EPB2.4 + V3f20 Installation - Start-Up Proc [PDF]

  • 0 0 0
  • Gefällt Ihnen dieses papier und der download? Sie können Ihre eigene PDF-Datei in wenigen Minuten kostenlos online veröffentlichen! Anmelden
Datei wird geladen, bitte warten...
Zitiervorschau

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 1

Compiled by: RES/T. Tinti Changed by: BU2/F. Dall’Olio Checked by: RES/F. Burroni Approved by:

Date: 6.9.1996 © KONE Corporation Product code: EPB No of drawing:

Issue: A-1.9.1998 No of Pages: 30 Language: en SW: FM5.1 Win

INSTALLATION AND START-UP PROCEDURES FOR EPB2.4 CONTROL PANEL WITH V3F-20 DRIVE 1

THE V3F-20 DRIVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2

CONTROL PANEL MOUNTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.1 Health and safety at work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2.2 Main components of EPB 2.4 control panel with V3F-20 drive . . . . . . . . . . . . . . . . . . . . . 5

3

TEMPORARY START-UP FOR PRELIMINARY TESTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 3.1 Control panel mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 3.2 Mechanical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

4

NORMAL DRIVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 Shaft device check . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2 Set-up drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3 Checks at full speed . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.1 Intermediate DC voltage. . . . . . . . . . . . . . . . . . . . . . . . . 4.3.2 Motor current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.3 Motor slip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.4 Heat sink temperature . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.5 Checking of the floor level . . . . . . . . . . . . . . . . . . . . . . . 4.4 Normal drive: MODO 0 and MODO 1 selected. . . . . . . . . . . . . 4.5 Sequence of the commands from the EPB 2.4 control panel to V3F-20 4.6 Error signals detected by the EPB 2.4 control panel with V3F-20 . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. . . . . . . . . . . .

. 13 . 13 . 16 . 18 . 18 . 19 . 19 . 20 . 20 . 21 . 22 . 23

5

FAULT FINDING ON V3F-20 DRIVE . . . . . . . . . 5.1 Related documentation . . . . . . . . . . . . . 5.2 Fault finding procedure . . . . . . . . . . . . . 5.3 General Rules for Changing V3F20 Parameters. 5.4 Leds, potentiometers and jumpers on V3F-20 . . 5.4.1 Motion Control board . . . . . . . . . . . . . . 5.4.2 Inverter board . . . . . . . . . . . . . . . . . . 5.4.3 Modulator board . . . . . . . . . . . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. 24 . 24 . 24 . 25 . 26 . 26 . 27 . 28

APPENDIX 1. APPENDIX 2.

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

. . . . . . . .

Main circuit of V3F-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 V3F-20 User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 2

1

THE V3F-20 DRIVE The main function of the V3F-20 drive is to adjust the motor speed by means of a change in frequency and voltage. The V3F-20 drive converts the three-phase current (AC) into direct-current voltage (DC) by means of an intermediate circuit made up of filters and capacitors. Direct-current voltage is converted again into three-phase alternating current by means of an intermediate circuit, thereby changing both voltage and frequency. V3F-20 is the first KONE drive system with a completely digital control system, which means an easier installation on the lift. As for V3F-20 technical specifications, see the product specification SOE-11.65.3. On the drive front panel there is an user interface board, which can show the various learning phases and the drive operating status. Fault finding is possible thanks to the LEDs positioned both on the interface board and on the board inside V3F-20.

P000394

This is the V3F-20 drive

m11658o.eps

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 3

2

CONTROL PANEL MOUNTING The EPB 2.4 control panel with the V3F-20 drive must be mounted according to the layout drawing of the machine room. The installation procedure with the V3F-20 drive does not modify the EPB 2.4 control panel one. The control panel complete with EPB 2.4 and V3F-20 is pre-tested and set in the factory according to the lifts characteristics. The control panel must be mounted on the floor with at least 100 mm clearance from the wall to permit the ventilation of the drive. The ventilation system is positioned on the back side of the drive. The V3F-20 system requires the grounding of both the motor power cable (both on the control panel side and on the motor side); cable for tachometer is grounded one end only.

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 4

2.1

Health and safety at work



After switching off the power, wait at least 5 minutes before working or taking any measurements inside the V3F-20 panel and in the motor connection box. As long as the led DANGER is lit on the drive, there are high voltage in the V3F-20 panel (look at the picture on page 6 “V3F-20 open view”).



Do not remove the V3F-20 front panel when the drive is supplied.



All grounding connections must be carried out properly.



Do not carry out flash tests on V3F-20 because the inside electronic circuits are sensitive to high voltage.



Do not connect or disconnect any wires while V3F-20 has power supplied to it.



Do not touch the braking resistor since there is high voltage on it.

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 5

2.2

Main components of EPB 2.4 control panel with V3F-20 drive Block diagram of EPB 2.4 control panel with V3F-20 drive:

Control Transformer 239

Door supply transformer

245

Allarm

Circuit breakers

228

Expansion Board EXP 2.4 371 306

Microcomputer EPB 2.4

Drive Unit V3F-20

375

385 303

V3F-20 Mains Filter Door Module

Relays

733

Earth Bar PE

Contactors Landing Call Interface (If provided)

Terminals DM - DG 369

m11658a.bmp

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 6

The drive module consists of: - Motion control board - Inverter board - Modulator board - User interface unit

385:A1 385:A2 385:A3 385:A4

- Braking resistor - Fan - Main circuits:

306 303 385:V5 385:C1...C2 385:R1...R2 385:T1

diode bridge capacitors resistors current/temperature sensors

385:A1

306

V3F-20 front

P000245

385:A4

303

m11658b.eps

385:R1...R2

385:C1...C2

385:C5

385:C6

385:V1...V3

385:V4

DANGER led

V3F-20 open 385:A3 385:A2

385:V5

385:T1 P000392

m11658c.eps

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 7

User interface unit (385:A4): The drive is provided with seven modes used as interface for the user (0...6), which can be selected by means of the up and down buttons. The selected mode is visualized on the seven segment display positioned on the user interface unit. Between MODE 1 and 2 there is an intermediate phase called “c”, which is used to reset possible errors visualized by pressing the button “CONFIRM”. The eleven leds on the user interface unit are visualized to indicate how to operate, the measuring scales and errors.

385:A4

P000245

User Interface Unit

m11658b.eps

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 8

3

TEMPORARY START-UP FOR PRELIMINARY TESTS

3.1

Control panel mounting The panel should be situated according to the layout drawing of the machine room. The panel must be mounted on the floor and there should be at least 100 mm clearance on both outer sides of the panel.

3.2

Mechanical installation Before carrying out the electrical connections to the EPB 2.4 control panel fitted with the V3F-20 drive, both the machine room components (gear, motor,...) and the shaft components (guiderails, ropes, slings, car, ...) have to be installed. The control panel and the drive can be used during the temporary operation phase by properly connecting the maintenance control station used during the inspection drive mode; both must be supplied.

DANGER! DISCONNECT THE MAIN SUPPLY TO THE CONTROL PANEL BEFORE GOING ON WITH THE INSTALLATION.

Power connections: CONTROL PANEL

POWER SUPPLY NETWORK PE



Connect the power supply network cable to the terminals DG/1, DG/2 and DG/3 and the yellow-green cable to the control panel earth bar PE.

CONTROL PANEL MACHINE ROOM CAR SHAFT DG/1 DG/2 DG/3

CONTROL PANEL



Connect the motor supply terminals DG/4, DG/5 and DG/6 to the gear motor terminal board by means of the power shielded cable. The cable shield and the yellow-green cable are to be grounded at both the motor side and the control panel side (as short as possible).

MACHINE ROOM DG/4 DG/5 DG/6

PE

M 3

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 9

The other connecting cables must be separated from the motor shielded one by a minimum of 100 mm.

(shielded) tachometer cable

(shielded) motor cable

m11658r.pcx

CONTROL PANEL



MACHINE ROOM DM/14

Connect the cable of the mechanical brake to the terminals DM/12 and DM/15; if the brake contact is present, connect it to the terminal DM/14.

11 DM/15

DM/12

DRIVE PANEL

MACHINE ROOM 33

6 M



Connect the tachometer between the drive terminals 33 and 31 and this cable shield to the drive terminal 32.

31

1

32

So that no possible interference occurs, the tachometer shielded cable is grounded at the control panel side only. In addition the tachometer cable must be separated from the motor one by a minimum of 100 mm. Warning. The tachometer is a very sensitive component. Therefore its connections and installation must be carried out carefully and correctly. Make sure that the tachometer driving belt is neither broken nor interrupted.

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 10





Connect the single-phase fan used to cool the motor to terminals DM/106 and DM/ 107. In case of a three-phase power supply fan, refer to the layout diagrams enclosed with the control panel.

Connect the motor thermal protection cable between the drive terminals 27 and 28. Make sure that the jumper between terminals XM8/2 and XM8/3 is present on the EPB 2.4 board.

CONTROL PANEL

MACHINE ROOM

DM/106

DM/107

10 10:T

DRIVE PANEL

M 1

MACHINE ROOM

27 t

t

28



Carry out all the grounding connections of the devices present.



Use the maintenance control station for the temporary operation tests; see the diagram below for the temporary connections to be carried out.

Service Buttons

Control Panel

m11658.spl

Numbering of BM connector



Connect all the already installed safety devices to the EPB 2.4 control panel: overspeed governor, safety gear contact, stop button in well pit, over travel, slack rope contact, car and landing door contact, .... As for the safety device arrangement refer to the circuit diagram (page 3) enclosed with the control panel.

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 11



Carry out the connection on the control panel connector between: a XH4/3-XH4/4-XH4/12 only if the deceleration and synchronization switches are not mounted yet. b XH3/10-XH3/11 only if the inspection mode limit switch in the shaft (if present) has not been mounted yet.



Check that the drive terminal 50 is grounded.



Switch off all circuit breakers (286:1-2-3; 291; 293; 298:1-2) on the control panel and give the main supply to it.



Switch on all the protection circuit breakers: a 286:1-2-3 (control panel main supply circuits) b 291 (brake circuit and/or 48/60 Volt circuits) and keep both the circuit breaker 293 (to supply the safety chain, so that the car does not run) and the circuit breaker 298:1-2 (to supply the drive) disconnected.

A

For further information regarding the EPB 2.4 control panel operation system, see the manual AME 10.21.3 (installation instruction). –

Check the tachometer polarity by making the car travel downwards. The led TPOL should light on the motion control board. If not then swap the tachometer wires in the control panel.

TPOL

P000394

m11658o.eps

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 12



Switch on the circuit breaker 298:1-2 (drive power supply). Select the MODE 2 on the user interface board by pushing the up or down arrow button). The leds CPU ON, CPU OK or V3F OK must be on. UP

CPU_ON CPU OK V3F OK SETUP DR SETUP_F DIS.DR TAC_FAIL REG_FAIL POS_FAIL TEMP.

CPU is running on MCB CPU check passed Inverter is ready to run Setup drive is activated Creating shaft image not succeeded Disable drive Not used Failure or wrong polarity in the tachometer Speed controller saturates V3F has lost its position Motor or braking transistor too hot

MODE

Explanation

DOWN PUSH TO CONFIRM

m11658e.eps

The elevator can now be operated on inspection drive mode, by connecting first the inspection drive mode and then the circuit breaker 293 (safety circuit power supply). Make sure that the brake opens and the motor rotates in the correct direction, by pressing the up or down button of the maintenance control station, and make sure that the car runs in the correct direction; if not, exchange two motor phases. The elevator can now be operated in inspection drive mode and all shaft equipment can be connected according to the shaft positioning circuit diagrams. Note! The elevator can not normally run on nominal speed, if the set-up drive has not been carried out.

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 13

4

NORMAL DRIVE Before proceeding, ensure that the tachometer polarity is correct and that the motor rotates in the right direction. Before proceeding, make sure that the elevator and its electrical and mechanical parts are completely mounted and that all safety equipment work properly.

4.1



Run the elevator to the topmost or bottom floor, in case there are some doubts whether the deceleration switches on limit floors and the over travel devices are positioned properly.



Turn the main switch off; disconnect and/or connect all the temporary connections previously carried out and disconnect the service buttons used during the preliminary tests.



Check again the connections carried out with the layout diagrams delivered with the control panel.



Make sure that the shaft has been installed according to the layout diagrams present in the machine room.

Shaft device check Check the oscillator switches 61:U-N and door zone switches 30 (in the machine room). They must be installed according to the circuit diagram present in the machine room. Check the switches 61:N, 61:U and 30 by means of the leds (L14, L15 & L24) positioned on the EPB 2.4 board and their corresponding ones (N61 and U61) present on the drive user interface. Make sure that the configuration parameter being visualized on the EPB 2.4 board is parameter “A1 = 2”. –

By means of the maintenance control station, run the car to the bottom floor level; make sure that the leds 61:U, 61:N and 30 are lit



Run the car upwards and when it reaches the floor, make sure that the leds switch on following this sequence of the shaft switches: 30, 61:U & 61:N.



Afterwards run the car downwards and as it reaches the floor, make sure that the leds switch on following this sequence of the shaft switches: 30, 61:N & 61:N. A

A

with oscillators

with bistables 300 mm

150 mm II

II

300 mm II

II

150 mm

61:U

61:N

30

61:U

61:N

30

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 14

If this is not the case, check the connections of the shaft switches. When the car is in the middle of the shaft and not close to a floor, the three leds must be off. POWER

S-CIR OK

STFAIL DRIVE MODE START CONT

385:A1

SP.LIMIT V3F OK RXD

PICKUP SYNC

TXD

BRAKE U61 N61 P000394

U136 N136 UN132

TPOL P000274

m11654o.eps m11654d.eps

Check the synchronization switches 132:U-N (optional) and the deceleration switches136:U-N (in the machine room) If the distance between the limit floors is less than the positioning distance of the limit switches 136:U/N, switches 132:U/N must be positioned between the limit floors and the previous ones. If switches 132:U/N are not present, make sure that the jumpers between terminals 15-36 and 14-35 are on the drive. A Switches must be installed according to the machine room diagram. Check the leds U136, N136 and UN132 on the V3F-20 user interface unit and the leds 136:N and 136:U on the EPB 2.4 board. –

By means of the inspection drive mode, run the car to the bottom floor. Make sure that the leds UN132 (if used) and N136 (136:N) are on and that the led U136 (136:U) is off.



Run the elevator upwards so that it is above the switch 132:N (if used). The led UN132 on the motion control board should switch off.



Run the elevator upwards so that it is above the limit switch 136:N. The leds N136 (136:N) and UN132 must switch off.

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 15

The car is now positioned above the limit switches on the limit floors and the leds U136 (136:U), N136 (136:N) and UN132 are all off; if this should not be the case, make sure that the shaft switches have been properly installed and/or check the connections. –

Run the elevator upwards so that it is above the limit switch 136:U. The led U136 (136:U) must be lit.



Run the elevator upwards so that it is above the limit switch 132:U, if used. The leds U136 (136:U) and UN132 must be lit.

Run the car to the topmost floor. The leds UN 132 (if present) and U136 (136:U) must be on, while N136 (136:N) must be off. If not, check both the switch positioning and the connections.

POWER

S-CIR OK

STFAIL DRIVE MODE START CONT

385:A1

SP.LIMIT V3F OK RXD

PICKUP SYNC

TXD

BRAKE U61 N61 P000394

U136 N136 UN132

TPOL P000274

m11654o.eps m11654d.eps

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 16

4.2

Set-up drive This set-up drive allows V3F-20 to learn the positions of all the floor levels and shaft devices. This is necessary before running on nominal speed. The elevator can normally work only when this set-up drive has been carried out. –

Turn the main switch off.



Switch on the inspection drive mode by means of the maintenance control station (42).



Disable the car and landing door opening by means of the jumpers (X2 and X5) on the EPB 2.4 board.



Turn the main switch on (286:1-2-3).



Run the elevator on inspection drive mode to the bottom floor. The leds U61 (61:U), N61 (61:N), 30, UN132 and N136 (136:N) must be on while the led U136 (136:U) must be off.

Make sure that the EPB 2.4 board does not generate error signals; in this case, see the manual AME-10.21.10 (fault-finding instruction). –

Set the V3F-20 to the “INPUT MODE 1” with the user interface unit by pressing the both arrow buttons at the same time (inspection drive switch 265 must be down). There now should be three horizontal lines on the display (see figure below):

Confirm P000358

m11658t.eps



Press the button CONFIRM.



Disable the inspection drive mode; the elevator should now run on set-up drive mode.

The elevator should automatically start at reduced speed about couple of seconds later. The led SET-UP on the user interface unit (MODE 2) should be lit when the elevator is moving. The elevator should run automatically to the topmost floor and stop.

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 17



Check that the elevator has passed the topmost floor.



Check also that the SET-UP led is off on the user interface unit MODE 2.

If the elevator stops before the topmost floor or the led S.FAIL is blinking, the set-up drive has failed and will have to be done again. Check that the shaft installation is done according to your delivery documents. After the new set-up, check that the led S.FAIL is not blinking anymore. If it is only lit, select the letter “c” on the display (between MODE 1 and 2) with the up and down arrow buttons and push CONFIRM. This resets the fault indications.

If this led is blinking after the SETUP drive, try the SETUP drive again

Explanation CPU_ON CPU OK V3F OK SETUP DR SETUP_F DIS.DR TAC_FAIL REG_FAIL POS_FAIL TEMP.

CPU is running on MCB CPU check passed Inverter is ready to run Setup drive is activated Creating shaft image not succeeded Disable drive Not used Failure or wrong polarity in the tachometer Speed controller saturates V3F has lost its position Motor or braking transistor too hot

MODE

This led is lit during the SETUP drive

PUSH TO CONFIRM m11658e.eps

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 18

4.3

Checks at full speed

4.3.1

Intermediate DC voltage –

Set the normal drive.



Set the user interface unit to mode 3 by pressing the up or down arrow buttons.



Run the elevator up and down at full speed and follow the leds on the user interface unit. Check that the DC voltage is like on the table below.

700 675 650 625 600 575 550 525 500 475 0...450

DC voltage display notes Maximum DC link voltage Maximum braking voltage

MODE

Voltage

Maximum drive voltage Nominal drive voltage

DC link undervoltage supervision

PUSH TO CONFIRM

m11658f.pcx

If the DC voltage increases to the maximum DC link voltage (all leds are lit), check the braking resistors 306 and the IGBT transistor (385:V4). Remember that, if this check is necessary, you must turn the main switch off and wait for at least 5 minutes (the led DANGER must be off) before working on the drive.

Table 1: Values to be checked Network voltage 380 V 400 V 415 V

Elevator standing 500 VDC 525VDC 550VDC

Running empty car down 550VDC 575VDC 600VDC

up 600VDC 625VDC 650VDC

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 19

Motor current –

Set the normal drive.



Set the user interface unit to mode 4 by pressing the up or down arrow button.



Run the elevator up and down and follow the leds on the user interface unit. Check that the motor current does not reach the maximum value. Current

MAX.

Motor current display notes Maximum instantaneous current

ACCEL.

Acceleration current

NOM.

Full car up or empty car down

MIN.

Empty car up or full car down

MODE

4.3.2

PUSH TO CONFIRM

m11658g.eps

If all leds are lit then the balancing of the elevator may be incorrect. The balancing is normally 50% (the mass of the counterweight is the weight of the car + 50% of the rated load of the elevator). Another reason for that might also be the wrong motor parameters in V3F-20. In this case check the parameters (see the training manual TC 05 213 00). Motor slip –

Set the normal drive.



Set the user interface unit to MODE 6, by pushing the up or down arrow button.



Run the elevator up and down at full speed and follow the leds on the user interface unit. Slip

12 10 8 6 4 2 0 -2 -4 -6 -8

Hz Hz Hz Hz Hz Hz Hz Hz Hz Hz Hz

Slip display notes Max. slip frequency (heavy direction) Slip frequency during acceleration

MODE

4.3.3

Nominal slip frequency (heavy direction)

Slip frequency (braking)

PUSH TO CONFIRM

m11658i.eps

The slip (the difference between the synchronous and the actual speed) should not be more than 6 Hz (empty car down) or -6 Hz (empty car up), because the motor may overheat. The reason for that might be the wrong motor parameters in V3F-20; in this case check the parameters (see the training manual TC 05 213 00).

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 20

Heat sink temperature –

Set the normal drive.



Set the user interface unit to MODE 6, by pushing the up or down arrow buttons.



Run the elevator up and down for about 30 minutes and follow the leds on the user interface unit. Check that the temperature does not reach the value 65.

HS.temp

Heat sink temperature display notes

80 75 70 65 60 55 50 45 40 30 20

Failures! Maintenance needed Hardware supervision stops the elevator Warning Check adjustments and ventilation

MODE

4.3.4

Heavy traffic temperature range

Low traffic temperature range

PUSH TO CONFIRM

m11658h.eps

If the temperature is too high, check the ventilation of the panel. The machine room temperature should be below 40 °C. The reason for overtemperature might also be the wrong motor parameters in V3F-20; in this case check the parameters (see the training manual TC 05 213 00). 4.3.5

Checking of the floor level –

Drive the car to each floor and record any floor level error (e.g. figure below). If the elevator stops too early, mark the error with a minus sign. If too late, mark the error with a plus sign.



Move the floor and door zone vanes if the error is more than 5 mm (controlled by oscillators 61:U, 61:N and 30) to adjust the floor level errors to zero. If the error is negative move the vane towards to the floor level and if positive, move it away from the floor level.

Example: FLOOR 6 5 4 3 2 1

LEVEL - 3 mm + 8 mm - 12 mm + 3 mm + 2 mm + 7 mm

reposition reposition reposition

Note: If any vanes are moved, the new “SET-UP” drive must be made according to the indication given in paragraph 4.2 (Set-up drive).

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 21

Normal drive: MODO 0 and MODO 1 selected The V3F-20 drive can update and generate status signals during the normal drive of the elevator. During the normal drive MODO 0 must be visualized on the display. The elevator status is normally shown in MODO 0 which specifies the signals provided by the EPB 2.4 to the drive.

Normal drive mode is selected Up start command is activated Down start command is activated Elevator is switched to inspection Relevelling drive is activated Correction drive is activated

1m/s 1.6m/s 1.8m/s 2.0m/s

Nominal speed of the elevator is 1m/s Nominal speed of the elevator is 1.6m/s Nominal speed of the elevator is 1.8m/s Nominal speed of the elevator is 2.0m/s

MODE

Explanation NORMAL U_START D_START INSPECT. RELEVEL. LOW_SP.

PUSH TO CONFIRM m11658p.eps

If the V3F-20 drive detects an error signal, MODO 1 is automatically selected and the corresponding fault leds start blinking. In order to reset the error, mode “c” must be selected and CONFIRM must be pressed.

Explanation M_CONT. BRAKE M.B.E

Main contactor activated Brake activated Motor bridge transistors enabled

RMS.OC

RMS overcurrent

BRES_FAIL HS.TEMP ACV_FAIL

Braking resistor circuit not OK Heat sink temperature too high AC voltages not OK

MODE

4.4

PUSH TO CONFIRM m11658q.eps

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 22

4.5

Sequence of the commands from the EPB 2.4 control panel to V3F-20 NORMAL START EPB 2.4

V3F-20

NORMAL RUN = ON

1

2

K5 = ON

V3F-20 ENABLES THE START

MAIN CONTACTOR (201) = ON

3

201:1 201:2

K1 = ON

UP / DOWN START = ON

3

K2 / K4 = ON

4

V3F-20 OPENS THE BRAKE

209

DECELERATION

V3F-20

EPB 2.4 2

PICK-UP

EPB DECIDES TO DECELERATE

1

V3F-20 ASKS TO DECELERATE

3

434 = OFF

434 UP / DOWN START = OFF

3

4

K2 / K4 = OFF

V3F-20 STARTS DECELERATION

STOP EPB 2.4

V3F-20

1

61:U E 61:N 2

EPB CHECKS IF THE CAR REACHES THE FLOOR

2

209 MAIN CONTACTOR (201) = OFF

4

4

K1 = OFF

V3F-20 ENABLES THE STOP

201:1 201:2 NORMAL RUN = OFF

K5 = OFF

3

V3F-20 RELEASES THE BRAKE

5

V3F-20 WAITS FOR A NEW START UP COMAND

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 23

4.6

Error signals detected by the EPB 2.4 control panel with V3F-20

ERROR CODE:

GENERATED IF:

The “Main contactor” signal from V3F-20 does not arrive to EPB during starting and stopping.

CONSEQUENCES:

During starting the 201:1 and 201:2 start relays are not activated and the lift stays at floor. In deceleration run, the lift oversteps the floor.

CAUSES:

- The “Main contactor” (201) signal is not activated in V3F-20 output. - Check the connection and diode polarity (in series) between EPB and V3F-20 (XM4/1 e 11). - Control the fault codes generated by V3F-20.

ERROR CODE:

GENERATED IF:

The V3F-20 drive is losing the shaft car position and it communicates to EPB that a synchronization run is needed.

CONSEQUENCES:

The controller enables the drive to start for a synchronization run.

CAUSES:

- The V3F-20 does not find the shaft signals. - The interface signals are not activated between EPB and V3F-20. - Check the switches and the signal to the shaft.

ERROR CODE:

GENERATED IF:

The V3F-20 is running set-up.

ERROR CODE:

GENERATED IF:

It indicates that the alarm signal has been activated with V3F-20.

CONSEQUENCES:

The car will arrive at the floor or stop immediately. Refer to the V3F-20 drive manual.

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 24

5

FAULT FINDING ON V3F-20 DRIVE This chapter is to be used by trained persons who have completed a V3F20 training course. The users must also be able to use the laptop based INVMON program for changing the V3F20 software parameters. This information is valid for V3F20 software rev 5.0 and later. The version number can be seen on the EPROM chips on the Motion Control Board 385:Al under the cover. The V3F20 has been developed to give high reliability and high resistance to failures. The engineer who works with the drive system will find much information in the forms of led's and the user interface card to aid in the correct commissioning of the drive, and to identify any difficulties that are encountered. The drive system will have passed many tests before the module is delivered for installation on site; ALL functions would have been tested and ALL parameters will have been programmed. Theoretically all that is necessary to commission a V3F20 for a new elevator would be to check that the tachometer wires are the correct polarity and the correct motor rotation direction, then to perform the set-up drive. Unfortunately there are occasionally difficulties during the life of any product. This chapter is designed to aid in the fault finding and trouble shooting of a V3F20 drive system. It is to be used in conjunction with the documentation listed below.

5.1

Related documentation SOE 11.65.3, AME 10.37.8 (Start-Up TMS600), AME 11.65.7, AR 11.65.5, AS 12.7.14, UM 11.65.3, TC OSA 213 00 and TC05 213 ME.

5.2

Fault finding procedure The first steps for trouble shooting is always to first read all LED's (inside and outside the V3F20 module), and ensure they give the correct indication for the system status. In order to drive, all green leds must be ON and all red leds OFF. Yellow leds may be ON or OFF depending on drive conditions. If one of the red leds is illuminated in the drive system: there is a failure in the boards; or in external devices, or disconnections in connectors/wiring. As the V3F20 follows the commands from the EPB control system, the elevator will not move without the MODE (i.e. Normal or Inspection drives) and START commands. The interface commands for a normal drive sequence are shown on page 22. Other drive modes are shown in SOE 11.65.3 appendix 4. It is recommended to fill in a failure report and keep a record of all jumpers at the start and during any problem investigation.

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 25

5.3

General Rules for Changing V3F20 Parameters Always use a PC if available or from User Interface menus (acceleration and jerk only). (Some changes are possible using the Motion Control Board potentiometer but this is difficult to use. Note that for software versions H08 or above a new voltage range is used - Use V20CAL50 or AS 12.7.14, issue-A parameter tables). INVMONx is used to read and change parameters in the V3F-20 drive unit. See UM-11.65.3 for details on how to use INVMON program. A set of default parameters are always initially set and are available to reset at any time. Parameters are normally configured to suit the site in the M3 control panel factory. If the program does not start, check the communication cables and the software versions. V3F20 MCB SW H01 to H04 H05 to H06

INVMONx version INVMON2 INVMON3 or above

*H07 *H08 H09 or above

INVMON3 or above *INVMON4 INVMON5 or above

Change Parameter "Overspeed limit" changed to "tacho input saturation". New parameter ranges added. H09 or above New features added

* H07, H08 and INVMON4 were pilot versions only! - not officially released. Before changing parameters please note the following. 1 Always start by setting parameters to the V20CALx Configuration Data values. 2 Always use INVMON parameter display if possible. 3 Elevator nominal speed can not be changed without recalculating parameters with V20CAL and adjusting Tacho Test Voltage on the Motion Control Board. 4 The tacho test voltage (TTV) must be set to the specified value. 5 Check TSPL value and adjust RSPL if needed. Value for 1.0, 1.6, 1.8 and 2.0 m/s speeds are listed on the inverter board (385:A2). Otherwise calculate as 1.35/nominal speed. 6 The links on the V3F-20 Modulator Board must be set according to the frequency range specified in V20CAL results. 7 Parameter loading accuracy. – Nominal speed. – Must be loaded accurately from V20CAL results to give correct speed. – Recommended to use standard speeds using Parameter Display option. – If not possible then load special speed using Monitor Display – Max. slip (Rotor Frequency Limit); load nearest higher value. – Fsn (Frequency scaling); within ± 1 Hz. – Kl, K2, K3, K4 parameters; load nearest possible value using parameter display. If outside the selection range then use monitor display. – P factor; load nearest value. Further information about V3F-20 Fault Finding see on AME-11.65.7

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 26

5.4

Leds, potentiometers and jumpers on V3F-20

5.4.1

Motion Control board Power supply leds: POWER

The led is on when power supply is working.

Supervision leds: S-CIR ST.FAIL

The led is on when the safety chain is closed. If the led is off, start-up is not enabled. The led is on, when there is current in the motor or the car runs without the DRIVE MODE command.

Input signal leds: DRIVE

The led is on if the control panel has selected one of the possible drive modes (normal, inspection, relevelling or correction drive modes). It is on when the control panel activates an up or down start command.

START Output signal leds: CONT. SP. LIMIT V3F OK PICK UP SYNC BRAKE

It is on when V3F-20 enables main contactors. It is on when the car speed is below 0,3 m/s. If it is on there are no internal faults in V3F-20 (it must be always on). It is on when V3F-20 asks the control panel to decelerate. It is on when there is a synchronization request because the car position has been lost. Note: PICK UP + SYNC = setup drive. It is on when V3F-20 releases the mechanical brake.

Shaft signal and tachometer leds: U61 N61 U136 N136 UN132 TPOL

Car is in 61:U floor level vane. Car is in 61:N floor level vane. Car is in top deceleration area Car is in bottom deceleration area. Car is in the synchronisation 132:U/N area at the top of bottom of the shaft Car is moving down (tacho polarity check).

Communication leds (used when a computer is connected to V3F-20): RXD TXD

Blinking when CPU is receiving data. Blinking when CPU is transmitting data.

Jumpers: S2 S4 S5

FOR PRODUCTION ONLY! DO NOT INSERT ANY JUMPERS Enable supervision tachometer. Insert S4 to enable supervision tacho tachometer scaling test (left position in normal run)

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 27

Potentiometers: RSPL 5VREF TACHO SCALING SUP. TACHO SCALING PARAM. CORRECT.

5.4.2

Adjustment of 0,3 m/s limit (test point = TSPL). Adjustment of 5V reference (test point = S5/1). Tacho scaling (tacho test voltage is adjusted to calculate value shown in delivery documents. Supervision Tacho Scaling. Adjust parameters.

Inverter board Fault leds: PROT DRV DCV ACV

(red) (red) (red) (red)

IMV TEMP

(red) (red)

Lit when there is overvoltage or overcurrent in DC link. Lit when there is an IGBT driver voltage fail. Lit when there is a DC voltage level fail. Lit when the line voltage is out of limits or when a phase is missing. Lit when the DC link voltage is out of limits. Lit when the heat sink temperature is too high (75 °C).

Leds: DANGER DC CURRENT (ZC) BRES

(red) (yellow) (yellow)

It is on when the DC link voltage is over 50 VDC; when this voltage reaches 600 VDC. Be careful! It is on when there is current in the DC link. It is on when the braking circuit is ok and the braking resistor is working properly.

Potentiometers: IMV

Adjustment of DC link voltage according to the drive. 400V

380V OC

415V

Overcurrent supervision adjustment. 40A 60A

20A

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 28

5.4.3

Modulator board Jumpers: SFL SFH UREF2

50 Hz frequency range. 60 Hz frequency range. If inserted then frequency is divided by 2.

Potentiometer: SWITCH FREQ

Switching frequency (6..9 kHz).

X10 X9

X9

PE

219

41

303 ~ 220VAC

385:C1

385:C3

306

U T1 U

E1/C2

1

6 7

B2

B2 2

V T2 V

E1/C2

E2

E1/C2

W T3 W

U V 3 W

~

389 T

B2 E2

Tachometer E2

385:V4 (6,7)

385:V1 (E1/C2,E2,B2)

385:V2 (E1/C2,E2,B2)

385:V3 (E1/C2,E2,B2)

X7G

X7B

X7D

X7F

42

385:A2

P000276

N/220

Motor

3

385:V3

389

PE

B1

385:C6

T

B1

B1

385:V2

L3 T

S

~ ~ ~

385:V4

L2 S

R

385:R7

L1 R

C1

C1

C1

Machinery

BR

385:R8

L3

201:1 201:2

DC +

385:V3 (B1,C1,E1)

385:V2 (B1,C1,E1)

INSTALLATION INSTRUCTION

L2

220

385:R6

L1

385:R5

R.1 385:R2

281

385:V1 (B1,C1,E1)

385:T1

+

385:C2

385:V5

385:V4 (1,2,3)

X7E

X7C

385:V1

S.1 385:R1

298

X7A

385:C5

V3F-20

385:C4

TMS control panel

X6/1,2,3

X10

APPENDIX 1. Main circuit of V3F-20

385:A3

385:A2

385:R5-R8 Capacitor discharge resistors 306 Braking resistor 389 Filter module 303 Fan 220 Main switch 281 Fuses 298 Circuit breaker 201,(214) Main contactors 219 Motor fan contactor

X13

X5

385:A1 X4

Page: 29

Note 385:R7,R8 and 385:C3-C4 only fitted for versions G07-G09 (60Amps)

385:A4 X4

AM-11.65.08 ESE

385:A1 Motion Control Board 385:A2 Inverter Board 385:A3 Modulator Board 385:A4 User Interface Board 385:V1-V4 Transistor modules (IGBT) 385:V5 Diode bridge module 385:C1-C4 Filter capacitors 385:C5-C6 Transistor protection capacitors 385:T1 Current/temperature sensor 385:R1-R2 Bridge charging resistors

X2 (31,32,33)

X5

INSTALLATION INSTRUCTION

AM-11.65.08 ESE Page: 30

APPENDIX 2. V3F-20 User Interface