ext2.qxd 13/02/01 17:01 Page 14

tyco

Fire & Security

Tyco Electronic Product Group

FM200 Equipment & Components - Standard FM200 (HFC 227ea) is known chemically as Heptafluoropropane. FM200 is a colourless gas which is liquified under pressure for storage. Like Halon 1301 it has a low toxicity level and is superpressurised with Nitrogen to 24.8bar (360psi). It rapidly extinguishes most commonly found fires through a combination of chemical and physical mechanisms.

FM200 contains no bromine or chlorine and therefore has zero Ozone Depleting Potential (ODP). The atmospheric lifetime of FM200 is between 31 and 42 years which along with its’ ODP presents a long term solution to fire protection requirements. FM200 has been found to be less toxic than Halon 1301, which makes it safe for use in the fully automatic mode in occupied areas.

Typically FM200 requires a design concentration of 7.5%, which is well below the 9% No Observable Adverse Effect Level (NOAEL). The NOAEL for Halon 1301 is only 5% (the same as the design concentration).

Agent Product Code 300.205.001 FM200

FM200 Containers - LPCB Approved Container Size Diameter BS5045 Pt.2* EEC/84/525 EEC/84/527 DOT 6.5 Litre 222 mm 303.205.001 n/a 303.205.009 n/a 8 Litre 254 mm n/a n/a n/a 303.205.015 13 Litre 222 mm 303.205.002 n/a 303.205.010 n/a 16 Litre 254 mm n/a n/a n/a 303.205.016 25.5 Litre 222 mm 303.205.003 n/a 303.205.011 n/a 32 Litre 254 mm n/a n/a n/a 303.205.017 40 Litre 267 mm n/a 303.205.025 n/a n/a 52 Litre 406 mm 303.205.004 n/a 303.205.012 303.205.018 80 Litre 267 mm n/a 303.205.024 n/a n/a 106 Litre 406 mm 303.205.005 n/a 303.205.013 303.205.019 147 Litre 406 mm 303.205.006 n/a 303.205.014 303.205.020 180 Litre 406 mm 303.205.007 n/a n/a 303.205.021 FM200 systems are configured around a range of * Containers manufactured to BS5045 Part 2 will containers specifically charged with the be supplied if available. Where these are not appropriate quantity of FM200. Containers are available an alternative (EEC or DOT) will be manufactured to meet the requirements of British, supplied as appropriate. European or US D.O.T. standards as follows: Applicable Standards BS5045 Part 2 - Welded EEC/84/525 - Seamless EEC/84/527 - Welded DOT 4BW 500/DOT 4BW (HSE) 34.5 - Welded FM200 Container Label FM200 Container Assembly

Container Dia (mm) Ht to Valve Outlet Size (l) (A) (mm) (B) 6.5 (BS) 222 300 6.5 (EC) 222 335 8 254 304 13 (BS) 222 495 13 (EC) 222 520 16 254 502 25.5 (BS/EC) 222 830 32 254 833 40 267 975 52 (BS) 406 580 52 (EC) 406 605 52 (DOT) 406 595 80 267 1785 106 (BS) 406 1021 106 (EC) 406 1040 106 (DOT) 406 1020 147 (BS) 406 1354 147 (EC) 406 1370 147 (DOT) 406 1360 180 (BS) 406 1634 180 (DOT) 406 1640

Tare Weight (Kg) 9 9 15 12 12 19 17 26 65 49 49 49 108 72 72 72 90 90 90 106 106

Max FM200 Weight (Kg) 6.5 6.5 8 13 13 16 25.5 32 40 52 52 52 80 106 106 106 147 147 147 180 180

All dimensions/tare weights are approximate due to manufacturing tolerances

Page 14

ext2.qxd 13/02/01 17:02 Page 15

tyco

Fire & Tyco Electronic Security Product Group Solenoid Actuator - Standard The solenoid actuator is used to electrically operate the container valve and is operated at 24Vd.c. (Power Consumption - 4.8 Watts). It is fitted directly onto the top of the container valve by means of a knurled swivel coupling which enables the unit to be positioned as preferred for electrical connection. When fitting it is only necessary for the unit to be hand tight. The solenoid actuator is normally fitted to the container designated as the ‘Master’. The actuator is an electro-mechanical device which when energised causes the central pin to move

downwards opening the schrader valve in the container valve. The central pin must be in the retracted position before the solenoid actuator is fitted, otherwise the container valve will be operated and the contents discharged. The power lead fitted with a DIN plug for connecting to the solenoid is to be ordered separately (P/C 304.001.001). Product Code 304.205.001 24V Solenoid actuator

FM200 Solenoid Lead Product Code 304.001.001 Solenoid lead

Solenoid Actuator - Flameproof The Flameproof solenoid actuator is BASEEFA approved to Ex d IIB requirements and is operated at 24Vd.c. (Power Consumption - 11.2 Watts). The CENELEC/BASEEFA Approved Explosion proof version is available to order to meet EEx d IIC requirements. The solenoid actuator is fitted to a schrader assembly on the side of the valve body by means of a brass swivel nut. It is designed to be removable from the schrader assembly. As there will be pressure in the brass swivel nut, upon removal of the solenoid the pressure will be released. A ‘pop’ will be heard at the time of removal. It is essential that the schrader assembly

is not dislodged or removed as this will cause an immediate and potentially hazardous discharge of FM200. It is recommended that at the time of removal all slave containers are disconnected from the ‘Master’. NOTE: Earlier versions of this actuator were not designed to be removable from the container valve and no attempt must be made to do so whilst the container is pressurised, otherwise this will result in immediate and potentially hazardous discharge of FM200.

The local manual actuator is used to mechanically operate the system at the container position. When fitting it is only necessary for the unit to be hand-tight. Accidental manual release is prevented by means of a steel safety pin. The steel safety pin must be removed to allow the use of the local manual actuator. After removing the safety pin, manual operation is caused by depressing the strike knob.

The unit is designed so that it may be fitted directly onto the top of the container

The pneumatic actuator is used where container operation is required by means of gas pressure from the system master container, remote manual release unit or from a pilot container. When fitting it is only necessary for the unit to be hand tight. The unit is designed so that it may be fitted directly onto the top of the container valve or be used in conjunction with a solenoid actuator, in which case it fits directly on top of the solenoid actuator.

A minimum pressure of 4 bar is required to ensure satisfactory operation. Connection to the actuator is 1/4” B.S.P.

The union adaptor is used to enable pipework to be easily connected to and disconnected from the FM200 container valve outlet adaptor. It is available in two sizes, 25mm and 50mm. One end is provided with a parallel female thread to provide a compatible joint to the container outlet adaptor. The other end is provided with a female NPT thread to enable pipework to be connected. A swivel joint makes disconnecting

containers from the pipework straightforward. It is recommended that the joint to the container valve adaptor is made using PTFE tape.

Product Code 304.205.002 24V Solenoid actuator (BASEEFA)

Local Manual Actuator Product Code 304.205.003 Local manual actuator

Pneumatic Actuator

Product Code 304.205.004 Pneumatic actuator

Union Adaptor

Product Codes 309.002.011 25mm (1”) Union adaptor 309.002.012 50mm (2”) Union adaptor Page 15

ext2.qxd 13/02/01 17:02 Page 16

tyco

Fire & Tyco Electronic Security Product Group Remote Manual Actuator (Mechanical) The Remote Manual Actuator may be used to operate the FM200 container from a remote position using the T528 mechanical manual release unit which is connected to the remote manual actuator by wire rope run in conduit. A shear strap is fitted to help guard against accidental release. Operation is caused by moving the lever through 90o, which will break the shear strap. The steel safety pin will prevent operation and is to be removed upon commissioning of the system.

A pneumatic actuation port is provided to allow the unit to double as a manual and pneumatic actuator. The unit is designed so that it may be fitted directly onto the top of the container valve or be used in conjunction with a solenoid actuator, in which case it fits directly on top of the solenoid actuator. When fitting it is only necessary for the swivel nut to be hand tightened. Product Code 304.205.005 Remote manual actuator (mechanical)

The T528 Manual Release Unit is used where remote mechanical manual release of the FM200 system is required. The unit comprises of a box with a hinged yellow lid which is held in the closed position by two frangible washers. Inside the unit is a red bar which is to be connected to a wire rope run through a system of conduit and corner pulleys to the Remote Manual Actuator. Operation of the FM200 system using the T528 is a two stage action. Firstly the hinged lid is pulled downwards towards the operator. This action will break the frangible washers and expose the red operating bar. System operation is caused by pulling hard on the red bar. System discharge will occur immediately.

Technical Specification Net Weight: 0.9Kg

The Pressure Switch is normally mounted on a connection in the pneumatic actuation tubing and may be used to provide an electrical indication of release of FM200 or to perform ventilation shutdowns or other interlock functions. The pressure switch requires to be manually reset following operation. A minimum pressure of 3 bar is required to ensure satisfactory operation. Connection to the pressure switch may be either 1/2” NPT (male) or 1/8” NPT (female).

Product Code 305.205.002 Gas released pressure switch

T528 Manual Release Unit Product Code 526.001.018 T528 Mechanical manual release unit

Pressure Switch - Standard

Pressure Switch - Flameproof The Flameproof Pressure Switch is BASEEFA Approved to meet Ex d IIB requirements. The Pressure Switch requires to be manually reset following operation. A minimum pressure of 2 bar is required to ensure satisfactory operation. Connection to the pressure switch is 1/4” NPT (female). A CENELEC/BASEEFA approved explosion proof version is available to order to meet EEx d IIC requirements.

Supervisory Pressure Switch The Supervisory Pressure Switch is an optional item that is factory fitted at the time of order and is used to continuously monitor the container pressure. In the event of the container pressure falling below 18 bar the switch will operate to provide an electrical signal. The operating pressure is factory set and no adjustments may be carries out on site. Product Code 305.205.001 Supervisory pressure switch

Page 16

Product Code 305.205.003 Gas released pressure switch (BASEEFA)

ext2.qxd 13/02/01 17:04 Page 17

tyco

Fire & Tyco Electronic Security Product Group Supervisory Pressure Switch - BASEEFA/CENELEC A BASEEFA Approved Supervisory Pressure Switch (P/C 305.205.004) is available to meet the Ex d IIB requirements. A CENELEC/BASEEFA Approved explosion proof version is available to order to meet EEx d IIC requirements. Both the Flameproof and Explosion proof versions are variations on the Flameproof and Explosion proof ‘gas discharged’ pressure switches. It is recommended that the Flameproof and Explosion proof switches are wall mounted adjacent to the container. Connection to the switch is 1/4” NPT (female).

To fit the Flameproof or Explosion proof switch requires connecting pneumatic actuation tubing between the supervisory pressure switch port on the valve and the supervisory pressure switch. This process involves removing the plug from the supervisory pressure switch port in the valve and quickly connecting the actuation tubing. Upon removal of the plug it is normal for a small quantity of gas to leak. It is critical that all connections are gas tight otherwise the container will gradually lose its charge. Product Code 305.205.004 Supervisory pressure switch (BASEEFA)

FM200 Nozzles - Engineered: Aluminium The Discharge Nozzles are available in a 180o and 360o pattern and are designed to uniformly distribute FM200 throughout the hazard area. The 180o type has seven ports and the 360o type has eight ports. For Pre-Engineered systems the nozzles are available pre-drilled in three sizes. Engineered nozzles are available in seven sizes and are drilled with the specific design requirement. PRODUCT CODE Nozzle Coverage Pre-Engineered Engineered 10mm (180o) Not Available 310.205.022 9 metres 15mm (180o) Not Available 310.205.011 20mm (180o) Not Available 310.205.024 180 Nozzle 25mm (180o) 310.205.001 310.205.012 32mm (180o) Not Available 310.205.026 40mm (180o) 310.205.003 310.205.013 9 metres 50mm (180o) 310.205.005 310.205.014 o 10mm (360 ) Not Available 310.205.023 360 Nozzle 15mm (360o) Not Available 310.205.015 20mm (360o) Not Available 310.205.025 25mm (360o) 310.205.002 310.205.016 o 32mm (360 ) Not Available 310.205.027 40mm (360o) 310.205.004 310.205.017 50mm (360o) 310.205.006 310.205.018 Thread Size 10mm NPT 15mm NPT 20mm NPT 25mm NPT 32mm NPT 40mm NPT 50mm NPT A 25.0mm 29.0mm 35.0mm 41.0mm 50.0mm 60.0mm 76.0mm B 33.5mm 41.0mm 47.0mm 52.0mm 62.0mm 68.0mm 89.0mm

Where the size of any hazard enclosure determines that one nozzle does not provide sufficient coverage the hazard should be theoretically sub divided into appropriately sized modules. Nozzles are provided in aluminium as standard, but are available in brass or stainless steel to order.

NOZZLE TYPE

Discharge Nozzles

o

o

FM200 Container Brackets (Welded Containers) - 6.5/13/25.5 Litre The Container Brackets are designed to securely fix a single container to a wall or supporting structure. The brackets are of a design that allows them to be wall mounted. They comprise of a steel cruciform section which is fixed to the wall or supporting structure and a steel strap used to firmly secure the container to the bracket. A lug at the bottom of the vertical back section is used to support the weight of the container. The strap is fixed around the container to the horizontal back section using nuts and bolts.

PRESENT ONLY ON BRACKET ASSEMBLY 311.205.003

Product Codes 311.205.001 6.5 litre container bracket assembly 311.205.002 13 litre container bracket assembly 311.205.003 25.5 litre container bracket assembly

HOLE DIA 11.5 (TYP)

PRODUCT CODE 311.205.001 311.205.002 311.205.003

DIM A 172 375 715

SEE DETAIL A

6.5/13/25.5 LITRE CONTAINER BRACKET

DETAIL A

Page 17

ext2.qxd 13/02/01 17:04 Page 18

tyco

Fire & Tyco Electronic Security Product Group FM200 Container Brackets (Welded Containers) - 8/16/32 Litre The container brackets are designed to securely fix a single container to a wall or supporting structure. The containers are to be floor mounted only. The bracket assembly comprises two steel straps, steel channel section (400mm long) and nut and bolt. Product Code 311.205.013 Container brackets 8/16/32 litre containers

FM200 Container Brackets (Seamless Containers) The bracket is designed to securely fix containers to a wall or supporting structure. It comprises of a section of steel channel and a universal clamp. The steel channel sections are fixed securely to the wall or supporting structure. The universal clamp has a special slotted section which allows each half to be fitted into the steel channel. The two halves are clamped together in position around the container using a nut and bolt.

Product Codes SL 93841 Container strap - 267mm SL 93852 Single container wall rack

FM200 Container Brackets (Welded Containers) - 52/106/147/180 Litre The Container Brackets are designed to securely fix a single container to a wall or supporting structure. The containers are to be floor mounted only. The bracket assembly comprises a steel strap, steel channel section and two spring nuts and bolts. Product Code 311.205.004 52-180 litre container bracket assembly

210

52/106/147/180 LITRE CONTAINER BRACKET

Manifolds Manifold

65/80/100mm NPT (both ends)

50mm Check Valve

Page 18

Manifolds are designed to enable all the containers in a row to be connected to the supply pipe and may be used in multi container applications or in main and reserve systems. All manifolds are pressure tested at the works to 90 bar. All Product Code Numbers include the manifold and Check Valves.

Type 65mm x 2 port 65mm x 3 port 65mm x 4 port 80mm x 2 port 80mm x 3 port 80mm x 4 port 80mm x 5 port 100mm x 2 port 100mm x 3 port 100mm x 4 port 100mm x 5 port 100mm x 6 port 150mm x 3 port 150mm x 4 port 150mm x 5 port 150mm x 6 port 150mm x 7 port 150mm x 8 port 150mm x 9 port 150mm x 10 port

Product Code 307.205.012 307.205.013 307.205.014 307.205.001 307.205.002 307.205.003 307.205.011 307.205.004 307.205.005 307.205.006 307.205.007 307.205.008 307.205.009 307.205.010 307.205.015 307.205.016 307.205.017 307.205.018 307.205.019 307.205.020

ext2.qxd 13/02/01 17:05 Page 19

tyco

Fire & Tyco Electronic Security Product Group FM200 Manifold Support Brackets Manifold support brackets are designed to provide a firm fixing of the manifold to a wall or supporting structure. Two brackets are required for each manifold used.

311.205.011 100mm Manifold support bracket 311.205.012 150mm Manifold support bracket

Product Codes 311.205.015 65mm Manifold support bracket 311.205.010 80mm Manifold support bracket

Discharge Hoses The flexible Discharge Hose connects the container to the check valve on the manifold. A swivel fitting at the end of the hose allows ease of installation. NOTE: The purpose of the 32mm hose is to prevent excessive pressure loss experienced when using a 25mm hose from the 25mm FM200 container valve. Connection to the 25mm container valve is by means of a 32mm x 25mm adaptor included as part of the 32mm hose assembly.

Product Codes 306.205.001 32mm flexible discharge hose 306.205.002 50mm flexible discharge hose

Manual Release Caution Plate The Manual Release Caution Plate provides instructions to personnel on the use of manual controls. One plate is to be fixed adjacent to all positions from where FM200 can be released manually. Four 4mm fixing holes are provided. Technical Specification Dimensions: 210 x 75 mm Product Code 314.205.003 Manual release plate

Door Caution Plate - Lock Off The Door Caution Plate (lock-off) provides instructions to personnel who may enter an area protected with FM200. This version of the caution plate is used when it is necessary to instruct personnel to place the system on manual control before entering the protected area. One plate is to be fixed to all entrance doors into an FM200 protected area. Four 4mm fixing holes are provided.

Technical Specification Dimensions: 210 x 210 mm Product Code 314.205.001 Door caution plate (lock off)

Door Caution Plate - No Lock-Off The Door Caution Plate (no lock-off) provides instructions to personnel who may enter an area protected with FM200. This version of the caution plate is used when it is permitted to leave the system on automatic control even while the area is occupied. One plate is to be fixed to all entrance doors into an FM200 protected area. Four 4mm fixing holes are provided.

Technical Specification Dimensions: 210 x 210 mm Product Code 314.205.002 Door caution plate (no lock off)

FM200 Actuation Ancillaries 309.013.001

309.010.002 309.010.003 309.011.001 308.002.001

Product Codes 308.002.001 6mm Kunifer tube 308.002.002 6mm Half hard copper tube 309.010.002 6mm x 1/8” NPT stud coupling 309.010.003 6mm x 1/4” NPT stud coupling 309.011.001 6mm Straight coupling 309.013.001 6mm Equal tee Page 19

ext2.qxd 13/02/01 17:05 Page 20

tyco

Fire & Security

Tyco Electronic Product Group

Typical Container Arrangement

Reference 1 2 3 4 5 6 6a 7 8 9 10 11 12 13 14 15

Description FM200 Container Assembly Container Bracket Container Nameplate Pressure Gauge Solenoid Actuator Local Manual Actuator Safety Pin Supervisory Pressure Switch* Pneumatic Actuator Pressure Switch Discharge Nozzle Manual Release Caution Plate Container Design Details Discharge Pipework Pneumatic Actuation Tubing Junction Box

* Optional or variable equipment - not included in the standard kits.

KITS - Master Containers (Solenoid Operated) In order to assist in the ordering of correct components to form the FM200 system a number of kits are available to cover the most popular range of containers. Each kit comprises the FM200 container, bracket,

solenoid, solenoid lead, manual actuator, pressure switch, actuation tubing/fittings and manual caution plate. The kit excludes items which are specific to a individual enclosure such as FM200, supervisory

KITS - Master Containers (Solenoid Operated) Description 6.5 Litre Solenoid operated container assy 13 Litre Solenoid operated container assy 25.5 Litre Solenoid operated container assy 52 Litre Solenoid operated container assy 106 Litre Solenoid operated container assy 147 Litre Solenoid operated container assy 180 Litre Solenoid operated container assy

Kit No. 901.505.048 901.505.049 901.505.050 901.505.051 901.505.052 901.505.053 901.505.054

Weight 13 Kgs 16 Kgs 22 Kgs 48 Kgs 69 Kgs 84 Kgs 98 Kgs

KITS - Slave Containers (Pneumatically Operated) Each kit comprises the FM200 container, bracket, pneumatic actuator and actuation tubing/fittings and manual caution plate. The kit excludes items which are specific to an individual enclosure such as FM200, supervisory

pressure switches, door caution plates, nozzles, pipework, fittings, fixings and any special items such as distribution valves.

KITS - Master Containers (Solenoid Operated) Description 6.5 Litre Pneumatically operated container assy 13 Litre Pneumatically operated container assy 25.5 Litre Pneumatically operated container assy 52 Litre Pneumatically operated container assy 106 Litre Pneumatically operated container assy 147 Litre Pneumatically operated container assy 180 Litre Pneumatically operated container assy

Page 20

Kit No. 901.505.041 901.505.042 901.505.043 901.505.044 901.505.045 901.505.046 901.505.047

Weight 10 Kgs 14 Kgs 19 Kgs 46 Kgs 67 Kgs 82 Kgs 96 Kgs

pressure switches, door caution plates, nozzles, pipework, fittings, fixings and any special items such as distribution valves.

ext2.qxd 13/02/01 17:06 Page 21

tyco

Fire & Security

Tyco Electronic Product Group

FM200 Equipment & Components - UL Listed Agent Product Code 300.205.001 FM200

FM200 Containers - Dot (UL) Systems are configured around a range of containers specifically charged with the appropriate quantity of FM200. Containers are manufactured to meet the requirements of DOT4BW500 / DOT4BW(HSE)34.5. Product Codes 303.205.015 8 Litre container assembly 303.205.016 16 Litre container assembly 303.205.017 32 Litre container assembly 303.205.018 52 Litre container assembly 303.205.019 106 Litre container assembly

303.205.020 147 Litre container assembly 303.205.021 180 Litre container assembly

Label fitted to containers on UL listed systems

Solenoid Actuator - Stackable (UL) The solenoid actuator is used to electrically operate the container valve. The solenoid is operated at 24Vd.c. (Power Consumption - 4.8 Watts). It is fitted directly onto the top of the container valve by means of a knurled swivel coupling which enables the unit to be positioned as preferred for electrical connection. When fitting it is only necessary for the unit to be hand tight. The solenoid actuator is normally fitted to the container designated as the ‘Master’. The actuator is an electro-mechanical device which

when energised causes the central pin to move downwards opening the schrader valve in the container valve. The central pin must be in the retracted position before the solenoid actuator is fitted, otherwise the container valve will be operated and the contents discharged. The power lead fitted with a DIN plug for connecting to the solenoid is to be ordered separately (P/C 304.001.001). Product Code 304.205.008 24V Solenoid actuator

Solenoid Actuator - Side Mounted (UL) The solenoid actuator is fitted to a schrader assembly on the side of the valve body by means of a brass swivel nut. It is designed to be removable from the schrader assembly. As there will be pressure in the brass swivel nut, upon removal of the solenoid the pressure will be released. A ‘pop’ will be heard at the time of removal. It is essential that the schrader assembly is not dislodged or removed as this will cause an immediate and potentially hazardous discharge of FM200.

Product Code 304.205.008 24V Solenoid actuator (side mounted)

The local manual actuator is used to mechanically operate the system at the container position. When fitting it is only necessary for the unit to be hand-tight. Accidental manual release is prevented by means of a steel safety pin. The steel safety pin must be removed to allow the use of the local manual actuator. After removing the safety pin, manual operation is caused by depressing the strike knob. The unit is designed so that it may be fitted directly onto the top of the container

Product Code 304.205.003 Local manual actuator

Local Manual Actuator

Page 21

ext2.qxd 13/02/01 17:07 Page 22

tyco

Fire & Tyco Electronic Security Product Group Solenoid Actuator - Pneumatic Actuator (UL) The pneumatic actuator is used where container operation is required by means of gas pressure from the system master container, remote manual release unit or from a pilot container. When fitting it is only necessary for the unit to be hand tight. The unit is designed so that it may be fitted directly onto the top of the container valve or be used in conjunction with a solenoid actuator, in which case it fits directly on top of the solenoid actuator. A minimum pressure of 4 bar is required to ensure satisfactory operation. Connection to the actuator is 1/4” B.S.P.

Product Code 304.205.004 Pneumatic actuator

FM200 Container Brackets (UL) The container brackets are designed to securely fix a single container to a wall or supporting structure. The containers are to be floor mounted only. The bracket assembly comprises two steel straps, steel channel section (400mm long) and nut and bolt. Product Codes 311.205.013 8-32 litre Container bracket assembly 311.205.014 52-180 litre Container bracket assembly

FM200 Actuation Ancillary (UL) 309.013.005

306.205.003 309.013.004

309.013.003

Product Codes 306.205.003 Flexible pilot hose 1/4” BSP swivel female 309.013.003 Male tee 1/4” BSPP x 1/4” BSPT 309.013.004 Male elbow 1/4” BSPT x 1/4” BSPP 309.013.005 1/4” BSPT x 1/4” BSPP adaptor

Supervisory Pressure Switch (UL) The Supervisory Pressure Switch is an optional item that is Factory fitted at the time of order and is used to continuously monitor the container pressure. In the event of the container pressure falling below 18 bar the switch will operate to provide an electrical signal. The operating pressure is factory set and no adjustments may be carries out on site.

Product Code 305.205.006 Supervisory pressure switch

Gas Released Pressure Switch (UL) The Pressure Switch is normally mounted on a connection in the pneumatic actuation tubing and may be used to provide an electrical indication of release of FM200 or to perform ventilation shutdowns or other interlock functions. The pressure switch requires to be manually reset following operation. A minimum pressure of 3 bar is required to ensure satisfactory operation. Connection to the pressure switch may be either 1/2” NPT (male) or 1/8” NPT (female).

Page 22

Product Code 305.205.007 Gas released pressure switch

ext2.qxd 13/02/01 17:07 Page 23

tyco

Fire & Tyco Electronic Security Product Group FM200 Manifolds (UL) Manifolds are designed to enable all the containers in a row to be connected to the supply pipe and may be used in multi container applications or in main and reserve systems. All manifolds are pressure tested at the works to 90 bar. All Product Code Numbers include the manifold and Check Valves.

Manifold

65/80/100mm NPT (both ends)

50mm Check Valve

Type 65mm x 2 port 65mm x 3 port 65mm x 4 port 80mm x 2 port 80mm x 3 port 80mm x 4 port 80mm x 5 port 100mm x 2 port 100mm x 3 port 100mm x 4 port 100mm x 5 port 100mm x 6 port 150mm x 3 port 150mm x 4 port 150mm x 5 port 150mm x 6 port 150mm x 7 port 150mm x 8 port 150mm x 9 port 150mm x 10 port

Product Code 307.205.012 307.205.013 307.205.014 307.205.001 307.205.002 307.205.003 307.205.011 307.205.004 307.205.005 307.205.006 307.205.007 307.205.008 307.205.009 307.205.010 307.205.015 307.205.016 307.205.017 307.205.018 307.205.019 307.205.020

FM200 Manifold Support Brackets Manifold support brackets are designed to provide a firm fixing of the manifold to a wall or supporting structure. Two brackets are required for each manifold used.

311.205.011 100mm Manifold support bracket 311.205.012 150mm Manifold support bracket

Product Codes 311.205.015 65mm Manifold support bracket 311.205.010 80mm Manifold support bracket

Discharge Hoses The flexible Discharge Hose connects the container to the check valve on the manifold. A swivel fitting at the end of the hose allows ease of installation. NOTE: The purpose of the 32mm hose is to prevent excessive pressure loss experienced when using a 25mm hose from the 25mm FM200 container valve. Connection to the 25mm container valve is by means of a 32mm x 25mm adaptor included as part of the 32mm hose assembly.

Product Codes 306.205.001 32mm Flexible discharge hose 306.205.002 50mm Flexible discharge hose

FM200 Nozzles: Engineered: Brass (UL) The Discharge Nozzles are available in a 180o and 360o pattern and are designed to uniformly distribute FM200 throughout the hazard area. The 180o type has seven ports and the 360o type has eight ports. Nozzles are available in seven sizes and are drilled with the specific design requirement. Where the size of any hazard enclosure determines that one nozzle does not provide sufficient coverage the hazard should be theoretically sub divided into appropriately sized modules. Nozzles are provided in brass as standard, but are available in stainless steel to order.

Product Codes 310.205.028 10mm x 180/360 Degree (state which) 310.205.029 15mm x 180/360 Degree (state which) 310.205.030 20mm x 180/360 Degree (state which) 310.205.031 25mm x 180/360 Degree (state which) 310.205.032 32mm x 180/360 Degree (state which) 310.205.033 40mm x 180/360 Degree (state which) 310.205.034 50mm x 180/360 Degree (state which)

Page 23

ext2.qxd 13/02/01 17:07 Page 24

tyco

Fire & Tyco Electronic Security Product Group FM200 Manual Release Caution Plate (UL) The Manual Release Caution Plate provides instructions to personnel on the use of manual controls. One plate is to be fixed adjacent to all positions from where FM200 can be released manually. Four 4mm fixing holes are provided. Technical Specification Dimensions: 210 x 75 mm Product Code 314.205.003 Manual release plate

FM200 Door Caution Plate - Lock Off (UL) The Door Caution Plate (lock-off) provides instructions to personnel who may enter an area protected with FM200. This version of the caution plate is used when it is necessary to instruct personnel to place the system on manual control before entering the protected area. One plate is to be fixed to all entrance doors into an FM200 protected area. Four 4mm fixing holes are provided. Technical Specification Dimensions: 210 x 210 mm

Product Code 314.205.001 Door caution plate (lock off)

FM200 Door Caution Plate - No Lock-Off (UL) The Door Caution Plate (no lock-off) provides instructions to personnel who may enter an area protected with FM200. This version of the caution plate is used when it is permitted to leave the system on automatic control even while the area is occupied. One plate is to be fixed to all entrance doors into an FM200 protected area. Four 4mm fixing holes are provided. Technical Specification Dimensions: 210 x 210 mm

Page 24

Product Code 314.205.002 Door caution plate (no lock off)

ext2.qxd 13/02/01 17:07 Page 25

tyco

Fire & Security

Tyco Electronic Product Group

Carbon Dioxide Equipment & Components Containers EC Container Details Water Capacity CO2 Capacity Length Outside Diameter Max. Working Pressure Test Pressure Nominal Tare Weight Nominal Gross Weight

67.0 Litres (nominal) 45Kg 1507mm +/- 10mm 267mm 194 Bar 250 Bar 76.9Kg 122Kg

The container valve is fitted with a burst disk rated to operate at 190 bar. Containers are painted signal red and are provided with a label providing handling and maintenance instructions. Product Codes 303.200.011 45Kg Container assy complete with solenoid and CO2 303.200.012 45Kg Container assy complete with CO2

The standard container is 67 Litre nominal capacity with a 45Kg fill of Carbon Dioxide. Containers are manufactured to the EC directive EEC/84/525 and the complete assembly consists of: . CO2 Container . CO2 Valve & Syphon Tube . Valve Protection Cap . 45 Kgs CO2

Local Manual/Pneumatic Actuator (Type D)

The Local Manual/Pneumatic Actuator may be used to operate the CO2 container by means of a local mechanical action or by pneumatic means. The actuator is fitted directly onto the top of the container valve and is retained by a steel locating clip. A grub screw in the front of the container valve may be tightened to secure the actuator in the preferred orientation.

Accidental manual release is prevented by means of a steel safety pin. The steel safety pin must be removed to allow the use of the operating lever. After removing the safety pin manual operation is caused by moving the operating lever through 105o. A maximum force of approximately 3kgf is required to operate the actuator. Pneumatic operation is possible by means of actuation ports in the main body of the actuator. At normal storage conditions ie 20oC approximately 8.5 bar is required. Two ports are provided at 180o to each other. One port is used as an inlet port and the other as an outlet port. Interconnection between adjacent actuators is by means of 3/16” pilot hoses. (Either port can be used as the inlet/outlet ports). No port must be left open ie. depending on the layout required, manual bleed valves, pilot hoses or pneumatic actuation plugs may be fitted. To

connect the 3/16” pilot hose to the inlet/outlet ports of the actuator requires the use of 3/16” x 1/8” adaptor (P/C 309.017.005). These adaptors must not be omitted as this could cause the system operation to fail. For remote manual actuation the actuator is fitted with a shear strap in place of the steel safety pin. This must be specified at time of order. When operated the actuator latches to keep the container valve open. The knurled reset plunger must be pulled to reset the actuator after operation. Technical Specification Net Weight: 0.4Kg

container valve and is retained by a steel locating clip. A grub screw in the front of the container valve may be tightened to secure the actuator in the preferred orientation. Pneumatic operation is through actuation ports in the main body of the actuator. A minimum operating pressure of 31 bar is required at a container pressure of 200 bar. At normal storage conditions ie. 20 oC approximately 8.5 bar is required. Two ports are provided at 180o to each other. One port is used as an inlet port and the other as an outlet port. Interconnection between adjacent actuators is by means of 3/16” pilot hoses (Either port can be used as the inlet/outlet ports). No port must be left open ie. depending on the

layout required, manual bleed valves, pilot hoses or pneumatic actuation plugs may be fitted. To connect the 3/16” pilot hose to the inlet/outlet ports of the actuator requires the use of 3/16” x 1/8” adaptor (P/C 309.017.005). These adaptors must not be omitted as this could cause the system operation to fail. When operated the actuator latches to keep the container valve open. The knurled reset plunger must be pulled to reset the actuator after operation. Technical Specification Net Weight: 0.3Kg Product Code 302.200.027 Double slave actuator

Product Code 302.200.026 Manual/pneumatic actuator

Pneumatic Actuator (Type D)

The Pneumatic Actuator may be used to operate slave containers by means of pressure from a pilot container or from the system master container. The actuator is fitted directly onto the top of the

PIlot Hoses (527mm & 374mm) 306.200.003

306.200.004

The 374mm Pilot Hose is used to take pilot pressure from one pneumatic actuator to the next in the container bank. The 527mm Pilot Hose is used to take pilot pressure from the type D check valve to the first slave container in the container bank and also between the end actuators of the front and back row on double row systems. NOTE: Adaptors are required to correctly connect the hoses to the local manual/pneumatic actuator or pneumatic actuator.

Each end is fitted with a 3/16” Enots (male) swivel fitting. A minimum bend radius of 75mm must be allowed. Technical Specification Net Weight: 0.04Kg (374mm) 0.05Kg (527mm) Product Codes 306.200.003 3/16” x 527mm Pilot hose 306.200.004 3/16” x 374mm Pilot hose

Page 25

ext2.qxd 13/02/01 17:08 Page 26

tyco

Fire & Security Manual Vent Valve

Tyco Electronic Product Group The Manual Vent Valve serves two functions. Firstly, it acts to relieve a gradual pressure build up occurring, perhaps as a result of a leaking pilot container, master container or solenoid. Secondly, it provides a means by which pressure trapped in the actuation circuits may be manually relieved. The manual vent valve relieves automatically up to a pressure of approximately 2 bar and seals at pressures above this. Pressure is relieved manually by pulling the knurled reset plunger.

Connection to the local manual/pneumatic actuator requires the use of one 3/16” x 1/4” BSP adaptor (P/C 309.017.004), one of 3/16” nipple (P/C 309.005.009) and one 3/16” x 1/8” BSP adaptor (P/C 309.017.005). Technical Specification Net Weight: 0.12Kg

The Pilot Non Return Valve is designed to allow CO2 pressure into various parts of the pneumatic actuation system, but prevent that pressure from being lost when the source pressure diminishes. It is essential that it is fitted the correct way round, otherwise the system may not operate.

Product Code 302.200.015 Pilot line non return valve

Product Code 302.200.021 Manual vent valve

Pilot Line Non Return Valve

Technical Specification Net Weight: 0.02Kg Thread Size: 3/16” Enots (male)

Pneumatic Actuation Fittings 309.017.004

309.017.005

309.005.009

A variety of pneumatic actuation fittings are available to connect the various actuation hoses and devices. Product Codes 309.017.004 3/16” x 1/4” Adaptor 309.017.005 3/16” x 1/8” Adaptor 309.005.009 3/16” Nipple

Manifold Check Valve The Manifold Check Valve allows for the temporary removal of a container from the system and is the means to connect the flexible discharge hose to the manifold. It may also be used as an adaptor between the pipework and the end of the flexible discharge hose on single container systems. The manifold check valve is not designed to give complete sealing, but will prevent a substantial loss of CO2 should the system discharge with a

container removed. The check valve is designed for use in the vertical position and one check valve is used for each container connected to the manifold. Technical Specification Net Weight: 0.1Kg Product Code 302.200.014 Manifold check valve

Manifold Check Valve (Type D) The type D manifold check valve has a dual function and is generally used with the master container to permit operation of slave containers. Its first function is that of the standard manifold check valve and its second is to provide a connection from which CO2 pressure may be tapped to pneumatically operate slave containers. Product Code 302.200.020 Type D manifold check valve

Discharge Hose The 1/2" flexible discharge hose connects the container valve outlet to the check valve on the manifold and is sufficiently flexible to accommodate the small variations found in container heights. Swivel female couplings allow ease of installation in any orientation. Technical Specification Net weight 0.85 kgs.

Page 26

Product Code 306.200.005 15mm Discharge hose

ext2.qxd 13/02/01 17:08 Page 27

tyco

Fire & Security CO2 Manifolds

Tyco Electronic Product Group Product Code 307.200.009 307.200.010 307.200.011 307.200.012 307.200.013 307.200.014 307.200.015 307.200.016

The CO2 manifold is designed to enable all the containers in a row to be connected to the supply pipe. The standard manifolds are for 2, 3, 4 or 5 containers and are available in two sizes, 25mm (1”) and 32mm (1 1/4”). The manifolds may be joined using sockets or tees to produce any

Description 25mm (1”) x 2 Point Manifold 25mm (1”) x 3 Point Manifold 25mm (1”) x 4 Point Manifold 25mm (1”) x 5 Point Manifold 32mm (1 1/4”) x 2 Point Manifold 32mm (1 1/4”) x 3 Point Manifold 32mm (1 1/4”) x 4 Point Manifold 32mm (1 1/4”) x 5 Point Manifold

Weight 2.5Kg 3.5Kg 4.5Kg 5.5Kg 3.0Kg 4.0Kg 6.0Kg 7.4Kg

configuration to suit any number of containers on a system. Non-standard sizes may be produced to order. All manifolds are galvanised inside and out and pressure tested to 190 bar.

Odouriser 2000 The Odouriser 2000 is designed to give a distinctive small to the CO2 and is particularly useful in basements or low lying areas in the vicinity of the system or any place where CO2 could drift to following a discharge. Liquid citrus odour is contained in the body of the odouriser and is sealed in by a lead disc. Pressure of the discharging CO2 causes the disc to rupture and allows the liquid to escape and mix with the CO2. One type odouriser is used for

each 2000Kg of CO2. The odouriser must be replaced after each operation of the system. Connection to the pipework is 1/2” A.P.I. (male). Technical Specification Net Weight: 0.275Kg Product Code 305.200.003 Odouriser

Pressure Operated Distribution Valve The Pressure Operated Distribution Valve is designed to be used as a safety stop valve or as a distribution / selector valve. The valve may be operated either via pilot pressure or manually through handwheel operation. A pressure of approximately 11 bar is required to open the valve and keep it open. Removal of the pilot pressure from the valve will allow it to close and depending on the requirements it may be Valve Sizes 20mm (3/4”) 25mm (1”) 32mm (1 1/4”) 40mm (1 1/2”) 50mm (2”) 80mm (3”) 100mm (4”) 150mm (6”)

necessary to lock the pressure in. The valve is provided with switches as standard to provide a signal to confirm operation of the valve. Sizes 20mm to 50mm are provided with NPT screwed connections. Sizes 80mm to 150mm are available to order and are provided with flanged connections. The actuation port is 1/8” A.P.I.

Product Code 302.200.028 302.200.029 302.200.030 302.200.031 302.200.032 302.200.033 302.200.034 302.200.035

‘S’ Type Nozzle

The ‘S’ Type Nozzle is used in most total flooding applications. It is normally recommended that the nozzles are uniformly positioned on the ceiling of an enclosure to ensure a satisfactory distribution of CO2. Where it is not practical to position the nozzles on the ceiling, it may be acceptable depending on the room dimensions to position them around the perimeter at high level. For CO2 total flooding systems there are no strict

rules governing the number of nozzles that should be applied to any type of hazard, however, nozzle spacing is dependent on the room height, flow rate, potential obstructions etc., but as a rule of thumb, the nozzle may be used to cover an area of approximately 30 square metres in a room 3 metres high, the nozzle coverage table provides additional guidance. In order to reduce the possibility of the nozzle orifice becoming blocked during discharge, terminal nozzles should be installed in a tee and a short length of pipe (100mm) capped/plugged should be fitted to act as a dirt trap. Technical Specification Net Weight: 0.135Kg Finish: Satin Chrome Connection to the pipework is 15mm (1/2”) NPT (female).

Enclosure Height Nozzle Coverage 3.6m 15m2 3.3m 20m2 3.0m 30m2 2.7m 40m2 2.4m 50m2 2.1m 60m2 1.8m 70m2 1.5m 80m2 1.2m 90m2 1.0m 100m 2 Product Code 310.200.001 Type ‘S’ nozzle 15mm (1/2”) (Code 3-18) Orifice codes must be stated at the time of order.

Page 27

ext2.qxd 13/02/01 17:09 Page 28

tyco

Fire & Security

Tyco Electronic Product Group

Fog Type Nozzle The fog nozzle is a discharge horn designed to project CO2 in the direction of the fire hazard. CO2 is discharged in the form of a mist or fog and the discharge velocity is relatively low, thus making it suitable for use in local application systems particularly where flammable liquids are involved and there could be a danger of splashing from the impingement of CO2. Nozzle positioning is dependent on the type of hazard, the method employed in calculating the CO2 quantity, the nozzle height and flow required. Connection to the pipework is 20mm (3/4”) NPT (male).

Product Code 310.200.007 describes a two hole version of the nozzle (Orifice Code 3 only) and Product Code 310.200.008 describes a four hole version (Orifice Codes 3.5 to 18). Technical Specification Net Weight: 0.46Kg

The Duct Nozzle is a variation on the fog type nozzle. It is provided with facilities to incorporate a flanged mounting plate and one of two types of burst disc - an internal (P/C 310.200.011) or external (P/C 310.200.012) type. The flanged mounting plate permits the nozzle to be mounted on the outside of trunking or steel enclosures. The burst discs are designed to prevent the ingress of dirt, insects or other particulate matter which could at some stage block the nozzle. Connection to the pipework is 20mm (3/4”) NPT (male).

Product Code 310.200.009 describes a two hole version (Orifice Code 3 Only) and Product Code 310.200.010 describes a four hole version (Orifice Codes 3.5 to 18). Technical Specification Net Weight: 1.1Kg

The Manual By-Pass Valve is used to allow CO2 to be safely vented to atmosphere if it becomes trapped within a closed pipework section. The valve is available as standard in 15mm (1/2”) NPT. The valve is used in the normally closed position and is provided with a locking bracket into which a standard padlock may be fitted. Technical Specification Net Weight: 0.25Kg

Product Code 302.001.008 15mm (1/2”) Manual ball valve

Product Codes 310.200.007 Fog nozzle (code 3 only) 310.200.008 Fog nozzle (code 3.5-18)

Duct Type Nozzle

Product Codes 310.200.009 Duct nozzle (code 3 only) 310.200.010 Duct nozzle (code 3.5-18)

Manual By-Pass Valve

Manual Stop Valves - Lockable/Contacted Product Code Description Weight 302.200.016 15mm (1/2”) Manual locking valve and switches 1.2Kg 302.200.017 20mm (3/4”)Manual locking ball valve and switches 1.42Kg 302.200.018 25mm (1”) Manual locking ball valve and switches 1.6Kg 302.200.019 32mm (1 1/4”) Manual locking ball valve and switches 1.75Kg Manual Stop Valves are used to isolate the supply closed’ to be given. The valves are also provided of CO2, (usually at the container manifold with a locking bracket into which a standard location), from the discharge pipework. padlock may be fitted. Other sizes are available to The valves and are each fitted with a switchbox to order. enable an indication of ‘valve open’ or ‘valve

Container Racking - Single Container The racking is designed to securely fix a single container to a wall or supporting structure. It comprises of two sections of steel channel and two pairs of universal clamps. The steel channel sections are fixed securely to the wall or supporting structure. The universal clamps have a special slotted section which allows each half to be fitted into the steel channel. The two halves are clamped together in position around the container using a nut and bolt.

Technical Specification Net Weight: 3.0Kg Product Code 311.006.015 Container bracket assy (single container)

Container Racking - Two/Three Containers - Single Row The racking is designed to securely fix a single row of containers to a wall or supporting structure. It comprises of two sections of steel channel and two pairs of universal clamps for each container used. Additional containers may be racked using any number or configuration of the two and three container racking assemblies. Technical Specification Net Weight: 5.5Kg ( Two containers) 8.5Kg (Three containers) Page 28

Product Codes 311.006.011 Container bracket assy (single row 2 cont.) 311.006.012 Container bracket assy (single row 3 cont.)