LV power air circuit-breakers and switch-disconnectors Masterpact Merlin Gerin
52387
Catalogue
■ Merlin Gerin ■ Modicon ■ Square D ■ Telemecanique
Sans titre-1
1
21/12/01, 9:26
0000 000 © 1996 Schneider Electric SA - All right reserved
Schneider Electric SA
5, rue Nadar 92506 Rueil-Malmaison Cedex France Tel: +33 (0)1 41 29 82 00 Fax:+33 (0)1 47 51 80 20
http://www.schneiderelectric.com
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
ce document a étéhas imprimé This document been printed on ecological paper. sur du papier écologique.
Created by: Photos: Schneider Printing by:
0000 000
Sans titre-1
12-96
2
21/12/01, 9:26
Masterpact: presentation
035928PC
Masterpact circuit breakers are used to protect and control low-voltage distribution systems. They may be installed in main LV switchboards (incoming units, main and secondary outgoers). Masterpact is a complete range offering a large selection of performance levels: c ratings from 800 to 6300 A AC, from 1000 to 8000 A DC; c breaking capacity from 40 to 150 kA rms; c operational voltages 690 V AC, 1000 V DC.
Many versions c 3 or 4 poles; c fixed or drawout versions; c current-limiting version up to 2500 A; c wide range of control units offering multiple functions. Circuit breakers designed for all applications c 1000 V AC version; c DC version; c anti-corrosion version; c source-changeover version; c merchant-marine and military versions. Masterpact circuit breakers comply with all major international standards and meet T2 tropicalisation criteria.
front face
2 5 1 6 12 13
4
E28760
7
c "charged"
charged
c "discharged"
discharged
13 main-contact position indicator c "OFF" (O);
8
9
10
11
c "ON" (I).
3
E28761
14
1 opening push-button (O) 2 closing push-button (I) 3 keylock for "connected", "disconnected" or "test" position 4 door interlock 5 stored-energy-mechanism charging handle 6 operations counter 7 "open" position keylock 8 racking handle storage 9 functional position indicator: "connected", "test" and "disconnected" 10 controls on fixed chassis (accessible with cubicle door closed) 11 padlocking facilities for "connected", "disconnected" or "test" position 12 stored-energy-mechanism status indicator
O
OFF
I
ON
E28791
14 fault-trip indicator/breaker reset button LV circuit-breaker: blue figures Enclosure: red figures
M63
M50
M40
M08 àtoM32 M32 M08
IG
LI
L
G off
LIG
I
reset V
push to reset
LG
MERLIN GERIN masterpact I
O
I3
I2
I1 90%
push OFF
I push ON
STR 58 UE
M32 H1 Ui
1000V
50/60Hz
Ue 380/440V
480/690V
Icu 100kA
85kA
Ics 100kA
85kA
Icw 75kA 1s
50%
IEC 947-2
discharged
20%
%Ir
.92 .95 60
.9
.88
0.8
0.63
90
.98 30
.85
1
.8
1
0.5
105
tr
Ir
Io
xIo
xIn Im
Ir :
t Ir fault
8
.2
.1 0 .1 2 on I t off
.2
10
xIo 12
8
17
6
22
4
Im :
480
off
2
xIn tr
th :
Ih
600 800
500
Ih
400
Im fault tm
fault th
T
th .4
.4 .3
.3
.2 .1 .1 2 on I t off
1000 .2 320 250
I
i +S–
1200
A
Ic1 .9
.8
–T+
R
Ic2.8
.93 .95
.7
.98
.6
.85 .9
.86 .85
test
F
00000
.3
6 .3
3 2 1.5
I
O OFF
240
15 at 1,5Ir
tm.4
5
4
120
Reduced dimensions c AC circuit breakers: v a single frame size from 800 to 3200 A, v common height and depth from 800 to 6300 A; c DC circuit breakers: v common height and length from 1000 to 8000 A for operational voltages of up to 500 V DC, v common height and length from 1000 to 4000 A for operational voltages greater than 500 V DC.
1 xIr
.95 1
.5 xIr
test
connected test disconnected
2 BTP207E-1.010-presentation
Merlin Gerin
2
21/12/01, 9:34
015159
1
2
3 4
6 7 8
5
10 9
drawout version 1 2 3 4 5 6 7 8 9 10
arc chute cover auxiliary terminal shield auxiliaries connection block fixed chassis safety shutters arc chute remote control voltage release motor for electrical charging of stored energy mechanism control unit (AC system) front cover
3
Merlin Gerin
BTP207E-1.010-presentation
3
21/12/01, 9:34
E29490
Masterpact: presentation
safety and reliability c reduced, simple maintenance (main contacts easily accessible, with wear indication feature); c double insulation from the front face; c positive contact indication; c auxiliary devices can be fitted on site without adjustment; c fewer parts than conventional ranges (by a factor of 5-10); c a trip interlock ensures that the circuit breaker is open during connection and disconnection; c connection to top or bottom terminals; c fully tropicalised as standard. STR 58 U
stored energy operating mechanism
50%
20% Io 0.8
0.63
90
.9
xIo
tm
Im
τ tr
3
6 .3
.2
2 1.5
8
.2
.1
I Ir : Ir fault
14
12
19 22 Max.
4 2
Ih
xIn Ih 1200A Max th
th :
th
600 800
500 400
Im fault tm
fault
0 .1 on I2t off
10
xIr
8
Im :
tr
320 250
I
i overcurrent
+
–
–
+
test
A
Ic2
Ic1
.9
.86
.8
.93 .95
.7
.98
.6
1
xIr
T
.4
.4
.3
.3
.2 1000 .2 .1 .1 1200 on I2t off
.85
ground
.3
.4
5
4
Masterpact circuit breakers are operated via a stored energy mechanism for instantaneous opening and closing. The mechanism is charged either manually or electrically. Closing and opening operations can be initiated either from the local pushbuttons on the circuit breaker front face, or by remote control.
15 at 1.5Ir
1
.8
xIn
norm min.
480
.98 30
.85
1
0.5
240
120 .92 .95 60
.88
%Ir 105
tr
Ir
R .85 .9
.8
.95 .5
1
xIr
test
isolation renforcée
séparation totale
classe II insulation double
entre phase chaque phase total separation
déclencheurs voltmétriques accessibles à l'avant voltage releases accessible from the front
c Fixed circuit breaker The fixed circuit breaker is derived from the moving part of the drawout circuit breaker by adding a fixing bracket on each side.
035929
other possibilities
c Switch version The switch (unprotected) version is derived directly from the standard circuit breaker, but does not implement a control unit (or the magnetic trip units used with the DC circuit breakers). Available models are: v standard: type HI and NI; v high performance: type HF, equipped with a protection system that instantaneously opens the circuit breaker in the event of closure under fault conditions.
Fixed circuit breaker
053060
c Earthing switch A special short-circuit and earthing switch is available on request for the M08 to M32H drawout types, 3 or 4 poles. Please consult us.
common auxiliaries from 800 A to 6300 A Auxiliaries c accessible from the front, mounted in a separate compartment insulated from power circuits; c secured by a single screw; c adjustment-free; c can be fitted on site. c Source changeover system Four solutions are available: v mechanical interlocking for 2 or 3 circuit breakers, adaptable to various sourcechangeover configurations; v automatic source-changeover controller, easy to implement on any two suitably equipped circuit breakers (electrically charged operating mechanism, etc.) (for 3 circuit breakers, consult us); v complete assembly including 2 or 3 mechanically (rod assembly) interlocked circuit breakers, adaptable to various source-changeover configurations; v complete assembly including 2 mechanically (rod assembly) interlocked circuit breakers and an automatic sourcechangeover controller, adaptable to various source-changeover configurations. Ready for connection.
053061
053058
c 1000 V AC circuit breakers
Automatic source-changeover controller
4 BTP207E-1.015-presentation
Merlin Gerin
4
21/12/01, 9:35
86094
DC circuit breakers
86096
Fixed Masterpact DC circuit breaker
Masterpact DC circuit breakers are available in fixed and drawout versions. They benefit from the AC range technology and advantages. c 5 available ratings from 1000 to 8000 A; c 2 breaking capacities, 100 kA at 500 V, 50 kA at 750 and 1000 V; c a circuit-breaker version offering instantaneous short-circuit protection with an adjustable, magnetic trip unit (DINA); c a switch (unprotected) version. note: up to 125 V DC, the devices in the AC range (M08 to M63) may be used only in the switch version, in which case a three-pole, type HI device should be used, with: c 1 pole for the positive polarity; c 1 pole for the negative polarity; c 1 pole not used.
Auxiliaries All the auxiliaries designed for the Masterpact AC circuit breakers may be used on the DC versions, with the exception of the position switches, indicating the connected (CE), disconnected (CD) and test (CT) positions. Auxiliary connections are made via one or two manually disconnectable plugs that remain accessible from the front. Accessories Standard Masterpact DC range equipment includes an arc-chute cover (CC) and, on drawout versions, safety shutters (VO). Interphase barriers (EIP) are not available for the DC range.
Drawout Masterpact DC circuit breaker
device identification M 20 H1 breaking capacity; c N1: standard; c H1: H2: high performance; c L1: current limiting; c DC: direct current. rating c rated current / 100. family c Masterpact: LV power air circuit breaker.
5
Merlin Gerin
BTP207E-1.015-presentation
5
21/12/01, 9:35
Masterpact circuit breakers are the product of Merlin Gerin’s vast experience in the field of power circuit breakers. They incorporate all the qualities of traditional air circuit breakers while drawing on certain of the advantages specific to moulded-case circuit breakers. In particular, they require no preventive maintenance.
ease of installation Masterpact is a complete and rationally designed range. c 10 ratings; c 4 breaking-capacity levels; c 6 control units; c a complete range of auxiliaries and accessories; c numerous versions (three and four-pole devices, fixed and drawout versions, etc.).
025179
2500 A Masterpact circuit breaker
Masterpact circuit breakers are easy to incorporate in switchboards. c a single frame size from 800 to 3200 A, thus making for standardised columns; c an upper safety clearance equal to zero due to the arc-chute cover, on both the fixed and drawout versions; c built-in measurement functions in the control units; c auxiliaries are the same for the entire range and may be easily implemented (only a screwdriver is required).
Top: front connection Bottom: rear vertical connection
Masterpact circuit breakers are easy to connect to the main distribution system. c all types of connections are available (horizontal and vertical terminals, front and mixed connections); c connections are possible with bars of any thickness; c connection to the input power source is possible on the upper or lower terminals of the circuit breakers. Due to their small size, Masterpact circuit breakers can replace most existing circuit breakers.
continuity of service Masterpact circuit breakers are designed with continuity of service in mind. The result is: c total time discrimination on the N1 and H1 circuit breakers and maximum discrimination on H2 circuit breakers; c factory pre-setting of Masterpact circuit breakers which never require any periodic maintenance; c high electrical endurance: 10 000 cycles at 1600 A and 30 cycles at 50 kA, without maintenance; c preventive indications: load-shedding indication switch, long-time threshold overrun alarm, etc.; c easy access to the main contacts fitted with mechanical wear indicators. An optional function on the STR68 control unit is the remote indication of contact wear, thus making possible continuous monitoring of circuit breakers during their service life. ,
036634
Masterpact: presentation
operating safety The insulating casing of Masterpact circuit breakers provides for: c user safety: v double insulation on the front face (class II), v auxiliary circuits in a compartment insulated from the power circuits; c switchboard safety when the circuit breaker is in the open position: v each pole is effectively isolated in its own housing, v limitation of external disturbances. Positive contact indication The position indicator cannot indicate «open» unless the poles are effectively separated by the required distance. The circuit breakers automatically open during racking in and out.
reliability c Masterpact circuit breakers comprise ten times fewer parts than traditional devices. They are easier to produce and more reliable. c the Masterpact circuit-breaker factory is certified ISO 9002; c the design of Masterpact circuit breakers is modular with delayed differentiation (highest possible number of common parts on all models). The result is shorter delivery times and enhanced reliability.
6 BTP207E-1.020-contents
Merlin Gerin
6
21/12/01, 9:38
LV power air circuit breakers and switch-disconnectors
Masterpact 2/ functions and characteristics page generales characteristics circuit breaker selection switch-disconnectors dimensions an weights control unit selection control unit accessories electrical auxiliaries mechanical accessories source changeover systems
0 0 0 0 0 0 0 0 0
7
BTP207E-2.001-content
7
21/12/01, 9:39
Masterpact: functions and characteristics
general characteristics
E29049
conformity with standards
MERLIN GERIN masterpact M32 H2 Ui
1000V
50/60Hz
Ue 380/440V 480/690V Icu 100kA
85kA
Ics 100kA
85kA
Icw 75kA 1s IEC 947-2
Masterpact circuit breakers comply with all the major international standards: c International standard IEC 947-2; c North American standards (please consult us): UL 489, ANSI C37-50, CSA C22-2, NEMA AB1 et SG3; c Japanese standards: JIS 160 and C 8372. They also comply with the following national standards: c France NF C 63-120; c Germany VDE 0660; c United Kingdom BS 4752; c Australia AS ; c Italy CEI. Masterpact circuit breakers comply with the specifications of the marine classification companies (Veritas, Lloyd's Register of Shipping, Det Norske Veritas, etc.).
Standardised characteristics indicated on the rating plate: Ui: rated insulation voltage Ue: rated operational voltage Icu: ultimate breaking capacity, for various values of the rated operational voltage Ue Ics: service breaking capacity Icw: short-time withstand current : suitable for isolation
IEC 947-2 This standard replaces IEC 157-1, applicable since 1973. The circuit breaker selection criteria are unchanged, but the new standard provides the user with a better guarantee concerning quality and performance. Circuit breakers are subjected to tests that are more representative of real operating conditions. IEC 947-2 also clarifies the notion of breaking capacity. c Icu : the ultimate breaking capacity, which must be greater than or equal to the 3-phase short-circuit current at the point of installation of the circuit breaker, a value unlikely to be reached under real conditions; c Ics : the service breaking capacity, generally expressed as a percentage of the ultimate breaking capacity (25, 50, 75 or 100 % of Icu). It corresponds to a shortcircuit current that is more likely to be reached under real conditions. The circuit breaker must continue to operate normally after having interrupted a current equal to Ics several times; c Icw : short-time withstand current for circuit breakers belonging to category B (category B refers to circuit breakers with time discrimination and category A to those without time discrimination). Furthermore, IEC 947-2 takes into account recent technological advances: c suitability for isolation recognised for circuit breakers having passed special electrical and mechanical tests; c industrial earth-fault circuit breakers covered by an appendix; c definition of tests designed to ensure coordination between two circuit breakers.
tropicalisation As standard, Masterpact circuit breakers comply with NF C 63-100 standard level 2 conditions (95 % relative humidity at 45 °C or 80 % at 55 °C, hot and humid climate conditions). They also comply with the following standards: c IEC 68-2-30 damp heat; c IEC 68-2-2 dry heat; c IEC 68-2-11 salt spray; c IEC 68-2-1 low temperatures during storage. Corrosive atmospheres: Special grease or other surface coatings available (please consult us).
pollution degree Masterpact circuit breakers are certified for operation in pollution degree IV environments as defined by IEC standard 947 (industrial environments).
8 BTP207E-2.020-gen. charact..
Merlin Gerin
8
21/12/01, 9:40
positive contact indication
All Masterpact circuit breakers are also disconnectors (suitable for isolation) as specified by IEC 947-2. They bear the corresponding symbol on the front cover:
All Masterpact circuit breakers offer positive contact indication. The toggle position rigorously reflects the position of the main contacts. It can indicate the "OFF" position only if the contacts are effectively open and a suitable distance apart.
E18569
035932RC
maximum dependability
This characteristic considerably increases the dependability of the circuit breaker. The conditions specified by IEC 947-2 for this function are: c positive contact indication; c impulse withstand: 8 kV at sea level; c very low leakage current, checked on new circuit breakers and on circuit breakers subjected to tests representative of the end of service life. Moreover Masterpact circuit breakers have a double-insulation front face (i.e. a class II device) allowing control from the outside.
installation Masterpact circuit breakers may be installed on horizontal metal surfaces or on rails. They are secured by four points accessible at the bottom of the chassis (drawout versions) or on either side of the circuit breaker (fixed versions). A single door cut-out is required for the entire range and provides access to Masterpact controls (see the description on page 2). .
degree of protection E28757
IP 30-5
circuit breaker installed in a cabinet with access to controls through a door cut-out
IP 40-5
circuit breaker installed in a cabinet behind a door with a cut-out fitted with a sealed, transparent cover
IP 54-9
E28763
circuit breaker installed free standing
E28758
(as defined by IEC 529)
9
Merlin Gerin
BTP207E-2.020-gen. charact..
9
21/12/01, 9:40
Masterpact: functions and characteristics
035928
circuit breaker selection
Masterpact circuit breakers number of poles
electrical characteristics as per IEC 947-2 and EN 60947-2 In
40 °C
Ui Uimp Ue
AC 50/60 Hz
ultimate breaking capacity (1) (kA rms)
Icu
AC 50/60 Hz
service breaking capacity short-time withstand current (kA rms)
Ics Icw
(% Icu) AC 50/60 Hz
making capacity (kA peak)
Icm
AC 50/60 Hz
electrodynamic withstand (kA peak) utilisation category suitability for isolation break time closing time endurance (C-O cycles) x 1000
mechanical
with maintenance no maintenance no maintenance
rated current (A) rating of 4th pole (A) rated insulation voltage (V) rated impulse withstand voltage (V) rated operational voltage (V)
type of circuit breaker Masterpact M16 H1
electrical
motor control (AC3-947-4) (2)
220/415 V 440 V 500/690 V 0.5 s 1s 3s 220/415 V 440 V 500/690 V
440 V - In 690 V - In 690 V
electrical characteristics as per standard Nema AB1 breaking capacity (kA)
480 V 600 V
protection (see following pages) sensor ratings (A) (see page 12) control unit protection type
instantaneous distribution selective universal
STR 18 M STR 28 D STR 38 S STR 58 U STR 68 U
installation and connections connection version
drawout fixed
indication and measurement auxiliaries auxiliary switches electronic trip unit related functions
control auxiliaries auxiliary releases (MN, MNR, MX, XF) motor mechanism (MCH) operation counter (CDM)
installation and connection accessories locking by padlock or keylock/mismatch protection
(1) Defined for a power factor of 0.25 if 20 < kA rms ≤ 50 or 0.20 of kA rms > 50. (2) Closing at 6 x Ie and opening at 0.17 x Un. (3) For control unit STR 68 U, the minimum rating In is 400 A.
safety shutters (VO) interphase barriers (EIP) partitioning fixture (AC) arc-chute cover (CC) terminal-block cover (CB) door frame (CDP) transparent cover (CCP) Merlin Gerin
6 BTP207E-2.060-M08...16
6
21/12/01, 9:41
M08
M10
M12
M16
3, 4
3, 4
3, 4
3, 4
800 800 1000 8000 690
1000 1000 1000 8000 690
1250 1250 1000 8000 690
1600 1600 1000 8000 690
N1
N1
H1
H2
L1
N1
H1
H2
L1
40 65 100 130 40 65 100 130 40 65 100 110 40 65 100 110 40 65 85 65 40 65 85 65 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 40 65 65 12 40 65 65 12 30 50 50 12 30 50 50 12 22 32 32 12 22 32 32 12 84 143 220 286 84 143 220 286 84 143 220 242 84 143 220 242 84 143 187 143 84 143 187 143 84 143 143 24 84 143 143 24 B B B B B B B B c c 25 to 30 ms without intentional time delay and 9 ms for type L1 70 ms 20 20 20 20 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 3 10 10 10 2.7 10 10 10 3 10 10 10 2.7 10 10 10 10 10 10 -
H1
40 40 40 100 % 40 30 22 84 84 84 84 B c
65 65 65 100 % 65 50 32 143 143 143 143 B
100 100 85 100 % 65 50 32 220 220 187 143 B
130 110 65 100 % 12 12 12 286 242 143 24 B
40 40 40 100 % 40 40 22 84 84 84 84 B c
65 65 65 100 % 65 50 32 143 143 143 143 B
100 100 85 100 % 65 50 32 220 220 187 143 B
130 110 65 100 % 17 17 12 286 242 143 34 B
20 10 10 10 10
20 10 10 10 10
20 10 10 10 10
15 10 2.5 2.5 -
20 10 10 10 10
20 10 10 10 10
20 10 10 10 10
15 10 2.2 2.2 -
40 40
-
40 40
65 65
100 65
-
40 40
65 65
100 65
-
c c c
200 to 1250 (3) c c c c c c c c c c
c c c
200 to 1600 (3) c c c c c c c c c c
c c c c c
c c c
65 65
200 to 800 (3) c c c c c c c c c c
H2
100 65
c c c c c
L1
N1
H1
-
40 40
65 65
c c c
200 to 1000 (3) c c c c c c c c c c
H2
100 65
c c c c c
L1
c c c c c
front and rear connections c c
c c
c c
c c
c c
c c
c c
c c
c c c
c c c
c c c
c c c
c
c
c
c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c 7
Merlin Gerin
BTP207E-2.060-M08...16
7
21/12/01, 9:41
Masterpact: functions and characteristics
036635
circuit breaker selection (cont.)
Masterpact circuit breakers number of poles
electrical characteristics as per IEC 947-2 and EN 60947-2 In
40 °C
Ui Uimp Ue
AC 50/60 Hz
ultimate breaking capacity (1) (kA rms)
Icu
AC 50/60 Hz
service breaking capacity short-time withstand current (kA rms)
Ics Icw
(% Icu) AC 50/60 Hz
making capacity (kA peak)
Icm
AC 50/60 Hz
electrodynamic withstand (kA peak) utilisation category suitability for isolation break time closing time endurance (C-O cycles) x 1000
mechanical
with maintenance no maintenance no maintenance
rated current (A) rating of 4th pole (A) rated insulation voltage (V) rated impulse withstand voltage (V) rated operational voltage (V)
type of circuit breaker Masterpact M50 H1
electrical
motor control (AC3-947-4) (2)
220/415 V 440 V 500/690 V 0.5 s 1s 3s 220/415 V 440 V 500/690 V
440 V - In 690 V - In 690 V
electrical characteristics as per standard Nema AB1 breaking capacity (kA)
480 V 600 V
protection (see following pages) sensor ratings (A) (see page 12) control unit protection type
instantaneous distribution selective universal
STR 18 M STR 28 D STR 38 S STR 58 U STR 68 U
installation and connections connection version
drawout fixed
indication and measurement auxiliaries auxiliary switches electronic trip unit related functions
control auxiliaries auxiliary releases (MN, MNR, MX, XF) motor mechanism (MCH) operation counter (CDM)
installation and connection accessories locking by padlock or keylock/mismatch protection
(1) Defined for a power factor of 0.25 if 20 < kA rms ≤ 50 or 0.20 of kA rms > 50. (2) Closing at 6 x Ie and opening at 0.17 x Un. (3) For control unit STR 68 U, the minimum rating In is 400 A. (4) 83% if Ue i 440 V. (5) Consult us for full rated neutral.
safety shutters (VO) interphase barriers (EIP) partitioning fixture (AC) arc-chute cover (CC) terminal-block cover (CB) door frame (CDP) transparent cover (CCP) Merlin Gerin
8 BTP207E-2.070-M20...63
8
21/12/01, 9:42
M20
M25
M32
M40
M50
M63
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
2000 2000 1000 8000 690
2500 2500 1000 8000 690
3200 3200 1000 8000 690
4000 4000 1000 8000 690
5000 2500 (5) 1000 8000 690
6300
N1
H1
H2
H1
H2
H1
H2
H1
H2
55 75 100 130 55 75 100 130 75 55 75 100 110 55 75 100 110 75 55 75 85 65 55 75 85 65 75 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 55 75 75 17 55 75 75 17 75 55 75 75 17 55 75 75 17 75 50 57 57 17 50 75 75 17 75 121 165 220 286 121 165 220 286 165 121 165 220 242 121 165 220 242 165 121 165 187 143 121 165 187 143 165 121 165 165 34 121 165 165 34 165 B B B B B B B B B c c c 25 to 30 ms without intentional time delay and 9 ms for type L1 70 ms 15 15 15 15 15 15 15 15 15 10 10 10 10 10 10 10 10 10 9 9 9 2 8 8 8 1.8 4 7 7 7 2 6 6 6 1.8 2.6 7 7 7 6 6 6 2.6
100 100 85 100 % 75 75 75 220 220 187 165 B
75 75 75 100 % 75 75 75 165 165 165 165 B c
100 100 85 100 % 75 75 75 220 220 187 165 B
100 100 85 100 % 100 100 100 220 220 187 220 B c
150 150 85 100 % (4) 100 100 100 330 330 187 220 B
100 100 85 100 % 100 100 100 220 220 187 220 B c
150 150 85 100 % (4) 100 100 100 330 330 187 220 B
15 10 4 2.6 2.6
80 ms 10 5 3 2.5 2.5
10 5 3 2.5 2.5
10 5 3 2.5 2.5
10 5 3 2.5 2.5
10 5 2 1.5 1.5
10 5 2 1.5 1.5
55 55
100 75
75 75
100 75
100 100
125 100
100 100
150 100
75 75
H2
100 75
200 to 2000 (3) c c c c c c c c c c c c c c c
L1
N1
H1
75 75
H2
-
55 55
100 75
c c c
300 to 2500 (3) c c c c c c c c c c c c c c c
L1
H1
3200 1000 8000 690
-
75 75
c c c
600 to 3200 c c c c c c c c c c
2000 to 4000 c c c c c c c c c c
2000 to 5000 c c c c c c c c c c
2000 to 6300 c c c c c c c c c c
front and rear connections c c
c c
c c
rear connections c c
c c (3P only)
c
c c
c c
c c
c c
c c
c c
c c c
c c c
c c c
c c c
c c c
c c c
c
c
c
c
c
c
c c c c c c c
c c c c c c c
c c c c c c c
c c (3P only) c c c c c
c
c
c c c c c
c c c c c 9
Merlin Gerin
BTP207E-2.070-M20...63
9
21/12/01, 9:42
Masterpact: functions and characteristics
052380
circuit breaker selection (cont.) Masterpact 1000 V AC Masterpact 1000 V AC circuit breakers number of poles
electrical characteristics as per IEC 947-2 and EN 60947-2 In
40 °C
Ui Uimp Ue
AC 50/60 Hz
ultimate breaking capacity (1) (kA rms)
Icu
AC 50/60 Hz
service breaking capacity short-time withstand current (kA rms)
Ics Icw
(% Icu) AC 50/60 Hz
making capacity (kA peak)
Icm
AC 50/60 Hz
electrodynamic withstand (kA peak) utilisation category suitability for isolation break time closing time endurance (C-O cycles) x 1000
mechanical
with maintenance no maintenance no maintenance
rated current (A) rating of 4th pole (A) rated insulation voltage (V) rated impulse withstand voltage (V) rated operational voltage (V)
type of circuit breaker Masterpact M20 H1 1000 V
electrical
motor control (AC3-947-4) (2)
220/415 V 440 V 500/690 V 1000 V 0.5 s 1s 3s 220/415 V 440 V 500/690 V 1000 V
440 V - In 690 V - In 690 V
protection (see following pages) sensor ratings (A) (see page 12) control unit protection type
instantaneous distribution selective universal
STR 18 M STR 28 D STR 38 S STR 58 U STR 68 U
installation and connections connection version
drawout fixed
indication and measurement auxiliaries auxiliary switches electronic trip unit related functions
control auxiliaries auxiliary releases (MN, MNR, MX, XF) motor mechanism (MCH) operation counter (CDM)
installation and connection accessories
(1) Defined for a power factor of 0.25 if 20 < kA rms ≤ 50 or 0.20 of kA rms > 50. (2) Closing at 6 x Ie and opening at 0.17 x Un. (3) For control unit STR 68 U, the minimum rating In is 400 A.
locking by padlock or keylock/mismatch protection safety shutters (VO) interphase barriers (EIP) partitioning fixture (AC) arc-chute cover (CC) (as standard on the 1000 V version) terminal-block cover (CB) door frame (CDP) transparent cover (CCP)
Merlin Gerin
10 BTP207E-2.080-M08...32
10
21/12/01, 9:42
M08
M10
M12
M16
M20
M25
M32
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
800 800 1000 8000 1000
1000 1000 1000 8000 1000
1250 1250 1000 8000 1000
1600 1600 1000 8000 1000
2000 2000 1000 8000 1000
2500 2500 1000 8000 1000
3200 3200 1000 8000 1000
H1
H1
H1
H1
H1
H1
H1
65 65 65 65 65 65 65 65 65 65 65 65 45 45 45 45 100 % 100 % 100 % 100 % 45 45 45 45 45 45 45 45 32 32 32 32 95 95 95 95 143 143 143 143 143 143 143 143 143 143 143 143 143 143 143 143 B B B B c c c c 25 to 30 ms without intentional time delay and 9 ms for type L1 70 ms 20 20 20 20 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
75 75 75 45 100 % 45 45 45 95 165 165 165 165 B c
75 75 75 45 100 % 45 45 45 95 165 165 165 165 B c
75 75 75 45 100 % 45 45 45 95 165 165 165 165 B c
15 10 9 7 7
15 10 8 6 6
15 10 4 2.6 2.6
200 to 800 (3) c c c c c
200 to 2000 (3) c c c c c
300 to 2500 (3) c c c c c
600 to 3200 c c c c c
rear connections only / supply by upstream terminals mandatory c c c c
c
c
c
c c
c c
c c
c c
c c
c c
c c
c c c
c c c
c c c
c c c
c c c
c c c
c c c
c c c c c c c c
c c c c c c c c
c c c c c c c c
c c c c c c c c
c c c c c c c c
c c c c c c c c
c c c c c c c c
200 to 1000 (3) c c c c c
200 to 1250 (3) c c c c c
200 to 1600 (3) c c c c c
11
Merlin Gerin
BTP207E-2.080-M08...32
11
21/12/01, 9:42
Masterpact: functions and characteristics
052384
switch-disconnectors
Masterpact switch-disconnectors number of poles
electrical characteristics as per IEC 947-2 and EN 60947-2 rated current (A) rating of 4th pole (A) rated insulation voltage (V) rated impulse withstand voltage (V) rated operational voltage (V)
In
40 °C
Ui Uimp Ue
AC 50/60 Hz
type of switch-disconnector short-time withstand current (kA rms)
Icw
AC 50/60 Hz
making capacity (kA peak)
Icm
AC 50/60 Hz
electrodynamic withstand (kA peak) suitability for isolation closing time endurance (C-O cycles) x 1000
mechanical
with maintenance no maintenance no maintenance
Masterpact M10 NI
electrical
motor control (AC3-947-4) (1)
0.5 s 1s 3s 440 V 500/690 V
440 V - In 690 V - In 690 V
protection STR 08 dummy unit (no protection) STR 18I (protection against short-circuits when closing)
installation and connections connection version
drawout fixed
indication and measurement auxiliaries auxiliary switches
control auxiliaries auxiliary releases (MN, MNR, MX, XF) motor mechanism (MCH) operation counter (CDM)
installation and connection accessories locking by padlock or keylock/mismatch protection safety shutters (VO) interphase barriers (EIP) partitioning fixture (AC) arc-chute cover (CC) terminal-block cover (CB) door frame (CDP) transparent cover (CCP)
(1) Closing at 6 x Ie and opening at 0.17 x Un. Merlin Gerin
12 BTP207E-2.082-inter M08
12
21/12/01, 9:42
M08
M10
M12
M16
3, 4
3, 4
3, 4
3, 4
800 800 1000 8000 690
1000 1000 1000 8000 690
1250 1250 1000 8000 690
1600 1600 1000 8000 690
NI
HI
HF
NI
HI
HF
NI
HI
HF
NI
HI
HF
40 30 22 84 84 84 c 70 ms 20 10 10 10 10
65 50 32 105 105 143
65 50 32 143 143 143
40 30 22 84 84 84 c
65 50 32 105 105 143
65 50 32 143 143 143
40 30 22 84 84 84 c
65 50 32 105 105 143
65 50 32 143 143 143
40 30 22 84 84 84 c
65 50 32 105 105 143
65 50 32 143 143 143
20 10 10 10 10
20 10 10 10 10
20 10 10 10 10
20 10 10 10 10
20 10 10 10 10
20 10 10 10 10
20 10 10 10 10
20 10 10 10 10
20 10 10 10 10
20 10 10 10 10
20 10 10 10 10
c
c
c
c
c
c
c
c
c
c
c
c
front and rear connections c c
c c
c c
c c
c
c
c
c
c c c
c c c
c c c
c c c
c c c c c c c c
c c c c c c c c
c c c c c c c c
c c c c c c c c
13
Merlin Gerin
BTP207E-2.082-inter M08
13
21/12/01, 9:42
Masterpact: functions and characteristics
052388
switch-disconnectors (cont.)
Masterpact switch-disconnectors number of poles
electrical characteristics as per IEC 947-2 and EN 60947-2 rated current (A) rating of 4th pole (A) rated insulation voltage (V) rated impulse withstand voltage (V) rated operational voltage (V)
In
40 °C
Ui Uimp Ue
AC 50/60 Hz
type of switch-disconnector
Masterpact M50 HI
short-time withstand current (kA rms)
Icw
AC 50/60 Hz
making capacity (kA peak)
Icm
AC 50/60 Hz
electrodynamic withstand (kA peak) suitability for isolation closing time endurance (C-O cycles) x 1000
mechanical
with maintenance no maintenance no maintenance
electrical
motor control (AC3-947-4) (1)
0.5 s 1s 3s 440 V 500/690 V
440 V - In 690 V - In 690 V
protection STR 08 dummy unit (no protection) STR 18 I (protection against short-circuits when closing)
installation and connections connection version
drawout fixed
indication and measurement auxiliaries auxiliary switches
control auxiliaries auxiliary releases (MN, MNR, MX, XF) motor mechanism (MCH) operation counter (CDM)
installation and connection accessories locking by padlock or keylock/mismatch protection safety shutters (VO) interphase barriers (EIP) partitioning fixture (AC) arc-chute cover (CC) terminal-block cover (CB) door frame (CDP) transparent cover (CCP)
(1) Closing at 6 x Ie and opening at 0.17 x Un. Merlin Gerin
12 BTP207E-2.084-inter M20
12
21/12/01, 9:43
M20
M25
M32
M40
M50
M63
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
2000 2000 1000 8000 690
2500 2500 1000 8000 690
3200 3200 1000 8000 690
4000 4000 1000 8000 690
5000 2500 1000 8000 690
6300 3200 1000 8000 690
NI
HI
HF
NI
HI
HF
HI
HF
HI
HF
HI
HF
HI
HF
55 55 50 84 84 121 c 70 ms 15 10 9 7 7
75 75 57 105 105 165
75 75 57 165 165 165
55 55 50 84 84 121 c
75 75 75 105 105 165
75 75 75 165 165 165
75 75 75 105 105 165 c
75 75 75 165 165 165
75 75 75 165 165 165
100 100 100 187 187 220 c
100 100 100 220 220 220
100 100 100 187 187 220 c
100 100 100 220 220 220
15 10 9 7 7
15 10 9 7 7
15 10 8 6 6
15 10 8 6 6
15 10 8 6 6
15 10 4 2.6 2.6
15 10 4 2.6 2.6
75 75 75 105 105 165 c 80 ms 10 5 3 2.5 2.5
10 5 3 2.5 2.5
10 5 3 2.5 2.5
10 5 3 2.5 2.5
10 5 2 1.5 1.5
10 5 2 1.5 1.5
c
c
c
c
c
c c
c c
c c
c c
c
front and rear connections c c
c c
c c
rear connections c c
c c (3P only)
c
c
c
c
c
c
c
c c c
c c c
c c c
c c c
c c c
c c c
c c c c c c c c
c c c c c c c c
c c c c c c c c
c c c (3P only) c c c c c
c c
c c
c c c c c
c c c c c
13
Merlin Gerin
BTP207E-2.084-inter M20
13
21/12/01, 9:43
Masterpact: functions and characteristics
dimensions and weights
Masterpact circuit breakers and switch-disconnectors type dimensions and weights dimensions W x H x D (mm)
drawout
3P 4P 3P 4P 3P 4P 3P 4P
fixed maximum weight (kg)
drawout fixed
Masterpact circuit breakers and switch-disconnectors type dimensions and weights dimensions W x H x D (mm)
drawout
3P 4P 3P 4P 3P 4P 3P 4P
fixed maximum weight (kg)
drawout fixed
Masterpact 1000 V circuit breakers type dimensions and weights dimensions W x H x D (mm)
drawout
maximum weight (kg)
drawout
3P 4P 3P 4P
sensor selection In (A) Ir threshold settings (A) In (A) Ir threshold settings (A)
200 80 to 200 1250 500 to 1250
250 100 to 250 1600 640 to 1600
320 125 to 320 2000 800 to 2000
400 160 to 400 2500 1000 to 2500
500 200 to 500 3000 1200 to 3000
600 240 to 600 3200 1280 to 3200
630 250 to 630 4000 1600 to 4000
800 320 to 800 5000 2000 to 5000
1000 400 to 1000 6000 2400 to 6000
1200 480 to 1200 6300 2500 to 6300
The table above indicates: c all the available sensor ratings In; c the limits of the long time Ir settings.
Merlin Gerin
12 BTP207E-2.090-M08...63
12
21/12/01, 9:47
M08
M10
M12
M16
M20
M25
M32
N1/H1/H2/L1 NI/HI/HF
N1/H1/H2/L1 NI/HI/HF
N1/H1/H2/L1 NI/HI/HF
N1/H1/H2 L1 NI/HI/HF
N1/H1/H2 L1 NI/HI/HF
N1/H1/H2 L1 NI/HI/HF
H1/H2 HI/HF
435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 65 80 43 54
435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 65 80 43 54
435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 65 80 43 54
435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 69 82 85 102 46 55 58 69
435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 82 130 102 150 55 80 69 90
435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 82 130 102 150 55 80 69 90
435 x 439 x 367 550 x 439 x 367 422 x 356 x 290 537 x 356 x 290 130 150 80 90
M40
M50
M63
H1/H2 HI/HF
H1/H2 HI/HF
H1/H2 HI/HF
550 x 439 x 367 815 x 484 x 367 537 x 356 x 290 801 x 356 x 290 150 200 90 110
815 x 484 x 367 1045 x 484 x 367 802 x 356 x 290
1045 x 484 x 367 1045 x 484 x 367
215 230 110
245 265
M08
M10
M12
M16
M20
M25
M32
H1
H1
H1
H1
H1
H1
H1
435 x 439 x 367 550 x 439 x 367 65 80
435 x 439 x 367 550 x 439 x 367 65 80
435 x 439 x 367 550 x 439 x 367 65 80
435 x 439 x 367 550 x 439 x 367 69 85
435 x 439 x 367 550 x 439 x 367 82 102
435 x 439 x 367 550 x 439 x 367 82 102
435 x 439 x 367 550 x 439 x 367 130 150
13
Merlin Gerin
BTP207E-2.090-M08...63
13
21/12/01, 9:47
Masterpact: functions and characteristics
control unit selection
current settings (A)
Masterpact M08 to M63 circuit breakers are equipped with microprocessor-based electronic control units.
80
160
400
E31218
All the protection functions are powered by the AC system and no auxiliary power supply is required. The same is true for most of the complementary functions.
1250
1600
2000
2500
3200
4000
5000
6300
STR 18 M STR 28 D STR 38 S
Each control unit of the Masterpact range corresponds to a certain type of application (instantaneous, distribution, selective, universal). All the STR control units measure the true rms value of the current and are therefore not affected by harmonics that may be present on the system.
STR 58 U STR 68 U
instantaneous protection distribution protection selective protection universal protection
protection
push to reset
1
E31219
E30703
STR 18 M
t
Key:
3
1
reset button: pops out when the circuit breaker has tripped on a fault and must be pressed (reset) before the circuit breaker can be closed again.
2
maximum protection rating.
3
instantaneous pick-up.
4
test connector.
5
holes for sealable cover plate screws.
STR 18 M
2 5 0
I
I
other functions c fault indication. I 12 14 8
19 2
+
3
22 max
4 xIn
–
4
test
5
Merlin Gerin
14 BTP207E-2.110-unité cont.
14
21/12/01, 9:47
protection 1
push to reset
E31220
E30704
STR 28 D
t
Key:
6
2 I1
I2
I
I3
3 STR 28 D
4
50%
20%
90
8
Ir 0.8
%Ir 105
7
11 Io 0.63
1
0.5
.88
.9 .92 .95
.85
.98 .8
xIn
xIo
0
6
1
4 5 6 2 8 1.5 xIr 10 3
c c c c
7
Ir :
Ir
2
ammeter digital display.
3
bar graph indicating load level (% Ir).
4
maximum protection rating.
Im :
Ir
I
I
8
overcurrent indicator LED.
9
noted settings.
10 test connector. 11 holes for sealable cover plate screws.
other functions
Im
t
reset button: pops out when the circuit breaker has tripped on a fault and must be pressed (reset) before the circuit breaker can be closed again.
5-6 long-time current setting as a function of: Io x Ir x In. 7 instantaneous pick-up.
90%
5
1
9
fault indication; indication of LT overrun; ammeter; self-monitoring (internal overheating).
Im
i +
–
10
test
11
protection
E33950
E31221
STR 38 S
t
Key: I2t ON
1
push to reset
1
reset button: pops out when the circuit breaker has tripped on a fault and must be pressed (reset) before the circuit breaker can be closed again.
2
ammeter digital display.
3
bar graph indicating load level (% Ir).
4
maximum protection rating.
5
overcurrent indicator LED.
7 I2t OFF
2 I1
I2
I
I3
90%
12
3 50%
4
20%
16 Ir 0.8
%Ir 1
0.5
.88
.9 .92 .95
.85
.98 .8
xIn
6
Im
8
tm
4 5
2 1.5
6
.3
8 10
.2
xIr t
0
.2
.1 0 .1 on I2t off
9 11
Im :
Ih fault th
14 16
max. off xIn th : Ih T th 500 600 .4 .4 Im fault 400 tm 800 .3 .3 I 320 1000 .2 .2 .1 250 1200 .1 i A on I2t off overcurrent +
–
–
+
12 13
I
c c c c c
short-time delay.
10 noted settings. 11 instantaneous pick-up. 12 earth fault pick-up.
fault indication; indication of LT overrun; ammeter; self-monitoring (internal overheating); indication of type of fault (F).
13 earth fault delay. 14 LEDs indicating tripping on long-time, short-time or earth fault. 15 test connector. 16 holes for sealable cover plate screws. 17 battery supplying backup power for fault indication. 18 fault indication reset and/or battery test.
15
test
I
.4 .3
I
Ir :
Im
other functions
Ir fault tr
Ir
7
1 xIo
3
10
9
11 Io 0.63
90 105
6-7 long-time current setting as a function of: Io x Ir x In. 8 short-time pick-up.
9
13
STR 38 S
5
8
ground
19 re-indication of last fault.
F test
17
19 18 15
Merlin Gerin
BTP207E-2.110-unité cont.
15
21/12/01, 9:47
Masterpact: functions and characteristics
control unit selection (cont.)
protection E31222
E30705
STR 58 U V
1 push to reset
reset V
I+T L+I L+I+T L+T T L off I
Key:
t I2t ON
2
1
8 I2t OFF
9 3 I1
I2
I
I3
10
90%
14
4 STR 58 U
11
15
5
50%
21 20%
6
Ir
Io 0.63
120 240 .9 .92 .95 60 480 .98 30 1 15 .8 xIn at 1.5Ir xIo Max. Im tm 4 5 .4 .3 τ tr 3 .3 6 .2 2 .2 norm 8 .1 0 1.5 10 .1 on I2t off xIr I 12 14 Ir : 8 19 Ir fault 4 22 Im : 2 off tr xIn th : Ih 1200A Max th T Ih 500 600 .4 .4 fault Im fault 400 800 .3 .3 tm th 320 1000 .2 .2 I .1 250 1200 .1 i A on I2t off overcurrent Ic1 Ic2 R + – .9 .93 .8 .85 test .86 .95 .7 .9 .85 – + .98 .6 .95 ground 1 8 1 .5 xIr xIr
90
0.8
%Ir
105
7 12 10
t
16
19 21 24 F
.88
.85
1
0.5
13
8
tr
test
0
9
Ir
Im
I
I
other functions c c c c c c
fault indication; indication of LT overrun; ammeter; self-monitoring (internal overheating); fault type indication (F); segregated alarm switch for selected fault type (V); c zone selective interlocking (Z); c load monitoring (R); c communication (COM).
11 13 14 15 17 18 20
23
22
protection 1
reset
E31223
E33949
STR 68 U
I2t ON
t
Key: 1
V N
1
2
3
LT setting (Ir)
2
Hz
I2t OFF
Cos ϕ
LT time delay (tr)
kW
2
MWh
ST pick-up (Im) ST time delay (tm)
STR 68 U
earth fault pick-up (Ih) 685812 A KA
3
S test
1
2
3
earth fault time delay (th)
0
instantaneous pick-up (I)
Ir
Im
I
max
other functions fault
s
4
tr
tm th Ih
Ir
Im
I
2
11
5
1
6
load monitoring
10 8
A
% maintenance
– trip
reset button: pops out when the circuit breaker has tripped on a fault and must be pressed (reset) before the circuit breaker can be closed again. 2 selection of fault type for segregated alarm: Ir and/or Im and/or Ih L: long-time fault (Ir) I: short-time fault (Im/l) T: earth fault (Ih) 3 ammeter digital display. 4 bar graph indicating load level (% Ir). 5 maximum protection rating. 6 overcurrent indicator LED. 7-8 long-time current setting as a function of: Io x Ir x In. 9 long-time trip delay 10 short-time pick-up. 11 short-time delay. 12 adjustment of thermal memory after tripping. 13 instantaneous pick-up. 14 earth fault pick-up. 15 earth fault delay. 16 noted settings. 17-18 load monitoring settings. 19 test connector. 20 battery supplying backup power for fault indication. 21 holes for sealable cover plate screws. 22 fault indication reset and/or battery test. 23 re-indication of last fault. 24 LEDs indicating tripping on long-time, short-time or earth fault.
no trip test
MEM
c c c c c c c
fault indications and memorisation; maintenance indicator; ammeter; integrated test; power measurement; load monitoring (R); self-monitoring (internal overheating, malfunction of the microprocessor); c zone selective interlocking for earth faults.
I
reset button: pops out when the circuit breaker has tripped on a fault and must be pressed (reset) before the circuit breaker can be closed again. 2 selection of displayed value (voltage, power, energy, power factor, frequency). 3 display of current or interrupted current (when flashing). 4 local fault indication and indication reset. 5 selection and indication of protection parameter to be set. 6 selection and indication of load monitoring parameters. 7 adjustment and saving of parameter settings. 8 holes for sealable cover plate screws. 9 test connector. 10 test. 11 maintenance indicator.
7
+ 24 V DC
9
adjustments
8 Merlin Gerin
16 BTP207E-2.120-unité cont.
16
21/12/01, 9:50
options for STR control units
"earth fault" protection (T or W)
E31225
zone selective interlocking (Z)
A number of circuit breakers are interconnected one after another by a pilotwire. In the event of a short-time or earth fault, the control unit applies the set time delay only if it receives a signal from a downstream circuit breaker. If not, it trips instantaneously (tripping time as 0.1 shorttime setting). In this way, the fault is cleared rapidly by the nearest circuit breaker. The thermal stresses in the installation are minimised while maintaining time discrimination throughout the entire
installation. Opto-electronic outputs The use of opto-transistors ensures total isolation between the internal circuits of the control unit and the circuits wired by the user.
t
This earth fault protection is designed to protect the installation against the risks of fire due to high earth faults (not to be confused with schemes designed for the protection of persons against electrical shock). Two types of earth protection are available for Masterpact: c residual current type (T): the control unit calculates the vector sum of the phase and neutral (if distributed) currents; c source ground return type (W): the control unit acts directly on the signal received from an external current transformer installed on the source earthing circuit.
I2t ON
I2t OFF
Ih Th
0
I
load monitoring (R)
E26037
earth fault curves for the STR 58
Remote indication of threshold overrun for load-shedding or load-reconnection purposes.
t
Ic2 Ic1
0
I
load monitoring curves for the STR 58
communication: STR 58 U transmission: STR 68 U
Transmission of the control unit settings, circuit breaker position and current, voltage and power measurements.
Other information that can be transmitted includes the value of the interrupted current, the state of the thermal memory and the maintenance indications
indication and measurement
c ammeter (I): a digital display continuously indicates the current of the phase with the greatest load (Imax). By pressing a scroll button, it is also possible to display successively the readings of I1, I2, I3, Ineutral and Ih. In addition, three bargraphs provide an immediate visual indication of the load on each of the three phases.
c indication of type of fault (F); c segregated alarm switch for selected fault type (V), wired in parallel with the opening button (MX), it disables circuit breaker closing for the selected type of fault.
17
Merlin Gerin
BTP207E-2.120-unité cont.
17
21/12/01, 9:50
Masterpact: functions and characteristics
048449
control unit selection (cont.) STR 18 M to STR 58 U control unit type of circuit breaker
basic protection long time protection LT current setting (Ir) as a function of Io and Ir settings tripping between 1.05 and 1.20 x Ir time delay (tr) accuracy: + 0 - 20 %
short-time protection ST pick-up (Im) adjustable by Im setting time delay (tm)
Io = In x ... Ir = Io x ... tr at 1.5 Ir (s) tr at 6 Ir (s) tr at 7.2 Ir (s) Im = Ir x ... tm setting with I2t OFF tm setting with I2t ON max. overcurrent time before tripping (ms) max. break time (ms)
instantaneous protection I pick-up setting setting range accuracy OFF switch on front face
STR 58 U
basic functions fault indication for tripping on a fault for LT setting overrun
self-monitoring
indicator button on front face fault trip alarm contact (SDE) LED (lights up at 0.9 Ir and flashes at 1.05 Ir) LT overrun alarm contact (optional) self-powered internal overheating
optional functions
(1) Plus the uncertainty of the built-in transformers: ± 3 %. (2) Max = In x ... 630 A 800 - 1000 A 1200 - 1600 A 2000 A 2500 A 3000 - 3200 A 4000 - 6300 A
N1/H1 22 22 22 17 12 10 8
H2 28 28 24 20 14 12 10
L1 14 10 8 6 6 – –
(3) Continuous display for the phase with the greatest load. (4) 0.2 x In to 1200 A without external power supply or 0.1 x In with external power supply. (5) Accuracy with respect to the long time LT protection.
ammeter (I) display between 0.2 and 1.20 In current readings with an accuracy of ± 1.5 % (1) (3) bargraph indication of current levels with a resolution of 10 % self-powered earth fault protection: residual current (T) or source ground return (W) type on request pick-up adjustable by Ih setting Ih = In x ... time delay (th) th setting with I2t ON and I2t OFF max. overcurrent time before tripping (ms) max. break time (ms) indication of type of fault (F) (LT - CT/Inst. - Earth) by LEDs on front face power supply with battery module with external power supply by AD module segregated alarm switch for selected fault type (V) (LT - CT/Inst. - Earth) output via relay contact power supply by AD module zone selective interlocking (Z) by opto-electronic contact on ST and earth (T/W) fault load monitoring (R) adjustment of load limit thresholds by Ic1 and Ic2 settings Ic1 = Ir x ... / Ic2 = Ir x ... time delay tr1 at 1.5 Ic1 time delay tr2 at 1.5 Ic2 output via opto-electronic contact 0.1 A / 240 V time delay for load reconnection communication (COM) 2 outputs for data transmission to Dialpact module transmitted values all control unit settings alarms: Ir warning, fault type, self-monitoring load monitoring thresholds current values I1, I2, I3, IN power supply by AD module
(6) Resettable maximum ammeter. Merlin Gerin
18 BTP207E-2.130-STR18…58
18
21/12/01, 9:51
STR 18 M
STR 28 D
STR 38 S
STR 58 U
N1, H1, H2
N1, H1, H2
N1, H1, H2, L1
N1, H1, H2, L1
c 0.5 to 1 (4 settings) 0.8 to 1 (8 settings) fixed 120 7.5 5.2
c 0.5 to 1 (4 settings) 0.8 to 1 (8 settings) fixed 120 7.5 5.2 c 1.5 to 10 ± 15 % 0 0.1 0.2 0.3 0.1 0.2 0.3 0 80 140 230 80 140 230 350 c I = In x ... fixed at high set (Max) (2) ± 20 % on types N1 and H1
c 0.5 to 1 (4 settings) 0.8 to 1 (8 settings) adjustable 15 30 60 120 0.94 1.88 3.75 7.50 0.65 1.30 2.60 5.20 c 1.5 to 10 ± 15 % 0 0.1 0.2 0.3 0.1 0.2 0.3 0 80 140 230 80 140 230 350 c I = In x ... 2 x In to Max (2) ± 15 % on types N1 and H1
0.4 350 500
240 15 10
480 30 21
0.4 350 500
c Im = In x ... 2 x In to Max (2) ± 15 % on types N1 and H1
c Im = Ir x ... 1.5 to 10 x Ir ± 15 %
c c
c c c c c c
c c c c c c
c c c c c c
c I1, I2, I3, IN, Imax (6) I1, I2, I3 c
c I1, I2, I3, IN, Ih, Imax (6) I1, I2, I3 c c 0.1 at 1 (max 1200 A) (4) ± 15 % 0.1 0.2 0.3 0.4 60 140 230 350 140 230 350 500 c c c
c I1, I2, I3, IN, Ih, Imax (6) I1, I2, I3 c c 0.1 at 1 (max 1200 A) (4) ± 15 % 0.1 0.2 0.3 0.4 60 140 230 350 140 230 350 500 c c c c c c 0.8 to 1 (8 settings) ± 1 % (5) 0.5 x tr 0.25 x tr c fixed at 10 s c c c c c c 19
Merlin Gerin
BTP207E-2.130-STR18…58
19
21/12/01, 9:51
Masterpact: functions and characteristics
036630
control unit selection (cont.) STR 68 U presentation The STR 68 U control unit offers measurement, supervision and energy management functions. Microprocessor technology, liquid crystal display and function keys ensure high accuracy and easy adjustment. The standard STR 68 U control unit provides the following: c universal protection; c ammeter function; c indication of fault type; c values of interrupted currents; c maintenance indicator; c integrated test. The following options can be added: c power measurement module (P); c "earth fault" protection module; c control and indication modules (M) with or without transmission to a supervisor. Certain M modules can provide load monitoring or zone selective interlocking for earth fault protection.
protection
The STR 68 control unit provides: c overload protection, with long time protection LT including: v adjustable time delay and thermal memory possibility; c short-circuit protection: v delayed, with short time function ST, for which the I2t curve can be disabled by the user, v instantaneous, with the INST function that can be disabled by the user;
basic functions
c ammeter; c maintenance indicator; c fault indications and values of the interrupted currents; c self-monitoring: in the event of overheating of the control unit or a malfunction of the microprocessor, an alarm signal is transmitted. Unless the "service continuity" option was ordered, the circuit breaker will trip ; c test.
c "earth" protection with time discrimination or zone selective interlocking. The protection is of the residual current type (or source ground return type on request).
Merlin Gerin
20 BTP207E-2.140-unité cont.
20
21/12/01, 9:51
optional functions
c power measurement (P); c indication and control (M) Thirty-one different modules offer various combinations of functions including: v load monitoring, v trip indication, v self-monitoring, v zone selective interlocking for "earth fault" protection, v transmission of data to a supervisor (modules M17 to M31 only). Each STR 68 U control unit can be equipped with only one M module. For the function offered by each M module, (see page xxx).
c "earth fault" protection (T) Of the residual current type (or source ground return type on request), it is possible to obtain zone selective interlocking by combining the T option with the appropriate M option.
21
Merlin Gerin
BTP207E-2.140-unité cont.
21
21/12/01, 9:51
Masterpact: functions and characteristics
control unit selection (cont.) STR 68 U control unit
STR 68 U
type of circuit breaker
N1. H1. H2. L1
basic protection long time protection LT current setting (Ir) adjustable in 2 % steps tripping time delay (tr) accuracy: + 0 - 20 %
thermal memory (30 mn) short time protection ST pick-up (Im) adjustable in 4 % steps time delay (tr)
Ir = In x ...
tr at 1.5 Ir (s) tr at 6 Ir (s) tr at 7.2 Ir (s)
Im = Ir x ... tm setting with I2t OFF tm setting with I2t ON max. overcurrent time before tripping (ms) max. break time (ms)
thermal memory (10 mn) instantaneous protection I fixed pick-up I (kA) pick-up (I) adjustable in 8 % steps accuracy OFF switch on front face
c 0.4 to 1 (mini 160 A) between 1.05 and 1.20 x Ir adjustable 15 30 60 120 240 480 0.94 1.88 3.75 7.50 15 30 0.65 1.30 2.60 5.20 10 21 standard + OFF position c 0.4 to 15 ± 10 % 0.1 0.2 0.3 0.4 0.1 0.2 0.3 0.4 60 140 230 350 140 230 350 500 standard c M08 to M16 : 65. M20 to M63: 75. from In to fixed pick-up (mini at 1.6 kA) ± 15 % on types N1 and H1
basic functions fault indication for tripping on a fault for Ir setting overrun indication of fault type and value of interrupted current self-monitoring maintenance indicator displays degree of wear of main contacts ammeter current readings with an accuracy of ± 3 % self-powered integrated test
button on front face fault trip alarm contact (SDE) LED on front face self powered LEDs on front face display on ammeter power supply internal overheating and microprocessor errors
c c c c c c 110 V - 220 V - 380 V AC 50/60 Hz c c between 0 and 655 c I1. I2. I3. Imax (1) c c
(1) Current of the phase carrying the highest load. Merlin Gerin
22 BTP207E-2.160-STR68U
22
21/12/01, 9:52
optional functions earth fault protection: residual current (T) or source ground return (W) type on request pick-up (Ih) adjustable in 2 % steps Ih = In x ... time delay (th) th setting max. overcurrent time before tripping (ms) max. break time (ms) thermal memory (10 mn) power measurement (P) (see opposite page for details) output characteristics integrated power supply voltage measurements U12. U23. U31 V1N. V2N. V3N frequency measurement: f power factor measurement: cos ϕ instantaneous active power measurement: P instantaneous active energy measurement: EP indication and control (M): 31 modules (1 per control unit) providing the following combinations: load monitoring option 1: 2 load limit pick-ups Ic1 and Ic2 Ic1 = In x ... delay tr1 = Ic2 = In x ... delay tr2 = option 2: 1 load limit pick-up Ic1 Ic1 = In x ... 1 load reconnection pick-up Ic2 delay tr1 = Ic2 = In x ... delay tr2 = zone selective interlocking trip indications for type of fault for self-monitoring (1) transmission characteristics type protocol speed max. number of addresses values transmitted: type of fault circuit breaker status self-monitoring settings circuit breaker status values transmitted: ammeter power system status voltmeter power factor, frequency instantaneous active power and energy: P. EP instantaneous reactive power and energy: Q. EQ power supply
c (zone selective interlocking with option M) 0.2 to 1 (maxi 1200 A. mini 160 A ) ± 15 % 0.1 0.2 0.3 0.4 60 140 230 350 140 230 350 500 c c opto-decoupled 0.2 A - 24 V DC c 160 to 690 ± 1 % 90 to 400 V ± 1 % 45 to 65 Hz ± 0.5 % - 1 to + 1 ± 2.5 % - 9000 to 9000 kW ± 5 % 0 to 9999 MWh ± 5 % c 2 possible options 0.2 to 1 In 2 % steps 0.5 x tr ± 5 % 0.2 to 1 In 2 % steps 0.25 x tr ± 5 % 0.2 to 1 In 2 % steps 0.5 x tr ± 5 % 0.2 to 1 In 2 % steps 60 s fixed ± 5 % for earth fault protection long-time, short-time, earth alarm RS 485 JBus 9600 bauds 255 tripping on Im, Ir, Ih alarm all pick-ups and delays open or closed currents I1, I2, I3 max voltages U12, U23, U31 voltages V1N, V2N, V3N cos ϕ, f - 9000 to 9000 kW. 0 to 9999 MWh ± 5 % - 9000 to 9000 kVar. 0 to 9999 MVahr ± 5 % 24, 48, 125 V DC or 100, 240 V AC
(1) Depending on the equipment, the "self-monitoring" alarm signal may or may not trip the circuit breaker, see "service continuity" option on the order form.
23
Merlin Gerin
BTP207E-2.160-STR68U
23
21/12/01, 9:52
Masterpact: functions and characteristics
control unit selection STR 68 U (cont.) option m selection
The following table indicates the functions of the different versions, designated m01 to m31. For terminal wiring see page xxxx.
Option M can be incorporated in control unit STR68U to provide the following functions: c RS485 data transmission at 9600 bauds to JBUS protocol; c remote signal via opto-electronic output; c zone selective interlocking for earth fault protection.
without data transmission option remoting load monitoring and control pick-up Ic1 indication load shedding pick-up Ic2 indication load shedding load reconnection fault indications Ir Im/I Ih self-monitoring zone selective interlocking on the earth fault protection
m01
m02
m03
m04
m05
m06
m07
m08
c c c c
c c c
c c
c c c c
c c
c c
c
c c
c c
c c
c c
c
c
m09
m10
c
c
c
c
m11
c c c c
c c c
c
c c
c
c
c
m12
m13
m14
m15
c
c c
c c
c
c
c
c c c c
c c c c
c c c c
c
c c c
c c
c
c c c
m16
c
c c c
c
c c
c c c
c
c
c c (1) c c
with data transmission option data transmission all parameters (see page xxxx) remoting load monitoring and control pick-up Ic1 indication load shedding pick-up Ic2 indication load shedding load reconnection fault indications Ir Im/I Ih self-monitoring zone selective interlocking on the earth fault protection
m17
m18
m19
m20
m21
m22
m23
m24
m25
m26
m27
m28
m29
m30
m31
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c c c c c
c c
c c
c c
c c c
c
c
c c
c
c
c c
c
(1) Two separate outputs for Im and I. Merlin Gerin
24 BTP207E-2.170-STR68U
24
21/12/01, 9:52
Basic functions: long time LT, short time ST, instantaneous INST
Earth fault protection (option T)
t
t
Factory adjustments The STR68U control unit is factory adjusted as follows: LT
E26042
E26039
operating zones
I2t ON
ST
I2t ON
1 I2t OFF
INST T
I2t OFF
2
setting Ir time delay tr pick-up Im time delay tm pick-up I earth fault pick-up Ih time delay th load monitor Ic1 Ic2
In 480 s 4 In 0,2 s maxi 0,2 In 0,1 s In In
T1
3
T2
4 5 0
Ir
Im
I
0
I
earth fault protection settings T1 : earth fault pick-up Ih T2 : earth fault time delay th
overcurrent settings 1 : LT setting Ir (long time) 2 : LT time delay tr (long time) 3 : ST pick-up Im ( short time) 4 : ST time delay tm ( short time) 5 : INST pick-up I (instantaneous)
load monitoring and control (option M) Operation with 2 load limit pick-ups
Operation with 1 load limit and 1 load reconnection pick-up
t
t
E26038
E26037
I
Ic2
Ic2
Ic1
Ic1
0
I
load monitoring and control settings Ic1 pick-up (load limit) Ic2 pick-up (load limit)
0
I
load monitoring and control settings Ic1 pick-up (load limit) Ic2 pick-up (load reconnection)
Merlin Gerin
BTP207E-2.170-STR68U
25
25
21/12/01, 9:52
Masterpact: functions and characteristics
control unit accessories
048327
battery module (PIL) Complementary to the local indication of the faults (F option for STR 38 and STR 58 trip units), the battery module avoids the need for any external power supply to save front face indications.
048321
interface module ET44 Compulsory with the data transmission option on the STR 68 trip unit, the ET44 interface module allows: c setting of the transmission speed; c definition of the address of the breaker (which will not be affected by any drawout breaker manipulation);
025172
relay module (MR6) For relaying of information from outputs of modules m01 to m32 of control unit STR 68 via output changeover contacts 10 A/220 V AC or 3 A/24 V DC.
025173
power supply module (AD) These modules can be used to power control unit complementary functions which cannot be self-powered by the built-in current transformers: c STR 38 and STR 58: fault type indication (F); c STR 58: segregated alarm switch (V); c STR 58: communication option (COM); c STR 28, STR 38, STR 58: ammeter (I) for load less than 20% of In. c STR 68: indication and saving of
025171
battery module (BAT) Providing a complement to the AD module, the battery module provides backup power for display indications and maintenance indicator data in the event of a power failure. Float connected between the power supply and the control unit, it ensures a backup time of approximately:
047035
mini test kit (BU) This self-contained portable unit is used to check STR 18 M to STR 58 U control units operations and breaker tripping. Power supply: five 9 V alkaline batteries (not supplied).
052172
portable test kit for STR 18 to STR 58 The portable test kit is used: c for control unit STR 68, to power, check and carry out adjustments and tests on the breaker/control unit assembly (control unit without auxiliary power supply connected);
This module is equipped with a button for reactivation, of fault indications that have been de-activated by the battery power-saving feature. A test button is used to check the battery status.
c the direct remote control of the breaker, thanks to two outputs directly controlled through the data transmission. Installation: on vertical plate or symmetrical rail. Power supply: 24 V DC with galvanic isolation, or AD type power module. Installation : on vertical plate or symmetrical rail. Power supply module (AD) is required.
measurements, alarms, maintenance indicator…; c MR6 module. Moreover, these modules protect the trip unit from transient overvoltages thanks to galvanic isolation. Available voltages: c AC 50/60 Hz: 110 V, 220 V or 380 V (–20 %; +15 %) (consumption 10 VA); c DC : 24/30 V, 48/60 V, 125 V (±20 %) (consumption 10 W). Installation: on vertical plate or symmetrical rail. c 12 h with STR 38 and STR 58 control units; c 1.5 h with STR 68 control unit. Installation: on vertical plate or symmetrical rail. (ambient temperature from: 0 °C to +50 °C).
This test kit is common to the Masterpact, Compact NS, C, CM ranges.
c for other control units, to check the operation of the trip unit by measuring the actual trip time: v long-time protection, v short-time protection, v instantaneous protection, v earth-fault protection. Power supply: 110, 220 V AC 50/60 Hz. This test kit is common to the Masterpact, Compact NS, C, CM ranges.
Merlin Gerin
26 BTP207E-2.180-unité cont
26
21/12/01, 9:56
Masterpact: functions and characteristics
auxiliary power supplies
The protection functions and most of the options available for the STR control units are self-powered. An auxiliary power supply is nevertheless required for certain uses.
self-powered
auxiliary power supply direct AD + BAT connection modules
terminals
battery
no (1)
yes (2)
F1/F2
no
no (1) no (1)
yes yes
F1/F2 F1/F2
yes no
no (1)
yes
F1/F2
no
STR 28 / 58 protection : LT, ST, INST option I if I u 20% In if I < 20% In or single phase load option F option FV option ALR option R option T/W if Ih u 0.2 x In if Ih < 0.2 x In
yes yes no no no yes yes yes no (3)
STR 68 protection : LT, ST, INST, T, W
yes
other functions : see drawings page 71 (1) Not recommended: possible with a 24 V DC source, class 2, 5 Watt, ripple factor < 10%. (2) Display will in this case be "❊❊❊❊". Auxiliary supply allows to save maximeter information. (3) Ih pick-ups for which protection is not self-powered are printed in red on the trip unit front face.
27
Merlin Gerin
BTP207E-2.180-unité cont
27
21/12/01, 9:56
Masterpact: functions and characteristics
013282
auxiliaries
electrical operating mechanism Added to the manual charging mechanism, a motor charges and automatically recharges the stored-energy spring upon breaker closing making possible fast O-C-O cycles. Opening and closing operations are instantaneous. The manual mechanism remains available for emergency use. characteristics power supply 50/60 Hz (V) consumption (VA) DC (V) consumption (W) motor start-up surge charging time
The electrical operating mechanism includes: c the gear motor(MCH); c a closing release (XF); c a shunt release (MX) or an undervoltage release (MN) for opening; c "springs charged" limit switch changeover contact (CH). The addition of the electrical operating mechanism does not alter circuit breaker dimensions.
geared motor MCH 100/127 - 200/240 - 250/277 - 380 - 415 - 440 - 480 180 24/30 - 48/60 - 100/125 - 200/250 180 2 to 3 In for 0.1 s 3 to 4 s
14 BTP207E-2.202-circuit-breaker
Merlin Gerin
14
21/12/01, 9:58
035932
operation counter (CDM) With gear-motor option only. The operation counter is read from the front and gives the total number of breaker operating cycles.
15
Merlin Gerin
BTP207E-2.202-circuit-breaker
15
21/12/01, 9:58
Masterpact: functions and characteristics
016813
auxiliaries (cont.)
releases Two types of voltage releases can be used for remote opening of Masterpact circuit breakers. Undervoltage releases c instantaneous (MN) This release instantaneously opens the breaker when its supply voltage drops below a value between 35 % and 70 % of its rated voltage. If the release is not energised, the breaker cannot be closed (either manually of electrically). Any attempt to close will have no effect on the main contacts. Closing is possible when the release voltage reaches 85 % of its rated value. c time delayed (MNR) To prevent the breaker tripping in the event of transient voltage dips, this release has a built-in time delay. A special version, available on request, allows instantaneous tripping (from a mushroom-head emergency off button) by the wiring of an external contact.
closing release (XF) This device releases the breaker closing mechanism when the spring is charged. Energisation can be maintained, as the closing release provides an antipumping function.
characteristics breaker response time at Un operating thresholds opening closing power supply AC 50/60 Hz (V)
036051
consumption (VA) DC (V) (2) consumption (W)
Shunt release (MX) This release instantaneously opens the breaker when energised. The supply can be maintained or automatically disconnected. In the latter case, the user can series connect an internal auxiliary contact (OF).
Note: anti-pumping function: After the breaker has been opened, either by fault trip or by manual or electrical operation, anti-pumping is provided by requiring cancellation of the initial closing command before reclosure of the breaker is possible. The closing release is supplied on request with the manual operating mechanism
undervoltage and shunt releases MN MNR MX 90 ms ± 5 0.5 s-0.9 s 50 ms ± 10 1.5 s-3 s
from 0.35 to 0.7 Un 0.85 Un
closing release XF 70 ms + 10, – 15 i 3 200 A 80 ms ±10 > 3 200 A
0.7 to 1.1 Un 0.85 to 1.1 Un
100 - 110/127 - 200 - 220/250 - 277 - 380/415 - 440/480 500/525(1) 20 24 - 30 - 48 - 60 - 100/110 - 125 - 200/220 - 250 15
Release combinations Each Masterpact circuit breaker can be equipped with: 1 MX + 1 MN + 1 XF, or 2 MX + 1 XF
(1) 500/525 V AC not available for MNR. (2) MNR: DC, 125 V only.
16 BTP207E-2.204-auxiliaries
Merlin Gerin
16
21/12/01, 10:08
016814
"spring charged" contact (CH)
auxiliary switches
018242
Double break changeover switches "OF"
Additional changeover switches ("OFSUP" block)
In addition to the main contact position indication on the front, 3 auxiliary switch blocks are available to indicate the open and closed breaker positions. c standard: 4 contacts (O) (2 normally open 2 normally closed); c optional: 4 directly-operated double break changeover switches (OF) which operate only when the minimum isolating distance between the main contacts is reached; c optional: 24 additional changeover switches (OFSUP block). These microswitches can be parallel connected in pairs to increase the rated current and breaking capacity (in drawout version only).
In addition to the local mechanical indicator and the "ready to close" contact, the gearmotor limit switch changeover contact can indicate that the operating mechanism is ready (spring charged). This contact is supplied as standard with the gear motor.
fault-trip indication (SDE) As standard and independent from the differentiated fault indications on the control unit, any fault-trip is indicated by: c 1 fault-trip indicator/reset button; c 1 changeover contact (SDE). The reset button must always be pressed after a fault-trip to enable breaker closing. Optional: automatic reset, allowing remote breaker closing without local resetting (the SDE contact operates up to the reset).
"ready to close" contact (PF)
016524
Optional: This contact simultaneously indicates the following: c the breaker is open; c the stored-energy mechanism is charged; c the mechanism is correctly reset; c the breaker opening pushbutton is not locked; c no opening order is present. This contact can be series connected to the closing release (XF) to disable the antipumping function.
connected/disconnected position carriage switches Changeover switches to indicate "connected" position "CE"
In addition to the local "connected/test/ disconnected" position indicator, two series of optional carriage switches are available for the fixed chassis (of drawout circuit breaker). c a block of 4 changeover switches to indicate "connected" position (CE); c a block of 2 changeover switches to indicate "disconnected" position (CD). The disconnected position is indicated only when the minimum isolating distance between main and auxiliary circuits has been reached. By series connection of these contacts the test position can be indicated. c 1 changeover switch to indicate "test" position (CT).
contact characteristics auxiliary contacts quantity
current rating (A) breaking capacity AC 50/60 Hz (A rms.) pf u 0.3
DC (A) L/R i 0.01 s
type O changeover NO 2 NO NC 2 NC 10 110 V 240 V 10 380 V 6 480 V 6 600 V 3 48 V 3 125 V 0.5 250 V 0.25 500 V
OF 4
OFSUP SDE PF 24 1 1
CE 4
CD 2
CT 1
CH 1
10 15 10 10 10 6 5 3 3 0.5
10
10
10
10
10
10
10
10 6 6 3 3 0.5 0.25
10 5
10 5
10 6 6 3 3 0.5 0.25
10 6 6 3 3 0.5 0.25
10 6 6 3 3 0.5 0.25
17
Merlin Gerin
BTP207E-2.204-auxiliaries
10 6 6 3 3 3 3 0.3 0,3 0.5 0.15 0.15 0.25
17
21/12/01, 10:08
Masterpact: functions and characteristics
013280
accessories
safety shutters (VO)
shutter lock (VVC)
Optional: mounted on the fixed portion of drawout breakers, the safety shutters automatically block access to the disconnection contacts when the breaker is in the disconnected or test position (degree of protection IP 20).
Optional: mounted on the fixed portion of drawout breakers, a mobile and lockable slide (padlocks not supplied) is used to: c lock the shutters in the closed position;, c hold the shutters in the open position. A support is provided at the back of the frame to hold the slide when not in use. A second slide is supplied: c on request for Masterpact i 3200 A ; c in standard for Masterpact 4000 A to 6300 A.
arc chute cover (CC)
terminal shield (CB)
Optional: attached to the fixed portion of drawout circuit breakers or on the fixed circuit breaker, this cover eliminates the safety clearance requirement above the breaker (this option is incompatible with front connection on top).
Optional: attached to the fixed portion of drawout circuit breakers, this cover prevents access to the electrical auxiliary connection terminals.
interphase barrier (EIP)
partitioning fixture (AC)
035928
Fixed portion of drawout circuit breakers with safety shutters
016818
Fixed portion of drawout circuit breakers with arc chute and terminal shield
Optional: attached to the fixed portion of drawout breakers (except when equipped with front connections), this fixture provides IP30 partitioning between the breaker compartment (accessible from the front) and the connection zone (located in the rear). It simplifies partition cut-outs. Example of partition cut-out for Masterpact M08 to M32. 445 (3 445 (3pole) pôles)
560 pole) etand 560 (4(4 pôles)
28518
Optional: attached to the fixed portion of drawout breaker (Masterpact i M40 3P), the insulated partitions for vertical installation between connection pads to: c reinforce insulation at connection points in insulated busbar installation; c prevent arc propagation to the breaker in the event of a line side fault on the main busbars.
360
datum référence a
plan de fixation chassis châssis fixing 60
b
a: partitioning fixture (AC) b: interphase barrier (EIP)
18 BTP207E-2.206-accessories
Merlin Gerin
18
21/12/01, 10:09
016819 016814
door frame (CDP)
transparent cover (CCP)
Optional: fixed to the cublicle door, this frame provides an equipment seal function (degree of protection IP 405). Suitable for fixed and drawout patterns.
Optional: hinge-mounted and equipped with a screw-closure, this cover is designed for the door frame (CDP). It provides a degree of protection of IP549. Suitable for fixed and drawout patterns.
auxiliaries connection
"Connected/disconnect/test" position contacts Installed on the fixed chassis, these contacts are directly connected by 6.35 mm connectors.
Fixed version Connection by one or two plugs, disconnectable and accessible from the front (screwless tunnel terminals for flex cable up to 2.5 mm2). Drawout version c standard: connection to a terminal block in the front of the fixed frame (screwless tunnel terminals for flex cable up to 2.5 mm2). The breaker auxiliary circuits are connected by connection blocks that operate automatically to isolate the auxiliaries when the breaker is in "disconnected" position. On request, an additional 5-way terminal block (BS) is available to provide five common points. c optional: by one or two plugs, disconnectable and accessible from the front, installed on the mobile part of the assembly.
015561
Auxiliaries for fixed version
Auxiliaries for drawout version
035940
breaker mismatch protection Optional: for drawout version only, this systems allows only correctly matched breakers (rating, type wiring, etc.) to be inserted in a given fixed frame. Two matching parts (1 for the fixed chassis and 1 for the mobile assembly) can be used to create 20 different user selected combinations.
Earth connection The earth connection terminal (drawout pattern) is on the left hand side of the chassis. It is marked with the symbol t
19
Merlin Gerin
BTP207E-2.206-accessories
19
21/12/01, 10:09
Masterpact: functions and characteristics
035932
accessories (cont.)
pushbutton locking device Optional: this padlockable device (padlocks not supplied) prevents direct operation of the circuit breaker by covering the "on" and "off" pushbuttons. This locking device can also be used for lead sealing.
"off" position locking device Optional: a Profalux key lock locks the breaker in "off" position by holding the pushbutton in its depressed position.
pushbutton locking device by padlocks (not supplied)
VBP
"off " position locking device (1)
035931
1 Profalux key lock 2 Profalux key locks, identical profiles adaptation fixture for 1 Profalux key lock, lock not supplied On request 1 Ronis key lock 2 Ronis key locks, identical profiles adaptation for 1 Castell key lock, lock not supplied adaptation for 1 Kirk key lock, lock not supplied
"disconnected", "connected" and "test" position locking (1) Mounted on the frame and accessible with the cubicle door locked, this system is available in two versions: c "disconnected" position locking; v as standard by 1 padlocking device (1 to 3 padlocks not supplied), v optional: by a locking device with 1 or 2 Profalux key locks; c "disconnected", "connected" and "test" position locking (optional); v by 1 padlocking device, with 1 to 3 padlocks not supplied (VEC), v by 1 locking device, with 1 or 2 Profalux key locks (VSPEC), padlocks "disconnected" standard "disconnected" standard "disconnected" standard "disconnected, connected" "disconnected, connected" "disconnected, connected"
1 keylock
VSPA1 VSPA2 VSPRAC VSRA1 VSRA2 VSCA VSKA
Remarks c the keylocks are of the captive key type, i.e. key free when locked; c Profalux and Ronis keylocks can be used together; c a second Profalux or Ronis lock, identical to the one mounted on the chassis, can be supplied separately.
2 keylocks
"disconnected" optional "disconnected" "disconnected" optional optional
"disconnected, connected" "disconnected, "disconnected, connected" connected"
(1) keylock types Profalux B24 D4Z Ronis 1351 B Kirk CN22-12 Castell SK7113/1 Trayvou L1P1E
20 BTP207E-2.208-accessories
Merlin Gerin
20
21/12/01, 10:09
"disconnected" position locking by padlocks (not supplied) 1 Profalux key lock 2 Profalux key locks, identical profiles 2 Profalux key locks, different profiles adaptation fixture for Profalux key lock (lock not supplied)
as standard VSPC1 VSPC2 2 VSPC1 VSPRCC
On request 1 Ronis key lock 2 Ronis key locks, identical profiles 2 Ronis key locks, different profiles adaptation fixture for Castell key lock (lock not supplied) adaptation fixture for Kirk key lock (lock not supplied) adaptation fixture for Trayvou key lock (lock not supplied)
VSRC1 VSRC2 2 VSRC1 VSCC VSKC VSTC
"disconnected", "connected" and "test" position locking by padlocks (not supplied) 1 Profalux key lock 2 Profalux key lock, different profiles
VEC VSEPC 2 VSEPC
On request 1 Ronis key lock 2 Ronis key locks, differents profiles adaptation fixture for Castell key lock (lock not supplied) adaptation fixture for Kirk key lock (lock not supplied)
VSERC 2 VSERC VSECC VSEKC
016817
door interlock Optional: mounted on the chassis, this lock prevents the cubicle door from being opened when the breaker is in the "connected" position. If the breaker is put into the "connected" position with the door open, the latter can be closed without disconnecting the breaker.
withdrawal/spring charged interlock Optional: this lock prevents withdrawal of the breaker from the chassis when the springs are charged. Incompatible with MN or MNR release.
racking interlock
a
Optional: this lock prevents insertion of the breaker racking handle when the cubicle door is open. It can be defeated by pressing on the unlocking mechanism.
b
door interlock right-hand side left-hand side racking interlock withdrawal/spring charged interlock
a: racking interlock b: door latch
VPECD VPECG VPOC VEAA
21
Merlin Gerin
BTP207E-2.208-accessories
21
21/12/01, 10:09
Masterpact: functions and characteristics
automatic source-changeover systems
053060
025186
Masterpact source-changeover systems can be used to implement various configurations involving several incoming feeders. The two or three Masterpact circuit breakers or switch-disconnectors used are mechanically interlocked to prevent certain combinations of operations. All types of Masterpact devices may be fitted (fixed and drawout versions, three-pole and four-pole, different ratings). The devices may be arranged: c vertically, i.e. stack-mounted and interconnected by a set of rods; c horizontally (two only), i.e. side-by-side and interconnected by a set of cables. An electrical interlock must be used when the source changeover is part of an automatic system.
053061
053058
Masterpact automatic source-changeover system
Controller
automatic source-changeover system with 2 devices without controller
In this case, the automatic control system to initiate changeovers between the «Normal» and «Replacement» sources under predefined conditions must be provided by the customer. Note that we can provide diagrams for the design of various automatic control systems for different sources.
E33079
A Masterpact automatic sourcechangeover system with 2 devices is made up of: 1 - circuit breaker QN connected to the "Normal" source; 2 - circuit breaker QR connected to the "Replacement" source; 3 - mechanical interlocking system by rods or cables;
1
automatic control of the system can be provided by adding: 4 - electrical interlocking unit IVE; 5 - auxiliaries control plate ACP; 6 - controller BA or UA.
E33078
3 2
Each Masterpact circuit breaker is equipped with: c a motor mechanism; c a shunt release (MX); c a «ready to close» contact (PF); c a block of 4 changeover switches (OF); c an additional terminal block (BS) and a block of 4 «connected» position switches (CE) for source-changeover systems made up of drawout breakers.
1
2
3
3
with controller E33082
In this case, conditional changeovers between the «Normal» and «Replacement» sources are initiated by a Merlin Gerin controller. IN GER
MERLIN
N R N
UN =
O
UN =
1
UR
0,5s
UN ON / ON / OFF
I
OFF
I
0,5s
/O
/O
R
fault
fault stop
test
manu
R N
4 6 GERIN MERLIN multi
9
0 . OFF
P25M
GERIN MERLIN multi
9
0 . OFF
660V 2-1 AC3-IEC29
P25M 660V 2-1 AC3-IEC29
Test
B US
Test
MERLIN
IN GER
N R
N
UN =
O
UN =
1
generat
or
UR
UN ON / ON / OFF
I
OFF
I /O
R
/O fault
fault auto stop
manu
test STOP
R N
5 Merlin Gerin
36 BTP207E-2.220-invers source
36
21/12/01, 10:10
automatic source-changeover system with 3 devices without controller
In this case, the automatic control system to initiate changeovers between the «Normal» and «Replacement» sources under predefined conditions must be provided by the customer. Note that we can provide diagrams for the design of various automatic control systems for different sources.
E33080
A Masterpact automatic sourcechangeover system with 3 devices is made up of: 1 - 2 circuit breakers QN1 and QN2 connected to the "Normal" source; 2 - circuit breaker QR connected to the "Replacement" source; 3 - mechanical interlocking system by rods;
1
for such applications (consult us) automatic control of the system can be provided by adding: 4 - 2 electrical interlocking unit IVE; 5 - auxiliaries control plate ACP; 6 - controller BA or UA.
3
Each Masterpact circuit breaker is equipped with: c a motor mechanism; c a shunt release (MX); c a "ready to close" contact (PF); c a block of 4 changeover switches (OF); c an additional terminal block (BS) and a block of 4 "connected" position switches (CE) for source-changeover systems made up of drawout breakers.
1
3 2
3
E33383
with controller (consult us)
GERIN MERLIN multi
9
0 . OFF
P25M
GERIN MERLIN multi
9
0 . OFF
660V 2-1 AC3-IEC29
P25M 660V 2-1 AC3-IEC29
MERLIN
IN GER
N
Test
R
UN =
O
UN =
1
UR
0,5s
Test
N
UN ON / I ON / OFF
OFF
I
0,5s
/O
/O
R
fault
fault stop
test
manu
R N
4
B US
6
5 MERLIN
IN GER
N R
N
UN =
O
UN =
1
UR
UN ON / ON / OFF
I
OFF
I /O
R
/O fault
fault auto stop
manu
test STOP
gen
erator
R N
In this case, conditional changeovers between the "Normal" and "Replacement" sources are initiated by a Merlin Gerin controller.
37
Merlin Gerin
BTP207E-2.220-invers source
37
21/12/01, 10:10
Masterpact: functions and characteristics
automatic source-changeover systems (cont.) mechanical interlock selection 025184
mechanical interlocking by connecting rods for 2 or 3 stack-mounted breakers This involves: c 2 or 3 Masterpact circuit breakers and/or switch-disconnectors; c an adaptation fixture on the right side of each breaker; c 1 or 2 sets of connecting rods with no-slip adjustments; The various parts are mounted by the user. The changeover system with interlocking by connecting rods is also available in a version which is factory mounted on a steel frame. Maximum distance between fixing planes: 900 mm.
025186
mechanical interlocking by cables for 2 side-by-side breakers This involves: c 2 Masterpact circuit breakers and/or switch-disconnectors; c an adaptation fixture on the right side of each breaker; c a set of cables with no-slip adjustments; The various parts are mounted by the user. Distance between fixing planes: c maximum: 2 000 mm; c minimum: breaker height with arc chute cover (see pages ????).
device combinations
assembly and installation
All combinations are possible: fixed and drawout versions, three-pole and four-pole, different ratings, circuit breakers or switchdisconnectors. All control units can be used on the circuit breakers.
The various parts of the Masterpact automatic source-changeover system are mounted and connected by the user. No circuit breaker modifications are required. The wiring diagrams are shown on pages ??? to ???. The Masterpact automatic sourcechangeover system may also be supplied factory-wired and mounted on a metal frame.
Merlin Gerin
38 BTP207E-2.230-invers source
38
21/12/01, 10:11
Masterpact: functions and characteristics
automatic source-changeover systems (cont.) automatic control: typical configurations c a motor mechanism (MCH); c a shunt release (MX); c a "ready to close" contact (PF); c a block of 4 changeover switches (OF); c an additional terminal block (BS) and a block of 4 "connected" position switches (CE) for changeover systems including drawout breakers.
Necessary auxiliaries and accessories To implement the configurations below, each Masterpact circuit breaker must be equipped with:
Option with "lockout after fault" With this option, the circuit breaker must be reset manually after a fault trip.
power circuit
possible combinations
configuration type
cat. No.
interlocking with 2 breakers
Q1 0 0 1
Q2 0 1 0
electrical interlocking automatic control with generator set with permanent "Replacement" source
685363
Q1 0 1 0 1 0
Q2 0 0 0 1 1
Q3 0 0 1 0 0
automatic control with permanent "Replacement" source with lockout after fault 685366 without lockout after fault 688183 automatic control with generator set with lockout after fault 689642 without lockout after fault 689644
Q1 0 1 0 0
Q2 0 0 1 0
Q3 0 0 0 1
electrical interlocking with lockout after fault without lockout after fault
688188 688187
Q1 0 1 0 0 1 0 1
Q2 0 0 1 0 1 1 0
Q3 0 0 0 1 0 1 1
electrical interlocking with lockout after fault without lockout after fault automatic control
688189 688190 689651
E30736
The electrical interlocking system and automatic control system for multiple sources must be wired by the user. It must be used in conjunction with the mechanical interlocking system. Typical wiring configurations are available on request. See examples below. For other configurations, consult us.
Q1
Q2
E30737
interlocking with 3 breakers 2 "Normal" sources + 1 "Replacement" source
Q1
Q2
Q3
E30738
interlocking with 3 breakers 3 sources, only one breaker closed
Q1
Q2
Q3
E30739
interlocking with 3 breakers 2 sources + 1 coupling
Q1
Q2
Q3
39
Merlin Gerin
BTP207E-2.230-invers source
688784 688942
39
21/12/01, 10:11
Masterpact: functions and characteristics
automatic source-changeover systems (cont.) controller option selection Used together with the auxiliaries control plate ACP, controllers BA and UA initiate the automatic changeover operations according to the status of the "Normal" and "Replacement" sources. c mounted on the front of the switchboard. The distance between the controller and the auxiliaries control plate must not exceed 2 metres. The interconnection wiring must be done by the customer.
E32704
E32705
Installation Two possibilities: c mounted directly on the auxiliaries control plate ACP.
MERLI multi
0 . OFF
N GERIN
9
MERLI multi
N GERIN
9
660V 292-1 AC3-IEC
0 . OFF
N GERIN
MERLI multi
9
0 . OFF
N GERIN
0 . OFF
660V 292-1 AC3-IEC
P25M 660V 292-1 AC3-IEC
660V 292-1 AC3-IEC
Test
Test
Test
Test
B US
multi
9
P25M
P25M
MERLI P25M
RIN IN GE MERL
N R
B US
N
RIN IN GE MERL
N R
N
UN =
O
/O
ON /
I
OFF
/O
I
OFF
/O
I
O
OFF
/O
UN =
1
R
fault
auto stop
I
OFF
ON /
ON /
fault
UR
UN
ON /
UN =
UR
UN
manu UN =
1
test
R
P
STO
genera
tor
R N
fault
fault auto stop
manu
test tor
P STO
genera
R N
customer connection
terminal block and electrical interlocking unit: IVE E32703
The terminal block and electrical interlocking unit IVE is used to connect the operating mechanism. Control voltage: c 48 to 415 V, 50/60 Hz - 440 V 60 Hz. The IVE control voltage must be the same as the motor mechanism voltage.
auxiliaries control plate: ACP 053060
The auxiliaries control plate ACP includes: c two P25M circuit breakers supplying and protecting the automatic control circuits for the "Normal" and "Replacement" sources. These circuit breakers have an infinite breaking capacity; c two relay contactors for the BA or UA controller; c the terminal block for connection to the controller.
Power supply: Power is supplied by the "Normal" and "Replacement" sources. The control voltage for the auxiliaries control plate must be the same as for the IVE unit and the motor mechanisms. Control voltages c 220 to 240 V 50/60 Hz; c 380 to 415 V 50/60 Hz - 440 V 60 Hz. Installation: The auxiliaries control plate ACP must be wired to the IVE unit by the customer.
Merlin Gerin
40 BTP207E-2.240-invers source
40
21/12/01, 10:12
053058
controller
Controller UA
controller
BA
compatible circuit breakers
All Masterpact circuit breakers
UA
4-position switch automatic operation forced operation on "Normal" source forced operation on "Replacement" source stop (both "Normal" and "Replacement" sources off)
c c c c
c c c c
c
c c c
automatic operation monitoring of the "Normal" source and automatic changeover generator set control load shedding and reconnection of non-priority circuits changeover to the "Replacement" source if one of the phases of the "Normal" phase is absent
c
test by opening the P25M circuit breaker supplying the controller by pressing the test button on the front of the controller
c c
indications circuit breaker status indication on the front of the controller: on, off, fault trip, automatic mode indicating contact automatic mode indicating contract
c c
c c
c
c c
other functions selection of type of "Normal" source (single-phase or three-phase) voluntary transfer to "Replacement" source (e.g. energy management commands) during peak-tariff periods (energy management commands), forced operation on "Normal" if "Replacement" source not operational supplementary control contact (not carried out by the controller). Transfer to "Replacement" source only if contact closed. (ex: UR frequency control) setting of maximum startup time for the replacement source
c c
c c
power supply control voltages (1)
220 to 240 V 50/60 Hz 380 to 415 V 50/60 Hz - 440 V 60 Hz
options c
communication option
(1) The same voltage must be used for the ACP plate, the IVE unit and the circuit breaker motor mechanisms. If this voltage is the same as the source voltage, then the “Normal” and “Replacement” sources can be used directly for the power supply. If not, a BC type or equivalent isolation transformer must be used.
Merlin Gerin
BTP207E-2.240-invers source
41 41
21/12/01, 10:12
Masterpact: functions and characteristics
automatic source-changeover systems controller option selection (cont.)
E30184
controller BA
Controller BA can be used with Masterpact circuit breakers to implement a straightforward automatic source-changeover system (switching from one source to another depending on the presence of voltage UN on the "Normal" source).
MERLIN GERIN compact / masterpact
BA automatism 220/240 V 50/60 Hz
N
R
UN
N
UR
ON/I
ON/I
OFF/O
OFF/O
fault
fault
UN = 0
2 4 t1 1 8 s 15 0.5 0.1 30
0.5s
0.5s
t2 s
stop manu
reset
N
15 30 8 60 120 4 0.1 240
UN = I
R
auto
Electrical characteristics Power is supplied from the auxiliaries control plate ACP. The same voltage must be used to supply the ACP plate, the IVE unit and the circuit breaker motor mechanisms. If this voltage is the same as the source voltage, the "Normal" and "Replacement" sources can be used directly for the power supply. If not, a BC type or equivalent isolation transformer must be used.
Control voltages c 220 to 240 V 50/60 Hz; c 380 to 415 V 50/60 Hz - 440 V 60 Hz.
Operation c a four-position switch can be used to select: v automatic operation; v forced operation on source N; v forced operation on source R; v stop (both "Normal" and "Replacement" sources off); c adjustment of time delays in front: v t1 from 0.1 to 30 seconds; v t2 from 0.1 to 240 seconds; c circuit breaker status indication on the front of the controller: on, off, fault trip;
c integrated terminal block for connection of the following signals: v inputs: – order for voluntary transfer to source R (e.g. energy management commands), – supplementary control contact: (not carried out by the controller). Transfer to "Replacement" source only if contact closed (ex: UR frequency control), v outputs: – indication of operation in automatic mode. Connection to the terminal block: see p.XXX. c controller BA can be tested by opening the P25M circuit breaker on the N circuit, thus simulating a failure of UN. See detailed transfer steps on page XXX.
R
Front face of controller BA
Time delay settings: QN: Masterpact circuit breaker with motor mechanism on “Normal” source, QR: Masterpact circuit breaker with motor mechanism on “Replacement” source, t1: time delay before QN opens when the voltage UN of the “Normal” source disappears, t2: time delay before QR opens when the voltage UN of the “Normal” source is restored.
Merlin Gerin
42 BTP207E-2.250-BA
42
21/12/01, 10:12
c 4-position switch in "auto" position (automatic operation)
QN et QR open
off
N I
operat. on source N
R O
4-position switch N et UN présente
UN fail (duration > t1) or voluntary switching order received UR present and supplementary control contact N➡R closed
"auto"
reset
c 4-position switch in "N " position (forced operation on "Normal" source) E30187
E27107
E21108
c 4-position switch in "stop" position
duration a 1 s
QR opens
QN opens
t > 0,5 s
end of reset t > 0,5 s
QN closes
QR closes
QN fermé
"stop" operat. on source N
QR closed
N O
operat. on source R
R I
N I
R O
action on 4-position switch
UN present for t > t2 or voluntary switching order stopped
c 4-position switch in "R" position (forced operation on "Replacement" source) E32708
QR opens
t > 0,5 s
4-position switch in "R" position UR present and supplementary control contact N➡R closed QN closes QN opens
QN closed t > 0,5 s
QR closes
QR closed
operat. on source R
N O
R I
action on 4-position switch
Merlin Gerin
BTP207E-2.250-BA
43 43
21/12/01, 10:12
Masterpact: functions and characteristics
automatic source-changeover systems controller option selection (cont.) controller UA
E30183
053059
Controller UA can be used with Masterpact circuit breakers to implement a sourcechangeover system offering the following automatic functions: c switching from one source to another depending on the presence of voltage UN on the "Normal" source; c control of an engine generating set; c shedding and reconnection of non-priority circuits; c switching to the "Replacement" source in the event of a failure on one of the phases of the "Normal" source. Electrical characteristics Power is supplied from the auxiliaries control plate ACP. The same voltage must be used to supply the ACP plate, the IVE unit and the circuit breaker motor mechanisms. If this voltage is the same as the source voltage, the "Normal" and "Replacement" sources can be used directly for the power supply. If not, a BC type or equivalent isolation transformer must be used.
Control voltages c 220 to 240 V 50/60 Hz; c 380 to 415 V 50/60 Hz - 440 V 60 Hz.
Operation c a four-position switch can be used to select: v automatic operation; v forced operation on source N; v forced operation on source R; v stop (circuit breakers open and manual operation); c adjustment of time delays in front: v t1 from 0.1 to 30 seconds; v t2 from 0.1 to 240 seconds; v t3 from 0.5 to 30 seconds; v t4 from 0.5 to 30 seconds; v t5 from 60 to 600 seconds; c circuit breaker status indication on the front of the controller: on, off, fault trip; c test button on the front of the controller to check the transfer from the “Normal” source to the "Replacement" source and the return to the "Normal" source;
c integrated terminal block for connection of the following signals: v inputs: – order for voluntary transfer to source R (e.g. energy management commands), – supplementary control contact: (not carried out by the controller). Transfer to "Replacement" source only if contact closed (ex: UR frequency control), v outputs: – control of engine generator set, – load shedding of non-priority circuits, – indication of operation in automatic mode; c 3 switches provide the following functions: v selection of the type of "Normal" source, i.e. single-phase or three-phase; v enable or disable voluntary energy management transfer if the "Replacement" source is not operational; v selection of the maximum tolerated starting time for the engine generator set ("Replacement" source): 120 s or 180 s.
Batibus option for controller UA A communication function can be used to check the following from a remote location: c status of the circuit breakers (open, closed or fault trip); c voltage presence on the “Normal” and “Replacement” sources; c presence of an order forcing operation on the “Replacement” source (e.g. for energy management purposes); c values of settings and configurations, c status of the non-priority circuits (whether subject to load shedding or not).
In automatic mode, this communications option also offers the possibility of remote forced operation on the “Replacement” source.
MERLIN GERIN compact / masterpact
UA automatism 220/240 V 50/60 Hz
N
R
UN ON/I
ON/I
OFF/O
OFF/O
fault
fault
stop manu
reset
auto test
N
N
UR
UN = 0
t4 s
5 10 2 15 20 1 0.5 30
t2 s
15 30 8 60 120 4 0.1 240
240 300 160 360 480 120 60 600
2 4 t1 1 8 s 15 0.5 0.1 30 5 10 t3 2 15 s 20 1 0.5 30
UN = I
R
t5 s
R STOP
generator
Front face of controller UA
Time delay settings: QN: Masterpact circuit breaker with motor mechanism on “Normal” source, QR: Masterpact circuit breaker with motor mechanism on “Replacement” source, t1: time delay before QN opens when the voltage UN of the “Normal” source disappears, t2: time delay before QR opens when the voltage UN of the “Normal” source is restored, t3: time delay before QR closes once QN has opened and the load has been shed, t4: time delay before QN closes once QR has opened and the load has been reconnected, t5: time delay for confirmation of presence of UN before stopping the generator set.
44 BTP207E-2.260-UA
Merlin Gerin
44
21/12/01, 10:12
E30185
E27107
QN and QR open
stop
"auto"
reset
c 4-position switch in "N" position (forced operation on "Normal" source) E30187
c 4-position switch in "auto" position (automatic operation)
c 4-position switch in "stop" position
N I
operat. on source N
R genset off O
4-position switch in "N" and UN present
UN fails (duration > t1) or voluntary switching order received duration a 1 s
end of reset
QR opens and load shedding
genset startup
t > t4
UR present for t < 120 s or 180 s and supplementary control contact N➡R closed
QN closes
QN opens and load shedding
QN closed
"stop"
operat. on source N
t > t3
QR closes
N I
R genset off O
action on 4-position switch
QR closed
R genset on I
UN present for t > t2 or voluntary switching order stopped
c 4-position switch in "R" position (forced operation on "Replacement" source) E30186
N O
operat. on source R
4-position switch in "R" and UN present
QR opens and load reconnection genset startup t > t4
UR present for t < 120 s or 180 s and supplementary control contact N➡R closed QN closes QN opens and load shedding
QN closed t > t3 genset remains on QR closes UN present for t > t5 and no voluntary switching order received QR closed genset off operat. on source R
N O
R genset on I
UR absent action on 4-position switch
45
Merlin Gerin
BTP207E-2.260-UA
45
21/12/01, 10:12
Merlin Gerin
40 BTP207E-3.001-sommaire
40
21/12/01, 10:13
LV power air circuit breakers and switch-disconnectors
Masterpact 3/ installation and connection page installation general safety clearance fixed circuit breakers M08 to M32 drawout circuit breakers M08 to M32 fixed circuit breaker M40 drawout circuit breaker M40 fixed circuit breaker M50 drawout circuit breaker M50 drawout circuit breaker M63 manual source changeover systems manual and automatic source changeover systems connection fixed and drawout circuit breakers M08N/M10N/M12N fixed and drawout circuit breakers M08H,L/M10H,L/M12H,L/M16N,H,L fixed and drawout circuit breakers M20N,H/M25N,H fixed and drawout circuit breakers M20L/M25L/M32H fixed and drawout circuit breaker M40 fixed and drawout circuit breaker M08 to M16 fixed and drawout circuit breaker M50 to M63 wiring diagrams: c STR 18 M / 28 D / 38 S / 58 U c STR 28 D / 38 S / 58 U avec options c STR 68 U avec options m01 à m31 c automatic source changeover c manual source changeover
0 0 0 0 0 0 0 0 0
0
0 0 0 0 0 0 0 0 0 0 0 0
41
BTP207E-3.001-sommaire
41
21/12/01, 10:13
Masterpact: installation and connection
general
installation
Masterpact circuit breakers must be installed in the vertical position on a base plate or on rails.
drawout circuit breaker (M08 to M63)
The drawout version makes it possible to: c rapidly remove and/or replace the circuit breaker without having to deal with connections; c install stand-by outgoers in a switchboard that will receive the necessary circuit breakers later in time
E31256
E31254
"Connected" position
26
"Test" position ample clearance between contacts
E31255
Installation on a metal base plate
018241
Installation on rails
45
"Disconnected" position easy withdrawal, short travel
E31257
E29026
E28811
fixed circuit breaker (M08 to M50)
305
"Withdrawn" position compact dimensions
Merlin Gerin
42 BTP207E-3.200-généralité
42
21/12/01, 10:14
Masterpact: installation and connection
safety clearance
Certain distances must be maintained between a circuit breaker and other elements such as panels, bars and other circuit breakers. Taken together, these distances form the safety clearance for the circuit breaker. The diagrams and the table below indicate the required distances when installing Masterpact circuit breakers.
These distances are the results of tests carried out in accordance with standard IEC 947-2 and are in part determined by the ultimate breaking capacities.
C
100
A
D
D
C A
E31230
100
E31233
E31232
fixed circuit breaker
A
A B
B
B
Masterpact M08 to M50 type of connection
to insulated barrier A B C front connection without cover (1) 360 30 0 rear connection without cover 150 30 20 rear connection with cover 0 0 20
to metal parts A B 360 70 250 70 0 0
D (2) 0 0 0
C – 95 95
D (2) 0 0 –
B
to live bars A B 1085 420 1085 420 145 105
C – 495 125
D (2) 0 0 0
100
C E31231
E31229
drawout circuit breaker
A
A
B
213
B
Masterpact M08 to M63 type of connection
to insulated barrier A B front connection without cover (1) 300 15 rear connection without cover 150 15 rear connection with cover 0 0
(1) Shield necessary. (2) D is the clearance required for connection of auxiliaries. D = 0 for fixed circuit breakers (required clearance included in the height of the connection plugs). D = 0 for drawout circuit breakers as well.
C 0 45 45
to metal parts A B 300 50 150 50 0 0
C – 45 45
C – 445 75
Note: For the fixed circuit breakers, a clearance of 130 mm is required on top for removal of the arc chutes.
43
Merlin Gerin
BTP207E-3.200-généralité
to live bars A B 1000 400 1000 400 60 85
43
21/12/01, 10:14
Masterpact: connection
general
Conductor materials The terminals of Masterpact circuit breakers can be used to connect bare copper, tinned copper or tinned aluminium conductors without any special surface treatment.
016807
016806
Four types of connection are possible: c rear horizontal; c rear vertical; c front; c mixed. The terminals are sized to allow circuit breaker connection with bars up to 20 mm thick (except for the M40, M50 and M63).
Rear vertical connection
016808
025179
Front connection
electrodynamic forces
Rear horizontal connection
Mixed connection. Upper terminals: front connection. Bottom terminals: vertical connection.
c the first bar spacers must be located at less than a certain distance from the circuit breaker connection point;
c this maximum distance must be respected to withstand the electrodynamic forces that are applied between the bars during a short-circuit.
Maximum distance between circuit breaker connection point and the first bar spacers for various short-circuit currents Isc (kA) distance (mm)
30 350
50 300
65 250
80 150
150 150
Merlin Gerin
44 BTP207E-3.210-généralité
100 150
44
21/12/01, 10:16
Note: The indicated values come from tests and theoretical calculations made for the parameters given below. These tables are intended to serve as a general guide for connection design and not to replace experience acquired for a certain type of connection or the need for subsequent tests.
parameters used in establishing the tables
c maximum admissible bar temperature: 100 °C; c temperature in the switchboard around the circuit breaker and its connections: Ta; c copper busbars.
drawout circuit breakers
E31258
connection selection table
drawout circuit breakers, edgewise bars maximum current
Ta = 40 °C
800 1000 1250 1400 1600 1800 2000 2200 2500 2800 3000 3200 3600 4000 4700 5000 5100 5700 6300
M08 M10 M12 M16 M16 M20 M20 M25 M25 M32 M32 M32 M40 M40 M50 M50 M63 M63 M63
Masterpact
Ta = 50 °C number of bars 5 thick bars 10 thick bars 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.63 x 5 1b.63 x 10 2b.63 x 5 1b.63 x 10 2b.80 x 5 1b.80 x 10 2b.80 x 5 1b.80 x 10 2b.100 x 5 2b.63 x 10 2b.100 x 5 2b.63 x 10 4b.80 x 5 2b.80 x 10 4b.100 x 5 2b.100 x 10 5b.100 x 5 3b.80 x 10 6b.100 x 5 3b.100 x 10 4b.100 x 10 4b.100 x 10 5b.100 x 10 5b.100 x 10 5b.100 x 10 6b.100 x 10 6b.100 x 10
Masterpact M08 M10 M12 M16 M16 M20 M20 M25 M25 M32 M32 M40 M40 M50 M50 M50 M63 M63
Ta = 60°C number of bars 5 thick bars 10 thick bars 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.63 x 5 1b.63 x 10 2b.63 x 5 1b.63 x 10 2b.80 x 5 1b.80 x 10 2b.80 x 5 2b.50 x 10 2b.100 x 5 2b.63 x 10 2b.100 x 5 2b.63 x 10 4b.80 x 5 2b.80 x 10 4b.100 x 5 2b.100 x 10 6b.100 x 5 3b.100 x 10 3b.100 x 10 4b.100 x 10 4b.100 x 10 5b.100 x 10 5b.100 x 10 6b.100 x 10 6b.100 x 10
Masterpact M08 M10 M12 M16 M20 M20 M25 M25 M32 M32 M40 M40 M50 M50 M50 M63 M63
Merlin Gerin
BTP207E-3.210-généralité
number of bars 5 thick bars 10 thick bars 2b.50 x 5 1b.50 x 10 2b.63 x 5 1b.63 x 10 3b.50 x 5 2b.50 x 10 3b.50 x 5 2b.50 x 10 3b.63 x 5 2b.50 x 10 3b.80 x 5 2b.63 x 10 3b.100 x 5 2b.80 x 10 3b.100 x 5 2b.80 x 10 4b.100 x 5 3b.80 x 10 4b.100 x 5 3b.80 x 10 3b.100 x 10 4b.100 x 10 4b.100 x 10 5b.100 x 10 5b.100 x 10 6b.100 x 10 6b.100 x 10
45 45
21/12/01, 10:16
Masterpact: installation
fixed circuit breakers M08 to M32
dimensions E30742
553
E30749
necessary space for removing the arc chutes (with or without arc chute cover)
E30748
3 or 4 poles
438 493 378
90 130
45
311 (*) (*)
30 mini 60 maxi
150
400
11
68
11
422 (3p)
290
515
11
11
537 (4p)
(*) Datum
mounting on a base plate
mounting detail Ø14
E30775
E30766
E30765
on rails
B
Ø11
150
150
30 mini 60 maxi
A B
30 mini 60 maxi
A
3 poles 150 400
2 Ø11 x 6
4 poles 150 515
cut-outs holes for escutcheon
E30764
E30763
cut-outs de porte
152,5
270 14,5 148,5
(*) 71,5
69
27 37,5
80 mini
80 mini
325
11 Ø5
180
180
17,5
(*)
(*) Datum Merlin Gerin
48 BTP207E-3.230-M08…32
48
21/12/01, 10:17
Masterpact: installation
a
drawout circuit breaker M08 to M32
E30746
3 or 4 poles
"disconnected" position
E30747
dimensions E30741
45
a 439
800 mini
(*)
60
101
175
55
325
55
128
435 (3p)
85
367
55
425
70
550 (4p)
(*)
(*) Datum
mounting
mounting detail
E30768
E30767
E30775
on rails
on a base plate
Ø14
B
Ø11
101
175
101
cut-outs
E30761
front panel cut-out
A B
175
A
3 poles 175 325
2 Ø11 x 6
4 poles 175 425
holes for escutcheon
E30760
ACB's side
152,5
270
148,5
71,5
47
55
100 mini ACB's basis
100 mini
325
Merlin Gerin
BTP207E-3.230-M08…32
19
69
18,5
11 Ø5
180
180
17,5
49
49
21/12/01, 10:17
Masterpact: installation
fixed circuit breaker M40
dimensions E31226
E30752
necessary space for removing the arc chutes (with or without arc chute cover) 90
45
819
E30753
3 or 4 poles
553 759 493
130
311 (*) (*)
30 mini 60 maxi
150 290
11
515
11
68
537 (3p)
11
780 11
802 (4p) (*) Datum
mounting on a base plate
mounting detail E30775
E30772
E30771
on rails
Ø14
B
Ø11
150
50 maxi
150
50 maxi
A B
30 mini 60 maxi
30 mini 60 maxi
A
3 poles 150 515
2 Ø11 x 6
4 poles 150 780
cut-outs holes for escutcheon
E30764
E30763
front panel cut-out
152,5
270 14,5 148,5
(*) 71,5
69
27 37,5
80 mini
80 mini
325
11 Ø5
180
180
17,5
(*)
(*) Datum Merlin Gerin
50 BTP207E-3.240-M40
50
21/12/01, 10:17
Masterpact: installation
a
drawout circuit breaker M40
E30743
E30750
3 or 4 poles
"disconnected" position
E30751
dimensions
45
a 439 484
(*)
800 mini
128
(1)
60
101
55
425
70
85
175
550 (3p)
367
60
55
350
350
815 (4p)
(*)
(*) Datum (1) 4-pole version only.
mounting
on a base plate
mounting detail
E30777
E30773
E30774
on rails
40
40
30
350
150
350
101
101
175
(1) 4-pole version only.
cut-outs
front panel cut-out
2 Ø11 x 6 (3p) 6 Ø11 x 22 (4p)
175
holes for escutcheon
ACB's side
E30760
E30762
175
(1)
(1)
152,5
270
47
19
45 (1)
55
100 mini
325
ACB's basis
(1) 4-pole version only.
69
18,5
11 Ø5
180
180
17,5
51
Merlin Gerin
BTP207E-3.240-M40
148,5
71,5
51
21/12/01, 10:17
Masterpact: installation
fixed circuit breaker M40
dimensions E31226
E30752
necessary space for removing the arc chutes (with or without arc chute cover) 90
45
819
E30753
3 or 4 poles
553 759 493
130
311 (*) (*)
30 mini 60 maxi
150 290
11
515
11
68
537 (3p)
11
780 11
802 (4p) (*) Datum
mounting on a base plate
mounting detail E30775
E30772
E30771
on rails
Ø14
B
Ø11
150
50 maxi
150
50 maxi
A B
30 mini 60 maxi
30 mini 60 maxi
A
3 poles 150 515
2 Ø11 x 6
4 poles 150 780
cut-outs holes for escutcheon
E30764
E30763
front panel cut-out
152,5
270 14,5 148,5
(*) 71,5
69
27 37,5
80 mini
80 mini
325
11 Ø5
180
180
17,5
(*)
(*) Datum Merlin Gerin
50 BTP207E-3.240-M40
50
21/12/01, 10:17
Masterpact: installation
a
drawout circuit breaker M40
E30743
E30750
3 or 4 poles
"disconnected" position
E30751
dimensions
45
a 439 484
(*)
800 mini
128
(1)
60
101
55
425
70
85
175
550 (3p)
367
60
55
350
350
815 (4p)
(*)
(*) Datum (1) 4-pole version only.
mounting
on a base plate
mounting detail
E30777
E30773
E30774
on rails
40
40
30
350
150
350
101
101
175
(1) 4-pole version only.
cut-outs
front panel cut-out
2 Ø11 x 6 (3p) 6 Ø11 x 22 (4p)
175
holes for escutcheon
ACB's side
E30760
E30762
175
(1)
(1)
152,5
270
47
19
45 (1)
55
100 mini
325
ACB's basis
(1) 4-pole version only.
69
18,5
11 Ø5
180
180
17,5
51
Merlin Gerin
BTP207E-3.240-M40
148,5
71,5
51
21/12/01, 10:17
Masterpact: installation
fixed circuit breaker M50
dimensions
90
45
E30757
E30756
necessary space for removing the arc chutes (with or without arc chute cover)
E31227
3 poles
819 759
130
311
(*) (*) 30 mini 60 maxi
150
780
11
68
11
802
290
(*) Datum
mounting on a base plate
mounting detail E30775
E30772
E30771
on rails
Ø14
B
Ø11
150
50 maxi
150
50 maxi
A B
30 mini 60 maxi
30 mini 60 maxi
A
2 Ø11 x 6
3 poles 150 780
cut-outs holes for escutcheon
E30764
E30763
front panel cut-out
152,5 270
14,5 148,5
(*)
71,5
69
27 37,5
80 mini
80 mini
325
11 Ø5
180
180
17,5
(*)
(*) Datum Merlin Gerin
52 BTP207E-3.250-M50
52
21/12/01, 10:18
Masterpact: installation
a
drawout circuit breaker M50
E30744
3 or 4 poles
"disconnected" position
E30755
E30754
dimensions
45
45
a 484
800 mini
(*)
128 60
101
175
60
85
55
350
350
815 (3p)
367
40
475
55
475
1045 (4p)
(*)
(*) Datum
mounting
on a base plate
mounting detail
E31228
E30770
E30769
on rails
40
40
30
350
150
350
175
101
101
175
cut-outs
175
holes for escutcheon
front panel cut-out
E30762
6 Ø11 x 22 (3p) 6 Ø11 x 33 (4p)
E30760
ACB's side
152,5
270
47
19
45 (1)
55
100 mini
325
ACB's basis
(1) 4-pole version only. Merlin Gerin
BTP207E-3.250-M50
148,5
71,5
69
18,5
11 Ø5
180
180
17,5
53
53
21/12/01, 10:18
Masterpact: installation
a
drawout circuit breaker M63
E30745
3 poles or 4 poles
"disconnected" position
E30759
E30758
dimensions
45
45
a 484
800 mini
(*)
128 60
101
175
40
85
55
475
475
1045
367
(*)
(*) Datum
mounting on a plate
mounting detail
E30778
E30770
E30769
on rails
40
40
30
475
150
475
175
101
101
175
cut-outs
175
holes for escutcheon
front panel cut-out
side of c.b.
E30760
E30762
6 Ø11 x 33
152,5
270
47
148,5
71,5
19
55
325
45 (1)
18,5
100 mini
11 Ø5
base of c.b.
(1) 4-pole version only.
180
180
17,5
Merlin Gerin
54
BTP207E-3.260-M63+inv sour
69
54
21/12/01, 10:18
Masterpact: installation
source-changeover system
Interlocking by connecting rods for 2 stack-mounted breakers drawout pattern, 3 or 4 poles E30780
E30779
fixed pattern, 3 or 4 poles
50 50 5 52
40
30
14
30
125
125
900 max.
900 max. 900 max.
175
153
105
(*)
163
30 base of c.b. 180 30 mini 60 maxi
45 65 166
base of c.b. for ratings : M08 to M40 (3p)
base of c.b. for ratings : M40 (4p) to M63
(*)
82 (*)
44 (*)
Interlocking by connecting rods for 3 stack-mounted breakers fixed pattern, 3 or 4 poles E30782
E30781
drawout pattern, 3 or 4 poles
50 5
40
52
180
60
14
60
14
60
180 900 max.
900 max.
50
50 5
40
52
180
60
180 900 max.
900 max.
153
175
900 max.
105
(*)
163
45 65 166
base of c.b. for ratings : M08 to M40 (3p)
base of c.b. for ratings : M40 (4p) to M63
100
(*)
30 base of c.b. 180 30 mini 60 maxi
62 (*)
(*) Datum Merlin Gerin
BTP207E-3.260-M63+inv sour
55 55
21/12/01, 10:18
Masterpact: installation
source-changeover system
Interlocking by cables for 2 side-by-side breakers E30783
fixed or drawout patterns, 3 or 4 poles 2m maxi
200 mini r= 120 mini
r= 120 mini
automatic source-changeover system
7
8
9
10
11 1 2 1 3 1 4 1 5 1 6
E33352
6
H48
5
E30784
E33353
electrical interlocking IVE
mounted on a frame
1
2
3
4
H47 H43
H49 R
N
controller P58
L33
P62
L34 L35
M32(4p) M40(3p) M32(3p)
E33354
E33355
auxiliaries control plate ACP and controller UA/BA
2100
P60
1940 H51
1640
H50
H52
940
P61 P59 P63
L36 L37
panel cut-out for controller UA/BA
56
56
56
E33364
E33363
150 56
600
750 C34
C34
Dimensions (mm) type C34 H43 140 120
H47 151
H48 137
H49 160
H50 200
H51 255
H52 22
L33 6
L34 48
L35 84
L36 138
L37 150
P58 61,5
P59 170
P61 90
P62 P63 150(min) 187 Merlin Gerin
56 BTP207E-3.270-inv sour+M08N
P60 95
56
21/12/01, 10:19
Masterpact: connection
fixed and drawout circuit breakers M08N/M10N/M12N fixed circuit breaker front connection
rear connection
front connection E30786
E30785
horizontal terminals vertical terminals
115
115
85 45
12,5
front connectors screen
115 25
10
N (1)
10
25
112
horizontal terminals
15
17
115
E30787
12,5 107
115
85
115 45
23
17,5
(*)
rear connection
132
53
175 (**)
2 Ø12
50
335
25
10
(*) 12,5
221
2 Ø12
10 233
(*) 12,5
vertical terminals E30788
278
115
115
85
115
10
2 Ø12
(*) Datum.
(*)
(**) Hole for securing front connection support bracket. (1) On request, neutral on the right.
drawout circuit breaker front connection
rear connection
front connection
E30789
E30790
horizontal terminals vertical terminals
115
115
115
47,5 80 25 25
front connectors screen
12,5
15
N (1)
3 Ø12
10
(*) 45
rear connection 112
25
92
10
horizontal terminals
112
74,5
115
E30791
306
115
25 12,5
273 300,5
12,5
47,5 45
25
30 175
115
10
15 12,5
2 Ø12
10
(*)
306
vertical terminals E30792
(*)
115
115
47,5
8
2 Ø12
(*) Datum.
(*)
(1) On request, neutral on the right. Merlin Gerin
BTP207E-3.270-inv sour+M08N
115
57
57
21/12/01, 10:19
Masterpact: connection
fixed and drawout circuit breaker M50 to M63 fixed circuit breaker M50 rear connection 3 poles vertical terminals
E30819
horizontal terminals
100
30 200
112
53 (*)
25
25 25 25 52
15
246
55 306
12,5 15
drawout circuit breaker M50 rear connection 3 or 4 poles vertical terminals
E30810
horizontal terminals
100 30 112 25 157 25 25
92 137
79,5 12,5 43
25 15
345
363
15
(*)
drawout circuit breaker M63 rear connection 3 or 4 poles vertical terminals
E30820
horizontal terminals
100 30 112 25 157 25 25
92 137
79,5 12,5 25
43
15
345
363
15
(*) (*) Datum. Merlin Gerin
64 BTP207E-3.310-raccord M50-M63
64
21/12/01, 10:22
fixed circuit breaker M50 rear connection 3 poles vertical terminals 248
E30826
E30827
horizontal terminals
248
248
213
248
226
142,5 35
142,5
Ø12
213
10
10
25 25 25
20
13
145
20 Ø12
175
145 (*)
(*)
drawout circuit breaker M50 rear connection 3 poles vertical terminals
E30828
E30829
horizontal terminals
252,5
252,5
252,5
252,5 10
Ø12
220 12,5
100 72,5
100
10
25 25 25 45 25 25 25
Ø12 145
(*)
(*)
rear connection 4 poles
297,5
vertical terminals
245
245
100
100 12,5
12,5
N
245
245
100
35 10
220
25 25 25
297,5
E30831
E30830
horizontal terminals
72,5
10
10
Ø12
10
25 25 25 45 25 25 25
N
Ø12
(1) 70
(*)
(1)
145 (*)
drawout circuit breaker M63 rear connection 3 poles vertical terminals E30823
horizontal terminals
E30822
350
350
350
350
117,5 92,5
117,5
10
Ø12
260
10
25 25 25 85 25 25 25
Ø12
(*)
185
(*)
rear connection 4 poles vertical terminals
E30824
E30825
horizontal terminals
206 100
287
287
260
260
206
287
Ø12
10
10
25 25 25 85 25 25 25
N
N
Ø12 (*)
(1) (*) Datum.
(1) 70
185 (*)
(1) On request, neutral on the right. Merlin Gerin
BTP207E-3.310-raccord M50-M63
117,5 92,5
260
25 25 25
287
35
117,5
65 65
21/12/01, 10:22
Masterpact: connection
fixed and drawout circuit breaker M40 fixed circuit breaker rear connection 3 or 4 poles vertical terminals
E30809
horizontal terminals
100
30 112 252 53 (*)
25
25 25 25
15
243
55 306
12,5 15
(*) Datum.
drawout circuit breaker rear connection 3 or 4 poles vertical terminals
E30810
horizontal terminals
100 30 112 25 157 25 25
92 137
79,5(4p) 12,5 175
34,5(3p) 15
345
363
15
(*)
(*) Datum. Merlin Gerin
62 BTP207E-3.300-raccord M40
62
21/12/01, 10:22
fixed circuit breaker rear connection 3 poles
180 100
vertical terminals 165
E30812
E30811
horizontal terminals 85
130
25 25 25
172,5
85 35
80
100
25 25 25
172,5 145
10
10
12,5
12,5
Ø12 (*)
Ø12
80 (*)
rear connection 4 poles
230 100
vertical terminals
216
165
100
85
130
25 25 25
208,5
172,5
85 35
80
100
25 25 25
230
E30814
E30813
horizontal terminals
80
145
10
10
12,5
12,5 Ø12
N
Ø12
(1)
N
(*)
80
(1)
(*)
(*) Datum. (1) On request, neutral on the right.
drawout circuit breaker rear connection 3 poles
E30815
155
vertical terminals 155
100 12,5
E30816
horizontal terminals 65
172,5
35
155
25 25 25
47,5
172,5 10
10
25 25 25 40
Ø12 (*)
Ø12
70 (*)
rear connection 4 poles vertical terminals
230 155
191 155
155 100
65
230
E30818
E30817
horizontal terminals
208,5
25 25 25
N
47,5 35
155
10
10
25 25 25 40
12,5
Ø12 Ø12
(1)
172,5
(*)
N
70
(1)
(*)
(*) Datum. (1) On request, neutral on the right. Merlin Gerin
BTP207E-3.300-raccord M40
63 63
21/12/01, 10:22
Masterpact: connection
fixed circuit breakers M20L/M25L/M32H fixed circuit breaker front connection
rear connection
front connection 115
E30901
E30802
horizontal terminals vertical terminals
115
85
115 80 25 25
15
front connectors screen
15
N (1)
3 Ø12
100 335
rear connection
112
horizontal terminals
25 162
87
18
12,5
15 18
(*) 221
30
E30803
25 25
53
175 (**)
(*)
30
115
140
115
72,5 85,5 25 25
7
11,5
15
15
3 Ø12
(*)
236 268 E30804
vertical terminals 115
140
140
60 25
4 Ø12
(*)
(*) Datum. (**) Hole for securing front connection support bracket. (1) On request, neutral on the right. Merlin Gerin
60 BTP207E-3.290-raccorde
60
21/12/01, 10:20
Masterpact: connection
drawout circuit breakers M20L/M25L/M32H drawout circuit breaker front connection
rear connection
front connection 115
E30805
E30806
horizontal terminals vertical terminals
125
125
37,5 100 25 25 25
front connectors sceen
12,5
15
N (1)
30
4 Ø12
(*)
100
rear connection
363 112
115
E30807
92
horizontal terminals 25 157 25 25
125
37,5 100
34,5 37
125 25 25 25
15
329 344
12,5
12,5 4 Ø12
30
(*)
15 344
15
vertical terminals E30808
(*)
115
152,5
152,5
10 25
4 Ø12
(*)
(*) Datum. (1) On request, neutral on the right. Merlin Gerin
BTP207E-3.290-raccorde
61 61
21/12/01, 10:20
Masterpact: connection
fixed and drawout circuit breakers M08H,L/M10H,L/M12H,L/M16N,H,L fixed circuit breaker rear connection
front connection
E30793
horizontal terminals vertical terminals front connectors screen
115
E30901
front connection
115
85
115 80
12,5
25 25
15
N (1)
10
112
107
15
horizontal terminals
17
17,5
115
E30832
15
(*)
rear connection
132 25 25
53
175 (**)
3 Ø12
80
335
115
115
85 80
8
25 25
15
(*) 12,5
221 10 233
12,5
(*)
115
85
vertical terminals 115
E30794
278
3 Ø12
115
10
3 Ø12
(*) Datum.
(*)
(**) Hole for securing front connection support bracket. (1) On request, neutral on the right.
drawout circuit breaker rear connection
front connection
E30795
horizontal terminals vertical terminals
115
E30790
front connection
115
115
47,5 80 25 25
front connectors screen
12,5
15
N (1)
3 Ø12
10
(*) 80
rear connection
306
112
92 15
horizontal terminals E30796
25 112 25
115
115
115
25 25
30 175
25 12,5
273 300,5
12,5
47,5 80
57
15
15 12,5
3 Ø12
10
(*) 306
vertical terminals E30797
(*)
115
115
47,5
10
3 Ø12
(*) Datum.
(*)
(1) On request, neutral on the right.
Merlin Gerin
58 BTP207E-3.280-raccorde
115
58
21/12/01, 10:19
Masterpact: connection
fixed and drawout circuit breakers M20N,H/M25N,H fixed circuit breaker rear connection
front connection
E30798
horizontal terminals vertical terminals
E30901
front connection
115
115
80 25 25
12,5
front connectors screen
85
115
15
N (1) 20
335
25 25
152
horizontal terminals 115
E30832
53
115
115
15
18
85 80
15 3
107
(*)
rear connection
112
175 (**)
3 Ø12
80
25 25
17,5
15
12,5
(*) 12,5
221
3 Ø12
16
(*)
233 283 E30799
vertical terminals 115
115
85
115 20
3 Ø12
(*) Datum.
(*)
(**) Hole for securing front connection support bracket. (1) On request, neutral on the right.
drawout circuit breaker rear connection
front connection
E30800
horizontal terminals vertical terminals
115
E30790
front connection
115
115
47,5 80 25 25
front connectors screen
12,5
15
N (1)
3 Ø12 (*)
20
80
rear connection
306
112
92 15
horizontal terminals 115
E30796
25 112 25
115
115
25 25
30 175
25 12,5
273 300,5
12,5
47,5 80
62
15
15 12,5
3 Ø12
20
(*) 306
vertical terminals E30801
(*)
115
115
47,5
16
3 Ø12
(*) Datum.
(*)
(1) On request, neutral on the right. Merlin Gerin
BTP207E-3.280-raccorde
115
59 59
21/12/01, 10:19
Masterpact: connection
E30721
wiring diagrams STR 18 M / 28 D / 38 S / 58 U CHASSIS AUXILIARIES CN 1
- CN
BREAKER AUXILIARIES
CONTROL UNIT
+ Fu
AT
fault
disconnected
connected
closed
ready to close
BPO
BPF
open
springs charged 314 312 324 322 334 332 344 342 352 354 362 364 372 374
82
84
212 222
234 244
12
14
24
22
32
34
44
42
D4
C12
C2
A4 252 254 262 B4
CE or
MN or MNR
M MX
XF MX
OF F
F
O
O CH
SDE
processing unit
CD
311
321
331
341
351
361
PF
CT
371
81
211 221
231 241
11
21
31
41
D1
C11
C1
A1
251
B1
Fu
- CN
–
AT: BPO: BPF: CE:
emergency off "open" pushbutton "close" pushbutton "connected" position contact (10 A/240 V AC) M: spring charging motor (180 VA/240 V AC) XF: closing release (20 VA/240 V AC) MX: shunt release (20 VA/240 V AC) MN: undervoltage release (20 VA/240 V AC) MNR: time delayed undervoltage release (20 VA/240 AC) OF: auxiliary changeover contacts (10 A/240 V AC) O: 2 auxiliary NO contacts (10 A/240 V AC) F: 2 auxiliary NC contacts (10 A/240 V AC) SDE: fault trip indication contact (10 A/240 V AC) CH: charging motor limit switch contact PF: "ready to close" contact (10 A/240 V AC) (closing possible if breaker is open, not locked and operating mechanism charged) CD: "disconnected" position contact (10 A/240 V AC) CT: test posiiton contact (10 A/240 V AC)
c diagram shown with circuits deenergised, breaker open and in "connected" position, springs charged and relays in released position; c accessories such as pushbuttons, lamps and fuses are not supplied with the circuit breaker.
Wiring of the MNR (modified diagram). Instantaneous tripping with MNR when contact 254-262 opens. E30718
CN2
D4
254
MNR D1
Note: the wiring of the external contact replaces the spring charged indication and the contact PF.
Merlin Gerin
66 BTP207E-3.320-raccord
262
66
21/12/01, 10:23
Masterpact: connection
E30720
wiring diagrams STR 28 D / 38 S / 58 U with options CHASSIS AUXILIARIES CN 1
- CN
BREAKER AUXILIARIES
CONTROL UNIT
+ Fu
N P1
S1
P2
S2
AT
(4)
(4) LR alarm
disconnected
connected
372
374
362 364
354
342
352
344
332
322
324
334
312
314
(2) Z11 Z12
LR2
BPF
closed
fault
ready to close
BPO
open springs charged
Ic1 Ic2 V2
T2 T1
R1 R2
e+ e–
82
(5) 84 212 222
234 244
12
14
22
24
32
34
42
44
D4
C12 C2
A4 252 254 262 B4
CE or MN or MNR
T
M MX
XF MX
OF F F
F
O
O
V CH
SDE ammeter
ALR
PF
processing unit
CD
311
321
331
341
351
361
C
R
CT
371
Z21
Z22 (3)
LR1
F2 F1
V1
C
81 211 221
231 241
11
21
41
31
D1
C11 C1
A1
251
B1
power supply (1)
Fu
–
AT: BPO: BPF: LR: CR: T: CE:
emergency off "open" pushbutton "close" pushbutton long time trip (LT) indicating lamp short time trip (ST) indicating lamp earth fault trip indicating lamp "connected" position contact (10 A/240 V AC) M: spring charging motor (180 VA/240 V AC) R: load monitoring and control XF: closing release (20 VA/240 V AC) T: earth fault protection (EZ and SZ: input and output for zone selective interlocking) MX: shunt release (20 VA/240 V AC) MN: undervoltage release (20 VA/240 V AC) MNR: time delayed undervoltage release (20 VA/240 V AC) OF: auxiliary changeover contacts (10 A/240 V AC) O: 2 auxiliary NC contacts (10 A/240 V AC) F: 2 auxiliary NC contacts (10 A/240 V AC) SDE: fault trip indication contact (10 A/240 V AC) CH: charging motor limit switch contact F: fault trip local indicator FV: segregated fault trip indication contact (5 A/240 V AC) PF: "ready to close" contact (10 A/240 V AC) (closing possible if breaker is open, not locked and operating mechanism charged)
CD: CT: C:
"disconnected" position contact (10 A/240 V AC) test position contact (10 A/240 V AC) communication.
c Ic1: load shedding command according to Ic1 setting Ic2: load shedding command according to Ic2 setting; c diagram shown with circuits deenergised, breaker open and in "connected" position, springs charged and relays in released position; c accessories such as pushbuttons, lamps and fuses are not supplied with the circuit breaker.
Wiring of the MNR (modified diagram). Instantaneous tripping with MNR when contact 254-262 opens. E30718
- CN
D4
D1
Note: the wiring of the external contact replaces the spring charged indication and the contact PF.
V contact wiring: for breaker locking, depending on the selected fault. CN1/CN + BPO C2
V V (1) Power supply terminals for I or T or F options (AD module with BAT battery module for backup power). (2) Zone selective interlocking with line side breaker. (3) Zone selective interlocking with load side breaker (remove jumper). (4) DC power supply. R contacts reset request wiring of an external contact. (5) With Z and/or C options, terminal 84 is not available.
CN2/CN –
V
MX C1
Selective locking needs: c external power supply (F1, F2); c an additional terminal (BS).
Merlin Gerin
BTP207E-3.320-raccord
262
254
MNR
E30719
CN2
67 67
21/12/01, 10:23
Masterpact: connection
E30722
wiring diagrams STR 68 U with options m01 to m31 CHASSIS AUXILIARIES CN 1
- CN
BREAKER AUXILIARIES
CONTROL UNIT
+ Fu
N P1
S1
P2
S2
AT
(5)
disconnected
connected
closed
ready to close
BPO
BPF
open
374
372
362 364
352 354
332
342
334
344
322
324
312
314
springs charged T21
T2 T1(3)
T22
234 244
82 212 222
12
14
22
24
32
34
42
44
D4
C12
A4 252 254 262 B4
C2
CE or MN or MNR
M MX
XF MX
OF F
F
O
O CH
SDE EZ(4) M01 to M16
processing unit
CD
311
321
331
341
351
361
PF
CT
371
F1 F2 F12 F11 512 522 532 542 552 562 + power supply (2)
81
211 221
231 241
11
21
31
41
D1
C11
C1
A1
251
B1
E56
E55
E54
E53
E52
E51
MR6
411 412 414 421 422 424 431 432 434 441 442 444 451 452 454 461 462 464
power supply (1)
E2
–
Fu
AT: BPO: BPF: CE: M: XF: MX: MN: MNR: OF: O: F: SDE: CH: M01: to M16
PF:
MR6:
- CN
–
emergency off "open" pushbutton "close" pushbutton "connected" position contact (10 A/240 V AC) spring charging motor (180 VA/240 V AC) closing release (20 VA/240 V AC) shunt release (20 VA/240 V AC) undervoltage release (20 VA/240 V AC) time delayed undervoltage release (20 VA/240 V AC) auxiliary changeover contacts (10 A/240 V AC) 2 auxiliary NO contacts (10 A/240 V AC) 2 auxiliary NC contacts (10 A/240 V AC) fault trip indication contact (10 A/240 V AC) charging motor limit switch contact indication option equipped with 6 opto-decoupled outputs to contacts (0.2 A/24 V DC), for programming as per table on page C54 (EZ: input for earth fault protection zone selective interlocking) "ready to close" contact (10 A/240 V AC) (closing possible if breaker is open, not locked and operating mechanism charged) relay module with 6 changeover contacts (3 A, 24 V DC)
CD: CT:
Wiring of the MNR (modified diagram). Instantaneous tripping with MNR when contact 254-262 opens.
"disconnected" position contact (10 A/240 V AC) test position contact (10 A/240 V AC).
c diagram shown with circuits deenergised, breaker open and in "connected" position, springs charged and relays in released position; c accessories such as pushbuttons, lamps and fuses are not supplied with the circuit breaker.
E30718
CN2
D4
254
MNR D1
Note: the wiring of the external contact replaces the spring charged indication and the contact PF.
(1) Power supply for control unit and modules. (2) Power supply for option M and module MR6 by module AD. (3) Terminals T1 and T2 must be imperatively short-circuited when the external CT is not connected. (4) The zone selective interlocking output is provided by one output of module m01 to m32.. (5) Zone selective interlocking with load side breaker: remove the jumper. Merlin Gerin
68 BTP207E-3.330-raccord
262
68
21/12/01, 10:24
relay outputs
basic version m01 other versions m02 m03 m04 m05 m06 m07 m08 m09 m10 m11 m12 m13 m14 m15 m16
transmission m17 reception outputs m18 m19 m20 m21 m22 m23 m24 m25 m26 m27 m28 m29 m30 m31
terminal number 512
522
LT
ST/Inst.
LT LT LT limit 2 LT LT LT LT LT limit 2 LT limit 1 limit 1 Z LT 512 ST/Inst. ST/Inst. T T T Z Z Z T ST/Inst. ST/Inst. limit 2 shed 2 reconn. 2 shed 1
ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST/Inst. ST 522 LT AS ST/Inst. AS Z AS limit 1 shed 1 shed 1 limit 1 shed 1 limit 1 shed 1 shed 1 AS
Protection: LT long time trip indication ST/Inst. short time or instantaneous trip indication T earth fault trip indication Z zone selective interlocking output Load monitoring and control: limit 1 indication of Ic1 setting overrun limit 2 indication of Ic2 setting overrun shed 1 load shedding command according to Ic1 setting (limit 1) shed 2 load shedding command according to Ic2 setting reconn. 2 load reconnection command according to Ic2 setting (limit 2)
532
542
552
562
shed 1 shed 1 shed 1 shed 1 shed 1 shed 1 limit 1 shed 1 shed 1 shed 1 shed 1 shed 1 shed 1 shed 1 T 5 ▲
shed 2 reconn. 1 shed 2 shed 2 reconn. 2 shed 2 Z shed 2 shed 2 shed 2 reconn. 2 shed 2 shed 2 reconn. 2
AS limit 1 limit 1 limit 1 limit 1 limit 1 T T T T T T T T T Inst. 1 ▲
limit 2 limit 2 AS AS AS limit 1 AS AS Z limit 1 Z AS Z AS AS 6 ▲
9 ▲
data transmission
e+ output
e– output
s+ input
s– input
▼
▼
▼
▼
connection modification for data transmission: options m17 to m31 E30723
module
T2
T1
T21
datatransmission
M17 to M31
processing unit
T22
e+
e–
r+
r–
self-monitoring: AS indication of control unit fault or overtemperature. F1
F2
F12 F11
+
532 542 552 562
512 522
–
power supply (2)
1
2
3
4
(3) 0V
4 5 8 9
ET 44 interface (1) (3) S1 (4) S2 (4)
24V
(1) Communication interface for RS485 - 9600 baud network. (2) Power supply for m option and ET44 interface (AD module). (3) Provided connectors. (4) Remote controlled relay output (10 A, 220 V AC). (5) JBUS, RS485, 9600 baud network.
1
2
1
3
Sub D9 connector (5)
2
(3)
Merlin Gerin
BTP207E-3.330-raccord
3
RD– TD– RD+ TD+
69 69
21/12/01, 10:24
Masterpact: connection
wiring diagrams STR 68 U with options m01 to m31 (cont.)
T2
T1
T21
E30725
E30724
power supply connection T22
module P
1 3
2 1 3
r– S1 S2 r+ 4 e– 3 ET 44 e+ 2 1
2 4 5 8 9
RD– TD– Sub D 9 RD+ connector (6) TD+
H1
H2
H1
H2
H4
BAT H4
processing unit
H3
H3
(4)
M17 to M31
e+e–r+ r–
Sub D 9 connector (1)
Sub D 15 connector module P
F1 F2
F12
F11 512 522 (7) (7) (7)
N L1 L2 L3 CN1 CN2 H1 H2 H3 H4
(5) + – power supply (2)
power supply for control units and complementary functions
(3)
All the protection functions of the control unit are powered by current sensors built into the circuit breaker. However power must be supplied: c to terminals F1 and F2 for the indication and display functions: v if the device has a low 3-phase load (less than 20% of the rated current) or a singlephase load, v if display and indications are required when the circuit breaker is off; c to terminals F11 and F12 for the M modules.
(1) Provided cable: length 1.5 m (connected to chassis). (2) Available supply sources: 24-48 V DC, 125 V DC, 100-240 V AC. (3) Backup power for trip unit information with BAT module (remove jumpers). (4) Provided cable. (5) Voltage connection (load side shown, line side also available). 3 or 4 poles available. (6) JBUS, RS 485-9600 baud network. (7) MR6 module wiring.
To ensure proper isolation of the circuits, two separate power supplies are required. They can be implemented as follows: c for terminals F1 and F2: v by direct supply of AC current (specify the required voltage when ordering: 100, 220, 380 V 50/60 Hz), v or by an AD module, with or without BAT (1 AD for each STR68), v or by direct supply of 24 V DC current (5 W, Class 2 insulation, < 10% ripple); c for terminals F11 and F12: v by another AD module (1 AD for each STR68, in addition to the modules supplying terminals F1 and F2), v or by direct supply of 24 V DC current, isolated from the circuit supplying terminals F1 and F2 (5 W, Class 2 insulation, < 10% ripple).
Merlin Gerin
70 BTP207E-3.340-raccord
70
21/12/01, 10:24
control unit STR 68 without power module E30728
E30727
AC supply without indicators maintained after tripping
control unit F1
M01 to M16 option
F2
F11
module MR6
control unit
F12
-
F1
M17 to M31 option
F2
F11
+
module ET 44
F12
-
0V
24V
+
module AD
module AD
110 - 220 - 380 V 50/60 Hz
110 - 220 - 380 V 50/60 Hz
AC supply with indicators maintained after tripping
E30729
E30730
DC supply with or without indicators maintained after tripping
control unit F1
M01 to M16 option
F2
F11
module MR6
F12
control unit F1
F2
M17 to M31 option F11
F12
module BAT
-
module BAT
+
-
module BAT
+
module AD
-
module AD
0V
24V
+ module BAT
+
-
module AD
110 - 220 - 380 V 50/60 Hz 24/30 - 48/60 - 110/125 V CC
module ET44
+ module AD
110 - 220 - 380 V 50/60 Hz 24/30 - 48/60 - 110/125 V CC
STR 68 control unit with power module E30732
E30731
AC or DC supply with or without indicators maintained after tripping
control unit F1
module BAT
F2
M17 to M31 option F11
F12
module P Cn1+
control unit
module MR6 F1
module BAT
F2
M01 to M16 option F11
module MR6
F12
module P Cn1+
Cn2-
Cn2-
100/240 V 50/60 Hz 24/28 - 125 V CC
100/240 V 50/60 Hz 24/28 - 125 V CC
Note: the battery module (BAT) provides back up power to the indicators on the trip unit front face to maintain indications after tripping. It can be omitted if the auxiliary supply is reliable. Merlin Gerin
BTP207E-3.340-raccord
71 71
21/12/01, 10:24
Masterpact: connection
wiring diagrams for automatic source-changeover systems (cont.) electrical interlocking - 2 sources + 1 coupling and lockout after fault (688189) possible states source 1 0 1 source 2 0 1 coupling 0 0
E33097
Version represented: c 2 sources + 1 coupling; c 2 circuit breakers closed; c electrical interlocking with lockout after a fault (SDE wiring): inoperative with automatic reset option.
"SOURCE 1" BREAKER AUXILIARIES
S1
1 0 1
0 1 1
1 0 0
0 1 0
0 0 1
"SOURCE 2" BREAKER AUXILIARIES
"COUPLING" BREAKER AUXILIARIES
S2
CN1 CN2
D to A
t1
COUPLING t2
t3
t4
R1
B4
262
254
252
A4
C2
34
32
84
24
22
82
322
14
12
CE
312 324
B4
262
254
252
A4
C2
34
32
84
24
22
82
322
14
314
CE
XF
12
CE
312 324
B4
262
254
252
A4
C2
34
32
84
24
22
82
322
14
314
CE
R3 12
312 324
314
R2
M MX Q1
OF
OF
CE
XF
CE
M
OF MX SDE
QC
OF
OF
XF
OF
M
CH
MX SDE
PF
OF
Q2
OF
CH
OF SDE
PF
Q1: QC: Q2: D: t1:
Masterpact on source 1 Masterpact used for coupling Masterpact on source 2 P25M circuit breaker (2 x 10 A) coupling signal: «source 1 failure» (minimum time delay 250 ms) t2: coupling signal: «source 2 failure» (minimum time delay 250 ms) t3: uncoupling signal: «source 1 restored» (minimum time delay 250 ms) t4: uncoupling signal: «source 2 restored» (minimum time delay 250 ms) R1,R2,R3: external relays for interlocking of SDE auxiliary switches.
M: XF: MX: CE: OF: SDE: CH: PF:
motor mechanism closing release shunt release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).
B1
A1
C1
31
81
21
251
A
c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system. The relays are not supplied with the circuit breakers.
Merlin Gerin
88 BTP207E-3.430-raccord
11
321
311
B1
251
A1
C1
31
81
21
11
321
311
B1
251
A1
C1
31
81
21
11
321
311
CH PF
88
21/12/01, 10:27
Masterpact: connection
wiring diagrams for automatic source-changeover systems (cont.) electrical interlocking - 2 sources + 1 coupling and wihtout lockout after fault (688190) possible states source 1 0 1 source 2 0 1 coupling 0 0
E33098
Version represented: c 2 sources + 1 coupling; c 2 circuit breakers closed; c electrical interlocking without lockout after a fault.
"SOURCE 1" BREAKER AUXILIARIES
S1
1 0 1
0 1 1
1 0 0
0 1 0
0 0 1
"SOURCE 2" BREAKER AUXILIARIES
"COUPLING" BREAKER AUXILIARIES
S2
CN1 CN2
D to A
t1
COUPLING t2
t3
B4
262
254
252
A4
C2
34
32
24
22
14
322
CE
XF
12
312 324
314
B4
262
254
252
A4
C2
34
32
24
22
14
322
12
CE
312 324
314
B4
262
254
252
A4
C2
34
32
24
22
14
322
12
312 324
314
t4
M MX Q1
OF
OF
CE
XF
OF
M XF
MX QC
OF
OF
M
OF MX
CH PF
Q2
OF
OF
OF
CH PF CH
Q1: QC: Q2: D: t1: t2: t3:
t4:
Masterpact on source 1 Masterpact used for coupling Masterpact on source 2 P25M circuit breaker (2 x 10 A) coupling signal: «source 1 failure» (minimum time delay 250 ms) coupling signal: «source 2 failure» (minimum time delay 250 ms) uncoupling signal: «source 1 restored» (minimum time delay 250 ms) uncoupling signal: «source 2 restored» (minimum time delay 250 ms)
M: XF: MX: CE: OF: SDE: CH: PF:
motor mechanism closing release shunt release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).
251
A1
C1
31
21
11
B1 A
c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system.
Merlin Gerin
BTP207E-3.430-raccord
321
311
B1
251
A1
C1
31
21
11
321
311
B1
251
A1
C1
31
21
11
321
311
PF
89 89
21/12/01, 10:27
Masterpact: connection
wiring diagrams for automatic source-changeover systems (cont.) electrical interlocking - 3 sources / 1 circuit breaker closed and lockout after fault (688188)
E33095
Version represented: c 3 sources, 1 circuit breaker closed; c electrical interlocking with lockout after a fault (SDE wiring).
possible states source 1 0 source 2 0 source 3 0
"SOURCE 2" BREAKER AUXILIARIES
"SOURCE 1" BREAKER AUXILIARIES
S1
S2
1 0 0
0 1 0
0 0 1
"SOURCE 3" BREAKER AUXILIARIES
S3
CN1 CN2
D to A
t1
t2
t3
R1
B4
262
254
252
A4
C2
34
32
84
82
22 24
14
322
12
CE
312 324
B4
262
254
252
A4
C2
34
32
24
84
82
22
322
14
314
CE
XF
12
CE
312 324
B4
262
254
252
A4
C2
34
32
24
84
82
22
322
14
314
CE
R3 12
312 324
314
R2
M MX Q1
OF
OF
CE
XF
CE
M
OF MX SDE
Q2
OF
OF
XF
OF
M
CH
MX SDE
PF
OF
Q3
OF
OF
CH
SDE
PF
B1
251
A1
C1
31
81
21
11
321
311
B1
251
A1
C1
31
81
21
11
321
311
B1
251
A1
C1
31
81
21
11
321
311
CH PF
A
Q1: Q2: Q3: D: t1:
Masterpact on source 1 Masterpact on source 2 Masterpact on source 3 P25M circuit breaker (2 x 10 A) signal for transfer to source 1 (minimum time delay 250 ms) t2: signal for transfer to source 2 (minimum time delay 250 ms) t3: signal for transfer to source 3 (minimum time delay 250 ms) R1,R2,R3: external relays for interlocking of SDE auxiliary switches.
M: XF: MX: CE: OF: SDE: CH: PF:
motor mechanism closing release shunt release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).
c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system. The relays are not supplied with the circuit breakers.
Merlin Gerin
86 BTP207E-3.420-raccord
86
21/12/01, 10:27
Masterpact: connection
wiring diagrams for automatic source-changeover systems (cont.) electrical interlocking - 3 sources / 1 circuit breaker closed and without lockout after fault (688187)
E33096
Version represented: c 3 sources, 1 circuit breaker closed; c electrical interlocking without lockout after a fault.
possible states source 1 0 source 2 0 source 3 0
"SOURCE 2" BREAKER AUXILIARIES
"SOURCE 1" BREAKER AUXILIARIES
S1
S2
1 0 0
0 1 0
0 0 1
"SOURCE 3" BREAKER AUXILIARIES
S3
CN1 CN2
D
to A
t1
t2
B4
262
254
252
A4
C2
34
24
32
22
14
322
12
CE
XF
312 324
314
B4
262
254
252
A4
C2
24
34
22
32
14
322
CE
12
312 324
314
B4
262
254
252
A4
C2
24
34
22
32
14
322
12
312 324
314
t3
M Q1
OF
OF
CE
XF
MX
M
OF MX OF
Q2
OF
XF M
OF MX
CH Q3
PF
OF
OF
OF
CH PF
B1
251
A1
31
C1
21
11
321
311
B1
A1
251
C1
31
21
11
321
311
B1
A1
251
C1
31
21
11
321
311
CH PF
A
Q1: Q2: Q3: D: t1: t2: t3:
Masterpact on source 1 Masterpact on source 2 Masterpact on source 3 P25M circuit breaker (2 x 10 A) signal for transfer to source 1 (minimum time delay 250 ms) signal for transfer to source 2 (minimum time delay 250 ms) signal for transfer to source 3 (minimum time delay 250 ms)
M: XF: MX: CE: OF: SDE: CH: PF:
motor mechanism closing release shunt release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).
c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system.
Merlin Gerin
BTP207E-3.420-raccord
87 87
21/12/01, 10:27
Masterpact: connection
wiring diagrams for automatic source-changeover systems (cont.) 3 circuit breakers - automatic control with generator set and lockout after fault (689642)
E33093
Version represented: c 2 sources + generator set; c electrical interlocking with lockout after a fault: inoperative with automatic reset option; c with auxiliary source; c with MN undervoltage release; c with choice of sources.
possible states "Normal 1" 0 "Normal 2" 0 "Replacement" 0
"NORMAL 1" BREAKER AUXILIARIES
1 1 0
0 0 1
1 0 0
0 1 0
"REPLACEMENT" BREAKER AUXILIARIES
"NORMAL 2" BREAKER AUXILIARIES
N1 N2 R
auxiliary source
genset startup signal G
D
undervoltage relay
to B
U=0
C
genset fault contact
OFF R
N AUTO CMa
Fu
Fu
N1 RTn2
N1-2
Fu N2
RTn3 RX3
Fu
RTn1
RX2
RX1 R1
OF
OF
B4
262
254
252
A4
D4
24
22
14
12
312
314
CE
84
CE
82
CE
XF QN1
322
324
B4
262
254
252
A4
D4
24
22
14
12
312
314
322
324
CE
84
CE
82
CE
332
334
B4
262
254
252
A4
D4
24
22
14
12
312
84
82
314
322
324
332
334
R2
M
MN
XF
SDE
CE
M
CE
MN OF
QN2
XF
OF
M
MN
SDE
CH
OF
QR
PF
OF
SDE
CH PF
CH
B1
251
A1
D1
21
11
81
311
321
B1
251
A1
D1
21
11
81
311
321
331
B1
251
A1
D1
21
11
81
311
321
331
PF
B
QN1: Masterpact on «Normal1» source QN2: Masterpact on «Normal2» source QR: Masterpact on «Replacement» source D: P25M circuit breaker (2 x 10 A) C: operation selection switch Cma: source selection switch FU: fuses Rtn1: voltage relay with 0.1 to 30 s time delay Rtn2: voltage relay with 10 to 180 s time delay Rtn3: voltage relay RX1: relay with 0.25 s time delay RX2: relay with 0.25 s time delay RX3: relay R1/R2: external relays for interlocking of SDE auxiliary switches (equipped with 2 contacts O).
M: XF: MN: CE: OF: SDE: CH: PF:
motor mechanism closing release undervoltage release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).
c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system. The two relays and selection switches are not supplied with the circuit breakers.
Merlin Gerin
84 BTP207E-3.410-raccord
84
21/12/01, 10:26
Masterpact: connection
wiring diagrams for automatic source-changeover systems (cont.) 3 circuit breakers - automatic control with generator set and without lockout after fault (689644)
E33094
Version represented: c 2 sources + generator set; c electrical interlocking with lockout after a fault: inoperative with automatic reset option; c with auxiliary source; c with MN undervoltage release; c with choice of sources.
possible states "Normal 1" 0 "Normal 2" 0 "replacement" 0
"NORMAL 2" BREAKER AUXILIARIES
"NORMAL 1" BREAKER AUXILIARIES
1 1 0
0 0 1
1 0 0
0 1 0
"REPLACEMENT" BREAKER AUXILIARIES
N1 N2 R
auxiliary source
genset startup signal G
D
undervoltage relay
to B
U=0
C
genset fault contact
OFF R
N AUTO CMa
Fu
Fu
N1 RTn2
N1-2
Fu N2
RTn3 RX3
Fu
RTn1
RX2
RX1 R1
OF
OF
B4
262
254
252
A4
D4
24
22
14
12
312
84
314
CE
82
CE
XF QN1
322
324
B4
262
254
252
A4
D4
24
22
14
12
84
312
314
CE
82
CE
322
324
B4
262
254
252
A4
D4
24
22
14
12
84
312
314
82
322
324
R2
M
MN
XF
SDE
CE
M
CE
MN QN2
OF
XF
OF
M
MN
SDE
CH
QR
PF
OF
OF
SDE
CH PF
CH
B1
251
A1
D1
21
11
81
311
321
B1
251
A1
D1
21
11
81
311
321
B1
251
A1
D1
21
11
81
311
321
PF
B
QN1: Masterpact on «Normal1» source QN2: Masterpact on «Normal2» source QR: Masterpact on «Replacement» source D: P25M circuit breaker (2 x 10 A) C: operation selection switch Cma: source selection switch FU: fuses Rtn1: voltage relay with 0.1 to 30 s time delay Rtn2: voltage relay with 10 to 180 s time delay Rtn3: voltage relay RX1: relay with 0.25 s time delay RX2: relay with 0.25 s time delay RX3: relay
M: XF: MN: CE: OF: SDE: CH: PF:
motor mechanism closing release undervoltage release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).
c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system. The relays and selection switches are not supplied with the circuit breakers.
Merlin Gerin
BTP207E-3.410-raccord
85 85
21/12/01, 10:26
Masterpact: connection
wiring diagrams for automatic source-changeover systems (cont.) 3 circuit breakers - automatic control with permanent "Replacement" source and lockout after fault (685366)
E33091
Version represented: c 2 «Normal» sources + 1 «Replacement» source; c electrical interlocking with lockout after a fault (SDE wiring): inoperative with automatic reset option.
possible states "Normal 1" 0 "Normal 2" 0 "Replacement" 0
N1
N2
0 0 1
1 0 0
0 1 0
"REPLACEMENT" BREAKER AUXILIARIES
"NORMAL 2" BREAKER AUXILIARIES
"NORMAL 1" BREAKER AUXILIARIES
1 1 0
R CN1 CN2
D to A
t1 t2
R1 (1)
QN1
OF
M OF
B4
262
254
XF
MX QN2
252
CE
XF
OF SDE
A4
C2
24
22
84
82
312
CE M
14
XF
MX
12
314
B4
262
254
252
A4
C2
24
22
84
82
312
14
CE
12
314
B4
262
254
252
A4
C2
24
22
84
82
312
14
12
314
R2 (1)
M
OF MX
CH SDE
PF
QR
OF
CH
OF SDE
PF CH
B1
251
A1
C1
21
81
11
311
B1
251
A1
C1
21
81
11
311
B1
251
A1
C1
21
81
11
311
PF
A
QN1: Masterpact on «Normal1» source QN2: Masterpact on «Normal2» source QR: Masterpact on «Replacement» source D: P25M circuit breaker (2 x 10 A) t1: signal for transfer to «Normal1» and «Normal2» sources (minimum time delay 250 ms) t1: signal for transfer to «Replacement» source (minimum time delay 250 ms) R1/R2:external relays for interlocking of SDE auxiliary switches (equipped with 2 contacts O).
M: XF: MX: CE: OF: SDE: CH: PF:
motor mechanism closing release shunt release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).
c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system. (1) The two relays are not supplied with the circuit breakers.
Merlin Gerin
82 BTP207E-3.400-raccord
82
21/12/01, 10:26
Masterpact: connection
wiring diagrams for automatic source-changeover systems (cont.) 3 circuit breakers - automatic control with permanent "Replacement" source and without lockout after fault (688183)
E33092
Version represented: c 2 «Normal» sources + 1 «Replacement» source; c electrical interlocking without lockout after a fault.
possible states "Normal 1" 0 "Normal 2" 0 "Replacement" 0
"NORMAL 2" BREAKER AUXILIARIES
"NORMAL 1" BREAKER AUXILIARIES
N1
N2
1 1 0
0 0 1
1 0 0
0 1 0
"REPLACEMENT" BREAKER AUXILIARIES
R
CN1 CN2
D to A
t1
B4
262
254
252
A4
C2
24
22
14
312
CE
XF
12
314
B4
262
254
252
A4
C2
24
22
14
312
CE
12
314
B4
262
254
252
A4
C2
24
22
14
312
12
314
t2
M QN1
OF
CE
XF
MX OF
M XF
MX QN2
OF
OF
M MX
CH
QR
PF
OF
OF
CH PF CH
B1
251
A1
C1
21
11
311
B1
251
A1
C1
21
11
311
B1
251
A1
C1
21
11
311
PF
A
QN1: Masterpact on «Normal1» source QN2: Masterpact on «Normal2» source QR: Masterpact on «Replacement» source D: P25M circuit breaker (2 x 10 A) t1: signal for transfer to «Normal1» and «Normal2» sources (minimum time delay 250 ms) t2: signal for transfer to «Replacement» source (minimum time delay 250 ms)
M: motor mechanism XF: closing release MX: shunt release CE: «connected» position switch OF: auxiliary changeover switch SDE: overcurrent fault-trip indication switch CH: «springs charged» switch PF: «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).
c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system.
Merlin Gerin
BTP207E-3.400-raccord
83 83
21/12/01, 10:26
Masterpact: connection
wiring diagrams for automatic source-changeover systems (cont.) 2 circuit breakers - automatic control with generator set (688784) c with auxiliary source; c with MN undervoltage release.
Version represented: c with generator set; c with lockout after a fault (SDE wiring): v inoperative with automatic reset option, v if lockout after a fault is not required, the SDE must be shorted on both breakers;
possible states "Normal" 0 "Replacement" 0
E33089
"NORMAL" BREAKER AUXILIARIES
N
1 0
0 1
"REPLACEMENT" BREAKER AUXILIARIES
R genset startup signal auxiliary source
G
D
unvoltage relay U=0
to B genset fault contact
C OFF STANDBY
N AUTO
Fu RTn2
RX3 RTn1
Fu
RX1
CE
XF
B4
262
254
252
A4
D1
24
22
14
12
84
312
82
CE
322 314
B4
262
254
252
A4
D1
24
22
14
12
312
84
324
CE
82
322 314
324
RX2
CE
M XF
MN QN
OF
OF
M MN
SDE
QR
OF
CH
OF
SDE
PF CH
B1
251
A1
D4
21
11
81
311
321
B1
251
A1
D4
21
11
81
311
321
PF
B
QN: QR: D: C: FU: Rtn1: Rtn2: RX1: RX2: RX3:
Masterpact on «Normal» source Masterpact on «Replacement» source P25M circuit breaker (2 x 10 A) 4-position switch fuses voltage relay with 0.1 to 30 s time delay voltage relay with 10 to 180 s time delay relay with 0.25 s time delay relay with 0.25 s time delay relay
M: XF: MN: CE: OF: SDE: CH: PF:
motor mechanism closing release undervoltage release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).
c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F and OF auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system.
Merlin Gerin
80 BTP207E-3.390-raccord
80
21/12/01, 10:26
Masterpact: connection
wiring diagrams for automatic source-changeover systems (cont.)
2 circuit breakers - automatic control with permanent "Replacement" source (688942)
E33090
Version represented: c with permanent «Replacement» source; c with lockout after a fault (SDE wiring): v inoperative with automatic reset option, v if lockout after a fault is not required, the SDE must be shorted;
c with auxiliary source; c with MN undervoltage release.
"NORMAL" BREAKER AUXILIARIES
N
possible states "Normal" 0 "Replacement" 0
1 0
0 1
"REPLACEMENT" BREAKER AUXILIARIES
R auxiliary source D
to B
C N STANDBY AUTO
OFF
Fu RTn2 RTn1
Fu Fu
RTn3 RX1
Fu
CE
XF
B4
262
254
252
A4
D1
24
22
14
12
84
312
82
CE
322 314
B4
262
254
252
A4
24
D1
22
14
12
312
84
324
CE
82
322 314
324
RX2
CE
M XF
MN QN
OF
OF
M MN
SDE
OF
QR CH
OF
SDE
PF CH
B1
251
A1
D4
21
11
81
311
321
B1
251
A1
D4
21
11
81
311
321
PF
B
QN: QR:
Masterpact on «Normal» source Masterpact on «Replacement» source D: P25M circuit breaker (2 x 10 A) C: 4-position switch FU: fuses Rtn1: voltage relay with 0.1 to 30 s time delay Rtn2: voltage relay with 10 to 180 s time delay Rtn3: voltage relay RX1: relay with 0.25 s time delay RX2: relay with 0.25 s time delay
CE: M: XF: MN: OF: SDE: CH: PF:
«connected» position switch motor mechanism closing release undervoltage release auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).
c diagram shown with circuits deenergised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F and OF auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system.
Merlin Gerin
BTP207E-3.390-raccord
81 81
21/12/01, 10:26
Masterpact: connection
automatic source-changeover systems controller option (cont.)
E27121
BA operation
I O I UR O I KR O
UN or KT
I O I QR O
QN
T1 0,1…30 s
500 ms
250 ms
T2 0,1…240 s
500 ms
250 ms
UA operation
E30189
UN or KT
I O
UR KR
I O I O
KG
I O
SH I O QN I O QR I O T1 0,1...30s
120-180s
Inputs UN : normal-source voltage UR : replacement-source voltage KT : forced operation on replacementsource control signal KR : additional check before transfer.
T3 0,5...30s
If UR is not in I state when the transfer order (KT or UN) is given, transfer is not carried out. If KR is not in I state when the transfer order (KT or UN) is given, transfer takes place only once KR has changed to I state.
T2 10...240s
T4 0,5...30s
T5 60...600s
Legend c O position: circuit open c I position: circuit closed : no effect O or I. c
Outputs KG : engine-generator set control signal SH : load-shedding control signal QN : normal-source Masterpact QR : replacement-source Masterpact.
Merlin Gerin
78 BTP207E-3.380-raccord
78
21/12/01, 10:25
Masterpact: connection
wiring diagrams for automatic source-changeover systems 2 circuit breakers - electrical interlocking (685363)
E33088
Version represented: With lockout after a fault. If lockout after a fault is not required, contact PF of the «Normal» breaker must be connected directly in series with auxiliary switch OF of the «Replacement» breaker and vice versa, without passing through the switch SDE.
The indication circuits, represented on the diagram by broken lines, are optional. Accessories such as voltage relays, indicating lights and fuses are not supplied with the circuit breaker.
"NORMAL" BREAKER AUXILIARIES
N
possible states "Normal" 0 "Replacement" 0
CONTROL PRINCIPLE
1 0
"REPLACEMENT" BREAKER AUXILIARIES
R
CN1
control voltage
CN2
F1 (1)
0 1
F2 (1) D to B to A
C
to C
fault
RTs
closed
fault
closed
RTn open
open
B4
262
254
252
A4
C2
24
22
14
(2)
12
84
82
314 CE
312
B4
262
254
252
A4
C2
24
22
14
(2)
F4 (1)
12
84
82
314
312
F3 (1)
CE
XF M
XF
MX QN
OF
OF
M MX
SDE
QR
OF
CH
OF
SDE
PF CH
B1
251
A1
C1
21
11
81
311
B1
251
A1
C1
21
11
81
311
PF
B A
QN: Masterpact on «Normal» source QR: Masterpact on «Replacement» source D: P25M circuit breaker (2 x 10 A) F1, F2, F3, F4: protective fuses 2 A Rts: «Replacement» source voltage relay (minimum time delay 250 ms) Rtn: «Normal» source voltage relay (minimum time delay 250 ms)
M: motor mechanism XF: closing release MX: shunt release CE: «connected» position switch OF: auxiliary changeover switch SDE:overcurrent fault-trip indication switch CH: «springs charged» switch PF: «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).
c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. (1) The fuses clear faults occurring on the indication circuits without disturbing the operation of the source-changeover system. (2) Terminal 84 does not exist on control units STR58 with options Z and/or C or STR68UM/UTM; in this case there is discrimination between the indications.
Merlin Gerin
BTP207E-3.380-raccord
79 79
21/12/01, 10:25
Masterpact: connection
automatic source-changeover systems controller option source-changeover system with 2 circuit breakers E33081
"NORMAL" BREAKER AUXILIARIES
1 0
0 1
"REPLACEMENT" BREAKER AUXILIARIES
(1)
N
(1)
R
WH
VT
BK
RD
R
GN
N
possible states "Normal" 0 "Replacement" 0
IVE
XF
WH B4
262
254
252
A4
C2
VT
BK 84
82
GN
RD 14
CE
312
314
(3)
12
B4
262
254
252
A4
C2
84
82
312
14
12
314
(3)
CE
M
MX OF
XF SDE OF SDE
CH
251
A1
C1
81
11
311 GY
YE
(2) BN
BN
(3)
QN: Masterpact on «Normal» source QR: Masterpact on «Replacement» source IVE: electrical interlocking and terminal block unit M: motor mechanism XF: closing release MX: shunt release CE: connected position switch
CH
B1
A1
251
C1
(2) YE
(3)
81
311
11
PF
B1
PF
M
MX
QR
GY
QN
OF: auxiliary changeover switch SDE: overcurrent fault-trip indication switch CH: «springs charged» switch PF: «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).
c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. This diagram doesn't operate with "automatic reset" option. (1) provided ready to connect wiring. (2) Don't wire for option "without lockout after fault". (3) Don't wire in fixed position.
Merlin Gerin
72 BTP207E-3.350-raccord
72
21/12/01, 10:25
E33075
N
controller UA
R
1
3
5
1
Q1
2
3
E33076
load shedding and genset management 5
UA
4
N
genset startup
Q2
6
2
4
6
23 22 27 26 28 30 29 31
ACP
24
load shedding
O
L
9
10
R
E
load shedding
25
load reconnection
genset startup genset shutdown
24
N
O
R
L
E
E33077
BatiBUS option 25
23 22
controller status indication
BatiBUS loop
BatiBUS loop
+ –
0V
24V
–
+
17 18 20
BA/UA
24V 0V
21
supplementary control contact N➡R
voluntary transfer command (e.j. for energy management)
11 12
13 14 15 16 10
9
8
7
6
5
UA
11 12 13 14 15 16
N
IVE R 1
Q1 : circuit breaker supplying and protecting the automatic control circuits for the "Normal" source Q2 : circuit breaker supplying and protecting the automatic control circuits for the "Replacement" source IVE : electrical interlocking and terminal block unit ACP : auxiliaries control plate BA/UA : controller
2
3
4
5
6
7
8
9
10
c diagram shown with circuits de-energised, all devices open and relays in the released position.
Tests on "Normal" and "Replacement" voltages BA: c single-phase check for UN and UR: v tested across terminals 1 and 5 of circuit breakers Q1 and Q2. UA: c three-phase check for UN: v tested across terminals 1, 3 and 5 of circuit breaker Q1, v selection switch A of controller set to 1; c single-phase check for UN : v tested across terminals 1 and 5 of circuit breaker Q1, v selection switch A of controller set to 0.
Merlin Gerin
BTP207E-3.350-raccord
73 73
21/12/01, 10:25
Masterpact: connection
wiring diagrams for automatic source-changeover systems (cont.) automatic control - 2 sources + 1 coupling and lockout after fault (689651) possible states source 1 0 1 source 2 0 0 coupling 0 0
E33099
Version represented: c 2 sources + 1 coupling; c 2 circuit breakers closed; c electrical interlocking with lockout after a fault: inoperative with automatic reset option.
"SOURCE 1" BREAKER AUXILIARIES
S1
0 1 0
0 0 1
1 1 0
0 1 1
1 0 1
"SOURCE 2" BREAKER AUXILIARIES
"COUPLING" BREAKER AUXILIARIES
S2
CMa permanent OFF auto
Fu RTn1 RTn2
Fu Fu
CMb RTn3
COUPLER
N1+C N1+N2 N2+C
RTn4
Fu
RX1 Fu RX2 Fu
B4
262
254
252
A4
C2
24
22
14
12
84
312
82
CE
322 314
B4
262
254
252
A4
C2
24
22
14
12
312
84
324
CE
XF
82
CE
322 314
324
B4
262
254
252
A4
C2
24
22
14
12
84
82
322 314 CE
312
324
RX3
M OF
CE
XF
MX OF
CE
M XF
MX SDE
OF
OF
M MX
CH
SDE
PF
OF CH
OF
SDE
PF CH
Q1: QC: Q2: Cma: FU: Rtn1: Rtn2: Rtn3: Rtn4: Cmb: RX1: RX2: RX3:
Masterpact on source 1 Masterpact used for coupling Masterpact on source 2 3-position switch fuses voltage relay with 10 to 180 s time delay voltage relay with 0.1 to 30 s time delay voltage relay with 10 to 180 s time delay voltage relay with 0.1 to 30 s time delay coupling selection switch relay with 0.25 s time delay relay with 0.25 s time delay relay with 0.25 s time delay
M: XF: MX: CE: OF: SDE: CH: PF:
motor mechanism closing release shunt release «connected» position switch auxiliary changeover switch overcurrent fault-trip indication switch «springs charged» switch «ready to close» contact (closing possible if device is open, unlocked and operating mechanism charged).
B1
251
A1
C1
21
11
c diagram shown with circuits de-energised, breakers open and in «connected» position, springs charged and relays in released position. Note: All indicating signals by O, F, OF, SDE, PF and CH auxiliary switches should be protected by fuses that discriminate with respect to the protection devices on the automatic control circuits to avoid disturbing the operation of the source-changeover system. The relays are not supplied with the circuit breakers.
Merlin Gerin
90 BTP207E-3.440-raccord
81
311
321
B1
251
A1
C1
21
11
81
311
321
B1
251
A1
C1
21
11
81
311
321
PF
90
21/12/01, 10:28
LV power air circuit breakers and switch-disconnectors
Masterpact 4/ complementary technical information page tripping curves effect of ambient temperature
0 0
77 BTP207E-4.001-sommaire
77
21/12/01, 10:29
Masterpact: complementary technical information
tripping curves (cont.)
E30715
STR 68 U: load monitoring with 2 load limits 10000 5000
Ir = 0,4…1 x In
2000
Ic1 = 0,2…1 x In 1000
Ic2 = 0,2…1 x In 500
tr = 15…480s 200
tr1 = tr / 2 100
tr2 = tr / 4 50
20 10 5
t(s)
2 1 .5
.2 .1 .05
.02 .01 .005
.002 .001 .05 .06
.08
.1
.2
.3
.4
.5 .6
.8
1
2
3
4
5
6
8 10
20
30
x In In: CT rating Ir: LT protection current setting (delay: tr)
Ic1: one load-shedding pick-up (delay: tr1) Ic2: another load-shedding pick-up (delay: tr2)
Merlin Gerin
86 BTP207E-4.100-courbe décl
86
21/12/01, 10:32
E30717
STR 68: load monitoring with 1 load-shedding and 1 load-reconnection pick-up 10000 5000
Ir = 0,4…1 x In
2000
Ic1 = 0,2…1 x In
1000
Ic2 = 0,2…1 x In
500
tr = 15…480s 200
tr1 = tr / 2 100 50
20
tr2 = 60s 10 5
t(s)
2 1 .5
.2 .1 .05
.02 .01 .005
.002 .001 .05.06
.08 .1
.2
.3
.4
.5 .6
.8
1
2
3
4
5 6
8
10
20
30
x In Ic1: load-shedding pick-up (delay: tr1) Ic2: load-reconnection pick-up 2 (delay: tr2)
Merlin Gerin
BTP207E-4.100-courbe décl
87 87
21/12/01, 10:32
Masterpact: complementary technical information
tripping curves (cont.)
E30714
STR 68 U 10000 5000
Ir = 0,4 …1 x In
2000
tr = 15…480s 1000 500
200 100 50
20 10 5
t(s)
2
I2t ON
Im = 0,4 …15 x In
1 .5
.2 .1
I2t OFF
0,4
0,4
0,3
0,3
0,2
0,2
0,1
0,1
.05
I (*)
.02 .01 .005
.002 .001 .5 .6
.8 1
2
3
4
5
6
8
10
30
20
40 50 60
80 100
x In
200
300
kA
(*)I In (A)
800
1000
type H2 : I = type H1 : I = type L1 : I =
1,6 kA ... 65 kA In ou 1,6 kA ... 50 kA 1,6 kA ... 11 kA
1250
1600
2000
2500
3200
5000
6000
In ... 75 kA In ... 15 kA Merlin Gerin
84 BTP207E-4.090-courbe décl
4000
84
21/12/01, 10:31
STR 68 U: earth fault protection E30716
10000 5000
2000
Ih = 0,2…1 x In… Max. 1200A
1000 500
200 100 50
20 10 5
t(s)
2 1 .5
0,4 0,3
.2
0,2
.1
0,1
.05
.02 .01 .005
.002 .001 .05 .06
.08 .1
.2
.3
.4
.5 .6
.8
2
1
3
4
5 6
8
10
20
30
x In In: CT rating Ir: LT protection current setting (delay: tr) Im: ST protection pick-up (delay: tm) INST: instantaneous protection pick-up
Ih: earth fault protection pick-up (delay: th) (0, 0.1, …: time delay settings)
Merlin Gerin
BTP207E-4.090-courbe décl
85 85
21/12/01, 10:31
Masterpact: complementary technical information
tripping curves (cont.)
STR 38 S/STR 58 U: earth fault protection E30713
10000 5000
2000
Ih = 0,1…1 x In Max 1200A
1000 500
200 100 50
20 10 5
t(s)
I2t ON
2 1 .5
0,4 0,3
.2
0,2 I2t OFF
.1
0,1
.05
.02 .01 .005
.002 .001 .05 .06
.08 .1
.2
.3
.4
.5 .6
.8
1
2
3
4
5
6
8
10
20
30
x In In: CT rating Ih: earth fault protection pick-up (delay: th)
Merlin Gerin
82 BTP207E-4.080-courbe décl
82
21/12/01, 10:31
E30710
STR 38 S/STR 58 U: load monitoring 10000 5000
Ir = 0,4…1 x In
2000
Ic1 = 0,8…1 x Ir
1000
Ic2 = 0,5…1 x Ir
500
tr1 = tr / 2 200
tr2 = tr / 4 100 50
20 10 5
t(s)
2 1 .5
.2 .1 .05
.02 .01 .005
.002 .001 .05 .06
.08 .1
.2
.3
.4
.5 .6
.8
1
2
3
4
5 6
8
10
20
30
x In Ir: LT protection current setting (delay: tr) Ic1: load-shedding pick-up 1 (delay: tr1) Ic2: load-shedding pick-up 2 (delay: tr2)
Merlin Gerin
BTP207E-4.080-courbe décl
83 83
21/12/01, 10:31
Masterpact: complementary technical information
tripping curves (cont.)
E30711
STR 38 S 10000 5000
Ir = 0,4 …1 x In
2000 1000 500
200 100 50
20 10 5
t(s)
Inst (*)
I2t ON
2
Im = 1,5 …10 x Ir 1 .5
0,4
.2
I2t OFF
.1
0,3
0,3
0,2
0,2
0,1
0,1
.05
.02
0 .01 .005
.002 .001
.5 .6
.8
2
1
3
4
5 6
8
10
3
20
4
5 6
8 10
20
30
x In
x Ir (*)Inst In (A)
630
800/1000
1200/1600
2000
2500
3000/3200
4000/5000/6300
I = In x ... (N-H)
28
28
24
20
14
12
10
I = In x ... (L)
14
10
8
6
6
-
Merlin Gerin
80 BTP207E-4.070-courbe décl
80
21/12/01, 10:30
E30712
STR 58 U 10000 5000
Ir = 0,4 …1 x In
2000
tr = 15…480s 1000 500
200 100 50
20 10 5
t(s)
Im = 1,5 …10 x Ir I2t ON
2 1 .5
0,4 0,3
.2 2
I t OFF
.1
0,3
0,2
0,2
0,1
0,1
.05
0 I = 2 x In…Max (*)
.02 .01 .005
.002 .001 .5 .6
.8
1
2
3
4
5 6
8
10
20
3
4
5 6
8
10
20
30
x In
x Ir (*)Max In (A)
630
800/1000
1200/1600
2000
2500
3000/3200
4000/5000/6300
Max = In x ... (N-H)
28
28
24
20
14
12
10
Max = In x ... (L)
14
10
8
6
6
-
-
Merlin Gerin
BTP207E-4.070-courbe décl
81 81
21/12/01, 10:30
Masterpact: complementary technical information
tripping curves
E30708
STR 18 M 10000 5000
2000 1000 500
200 100 50
20
I = 2 x In… Max (*) 10 5
t(s)
2 1 .5
.2 .1 .05
.02 .01 .005
.002 .001 .5 .6
.8
1
2
3
4
5
6
8 10
20
30
40 50 60
80 100
200
300
x In (*)Max In (A)
630
800/1000
1200/1600
2000
2500
3000/3200
4000/5000/6300
Max = In x ...
28
28
24
20
14
12
10
Merlin Gerin
78 BTP207E-4.060-courbe décl
78
21/12/01, 10:30
E30709
STR 28 D 10000 5000
Ir = 0,4 …1 x In
2000 1000 500
200 100 50
20 10 5
t(s)
2
Im = 1,5 …10 x Ir
Inst (*)
1 .5
.2 .1 .05
.02 .01 .005
.002 .001
.5 .6
.8
1
2
3
4
5 6
8
10
20
3
x Ir
4
5 6
8
10
20
30
x In
Inst (*): fixed pick-up at 10 In Merlin Gerin
BTP207E-4.060-courbe décl
79 79
21/12/01, 10:30
Masterpact: complementary technical information
effect of ambient temperature
ambient temperature
The electrical and mechanical characteristics are specified for an ambient temperature between –5 and +60 °C. Masterpact circuit breakers operate from –10 and +70 °C. First closing minimum temperature: –30 °C. In addition, Masterpact circuit breakers comply with IEC standards 68.2.1 and 68.2.2: exceptional storage temperature from: –50 to +100 °C. The table below indicates the maximum current rating, for each connection type, as a function of the ambient temperature around the circuit breaker and the busbars.
Current rating (A) as a function ambient temperature (°C) Masterpact version drawout
M08N/H/L M10N/H/L M12N connection T °C front or rear 40 800 1 000 1 250 horizontal 45 800 1 000 1 250 50 800 1 000 1 250 55 800 1 000 1 250 60 800 1 000 1 200 rear vertical 40 800 1 000 1 250 45 800 1 000 1 250 50 800 1 000 1 250 55 800 1 000 1 250 60 800 1 000 1 250 fixed front or rear 40 800 1 000 1 250 horizontal 45 800 1 000 1 250 50 800 1 000 1 250 55 800 1 000 1 250 60 800 1 000 1 250 rear vertical 40 800 1 000 1 250 45 800 1 000 1 250 50 800 1 000 1 250 55 800 1 000 1 250 60 800 1 000 1 250 Power dissipation and resistance between inputs/outputs power(1) drawout 160 250 360 dissipated (W) fixed 66 103 150 input/output(2) drawout 53 53 53 resistance (µΩ) fixed 33 33 33
M12H
M12L
M16N/H M16L
M20N/H M20L
M25N/H M25L
M32H
M40H
M50H
M63H
1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250
1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250 1 250
1 600 1 600 1 600 1 600 1 550 1 600 1 600 1 600 1 600 1 550 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600
1 600 1 600 1 600 1 600 1 500 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600 1 600
2 000 2 000 2 000 2 000 1 900 2 000 2 000 2 000 2 000 1 900 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000
2 000 2 000 2 000 2 000 1 900 2 000 2 000 2 000 2 000 1 900 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000 2 000
2 500 2 500 2 430 2 350 2 250 2 500 2 500 2 500 2 500 2 400 2 500 2 500 2 500 2 500 2 500 2 500 2 500 2 500 2 500 2 500
2 500 2 350 2 250 2 150 2 000 2 500 2 500 2 500 2 350 2 200 2 500 2 500 2 500 2 500 2 300 2 500 2 500 2 500 2 500 2 500
3 150 3 080 3 000 2 900 2 800 3 200 3 200 3 100 3 000 2 900 3 200 3 200 3 200 3 200 3 100 3 200 3 200 3 200 3 200 3 100
3 800 3 650 3 500 3 300 3 100 4 000 3 800 3 600 3 400 3 200 4 000 4 000 4 000 3 900 3 800 4 000 4 000 4 000 4 000 3 900
5 000 4 750 4 500 4 250 4 000 5 000 5 000 5 000 5 000 4 700 5 000 5 000 5 000 5 000 5 000 5 000 5 000 5 000 5 000 5 000
6 000 5 700 5 400 5 100 4 800 6 300 6 000 5 700 5 400 5 100 – – – – – – – – – –
230 100 32 16
360 150 50 36
390 170 32 16
460 220 31 12
365 180 18 9
500 250 23 10
520 260 17 8
780 390 23 10
803 500 15 10
1 250 780 15 10
1 150 700 9 8
1 200 – 9 –
(1) Values measured at In, 50/60 Hz for a 3-pole or 4-pole breaker. (2) Values measured per pole.
Merlin Gerin
88 BTP207E-4.110-déclassement
88
21/12/01, 10:32
Merlin Gerin
BTP207E-4.110-déclassement
89 89
21/12/01, 10:32