5 35

142,5

Ø12

213

10

10

25 25 25

20

13

145

20 Ø12

175

145 (*)

(*)

drawout circuit breaker M50 rear connection 3 poles vertical terminals

E30828

E30829

horizontal terminals

252,5

252,5

252,5

252,5 10

Ø12

220 12,5

100 72,5

100

10

25 25 25 45 25 25 25

Ø12 145

(*)

(*)

rear connection 4 poles

297,5

vertical terminals

245

245

100

100 12,5

12,5

N

245

245

100

35 10

220

25 25 25

297,5

E30831

E30830

horizontal terminals

72,5

10

10

Ø12

10

25 25 25 45 25 25 25

N

Ø12

(1) 70

(*)

(1)

145 (*)

drawout circuit breaker M63 rear connection 3 poles vertical terminals E30823

horizontal terminals

E30822

350

350

350

350

117,5 92,5

117,5

10

Ø12

260

10

25 25 25 85 25 25 25

Ø12

(*)

185

(*)

rear connection 4 poles vertical terminals

E30824

E30825

horizontal terminals

206 100

287

287

260

260

206

287

Ø12

10

10

25 25 25 85 25 25 25

N

N

Ø12 (*)

(1) (*) Datum.

(1) 70

185 (*)

(1) On request, neutral on the right. Merlin Gerin

BTP207E-3.310-raccord M50-M63

117,5 92,5

260

25 25 25

287

35

117,5

65 65

21/12/01, 10:22

Masterpact: connection

fixed and drawout circuit breaker M40 fixed circuit breaker rear connection 3 or 4 poles vertical terminals

E30809

horizontal terminals

100

30 112 252 53 (*)

25

25 25 25

15

243

55 306

12,5 15

(*) Datum.

drawout circuit breaker rear connection 3 or 4 poles vertical terminals

E30810

horizontal terminals

100 30 112 25 157 25 25

92 137

79,5(4p) 12,5 175

34,5(3p) 15

345

363

15

(*)

(*) Datum. Merlin Gerin

62 BTP207E-3.300-raccord M40

62

21/12/01, 10:22

fixed circuit breaker rear connection 3 poles

180 100

vertical terminals 165

E30812

E30811

horizontal terminals 85

130

25 25 25

172,5

85 35

80

100

25 25 25

172,5 145

10

10

12,5

12,5

Ø12 (*)

Ø12

80 (*)

rear connection 4 poles

230 100

vertical terminals

216

165

100

85

130

25 25 25

208,5

172,5

85 35

80

100

25 25 25

230

E30814

E30813

horizontal terminals

80

145

10

10

12,5

12,5 Ø12

N

Ø12

(1)

N

(*)

80

(1)

(*)

(*) Datum. (1) On request, neutral on the right.

drawout circuit breaker rear connection 3 poles

E30815

155

vertical terminals 155

100 12,5

E30816

horizontal terminals 65

172,5

35

155

25 25 25

47,5

172,5 10

10

25 25 25 40

Ø12 (*)

Ø12

70 (*)

rear connection 4 poles vertical terminals

230 155

191 155

155 100

65

230

E30818

E30817

horizontal terminals

208,5

25 25 25

N

47,5 35

155

10

10

25 25 25 40

12,5

Ø12 Ø12

(1)

172,5

(*)

N

70

(1)

(*)

(*) Datum. (1) On request, neutral on the right. Merlin Gerin

BTP207E-3.300-raccord M40

63 63

21/12/01, 10:22

Masterpact: connection

fixed circuit breakers M20L/M25L/M32H fixed circuit breaker front connection

rear connection

front connection 115

E30901

E30802

horizontal terminals vertical terminals

115

85

115 80 25 25

15

front connectors screen

15

N (1)

3 Ø12

100 335

rear connection

112

horizontal terminals

25 162

87

18

12,5

15 18

(*) 221

30

E30803

25 25

53

175 (**)

(*)

30

115

140

115

72,5 85,5 25 25

7

11,5

15

15

3 Ø12

(*)

236 268 E30804

vertical terminals 115

140

140

60 25

4 Ø12

(*)

(*) Datum. (**) Hole for securing front connection support bracket. (1) On request, neutral on the right. Merlin Gerin

60 BTP207E-3.290-raccorde

60

21/12/01, 10:20

Masterpact: connection

drawout circuit breakers M20L/M25L/M32H drawout circuit breaker front connection

rear connection

front connection 115

E30805

E30806

horizontal terminals vertical terminals

125

125

37,5 100 25 25 25

front connectors sceen

12,5

15

N (1)

30

4 Ø12

(*)

100

rear connection

363 112

115

E30807

92

horizontal terminals 25 157 25 25

125

37,5 100

34,5 37

125 25 25 25

15

329 344

12,5

12,5 4 Ø12

30

(*)

15 344

15

vertical terminals E30808

(*)

115

152,5

152,5

10 25

4 Ø12

(*)

(*) Datum. (1) On request, neutral on the right. Merlin Gerin

BTP207E-3.290-raccorde

61 61

21/12/01, 10:20

Masterpact: connection

fixed and drawout circuit breakers M08H,L/M10H,L/M12H,L/M16N,H,L fixed circuit breaker rear connection

front connection

E30793

horizontal terminals vertical terminals front connectors screen

115

E30901

front connection

115

85

115 80

12,5

25 25

15

N (1)

10

112

107

15

horizontal terminals

17

17,5

115

E30832

15

(*)

rear connection

132 25 25

53

175 (**)

3 Ø12

80

335

115

115

85 80

8

25 25

15

(*) 12,5

221 10 233

12,5

(*)

115

85

vertical terminals 115

E30794

278

3 Ø12

115

10

3 Ø12

(*) Datum.

(*)

(**) Hole for securing front connection support bracket. (1) On request, neutral on the right.

drawout circuit breaker rear connection

front connection

E30795

horizontal terminals vertical terminals

115

E30790

front connection

115

115

47,5 80 25 25

front connectors screen

12,5

15

N (1)

3 Ø12

10

(*) 80

rear connection

306

112

92 15

horizontal terminals E30796

25 112 25

115

115

115

25 25

30 175

25 12,5

273 300,5

12,5

47,5 80

57

15

15 12,5

3 Ø12

10

(*) 306

vertical terminals E30797

(*)

115

115

47,5

10

3 Ø12

(*) Datum.

(*)

(1) On request, neutral on the right.

Merlin Gerin

58 BTP207E-3.280-raccorde

115

58

21/12/01, 10:19

Masterpact: connection

fixed and drawout circuit breakers M20N,H/M25N,H fixed circuit breaker rear connection

front connection

E30798

horizontal terminals vertical terminals

E30901

front connection

115

115

80 25 25

12,5

front connectors screen

85

115

15

N (1) 20

335

25 25

152

horizontal terminals 115

E30832

53

115

115

15

18

85 80

15 3

107

(*)

rear connection

112

175 (**)

3 Ø12

80

25 25

17,5

15

12,5

(*) 12,5

221

3 Ø12

16

(*)

233 283 E30799

vertical terminals 115

115

85

115 20

3 Ø12

(*) Datum.

(*)

(**) Hole for securing front connection support bracket. (1) On request, neutral on the right.

drawout circuit breaker rear connection

front connection

E30800

horizontal terminals vertical terminals

115

E30790

front connection

115

115

47,5 80 25 25

front connectors screen

12,5

15

N (1)

3 Ø12 (*)

20

80

rear connection

306

112

92 15

horizontal terminals 115

E30796

25 112 25

115

115

25 25

30 175

25 12,5

273 300,5

12,5

47,5 80

62

15

15 12,5

3 Ø12

20

(*) 306

vertical terminals E30801

(*)

115

115

47,5

16

3 Ø12

(*) Datum.

(*)

(1) On request, neutral on the right. Merlin Gerin

BTP207E-3.280-raccorde

115

59 59

21/12/01, 10:19

Masterpact: connection

E30721

wiring diagrams STR 18 M / 28 D / 38 S / 58 U CHASSIS AUXILIARIES CN 1

- CN

BREAKER AUXILIARIES

CONTROL UNIT

+ Fu

AT

fault

disconnected

connected

closed

ready to close

BPO

BPF

open

springs charged 314 312 324 322 334 332 344 342 352 354 362 364 372 374

82

84

212 222

234 244

12

14

24

22

32

34

44

42

D4

C12

C2

A4 252 254 262 B4

CE or

MN or MNR

M MX

XF MX

OF F

F

O

O CH

SDE

processing unit

CD

311

321

331

341

351

361

PF

CT

371

81

211 221

231 241

11

21

31

41

D1

C11

C1

A1

251

B1

Fu

- CN



AT: BPO: BPF: CE:

emergency off "open" pushbutton "close" pushbutton "connected" position contact (10 A/240 V AC) M: spring charging motor (180 VA/240 V AC) XF: closing release (20 VA/240 V AC) MX: shunt release (20 VA/240 V AC) MN: undervoltage release (20 VA/240 V AC) MNR: time delayed undervoltage release (20 VA/240 AC) OF: auxiliary changeover contacts (10 A/240 V AC) O: 2 auxiliary NO contacts (10 A/240 V AC) F: 2 auxiliary NC contacts (10 A/240 V AC) SDE: fault trip indication contact (10 A/240 V AC) CH: charging motor limit switch contact PF: "ready to close" contact (10 A/240 V AC) (closing possible if breaker is open, not locked and operating mechanism charged) CD: "disconnected" position contact (10 A/240 V AC) CT: test posiiton contact (10 A/240 V AC)

c diagram shown with circuits deenergised, breaker open and in "connected" position, springs charged and relays in released position; c accessories such as pushbuttons, lamps and fuses are not supplied with the circuit breaker.

Wiring of the MNR (modified diagram). Instantaneous tripping with MNR when contact 254-262 opens. E30718

CN2

D4

254

MNR D1

Note: the wiring of the external contact replaces the spring charged indication and the contact PF.

Merlin Gerin

66 BTP207E-3.320-raccord

262

66

21/12/01, 10:23

Masterpact: connection

E30720

wiring diagrams STR 28 D / 38 S / 58 U with options CHASSIS AUXILIARIES CN 1

- CN

BREAKER AUXILIARIES

CONTROL UNIT

+ Fu

N P1

S1

P2

S2

AT

(4)

(4) LR alarm

disconnected

connected

372

374

362 364

354

342

352

344

332

322

324

334

312

314

(2) Z11 Z12

LR2

BPF

closed

fault

ready to close

BPO

open springs charged

Ic1 Ic2 V2

T2 T1

R1 R2

e+ e–

82

(5) 84 212 222

234 244

12

14

22

24

32

34

42

44

D4

C12 C2

A4 252 254 262 B4

CE or MN or MNR

T

M MX

XF MX

OF F F

F

O

O

V CH

SDE ammeter

ALR

PF

processing unit

CD

311

321

331

341

351

361

C

R

CT

371

Z21

Z22 (3)

LR1

F2 F1

V1

C

81 211 221

231 241

11

21

41

31

D1

C11 C1

A1

251

B1

power supply (1)

Fu



AT: BPO: BPF: LR: CR: T: CE:

emergency off "open" pushbutton "close" pushbutton long time trip (LT) indicating lamp short time trip (ST) indicating lamp earth fault trip indicating lamp "connected" position contact (10 A/240 V AC) M: spring charging motor (180 VA/240 V AC) R: load monitoring and control XF: closing release (20 VA/240 V AC) T: earth fault protection (EZ and SZ: input and output for zone selective interlocking) MX: shunt release (20 VA/240 V AC) MN: undervoltage release (20 VA/240 V AC) MNR: time delayed undervoltage release (20 VA/240 V AC) OF: auxiliary changeover contacts (10 A/240 V AC) O: 2 auxiliary NC contacts (10 A/240 V AC) F: 2 auxiliary NC contacts (10 A/240 V AC) SDE: fault trip indication contact (10 A/240 V AC) CH: charging motor limit switch contact F: fault trip local indicator FV: segregated fault trip indication contact (5 A/240 V AC) PF: "ready to close" contact (10 A/240 V AC) (closing possible if breaker is open, not locked and operating mechanism charged)

CD: CT: C:

"disconnected" position contact (10 A/240 V AC) test position contact (10 A/240 V AC) communication.

c Ic1: load shedding command according to Ic1 setting Ic2: load shedding command according to Ic2 setting; c diagram shown with circuits deenergised, breaker open and in "connected" position, springs charged and relays in released position; c accessories such as pushbuttons, lamps and fuses are not supplied with the circuit breaker.

Wiring of the MNR (modified diagram). Instantaneous tripping with MNR when contact 254-262 opens. E30718

- CN

D4

D1

Note: the wiring of the external contact replaces the spring charged indication and the contact PF.

V contact wiring: for breaker locking, depending on the selected fault. CN1/CN + BPO C2

V V (1) Power supply terminals for I or T or F options (AD module with BAT battery module for backup power). (2) Zone selective interlocking with line side breaker. (3) Zone selective interlocking with load side breaker (remove jumper). (4) DC power supply. R contacts reset request wiring of an external contact. (5) With Z and/or C options, terminal 84 is not available.

CN2/CN –

V

MX C1

Selective locking needs: c external power supply (F1, F2); c an additional terminal (BS).

Merlin Gerin

BTP207E-3.320-raccord

262

254

MNR

E30719

CN2

67 67

21/12/01, 10:23

Masterpact: connection

E30722

wiring diagrams STR 68 U with options m01 to m31 CHASSIS AUXILIARIES CN 1

- CN

BREAKER AUXILIARIES

CONTROL UNIT

+ Fu

N P1

S1

P2

S2

AT

(5)

disconnected

connected

closed

ready to close

BPO

BPF

open

374

372

362 364

352 354

332

342

334

344

322

324

312

314

springs charged T21

T2 T1(3)

T22

234 244

82 212 222

12

14

22

24

32

34

42

44

D4

C12

A4 252 254 262 B4

C2

CE or MN or MNR

M MX

XF MX

OF F

F

O

O CH

SDE EZ(4) M01 to M16

processing unit

CD

311

321

331

341

351

361

PF

CT

371

F1 F2 F12 F11 512 522 532 542 552 562 + power supply (2)

81

211 221

231 241

11

21

31

41

D1

C11

C1

A1

251

B1

E56

E55

E54

E53

E52

E51

MR6

411 412 414 421 422 424 431 432 434 441 442 444 451 452 454 461 462 464

power supply (1)

E2



Fu

AT: BPO: BPF: CE: M: XF: MX: MN: MNR: OF: O: F: SDE: CH: M01: to M16

PF:

MR6:

- CN



emergency off "open" pushbutton "close" pushbutton "connected" position contact (10 A/240 V AC) spring charging motor (180 VA/240 V AC) closing release (20 VA/240 V AC) shunt release (20 VA/240 V AC) undervoltage release (20 VA/240 V AC) time delayed undervoltage release (20 VA/240 V AC) auxiliary changeover contacts (10 A/240 V AC) 2 auxiliary NO contacts (10 A/240 V AC) 2 auxiliary NC contacts (10 A/240 V AC) fault trip indication contact (10 A/240 V AC) charging motor limit switch contact indication option equipped with 6 opto-decoupled outputs to contacts (0.2 A/24 V DC), for programming as per table on page C54 (EZ: input for earth fault protection zone selective interlocking) "ready to close" contact (10 A/240 V AC) (closing possible if breaker is open, not locked and operating mechanism charged) relay module with 6 changeover contacts (3 A, 24 V DC)

CD: CT:

Wiring of the MNR (modified diagram). Instantaneous tripping with MNR when contact 254-262 opens.

"disconnected" position contact (10 A/240 V AC) test position contact (10 A/240 V AC).

c diagram shown with circuits deenergised, breaker open and in "connected" position, springs charged and relays in released position; c accessories such as pushbuttons, lamps and fuses are not supplied with the circuit breaker.

E30718

CN2

D4

254

MNR D1

Note: the wiring of the external contact replaces the spring charged indication and the contact PF.

(1) Power supply for control unit and modules. (2) Power supply for option M and module MR6 by module AD. (3) Terminals T1 and T2 must be imperatively short-circuited when the external CT is not connected. (4) The zone selective interlocking output is provided by one output of module m01 to m32.. (5) Zone selective interlocking with load side breaker: remove the jumper. Merlin Gerin

68 BTP207E-3.330-raccord

262

68

21/12/01, 10:24

relay outputs

basic version m01 other versions m02 m03 m04 m05 m06 m07 m08 m09 m10 m11 m12 m13 m14 m15 m16

transmission m17 reception outputs m18 m19 m20 m21 m22 m23 m24 m25 m26 m27 m28 m29 m30 m31

terminal number 512

522

LT

ST/Inst.

LT LT LT limit 2 LT LT LT LT LT limit 2 LT limit 1 limit 1 Z LT 512 ST/Inst. ST/Inst. T T T Z Z Z T ST/Inst. ST/Inst. limit 2 shed 2 reconn. 2 shed 1

ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST 522 LT AS ST/Inst. AS Z AS limit 1 shed 1 shed 1 limit 1 shed 1 limit 1 shed 1 shed 1 AS

Protection: LT long time trip indication ST/Inst. short time or instantaneous trip indication T earth fault trip indication Z zone selective interlocking output Load monitoring and control: limit 1 indication of Ic1 setting overrun limit 2 indication of Ic2 setting overrun shed 1 load shedding command according to Ic1 setting (limit 1) shed 2 load shedding command according to Ic2 setting reconn. 2 load reconnection command according to Ic2 setting (limit 2)

532

542

552

562

shed 1 shed 1 shed 1 shed 1 shed 1 shed 1 limit 1 shed 1 shed 1 shed 1 shed 1 shed 1 shed 1 shed 1 T 5 ▲

shed 2 reconn. 1 shed 2 shed 2 reconn. 2 shed 2 Z shed 2 shed 2 shed 2 reconn. 2 shed 2 shed 2 reconn. 2

AS limit 1 limit 1 limit 1 limit 1 limit 1 T T T T T T T T T Inst. 1 ▲

limit 2 limit 2 AS AS AS limit 1 AS AS Z limit 1 Z AS Z AS AS 6 ▲

9 ▲

data transmission

e+ output

e– output

s+ input

s– input









connection modification for data transmission: options m17 to m31 E30723

module

T2

T1

T21

datatransmission

M17 to M31

processing unit

T22

e+

e–

r+

r–

self-monitoring: AS indication of control unit fault or overtemperature. F1

F2

F12 F11

+

532 542 552 562

512 522



power supply (2)

1

2

3

4

(3) 0V

4 5 8 9

ET 44 interface (1) (3) S1 (4) S2 (4)

24V

(1) Communication interface for RS485 - 9600 baud network. (2) Power supply for m option and ET44 interface (AD module). (3) Provided connectors. (4) Remote controlled relay output (10 A, 220 V AC). (5) JBUS, RS485, 9600 baud network.

1

2

1

3

Sub D9 connector (5)

2

(3)

Merlin Gerin

BTP207E-3.330-raccord

3

RD– TD– RD+ TD+

69 69

21/12/01, 10:24

Masterpact: connection

wiring diagrams STR 68 U with options m01 to m31 (cont.)

T2

T1

T21

E30725

E30724

power supply connection T22

module P

1 3

2 1 3

r– S1 S2 r+ 4 e– 3 ET 44 e+ 2 1

2 4 5 8 9

RD– TD– Sub D 9 RD+ connector (6) TD+

H1

H2

H1

H2

H4

BAT H4

processing unit

H3

H3

(4)

M17 to M31

e+e–r+ r–

Sub D 9 connector (1)

Sub D 15 connector module P

F1 F2

F12

F11 512 522 (7) (7) (7)

N L1 L2 L3 CN1 CN2 H1 H2 H3 H4

(5) + – power supply (2)

power supply for control units and complementary functions

(3)

All the protection functions of the control unit are powered by current sensors built into the circuit breaker. However power must be supplied: c to terminals F1 and F2 for the indication and display functions: v if the device has a low 3-phase load (less than 20% of the rated current) or a singlephase load, v if display and indications are required when the circuit breaker is off; c to terminals F11 and F12 for the M modules.

(1) Provided cable: length 1.5 m (connected to chassis). (2) Available supply sources: 24-48 V DC, 125 V DC, 100-240 V AC. (3) Backup power for trip unit information with BAT module (remove jumpers). (4) Provided cable. (5) Voltage connection (load side shown, line side also available). 3 or 4 poles available. (6) JBUS, RS 485-9600 baud network. (7) MR6 module wiring.

To ensure proper isolation of the circuits, two separate power supplies are required. They can be implemented as follows: c for terminals F1 and F2: v by direct supply of AC current (specify the required voltage when ordering: 100, 220, 380 V 50/60 Hz), v or by an AD module, with or without BAT (1 AD for each STR68), v or by direct supply of 24 V DC current (5 W, Class 2 insulation, < 10% ripple); c for terminals F11 and F12: v by another AD module (1 AD for each STR68, in addition to the modules supplying terminals F1 and F2), v or by direct supply of 24 V DC current, isolated from the circuit supplying terminals F1 and F2 (5 W, Class 2 insulation, < 10% ripple).

Merlin Gerin

70 BTP207E-3.340-raccord

70

21/12/01, 10:24

control unit STR 68 without power module E30728

E30727

AC supply without indicators maintained after tripping

control unit F1

M01 to M16 option

F2

F11

module MR6

control unit

F12

-

F1

M17 to M31 option

F2

F11

+

module ET 44

F12

-

0V

24V

+

module AD

module AD

110 - 220 - 380 V 50/60 Hz

110 - 220 - 380 V 50/60 Hz

AC supply with indicators maintained after tripping

E30729

E30730

DC supply with or without indicators maintained after tripping

control unit F1

M01 to M16 option

F2

F11

module MR6

F12

control unit F1

F2

M17 to M31 option F11

F12

module BAT

-

module BAT

+

-

module BAT

+

module AD

-

module AD

0V

24V

+ module BAT

+

-

module AD

110 - 220 - 380 V 50/60 Hz 24/30 - 48/60 - 110/125 V CC

module ET44

+ module AD

110 - 220 - 380 V 50/60 Hz 24/30 - 48/60 - 110/125 V CC

STR 68 control unit with power module E30732

E30731

AC or DC supply with or without indicators maintained after tripping

control unit F1

module BAT

F2

M17 to M31 option F11

F12

module P Cn1+

control unit

module MR6 F1

module BAT

F2

M01 to M16 option F11

module MR6

F12

module P Cn1+

Cn2-

Cn2-

100/240 V 50/60 Hz 24/28 - 125 V CC

100/240 V 50/60 Hz 24/28 - 125 V CC

Note: the battery module (BAT) provides back up power to the indicators on the trip unit front face to maintain indications after tripping. It can be omitted if the auxiliary supply is reliable. Merlin Gerin

BTP207E-3.340-raccord

71 71

21/12/01, 10:24

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.) electrical interlocking - 2 sources + 1 coupling and lockout after fault (688189) possible states source 1 0 1 source 2 0 1 coupling 0 0

E33097

Version represented: c 2 sources + 1 coupling; c 2 circuit breakers closed; c electrical interlocking with lockout after a fault (SDE wiring): inoperative with automatic reset option.

"SOURCE 1" BREAKER AUXILIARIES

S1

1 0 1

0 1 1

1 0 0

0 1 0

0 0 1

"SOURCE 2" BREAKER AUXILIARIES

"COUPLING" BREAKER AUXILIARIES

S2

CN1 CN2

D to A

t1

COUPLING t2

t3

t4

R1

B4

262

254

252

A4

C2

34

32

84

24

22

82

322

14

12

CE

312 324

B4

262

254

252

A4

C2

34

32

84

24

22

82

322

14

314

CE

XF

12

CE

312 324

B4

262

254

252

A4

C2

34

32

84

24

22

82

322

14

314

CE

R3 12

312 324

314

R2

M MX Q1

OF

OF

CE

XF

CE

M

OF MX SDE

QC

OF

OF

XF

OF

M

CH

MX SDE

PF

OF

Q2

OF

CH

OF SDE

PF

Q1: QC: Q2: D: t1:

Masterpact on source 1 Masterpact used for coupling Masterpact on source 2 P25M circuit breaker (2 x 10 A) coupling signal: «source 1 failure» (minimum time delay 250 ms) t2: coupling signal: «source 2 failure» (minimum time delay 250 ms) t3: uncoupling signal: «source 1 restored» (minimum time delay 250 ms) t4: uncoupling signal: «source 2 restored» (minimum time delay 250 ms) R1,R2,R3: external relays for interlocking of SDE auxiliary switches.

M: XF: MX: CE: OF: SDE: CH: PF:

motor mechanism closing release shunt release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).

B1

A1

C1

31

81

21

251

A

c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system. The relays are not supplied with the circuit breakers.

Merlin Gerin

88 BTP207E-3.430-raccord

11

321

311

B1

251

A1

C1

31

81

21

11

321

311

B1

251

A1

C1

31

81

21

11

321

311

CH PF

88

21/12/01, 10:27

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.) electrical interlocking - 2 sources + 1 coupling and wihtout lockout after fault (688190) possible states source 1 0 1 source 2 0 1 coupling 0 0

E33098

Version represented: c 2 sources + 1 coupling; c 2 circuit breakers closed; c electrical interlocking without lockout after a fault.

"SOURCE 1" BREAKER AUXILIARIES

S1

1 0 1

0 1 1

1 0 0

0 1 0

0 0 1

"SOURCE 2" BREAKER AUXILIARIES

"COUPLING" BREAKER AUXILIARIES

S2

CN1 CN2

D to A

t1

COUPLING t2

t3

B4

262

254

252

A4

C2

34

32

24

22

14

322

CE

XF

12

312 324

314

B4

262

254

252

A4

C2

34

32

24

22

14

322

12

CE

312 324

314

B4

262

254

252

A4

C2

34

32

24

22

14

322

12

312 324

314

t4

M MX Q1

OF

OF

CE

XF

OF

M XF

MX QC

OF

OF

M

OF MX

CH PF

Q2

OF

OF

OF

CH PF CH

Q1: QC: Q2: D: t1: t2: t3:

t4:

Masterpact on source 1 Masterpact used for coupling Masterpact on source 2 P25M circuit breaker (2 x 10 A) coupling signal: «source 1 failure» (minimum time delay 250 ms) coupling signal: «source 2 failure» (minimum time delay 250 ms) uncoupling signal: «source 1 restored» (minimum time delay 250 ms) uncoupling signal: «source 2 restored» (minimum time delay 250 ms)

M: XF: MX: CE: OF: SDE: CH: PF:

motor mechanism closing release shunt release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).

251

A1

C1

31

21

11

B1 A

c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system.

Merlin Gerin

BTP207E-3.430-raccord

321

311

B1

251

A1

C1

31

21

11

321

311

B1

251

A1

C1

31

21

11

321

311

PF

89 89

21/12/01, 10:27

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.) electrical interlocking - 3 sources / 1 circuit breaker closed and lockout after fault (688188)

E33095

Version represented: c 3 sources, 1 circuit breaker closed; c electrical interlocking with lockout after a fault (SDE wiring).

possible states source 1 0 source 2 0 source 3 0

"SOURCE 2" BREAKER AUXILIARIES

"SOURCE 1" BREAKER AUXILIARIES

S1

S2

1 0 0

0 1 0

0 0 1

"SOURCE 3" BREAKER AUXILIARIES

S3

CN1 CN2

D to A

t1

t2

t3

R1

B4

262

254

252

A4

C2

34

32

84

82

22 24

14

322

12

CE

312 324

B4

262

254

252

A4

C2

34

32

24

84

82

22

322

14

314

CE

XF

12

CE

312 324

B4

262

254

252

A4

C2

34

32

24

84

82

22

322

14

314

CE

R3 12

312 324

314

R2

M MX Q1

OF

OF

CE

XF

CE

M

OF MX SDE

Q2

OF

OF

XF

OF

M

CH

MX SDE

PF

OF

Q3

OF

OF

CH

SDE

PF

B1

251

A1

C1

31

81

21

11

321

311

B1

251

A1

C1

31

81

21

11

321

311

B1

251

A1

C1

31

81

21

11

321

311

CH PF

A

Q1: Q2: Q3: D: t1:

Masterpact on source 1 Masterpact on source 2 Masterpact on source 3 P25M circuit breaker (2 x 10 A) signal for transfer to source 1 (minimum time delay 250 ms) t2: signal for transfer to source 2 (minimum time delay 250 ms) t3: signal for transfer to source 3 (minimum time delay 250 ms) R1,R2,R3: external relays for interlocking of SDE auxiliary switches.

M: XF: MX: CE: OF: SDE: CH: PF:

motor mechanism closing release shunt release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).

c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system. The relays are not supplied with the circuit breakers.

Merlin Gerin

86 BTP207E-3.420-raccord

86

21/12/01, 10:27

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.) electrical interlocking - 3 sources / 1 circuit breaker closed and without lockout after fault (688187)

E33096

Version represented: c 3 sources, 1 circuit breaker closed; c electrical interlocking without lockout after a fault.

possible states source 1 0 source 2 0 source 3 0

"SOURCE 2" BREAKER AUXILIARIES

"SOURCE 1" BREAKER AUXILIARIES

S1

S2

1 0 0

0 1 0

0 0 1

"SOURCE 3" BREAKER AUXILIARIES

S3

CN1 CN2

D

to A

t1

t2

B4

262

254

252

A4

C2

34

24

32

22

14

322

12

CE

XF

312 324

314

B4

262

254

252

A4

C2

24

34

22

32

14

322

CE

12

312 324

314

B4

262

254

252

A4

C2

24

34

22

32

14

322

12

312 324

314

t3

M Q1

OF

OF

CE

XF

MX

M

OF MX OF

Q2

OF

XF M

OF MX

CH Q3

PF

OF

OF

OF

CH PF

B1

251

A1

31

C1

21

11

321

311

B1

A1

251

C1

31

21

11

321

311

B1

A1

251

C1

31

21

11

321

311

CH PF

A

Q1: Q2: Q3: D: t1: t2: t3:

Masterpact on source 1 Masterpact on source 2 Masterpact on source 3 P25M circuit breaker (2 x 10 A) signal for transfer to source 1 (minimum time delay 250 ms) signal for transfer to source 2 (minimum time delay 250 ms) signal for transfer to source 3 (minimum time delay 250 ms)

M: XF: MX: CE: OF: SDE: CH: PF:

motor mechanism closing release shunt release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).

c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system.

Merlin Gerin

BTP207E-3.420-raccord

87 87

21/12/01, 10:27

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.) 3 circuit breakers - automatic control with generator set and lockout after fault (689642)

E33093

Version represented: c 2 sources + generator set; c electrical interlocking with lockout after a fault: inoperative with automatic reset option; c with auxiliary source; c with MN undervoltage release; c with choice of sources.

possible states "Normal 1" 0 "Normal 2" 0 "Replacement" 0

"NORMAL 1" BREAKER AUXILIARIES

1 1 0

0 0 1

1 0 0

0 1 0

"REPLACEMENT" BREAKER AUXILIARIES

"NORMAL 2" BREAKER AUXILIARIES

N1 N2 R

auxiliary source

genset startup signal G

D

undervoltage relay

to B

U=0

C

genset fault contact

OFF R

N AUTO CMa

Fu

Fu

N1 RTn2

N1-2

Fu N2

RTn3 RX3

Fu

RTn1

RX2

RX1 R1

OF

OF

B4

262

254

252

A4

D4

24

22

14

12

312

314

CE

84

CE

82

CE

XF QN1

322

324

B4

262

254

252

A4

D4

24

22

14

12

312

314

322

324

CE

84

CE

82

CE

332

334

B4

262

254

252

A4

D4

24

22

14

12

312

84

82

314

322

324

332

334

R2

M

MN

XF

SDE

CE

M

CE

MN OF

QN2

XF

OF

M

MN

SDE

CH

OF

QR

PF

OF

SDE

CH PF

CH

B1

251

A1

D1

21

11

81

311

321

B1

251

A1

D1

21

11

81

311

321

331

B1

251

A1

D1

21

11

81

311

321

331

PF

B

QN1: Masterpact on «Normal1» source QN2: Masterpact on «Normal2» source QR: Masterpact on «Replacement» source D: P25M circuit breaker (2 x 10 A) C: operation selection switch Cma: source selection switch FU: fuses Rtn1: voltage relay with 0.1 to 30 s time delay Rtn2: voltage relay with 10 to 180 s time delay Rtn3: voltage relay RX1: relay with 0.25 s time delay RX2: relay with 0.25 s time delay RX3: relay R1/R2: external relays for interlocking of SDE auxiliary switches (equipped with 2 contacts O).

M: XF: MN: CE: OF: SDE: CH: PF:

motor mechanism closing release undervoltage release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).

c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system. The two relays and selection switches are not supplied with the circuit breakers.

Merlin Gerin

84 BTP207E-3.410-raccord

84

21/12/01, 10:26

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.) 3 circuit breakers - automatic control with generator set and without lockout after fault (689644)

E33094

Version represented: c 2 sources + generator set; c electrical interlocking with lockout after a fault: inoperative with automatic reset option; c with auxiliary source; c with MN undervoltage release; c with choice of sources.

possible states "Normal 1" 0 "Normal 2" 0 "replacement" 0

"NORMAL 2" BREAKER AUXILIARIES

"NORMAL 1" BREAKER AUXILIARIES

1 1 0

0 0 1

1 0 0

0 1 0

"REPLACEMENT" BREAKER AUXILIARIES

N1 N2 R

auxiliary source

genset startup signal G

D

undervoltage relay

to B

U=0

C

genset fault contact

OFF R

N AUTO CMa

Fu

Fu

N1 RTn2

N1-2

Fu N2

RTn3 RX3

Fu

RTn1

RX2

RX1 R1

OF

OF

B4

262

254

252

A4

D4

24

22

14

12

312

84

314

CE

82

CE

XF QN1

322

324

B4

262

254

252

A4

D4

24

22

14

12

84

312

314

CE

82

CE

322

324

B4

262

254

252

A4

D4

24

22

14

12

84

312

314

82

322

324

R2

M

MN

XF

SDE

CE

M

CE

MN QN2

OF

XF

OF

M

MN

SDE

CH

QR

PF

OF

OF

SDE

CH PF

CH

B1

251

A1

D1

21

11

81

311

321

B1

251

A1

D1

21

11

81

311

321

B1

251

A1

D1

21

11

81

311

321

PF

B

QN1: Masterpact on «Normal1» source QN2: Masterpact on «Normal2» source QR: Masterpact on «Replacement» source D: P25M circuit breaker (2 x 10 A) C: operation selection switch Cma: source selection switch FU: fuses Rtn1: voltage relay with 0.1 to 30 s time delay Rtn2: voltage relay with 10 to 180 s time delay Rtn3: voltage relay RX1: relay with 0.25 s time delay RX2: relay with 0.25 s time delay RX3: relay

M: XF: MN: CE: OF: SDE: CH: PF:

motor mechanism closing release undervoltage release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).

c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system. The relays and selection switches are not supplied with the circuit breakers.

Merlin Gerin

BTP207E-3.410-raccord

85 85

21/12/01, 10:26

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.) 3 circuit breakers - automatic control with permanent "Replacement" source and lockout after fault (685366)

E33091

Version represented: c 2 «Normal» sources + 1 «Replacement» source; c electrical interlocking with lockout after a fault (SDE wiring): inoperative with automatic reset option.

possible states "Normal 1" 0 "Normal 2" 0 "Replacement" 0

N1

N2

0 0 1

1 0 0

0 1 0

"REPLACEMENT" BREAKER AUXILIARIES

"NORMAL 2" BREAKER AUXILIARIES

"NORMAL 1" BREAKER AUXILIARIES

1 1 0

R CN1 CN2

D to A

t1 t2

R1 (1)

QN1

OF

M OF

B4

262

254

XF

MX QN2

252

CE

XF

OF SDE

A4

C2

24

22

84

82

312

CE M

14

XF

MX

12

314

B4

262

254

252

A4

C2

24

22

84

82

312

14

CE

12

314

B4

262

254

252

A4

C2

24

22

84

82

312

14

12

314

R2 (1)

M

OF MX

CH SDE

PF

QR

OF

CH

OF SDE

PF CH

B1

251

A1

C1

21

81

11

311

B1

251

A1

C1

21

81

11

311

B1

251

A1

C1

21

81

11

311

PF

A

QN1: Masterpact on «Normal1» source QN2: Masterpact on «Normal2» source QR: Masterpact on «Replacement» source D: P25M circuit breaker (2 x 10 A) t1: signal for transfer to «Normal1» and «Normal2» sources (minimum time delay 250 ms) t1: signal for transfer to «Replacement» source (minimum time delay 250 ms) R1/R2:external relays for interlocking of SDE auxiliary switches (equipped with 2 contacts O).

M: XF: MX: CE: OF: SDE: CH: PF:

motor mechanism closing release shunt release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).

c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system. (1) The two relays are not supplied with the circuit breakers.

Merlin Gerin

82 BTP207E-3.400-raccord

82

21/12/01, 10:26

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.) 3 circuit breakers - automatic control with permanent "Replacement" source and without lockout after fault (688183)

E33092

Version represented: c 2 «Normal» sources + 1 «Replacement» source; c electrical interlocking without lockout after a fault.

possible states "Normal 1" 0 "Normal 2" 0 "Replacement" 0

"NORMAL 2" BREAKER AUXILIARIES

"NORMAL 1" BREAKER AUXILIARIES

N1

N2

1 1 0

0 0 1

1 0 0

0 1 0

"REPLACEMENT" BREAKER AUXILIARIES

R

CN1 CN2

D to A

t1

B4

262

254

252

A4

C2

24

22

14

312

CE

XF

12

314

B4

262

254

252

A4

C2

24

22

14

312

CE

12

314

B4

262

254

252

A4

C2

24

22

14

312

12

314

t2

M QN1

OF

CE

XF

MX OF

M XF

MX QN2

OF

OF

M MX

CH

QR

PF

OF

OF

CH PF CH

B1

251

A1

C1

21

11

311

B1

251

A1

C1

21

11

311

B1

251

A1

C1

21

11

311

PF

A

QN1: Masterpact on «Normal1» source QN2: Masterpact on «Normal2» source QR: Masterpact on «Replacement» source D: P25M circuit breaker (2 x 10 A) t1: signal for transfer to «Normal1» and «Normal2» sources (minimum time delay 250 ms) t2: signal for transfer to «Replacement» source (minimum time delay 250 ms)

M: motor mechanism XF: closing release MX: shunt release CE: «connected» position switch OF: auxiliary changeover switch SDE: overcurrent fault-trip indication switch CH: «springs charged» switch PF: «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).

c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system.

Merlin Gerin

BTP207E-3.400-raccord

83 83

21/12/01, 10:26

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.) 2 circuit breakers - automatic control with generator set (688784) c with auxiliary source; c with MN undervoltage release.

Version represented: c with generator set; c with lockout after a fault (SDE wiring): v inoperative with automatic reset option, v if lockout after a fault is not required, the SDE must be shorted on both breakers;

possible states "Normal" 0 "Replacement" 0

E33089

"NORMAL" BREAKER AUXILIARIES

N

1 0

0 1

"REPLACEMENT" BREAKER AUXILIARIES

R genset startup signal auxiliary source

G

D

unvoltage relay U=0

to B genset fault contact

C OFF STANDBY

N AUTO

Fu RTn2

RX3 RTn1

Fu

RX1

CE

XF

B4

262

254

252

A4

D1

24

22

14

12

84

312

82

CE

322 314

B4

262

254

252

A4

D1

24

22

14

12

312

84

324

CE

82

322 314

324

RX2

CE

M XF

MN QN

OF

OF

M MN

SDE

QR

OF

CH

OF

SDE

PF CH

B1

251

A1

D4

21

11

81

311

321

B1

251

A1

D4

21

11

81

311

321

PF

B

QN: QR: D: C: FU: Rtn1: Rtn2: RX1: RX2: RX3:

Masterpact on «Normal» source Masterpact on «Replacement» source P25M circuit breaker (2 x 10 A) 4-position switch fuses voltage relay with 0.1 to 30 s time delay voltage relay with 10 to 180 s time delay relay with 0.25 s time delay relay with 0.25 s time delay relay

M: XF: MN: CE: OF: SDE: CH: PF:

motor mechanism closing release undervoltage release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).

c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F and OF auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system.

Merlin Gerin

80 BTP207E-3.390-raccord

80

21/12/01, 10:26

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.)

2 circuit breakers - automatic control with permanent "Replacement" source (688942)

E33090

Version represented: c with permanent «Replacement» source; c with lockout after a fault (SDE wiring): v inoperative with automatic reset option, v if lockout after a fault is not required, the SDE must be shorted;

c with auxiliary source; c with MN undervoltage release.

"NORMAL" BREAKER AUXILIARIES

N

possible states "Normal" 0 "Replacement" 0

1 0

0 1

"REPLACEMENT" BREAKER AUXILIARIES

R auxiliary source D

to B

C N STANDBY AUTO

OFF

Fu RTn2 RTn1

Fu Fu

RTn3 RX1

Fu

CE

XF

B4

262

254

252

A4

D1

24

22

14

12

84

312

82

CE

322 314

B4

262

254

252

A4

24

D1

22

14

12

312

84

324

CE

82

322 314

324

RX2

CE

M XF

MN QN

OF

OF

M MN

SDE

OF

QR CH

OF

SDE

PF CH

B1

251

A1

D4

21

11

81

311

321

B1

251

A1

D4

21

11

81

311

321

PF

B

QN: QR:

Masterpact on «Normal» source Masterpact on «Replacement» source D: P25M circuit breaker (2 x 10 A) C: 4-position switch FU: fuses Rtn1: voltage relay with 0.1 to 30 s time delay Rtn2: voltage relay with 10 to 180 s time delay Rtn3: voltage relay RX1: relay with 0.25 s time delay RX2: relay with 0.25 s time delay

CE: M: XF: MN: OF: SDE: CH: PF:

«connected» position switch motor mechanism closing release undervoltage release auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).

c diagram shown with circuits deenergised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F and OF auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system.

Merlin Gerin

BTP207E-3.390-raccord

81 81

21/12/01, 10:26

Masterpact: connection

automatic source-changeover systems controller option (cont.)

E27121

BA operation

I O I UR O I KR O

UN or KT

I O I QR O

QN

T1 0,1…30 s

500 ms

250 ms

T2 0,1…240 s

500 ms

250 ms

UA operation

E30189

UN or KT

I O

UR KR

I O I O

KG

I O

SH I O QN I O QR I O T1 0,1...30s

120-180s

Inputs UN : normal-source voltage UR : replacement-source voltage KT : forced operation on replacementsource control signal KR : additional check before transfer.

T3 0,5...30s

If UR is not in I state when the transfer order (KT or UN) is given, transfer is not carried out. If KR is not in I state when the transfer order (KT or UN) is given, transfer takes place only once KR has changed to I state.

T2 10...240s

T4 0,5...30s

T5 60...600s

Legend c O position: circuit open c I position: circuit closed : no effect O or I. c

Outputs KG : engine-generator set control signal SH : load-shedding control signal QN : normal-source Masterpact QR : replacement-source Masterpact.

Merlin Gerin

78 BTP207E-3.380-raccord

78

21/12/01, 10:25

Masterpact: connection

wiring diagrams for automatic source-changeover systems 2 circuit breakers - electrical interlocking (685363)

E33088

Version represented: With lockout after a fault. If lockout after a fault is not required, contact PF of the «Normal» breaker must be connected directly in series with auxiliary switch OF of the «Replacement» breaker and vice versa, without passing through the switch SDE.

The indication circuits, represented on the diagram by broken lines, are optional. Accessories such as voltage relays, indicating lights and fuses are not supplied with the circuit breaker.

"NORMAL" BREAKER AUXILIARIES

N

possible states "Normal" 0 "Replacement" 0

CONTROL PRINCIPLE

1 0

"REPLACEMENT" BREAKER AUXILIARIES

R

CN1

control voltage

CN2

F1 (1)

0 1

F2 (1) D to B to A

C

to C

fault

RTs

closed

fault

closed

RTn open

open

B4

262

254

252

A4

C2

24

22

14

(2)

12

84

82

314 CE

312

B4

262

254

252

A4

C2

24

22

14

(2)

F4 (1)

12

84

82

314

312

F3 (1)

CE

XF M

XF

MX QN

OF

OF

M MX

SDE

QR

OF

CH

OF

SDE

PF CH

B1

251

A1

C1

21

11

81

311

B1

251

A1

C1

21

11

81

311

PF

B A

QN: Masterpact on «Normal» source QR: Masterpact on «Replacement» source D: P25M circuit breaker (2 x 10 A) F1, F2, F3, F4: protective fuses 2 A Rts: «Replacement» source voltage relay (minimum time delay 250 ms) Rtn: «Normal» source voltage relay (minimum time delay 250 ms)

M: motor mechanism XF: closing release MX: shunt release CE: «connected» position switch OF: auxiliary changeover switch SDE:overcurrent fault-trip indication switch CH: «springs charged» switch PF: «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).

c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. (1) The fuses clear faults occurring on the indication circuits without disturbing the operation of the source-changeover system. (2) Terminal 84 does not exist on control units STR58 with options Z and/or C or STR68UM/UTM; in this case there is discrimination between the indications.

Merlin Gerin

BTP207E-3.380-raccord

79 79

21/12/01, 10:25

Masterpact: connection

automatic source-changeover systems controller option source-changeover system with 2 circuit breakers E33081

"NORMAL" BREAKER AUXILIARIES

1 0

0 1

"REPLACEMENT" BREAKER AUXILIARIES

(1)

N

(1)

R

WH

VT

BK

RD

R

GN

N

possible states "Normal" 0 "Replacement" 0

IVE

XF

WH B4

262

254

252

A4

C2

VT

BK 84

82

GN

RD 14

CE

312

314

(3)

12

B4

262

254

252

A4

C2

84

82

312

14

12

314

(3)

CE

M

MX OF

XF SDE OF SDE

CH

251

A1

C1

81

11

311 GY

YE

(2) BN

BN

(3)

QN: Masterpact on «Normal» source QR: Masterpact on «Replacement» source IVE: electrical interlocking and terminal block unit M: motor mechanism XF: closing release MX: shunt release CE: connected position switch

CH

B1

A1

251

C1

(2) YE

(3)

81

311

11

PF

B1

PF

M

MX

QR

GY

QN

OF: auxiliary changeover switch SDE: overcurrent fault-trip indication switch CH: «springs charged» switch PF: «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).

c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. This diagram doesn't operate with "automatic reset" option. (1) provided ready to connect wiring. (2) Don't wire for option "without lockout after fault". (3) Don't wire in fixed position.

Merlin Gerin

72 BTP207E-3.350-raccord

72

21/12/01, 10:25

E33075

N

controller UA

R

1

3

5

1

Q1

2

3

E33076

load shedding and genset management 5

UA

4

N

genset startup

Q2

6

2

4

6

23 22 27 26 28 30 29 31

ACP

24

load shedding

O

L

9

10

R

E

load shedding

25

load reconnection

genset startup genset shutdown

24

N

O

R

L

E

E33077

BatiBUS option 25

23 22

controller status indication

BatiBUS loop

BatiBUS loop

+ –

0V

24V



+

17 18 20

BA/UA

24V 0V

21

supplementary control contact N➡R

voluntary transfer command (e.j. for energy management)

11 12

13 14 15 16 10

9

8

7

6

5

UA

11 12 13 14 15 16

N

IVE R 1

Q1 : circuit breaker supplying and protecting the automatic control circuits for the "Normal" source Q2 : circuit breaker supplying and protecting the automatic control circuits for the "Replacement" source IVE : electrical interlocking and terminal block unit ACP : auxiliaries control plate BA/UA : controller

2

3

4

5

6

7

8

9

10

c diagram shown with circuits de-energised, all devices open and relays in the released position.

Tests on "Normal" and "Replacement" voltages BA: c single-phase check for UN and UR: v tested across terminals 1 and 5 of circuit breakers Q1 and Q2. UA: c three-phase check for UN: v tested across terminals 1, 3 and 5 of circuit breaker Q1, v selection switch A of controller set to 1; c single-phase check for UN : v tested across terminals 1 and 5 of circuit breaker Q1, v selection switch A of controller set to 0.

Merlin Gerin

BTP207E-3.350-raccord

73 73

21/12/01, 10:25

Masterpact: connection

wiring diagrams for automatic source-changeover systems (cont.) automatic control - 2 sources + 1 coupling and lockout after fault (689651) possible states source 1 0 1 source 2 0 0 coupling 0 0

E33099

Version represented: c 2 sources + 1 coupling; c 2 circuit breakers closed; c electrical interlocking with lockout after a fault: inoperative with automatic reset option.

"SOURCE 1" BREAKER AUXILIARIES

S1

0 1 0

0 0 1

1 1 0

0 1 1

1 0 1

"SOURCE 2" BREAKER AUXILIARIES

"COUPLING" BREAKER AUXILIARIES

S2

CMa permanent OFF auto

Fu RTn1 RTn2

Fu Fu

CMb RTn3

COUPLER

N1+C N1+N2 N2+C

RTn4

Fu

RX1 Fu RX2 Fu

B4

262

254

252

A4

C2

24

22

14

12

84

312

82

CE

322 314

B4

262

254

252

A4

C2

24

22

14

12

312

84

324

CE

XF

82

CE

322 314

324

B4

262

254

252

A4

C2

24

22

14

12

84

82

322 314 CE

312

324

RX3

M OF

CE

XF

MX OF

CE

M XF

MX SDE

OF

OF

M MX

CH

SDE

PF

OF CH

OF

SDE

PF CH

Q1: QC: Q2: Cma: FU: Rtn1: Rtn2: Rtn3: Rtn4: Cmb: RX1: RX2: RX3:

Masterpact on source 1 Masterpact used for coupling Masterpact on source 2 3-position switch fuses voltage relay with 10 to 180 s time delay voltage relay with 0.1 to 30 s time delay voltage relay with 10 to 180 s time delay voltage relay with 0.1 to 30 s time delay coupling selection switch relay with 0.25 s time delay relay with 0.25 s time delay relay with 0.25 s time delay

M: XF: MX: CE: OF: SDE: CH: PF:

motor mechanism closing release shunt release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).

B1

251

A1

C1

21

11

c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system. The relays are not supplied with the circuit breakers.

Merlin Gerin

90 BTP207E-3.440-raccord

81

311

321

B1

251

A1

C1

21

11

81

311

321

B1

251

A1

C1

21

11

81

311

321

PF

90

21/12/01, 10:28

LV power air circuit breakers and switch-disconnectors

Masterpact 4/ complementary technical information page tripping curves effect of ambient temperature

0 0

77 BTP207E-4.001-sommaire

77

21/12/01, 10:29

Masterpact: complementary technical information

tripping curves (cont.)

E30715

STR 68 U: load monitoring with 2 load limits 10000 5000

Ir = 0,4…1 x In

2000

Ic1 = 0,2…1 x In 1000

Ic2 = 0,2…1 x In 500

tr = 15…480s 200

tr1 = tr / 2 100

tr2 = tr / 4 50

20 10 5

t(s)

2 1 .5

.2 .1 .05

.02 .01 .005

.002 .001 .05 .06

.08

.1

.2

.3

.4

.5 .6

.8

1

2

3

4

5

6

8 10

20

30

x In In: CT rating Ir: LT protection current setting (delay: tr)

Ic1: one load-shedding pick-up (delay: tr1) Ic2: another load-shedding pick-up (delay: tr2)

Merlin Gerin

86 BTP207E-4.100-courbe décl

86

21/12/01, 10:32

E30717

STR 68: load monitoring with 1 load-shedding and 1 load-reconnection pick-up 10000 5000

Ir = 0,4…1 x In

2000

Ic1 = 0,2…1 x In

1000

Ic2 = 0,2…1 x In

500

tr = 15…480s 200

tr1 = tr / 2 100 50

20

tr2 = 60s 10 5

t(s)

2 1 .5

.2 .1 .05

.02 .01 .005

.002 .001 .05.06

.08 .1

.2

.3

.4

.5 .6

.8

1

2

3

4

5 6

8

10

20

30

x In Ic1: load-shedding pick-up (delay: tr1) Ic2: load-reconnection pick-up 2 (delay: tr2)

Merlin Gerin

BTP207E-4.100-courbe décl

87 87

21/12/01, 10:32

Masterpact: complementary technical information

tripping curves (cont.)

E30714

STR 68 U 10000 5000

Ir = 0,4 …1 x In

2000

tr = 15…480s 1000 500

200 100 50

20 10 5

t(s)

2

I2t ON

Im = 0,4 …15 x In

1 .5

.2 .1

I2t OFF

0,4

0,4

0,3

0,3

0,2

0,2

0,1

0,1

.05

I (*)

.02 .01 .005

.002 .001 .5 .6

.8 1

2

3

4

5

6

8

10

30

20

40 50 60

80 100

x In

200

300

kA

(*)I In (A)

800

1000

type H2 : I = type H1 : I = type L1 : I =

1,6 kA ... 65 kA In ou 1,6 kA ... 50 kA 1,6 kA ... 11 kA

1250

1600

2000

2500

3200

5000

6000

In ... 75 kA In ... 15 kA Merlin Gerin

84 BTP207E-4.090-courbe décl

4000

84

21/12/01, 10:31

STR 68 U: earth fault protection E30716

10000 5000

2000

Ih = 0,2…1 x In… Max. 1200A

1000 500

200 100 50

20 10 5

t(s)

2 1 .5

0,4 0,3

.2

0,2

.1

0,1

.05

.02 .01 .005

.002 .001 .05 .06

.08 .1

.2

.3

.4

.5 .6

.8

2

1

3

4

5 6

8

10

20

30

x In In: CT rating Ir: LT protection current setting (delay: tr) Im: ST protection pick-up (delay: tm) INST: instantaneous protection pick-up

Ih: earth fault protection pick-up (delay: th) (0, 0.1, …: time delay settings)

Merlin Gerin

BTP207E-4.090-courbe décl

85 85

21/12/01, 10:31

Masterpact: complementary technical information

tripping curves (cont.)

STR 38 S/STR 58 U: earth fault protection E30713

10000 5000

2000

Ih = 0,1…1 x In Max 1200A

1000 500

200 100 50

20 10 5

t(s)

I2t ON

2 1 .5

0,4 0,3

.2

0,2 I2t OFF

.1

0,1

.05

.02 .01 .005

.002 .001 .05 .06

.08 .1

.2

.3

.4

.5 .6

.8

1

2

3

4

5

6

8

10

20

30

x In In: CT rating Ih: earth fault protection pick-up (delay: th)

Merlin Gerin

82 BTP207E-4.080-courbe décl

82

21/12/01, 10:31

E30710

STR 38 S/STR 58 U: load monitoring 10000 5000

Ir = 0,4…1 x In

2000

Ic1 = 0,8…1 x Ir

1000

Ic2 = 0,5…1 x Ir

500

tr1 = tr / 2 200

tr2 = tr / 4 100 50

20 10 5

t(s)

2 1 .5

.2 .1 .05

.02 .01 .005

.002 .001 .05 .06

.08 .1

.2

.3

.4

.5 .6

.8

1

2

3

4

5 6

8

10

20

30

x In Ir: LT protection current setting (delay: tr) Ic1: load-shedding pick-up 1 (delay: tr1) Ic2: load-shedding pick-up 2 (delay: tr2)

Merlin Gerin

BTP207E-4.080-courbe décl

83 83

21/12/01, 10:31

Masterpact: complementary technical information

tripping curves (cont.)

E30711

STR 38 S 10000 5000

Ir = 0,4 …1 x In

2000 1000 500

200 100 50

20 10 5

t(s)

Inst (*)

I2t ON

2

Im = 1,5 …10 x Ir 1 .5

0,4

.2

I2t OFF

.1

0,3

0,3

0,2

0,2

0,1

0,1

.05

.02

0 .01 .005

.002 .001

.5 .6

.8

2

1

3

4

5 6

8

10

3

20

4

5 6

8 10

20

30

x In

x Ir (*)Inst In (A)

630

800/1000

1200/1600

2000

2500

3000/3200

4000/5000/6300

I = In x ... (N-H)

28

28

24

20

14

12

10

I = In x ... (L)

14

10

8

6

6

-

Merlin Gerin

80 BTP207E-4.070-courbe décl

80

21/12/01, 10:30

E30712

STR 58 U 10000 5000

Ir = 0,4 …1 x In

2000

tr = 15…480s 1000 500

200 100 50

20 10 5

t(s)

Im = 1,5 …10 x Ir I2t ON

2 1 .5

0,4 0,3

.2 2

I t OFF

.1

0,3

0,2

0,2

0,1

0,1

.05

0 I = 2 x In…Max (*)

.02 .01 .005

.002 .001 .5 .6

.8

1

2

3

4

5 6

8

10

20

3

4

5 6

8

10

20

30

x In

x Ir (*)Max In (A)

630

800/1000

1200/1600

2000

2500

3000/3200

4000/5000/6300

Max = In x ... (N-H)

28

28

24

20

14

12

10

Max = In x ... (L)

14

10

8

6

6

-

-

Merlin Gerin

BTP207E-4.070-courbe décl

81 81

21/12/01, 10:30

Masterpact: complementary technical information

tripping curves

E30708

STR 18 M 10000 5000

2000 1000 500

200 100 50

20

I = 2 x In… Max (*) 10 5

t(s)

2 1 .5

.2 .1 .05

.02 .01 .005

.002 .001 .5 .6

.8

1

2

3

4

5

6

8 10

20

30

40 50 60

80 100

200

300

x In (*)Max In (A)

630

800/1000

1200/1600

2000

2500

3000/3200

4000/5000/6300

Max = In x ...

28

28

24

20

14

12

10

Merlin Gerin

78 BTP207E-4.060-courbe décl

78

21/12/01, 10:30

E30709

STR 28 D 10000 5000

Ir = 0,4 …1 x In

2000 1000 500

200 100 50

20 10 5

t(s)

2

Im = 1,5 …10 x Ir

Inst (*)

1 .5

.2 .1 .05

.02 .01 .005

.002 .001

.5 .6

.8

1

2

3

4

5 6

8

10

20

3

x Ir

4

5 6

8

10

20

30

x In

Inst (*): fixed pick-up at 10 In Merlin Gerin

BTP207E-4.060-courbe décl

79 79

21/12/01, 10:30

Masterpact: complementary technical information

effect of ambient temperature

ambient temperature

The electrical and mechanical characteristics are specified for an ambient temperature between –5 and +60 °C. Masterpact circuit breakers operate from –10 and +70 °C. First closing minimum temperature: –30 °C. In addition, Masterpact circuit breakers comply with IEC standards 68.2.1 and 68.2.2: exceptional storage temperature from: –50 to +100 °C. The table below indicates the maximum current rating, for each connection type, as a function of the ambient temperature around the circuit breaker and the busbars.

Current rating (A) as a function ambient temperature (°C) Masterpact version drawout

M08N/H/L M10N/H/L M12N connection T °C front or rear 40 800 1 000 1 250 horizontal 45 800 1 000 1 250 50 800 1 000 1 250 55 800 1 000 1 250 60 800 1 000 1 200 rear vertical 40 800 1 000 1 250 45 800 1 000 1 250 50 800 1 000 1 250 55 800 1 000 1 250 60 800 1 000 1 250 fixed front or rear 40 800 1 000 1 250 horizontal 45 800 1 000 1 250 50 800 1 000 1 250 55 800 1 000 1 250 60 800 1 000 1 250 rear vertical 40 800 1 000 1 250 45 800 1 000 1 250 50 800 1 000 1 250 55 800 1 000 1 250 60 800 1 000 1 250 Power dissipation and resistance between inputs/outputs power(1) drawout 160 250 360 dissipated (W) fixed 66 103 150 input/output(2) drawout 53 53 53 resistance (µΩ) fixed 33 33 33

M12H

M12L

M16N/H M16L

M20N/H M20L

M25N/H M25L

M32H

M40H

M50H

M63H

1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250

1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250

1 600 1 600 1 600 1 600 1 550 1 600 1 600 1 600 1 600 1 550 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600

1 600 1 600 1 600 1 600 1 500 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600

2 000 2 000 2 000 2 000 1 900 2 000 2 000 2 000 2 000 1 900 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000

2 000 2 000 2 000 2 000 1 900 2 000 2 000 2 000 2 000 1 900 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000

2 500 2 500 2 430 2 350 2 250 2 500 2 500 2 500 2 500 2 400 2 500 2 500 2 500 2 500 2 500 2 500 2 500 2 500 2 500 2 500

2 500 2 350 2 250 2 150 2 000 2 500 2 500 2 500 2 350 2 200 2 500 2 500 2 500 2 500 2 300 2 500 2 500 2 500 2 500 2 500

3 150 3 080 3 000 2 900 2 800 3 200 3 200 3 100 3 000 2 900 3 200 3 200 3 200 3 200 3 100 3 200 3 200 3 200 3 200 3 100

3 800 3 650 3 500 3 300 3 100 4 000 3 800 3 600 3 400 3 200 4 000 4 000 4 000 3 900 3 800 4 000 4 000 4 000 4 000 3 900

5 000 4 750 4 500 4 250 4 000 5 000 5 000 5 000 5 000 4 700 5 000 5 000 5 000 5 000 5 000 5 000 5 000 5 000 5 000 5 000

6 000 5 700 5 400 5 100 4 800 6 300 6 000 5 700 5 400 5 100 – – – – – – – – – –

230 100 32 16

360 150 50 36

390 170 32 16

460 220 31 12

365 180 18 9

500 250 23 10

520 260 17 8

780 390 23 10

803 500 15 10

1 250 780 15 10

1 150 700 9 8

1 200 – 9 –

(1) Values measured at In, 50/60 Hz for a 3-pole or 4-pole breaker. (2) Values measured per pole.

Merlin Gerin

88 BTP207E-4.110-déclassement

88

21/12/01, 10:32

Merlin Gerin

BTP207E-4.110-déclassement

89 89

21/12/01, 10:32