INDEX 20nb L C D Auto Mpv 1 2 3 4 5
Introduction and Features of SOLOMATIC Possibilities and Scope of Automation Installation Guidelines and Piping diagram Specifications Programming Instructions a. Glossary of terms b. How to enter Password , required Time and select required option / Operations of Keys? c. How to SKIP , HOLD an operation? d. VIEW Mode e. Advance Programming f. Operating sequence 6 Wiring connections 7 Exploded view of SOLOMATIC Auto MPV 1. Introduction and Features of SOLOMATIC Introduction : Solomatic is the most , Advanced Microprocessor Based , Fully Automatic Multi Port Valve in India .It automatically carries out all the operations like Brine Injection / Slow Rinse / Fast Rinse & back to Service in fresh recharged condition. The advanced components like current limiter, watch dog IC and high quality electronics ensure trouble free operations for years in tough Indian conditions. Being indigenously made to suit tough Indian conditions Solomatic Automatic Softener comes with full one year guaranty , easy availability of spares & after sales services. Unique Brine Director ensures that Brine Solution is prepared automatically (no need to stir salt for half an hour ) during service cycle of softener with soft water to ensure that you get more output from your plant. Features of SOLOMATIC AUTO MPV : 1. The SOLOMATIC AUTO MPV automatically counts down the timing of each step, goes on to the next step and comes back to service. 2. Regeneration / Backwash cycle can be started by: a. Pressing a key b. From an external pulse c. From a pulse signal from the previous unit d. By pump-on timing settable which is up to __ Hrs with least count 1 min e. By volume, which means by using electronic flow sensor f. By time of the day /week (OPTIONAL) 3. Two auxiliary outputs to control additional solenoid valves. 4. Optional inputs are: a. Brine switch interlock b. Raw water / Treated water tank level control Added advantages: 1. Robust power supply 80 Volts to 280 Volts. 2. Automatic Start up Rinse possible. 3. Counter: This tells how many cycles have been completed. 4. Hold-Release Skip facility to assist trouble shooting 5. External input count 6. IP 55 actuator box 7. External buzzer for audio alarm in case of malfunction. 8. Conductivity interlock for D.M.Plants. 9. Combined volume & conductivity interlock.
Page - 1 -
Back to Index
2. Possibilities and Scope of Automation ( For STAND ALONE UNIT ) 1. Semi – Auto : Press a button to initiate regeneration / backwash. Unit goes into regeneration and back to service on its own. 2. Fully Auto : Automatic regeneration takes place based on external signals ; A..Pump ON time: Selecting this feature allows one to program the number of hours & minutes that the raw water pump keeps water flowing through the unit before regeneration starts. It is settable up to 99 Hrs & 59 Mins. with a least count of 1 min. for the auto wash processor to know that the pump is “ON” the auxiliary output of pump starter is to be connected to the auto MPV. This will also ensure that even the regeneration timing count down will happen ONLY when the pump is ON. B. Flow sensor : The Auto valve counts down the programmed output based on signal from flow sensor. When it reaches zero, the unit goes into regeneration automatically. C. Real Time clock (optional) : Regeneration starts at the programmed time and day of the week and unit goes back into service on its own once the regeneration is over. D. External Input Signal from PLC or Previous Auto MPV. Brine Tank Automation : A brine level switch can be inserted in the brine tank which switches between brine and water. 1. When regeneration is initiated by any means , the Auto MPV first checks whether the Brine switch indicates presence of brine. If not it gives an alarm indicator. 2. When regeneration step is over , if the brine switch still detects brine it gives an alarm ‘Regeneration incomplete’. ‘REGENERATION FAIL’ Spare Relay (Standard) : A spare relay output is available which can be programmed to start any time after start of cycle and for any duration up to 99 min. It’s possible uses are as follows; 1. Remote (Panel) indication of regeneration in progress. 2. Operation of ‘ fast rinse ’ solenoid valve for down flow softeners. 3. Operation of ‘ raw water bypass ‘ solenoid valve during regeneration. 4. Operation of ‘ regeneration suction ‘ solenoid valve in Auto D.M. plant. 5. To bypass high pressure cut off of Hydro-pneumatic system during regeneration. Second Spare Relay ( Optional) : This relay can be used to operate a remote (panel) annunciator whenever any fault condition occurs. Conditions under which annunciator (buzzer) will activate ; 1. If unit does not go from one step to another within specified time limit (200 sec.) 2. When brine switch is provided and if brine is not ready at the start of regeneration. 3. If brine still remains in brine tank at end of regeneration. 4. Internal malfunction. (Reed switch short) 3. Installation Guidelines and Piping diagram Solomatic is Advance microprocessor Based Mini Computer. Install the Solomatic in Shade / inside a covered room.Keep it away from sunlight ( the way you keep your Computer / TV / Washing M/c ).Keep it away from dust & water.Kindly go through the various installations recommended below & ensure that you have installed each & every required component for trouble free operation of the plant. TWT Piping Precautions. 1) Ensure that Inlet / Outlet pipe is well supported & it does not transfer any load on the MPV. 2 2) Ensure that shut off head of Raw Water Pump is below 5 Kg / Cm Piping Diagram
1) Standard: When Raw Water Tank is on ground level Install Vacuum Breaker at the Inlet of Softener to Prevent Brine Solution from Entering the Raw Water Tank
RWT
RWT
Page -2-
5. Programming Instructions 5a. Glossary of terms :
MOT ON DELAY:XXX
Motor ON delay time :-
When AutoMPV changes its position from Service to Regeneration or Regeneration to Rinse and so on it will send signal to Raw water pump / Solenoid valve to stop. Once the pump or solenoid valve stops , the pressure in the system reduces. However it takes some time for system pressure to become zero. The time in which system pressure goes to zero after Raw water pump / Solenoid valve is stopped, can be programmed as Motor ON delay time.Normally even in same system the time required by system to attain zero pressure also varies . e.g. Position change
Normally time required for system pressure to become zero
From Service to regeneration
Less time required.
From Rinse to Service
Less time required.
From Regeneration to rinse
More time required.
Always program maximum time required for system pressure to become zero as Motor ON delay time. CYCE COUNT:XXX Cycle count :Displays number of time the unit had finished regeneration.
REGN TIME: XX
Regeneration Time:The required duration of regeneration in XX mins.
RINSE TIME: XX
Rinse Time:The required duration of rinse in XX mins.
RST CYC. CNT?
Reset cycle counter:Select YES or NO if you wish to reset cycle counter
RINSE TIME: XX
Default Settings:Select YES or NO if you wish to continue with default settings External Pulse:-
EXT PULS: XX SENSOR:
Sensors :None - No Sensor is selected & Auto MPV will go in Regeneration mode once the REGN key is pressed or When External Signal Auto MPV / PLC or Cond. Meter/ Batcher / pH meter / External Timer etc. is used to give potential free pulse input to Auto MPV to go in Mode. Pump Time - When Astero Panel is used to give signal to Auto MPV to go into regeneration mode. Pump Tim is to be used when regenerate the Softener / Backwash the Filter after X hrs of pump operation. This is fairly accurate & economical alternative to flow batcher.
like Another regeneration you want to sensor / flow
Flow Sensor – If this feature is active then sensor can send Auto MPV in continuous loop. Startup Rinse :ST RINSE MAN (Manual) - Unit goes into Rinse mode when RESET key is pressed. AUTO (Automatic) - Unit goes into Rinse mode automatically whenever unit restarts / switched ON. BRINE Brine I/L (Interlock) :It is to be selected as ON whenever Brine switch is used and as OFF when Brine switch is not used. A brine level switch can be inserted in the brine tank and it switches between brine and water. 1.When regeneration is initiated by any means , the Auto MPV first checks whether the Brine switch indicates presence of brine. If not it gives an alarm indicator. 2. When regeneration step is over , if the brine switch still detects brine it gives an alarm “Regeneration incomplete’. Also refer Installation Drawing for brine switch.
EXT IP CNT
External I/P count :It indicates no. of External input signals after which unit would go into regeneration mode. This is useful when more than one units are operating
in series or parallel. E.g. If External I/P count is set as 3 , then unit will go into regeneration only after receiving the signal 3 times. PUMP IL Pump Interlock :When Pump Interlock is kept ON , if pump stops during regeneration cycle for any reason , the Solomatic will STOP countdown of the regeneration time. When pump restarts , the Solomatic will restart the countdown from position / time where pump was stopped. When Pump Interlock is kept
OFF & if pump stops during regeneration cycle for any reason the unit ADVISABLE for healthy running of Softener.
still counts down the Regeneration Time. However this is NOT
2) When Raw Water Tank and Treated Water Tank is on ground level Inlet
3) When Raw Water Tank is above ground level giving Positive Head
Outlet
Intisoft
Outlet
RWT
Requires vacuum Breaker or Pipe open to atmosphere at the outlet to prevent Brine entering the soft water when RWP is stopped.
TWT
NRV
Solenoid Valve
Intisoft
Air gap
RWT
RWP
TWT
Water Level
RWT
RWP
4) When softener is getting the raw water supply from common pump ( Not dedicated)
5) Hydro-Pneumatic System
Common Supply
HydroPneumatic Tank
TWT
Intisoft
RWP
Note: Solenoid Valve is necessary to stop the water flow before disc of MPV starts rotating from one step to other
Inlet
Outlet
Solenoid Valve 1
Solenoid Valve
RWT
Inlet
NRV
Solenoid Valve 2 NOTE: The function of the Solenoid valve here is to isolate the softener from the Hydropneumatic pressure
Page-3-
Intisoft
AUX2 OP
AUX1 OP
Auxiliary Output :Mode 1 :The Relay will remain energized during entire regeneration cycle. Mode 2 : After regeneration start, relay energizes. After motor on delay time is over, relay will be off. Mode 3 : Relay will start when valve is in service and will stop once regeneration starts. Mode 4 : ON DLY: This is the time for which relay will not get energized after the regeneration starts. Once this set time is over relay will start. OFF DLY: This is the time for which the relay will stay on and will switch off once the time is elapsed. Mode 5 : ON DLY: This is the time for which relay will not get energized after the rinse starts. Once this set time is over relay will start. OFF DLY: This is the time for which the relay will stay on and will switch off once the time is elapsed. Mode 6 : This will give pulse output after completing one cycle of operation. Mode 7 : Any fault condition on valve, this relay will get energized to get an alarm. Mode 8 – In this mode pump relay is on during service & the output configured in mode 8 will work as a pump relay during regn/backwash cycle.NO contact of pump relay to be used for controlling pump starter/contactor. Mode 9 – In this mode pump relay / output configured in mode 9 will work as pump relay for alternate service & regn/backwash cycles. NO contact of pump relay to be used for controlling pump starter/contactor. Default Display :-
DEF DISP
Default Display this feature enables you to select Display on Auto MPV as Softener / Cation / Anion / Filter / Downflow Softener Auxiliary Inputs:AUX IP OFF: No auxiliary input. BRINE: This will enable Brine Interlock. COND: This will enable conductivity interlock. RWLVL: Raw water tank level control TWLVL: Treated water tank level control 5b. How to enter Password , required Time and select required Option / Operations of Keys? The Password is a two digit number. When display shows
PASSWORD : 00,
in TEN’s place blinks. Increment it till desired number appears by pressing the press
first the digit key. Then
key to move to UNIT’s place. Increment till desired number appears. Press
key to enter the password. There are two password :- 1. Password 64 ( Basic Programming ) 2. Password 84 ( Advance Programming Not to be used by User ) If an incorrect password is entered, the display shows to SET MODE.
PASSWORD ERROR
. To again enter the password go back
Similarly , you can enter the required time for Regeneration , Rinse etc. by pressing
and
Keys. The key is used to increment the blinking digit from 0 to 9 only and the the digit position among HUNDRED , TEN and UNIT ‘s place. The
key is used to Toggle
key is also useful to toggle between the various options available in SET MODE.
Whenever any fault conditions occur the inbuilt buzzer sounds, The fault condition can be accepted byPressing RESET key. 5c. How To SKIP , HOLD an operation ? To SKIP an operation :- To SKIP an operation (Regeneration / Rinse) press in following cases ;
1. If by mistake
key once. An operation can be skipped
start key is pressed or by error an external unit has sent a signal to start
Regeneration , press
key to SKIP the operation & take the unit back to Service mode.
2. It can also be used to shorten Regeneration / Rinse operation time than the programmed time. E.g. If programmed time for a operation is 45 min. and you want to shorten it to 25 min. then press
key when countdown of the operation has reached (45 – 25 =) 20 min.
To HOLD an operation :- An operation (Regeneration / Rinse) can be put on HOLD , to extend its time than the programmed time by pressing position until you press
key. The valve will remain in the same
key once again. E.g. The programmed time of an operation is 45
min. and you want to extend it to 50 min. , then press After (50 – 45 =) 5 min. are over again press
key anytime during the operation.
key to restart the time countdown.
Page – 5 -
20NB LCD TECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS : FOR FILTER / SOFTNER 1) Valve Connection with top opening vessel 2) Max Flow rate (valve + strainers + riser pipe) 3) Max.Operating pressure 4) Riser Pipe size 5) Inlet,Outlet,Drain Connections
: : : : :
2.5''npsm (8 tpi). 2000 lph @ 0.5 kg/Cm2 5 kg/Cm2. 25mm PVC pipe. ¾''BSPF Quick release coupling elbow 'OR' straight (adaptor for converting to ½'' BSPF also available) 6) Riser pipe lenth with bottom strainer attached should be 9mm below vessel top. 7) 1/8'' BSPF nozzles across inlet,outlet for pressure gauge/sample valve. ADDITIONAL FOR SOFTENER: 8) Regenerant suction tubing size 9) Maximum resin quantity 10) Injector ratio 11) Minimum pressure for uniform suction
: : : :
¼'' 100 Lr. 1:2 2 Kg/Cm2.
Electrical Supply Voltage 80 to 280 Volts80 to 280 Volts Frequency 50 Hzs50 Hzs Power consumption 5VA5VA Memory retention 5 years5 years Display 16 Character LCD16 Character LCD Relay outputs Aux I and Aux II Both programmable in 6 ModesBoth programmable in 6 Modes Others Operating Temperature 0 - 500 0 - 500 Humidity 80% Max80% Max
Electrical Supply Voltage Frequency
80 to 280 Volts 50 Hzs
80 to 280 Volts 50 Hzs
Power consumption Memory retention
5VA 5 years
5VA 5 years
Display
16 Character LCD
16 Character LCD
Relay outputs Aux I and Aux II
Both programmable Both programmable in 6 Modes in 6 Modes
Others Operating Temperature Humidity
0
0 - 50 80% Max
0
0 - 50 80% Max
==================================================================================================
VIEW MODE SOFTNER / FILTER
MODE MODE VIEW MODE VIEW MODE MODE
RESET
SET MODE QUIT
CYCLE COUNT : XXX RESET SET MODE
PASSWORD:XX REGN
PASSWORD:64
RESET
SET TIMERS?
MODE
MOT ON DELAY
RESET
REGN TIME : XX
RESET
RINSE TIME: XX
MODE RESET
RST CYC.CNT MOT ON DELAY MODE RESET
EXIT
MOT ON DELAY : XXX
RESET
RST CYC. CNT : NO/YES
RESET
EXIT
RESET
QUIT
RESET
SOFTNER
ADVANCE PROGRAMMING SOFTNER
MODE
AUX1 OP
VIEW MODE
MODE RESET
SET MODE AUX1 OP : MODE X MODE RESET RESET QUIT PASSWORD:XX AUX2 OP PASSWORD:84 RESET RESET AUX1 OP : MODE X DEFF SETT? RESET MODE RESET
AUX3 OP
SENSOR DEF SETT : NO
RESET
MODE RESET
AUX1 OP : MODE X
AUX1 OP
MODE
AUX2 OP
MODE
AUX3 OP
ST RINSE
RESET
SENSOR : NONE
RESET
RESET
RESET
MODE
ST RINSE : MAN
MODE SENSOR : PMP TIM
ST RINSE
RESET
SENSOR :
RESET
TIME : XXX
MODE
RESET
RESET ST RINSE TIME : XX
MODE
SENSOR : FLO SEN
RESET
VOLUME : XXX: 2M³ RESET
DEF DISP DEF DISP? MODE
RESET AUX3 IP
MODE
DEF DISP? SOFTNER
RESET AUX2 IP
AUX1 IP
RESET
AUX1 IP : PULSE
B
A
MODE
AUX2 IP
RESET AUX3 IP
MODE
AUX IP: OFF
RESET EXIT
AUX IP
RESET
AUX IP
RESET
EXIT
SOFTNER
MODE
VIEW MODE
MODE
SET MODE QUIT RESET
PASSWORD:XX
RESET
PASSWORD:44
PASSWORD:44
PASSWORD:24
RESET
RESET
RESET
MODE : WORKING
RESET
RTC PRESENTS:YES
ML/PULSE:XXX.0
MODE
CHECKING RTC...OK
MODE
RESET
RTC PRESENTS:NO
QUIT
RESET
RESET
RESET
STANDING BY
QUIT
VOLUME:XXX.2M ³
TIME:XXX
QUIT MODE : STAND BY
12 V
RED
INPUT 1 INPUT 2
PUMP TIME
COM. FOR INPUTES
GREEN
BLACK
FLOWSENSOR
INPUT 3
COM. FOR INPUTES
COM. OUTPUT 2
NO.
COM. OUTPUT 1
NO.
COM. OUTPUT 3
NO.
COM. TO PUMP CONTACTOR
NC.
PUMP OUT 10 AMP MAX
5
6
7
8
C NC MPV POWER TOP JMP SUPPLY CONTRACTOR
9
10
C
NO AUX CONTACT
15
14 COM
NC
TO PUMP CONTRACTOR
13 OUTPUT 3 10 COM
NO
12 OUTPUT 1 COM 9
NO
11 NO OUTPUT 2
COM. FOR INPUTS 7
COM
INPUT 3 6
8
COM. FOR INPUTES 5
OR
PUMP TIME 4-5 GREEN
4
PRESSURE SWITCH
P N INPUT
3
TREATED WATER FLOATY
2
C
1
NO
SINGLE PHASE PUMP CONTROLLER
BLACK
MCB 16A
A1
4
14
INPUT 2
T2
3
T1
INPUT 1
13
2
L2
+12V
L1
1
A2
N
LCD MPV 20NB
AUX SUPPLY FOR MPV
P
FLOW SENSOR 1-4-5 R-G-B
STAND ALONE FILTER LCD MPV 20/25 NB - SINGLE PHASE CONTROLLER
In set mode. password 84; programmable inputes (filter): 1. Inpute 1 (1-7) - raw water level / treated water level 2. Inpute 2 (3-7) - inpute pulse or treated water level 3. Inpute 4 - flow sensor (1-4-5) or pump time (4-5) Programmable output 1(9-12), 2(8-11) & output3(10-13) can be configured in 9 modes as per requirement
M/S INITIATIVE INI-SYS-MPV20NB-WD-401-01
All connections should be made with Tinned-Cu wires with Gray Insulatio,Appropriately Ferruled and lugged
1 2 3 4 R Y B N
5 6 7 R Y B
8
9
10
11
TO PUMP CONTACTOR C NC
MPV POWER SUPPLY
12
13
C
R Y B
NO
R Y B N
15
14 COM
NC
TO PUMP CONTRACTOR
13 OUTPUT 3 10 COM
NO
12 OUTPUT 1 COM 9
NO
11 NO OUTPUT 2 COM
AUX CONT. C
NC
In set mode. password 84; programmable inputes (filter): 1. Inpute 1 (2-7) - raw water level / treated water level 2. Inpute 2 (3-7) - inpute pulse or treated water level 3. Inpute 4 - flow sensor (1-4-5) or pump time (4-5) Programmable output 1(9-12), 2(8-11) & output 3(10-13) can be configured in 9 modes as per requirement
Power Wiring: 1.5 sq. mm Control Wiring : 0.5 sq. mm
8
OR
PUMP TIME 4-5
COM. FOR INPUTS
B
7
Y
INPUT 3
R
6
B
BLACK
Y
PRESSURE SWITCH
THREE PHASE PUMP CONTROLLER
R
COM. FOR INPUTES
A2
5
14
4
T3
GREEN
T2
INPUT 2
T1
3
13
TREATED WATER FLOATY
L3
INPUT 1
L2
2
L1
LCD MPV 20NB
A1
+12V
N
1
P
FLOW SENSOR 1-4-5 R-G-B
STAND ALONE FILTER LCD MPV 20/25 NB - THREE PHASE CONTROLLER
M/S INITIATIVE INI-SYS-MPV20NB-WD-402-01
All connections should be made with Tinned-Cu wires with Gray Insulatio,Appropriately Ferruled and lugged
STAND ALONE FILTER LCD MPV 20/25 NB - SINGLE PHASE CONTROLLER
15
14 COM
NC
TO PUMP CONTRACTOR
13 OUTPUT 3 10 COM
NO
12 OUTPUT 1 COM 9
NO
11 OUTPUT 2 COM
COM. FOR INPUTS 7
8
INPUT 3 6
NO
PUMP TIME 4-5
OR
MCB 16A
A2
COM. FOR INPUTES
14
5
T3
4
T2
INPUT 2
T1
3
13
INPUT 1
L3
2
L2
+12V
L1
LCD MPV 20NB
A1
AUX SUPPLY FOR MPV
N
1
P
FLOW SENSOR 1-4-5 R-G-B
(TYPICAL WIRING SCHEME FOR CLINT MANUFACTURED CONTROLLER)
PRESSURE SWITCH
PUMP OUT
TREATED WATER FLOATY
INPUT POWER
GREEN
N
BLACK
P
C
THREE PHASE PUMP CONTROLLER
N
NO
P
In set mode. password 84; programmable inputes (filter): 1. Inpute 1 (3-5) - raw water level / treated water level 2. Inpute 2 (2-5) - inpute pulse or treated water level 3. Inpute 4 - flow sensor (1-4-5) or pump time (4-5) Programmable output 1(8-9) & 2(6-7) can be configured in 9 modes as per requirement
Power Wiring: 1.5 sq. mm Control Wiring : 0.5 sq. mm
M/S INITIATIVE INI-SYS-MPV20NB-WD-403-01 All connections should be made with Tinned-Cu wires with Gray Insulatio,Appropriately Ferruled and lugged
THREE PHASE PUMP CONTROLLER
R Y B N
R Y B
1 2 3 4 R Y B N
5 6 7 R Y B
8
9
10
11
TO PUMP CONTACTOR C NC
MPV POWER SUPPLY
12
13
AUX CONT. C
NC
4
Power Wiring: 1.5 sq. mm Control Wiring : 0.5 sq. mm
15
14 COM
NC
TO PUMP CONTRACTOR
13 OUTPUT 3 10 COM
NO
12 OUTPUT 1 COM 9
NO
11 OUTPUT 2 COM 8
COM. FOR INPUTS
TREATED WATER FLOATY
BRINE SWITCH In set mode. password 84; programmable inputes (filter): 1. Inpute 1 (2-7) - raw water level / treated water level 2. Inpute 2 (3-7) - inpute pulse or treated water level 3. Inpute 4 - flow sensor (1-4-5) or pump time (4-5) Programmable output 1(9-12), 2(8-11) & output 3(10-13) can be configured in 9 modes as per requirement
7
NO
PUMP TIME 4-5
5
GREEN
1
INPUT 3
B
6
Y
BLACK
R
GREEN
B
RED
Y
RED
R
COM. FOR INPUTES
A2
5
14
4
T3
INPUT 2
T2
3
T1
INPUT 1
13
2
L3
BLACK
L2
BLACK
L1
LCD MPV 20NB
A1
+12V
N
1
FLOW SENSOR 1-4-5 R-G-B
P
OR
STAND ALONE SOFTNER LCD MPV 20/25 NB - THREE PHASE CONTROLLER
PUMP TIME
M/S INITIATIVE INI-SYS-MPV20NB-WD-407-01
All connections should be made with Tinned-Cu wires with Gray Insulatio,Appropriately Ferruled and lugged
15
14 COM
NC
TO PUMP CONTRACTOR
13 OUTPUT 3 10 COM
NO
12 OUTPUT 1 COM 9
NO
11 NO OUTPUT 2
COM. FOR INPUTS 7
COM
INPUT 3 6
8
COM. FOR INPUTES 5
4
OR
PUMP TIME 4-5 INPUT 2 TREATED WATER FLOATY
PRESSURE SWITCH
In set mode. password 84; programmable inputes (filter): 1. Inpute 1 (2-7) - raw water level / treated water level 2. Inpute 2 (3-7) - inpute pulse or treated water level 3. Inpute 4 - flow sensor (1-4-5) or pump time (4-5) Programmable output 1(9-12), 2(8-11) & output 3(10-13) can be configured in 9 modes as per requirement
GREEN
TO SUBMERSIBLE PUMP
NO
Power Wiring: 1.5 sq. mm Control Wiring : 0.5 sq. mm
3
INPUT 1 2
B RUNNING WINDING
BLACK
230 V AC
OUTPUT Y RUNNING WINDING
+12V
P PHASE
N NEUTRAL
R RUNNING WINDING
PUMP TIME
C
INPUT
TO PUMP CONTACTOR
N
1
KHYATEE PANEL (KDP99)
P
LCD MPV 20NB
MPV POWER SUPPLY 230 VAC
FLOW SENSOR 1-4-5 R-G-B
STAND ALONE FILTER LCD MPV 20/25 NB - SUBMERSIBLE PUMP CONTROLLER
PUMP TIME
M/S INITIATIVE INI-SYS-MPV20NB-WD-405-01
All connections should be made with Tinned-Cu wires with Gray Insulatio,Appropriately Ferruled and lugged
15
14 COM
NC
TO PUMP CONTRACTOR
13 OUTPUT 3 10 COM
NO
12 OUTPUT 1 COM 9
NO
11 OUTPUT 2 COM
COM. FOR INPUTS 7
8
INPUT 3 6
COM. FOR INPUTES
NO
PUMP TIME 4-5
OR
MCB 16A
A1
5
14
4
T2
INPUT 2
T1
3
13
INPUT 1
L2
2
L1
LCD MPV 20NB
A2
+12V
N
1
P
FLOW SENSOR 1-4-5 R-G-B
STAND ALONE SOFTNER LCD MPV 20/25 NB - SINGLE PHASE CONTROLLER
6
7
8
C NC MPV POWER TOP JMP SUPPLY CONTRACTOR
9
10
C
NO AUX CONTACT
BRINE SWITCH
In set mode. password 84; programmable inputes (filter): 1. Inpute 1 (2-7) - raw water level / treated water level 2. Inpute 2 (3-7) - inpute pulse or treated water level 3. Inpute 4 - flow sensor (1-4-5) or pump time (4-5) Programmable output 1(9-12), 2(8-11) & output 3(10-13) can be configured in 9 modes as per requirement
Power Wiring: 1.5 sq. mm Control Wiring : 0.5 sq. mm
GREEN
PUMP OUT 10 AMP MAX
5
BLACK
4
BLACK
P N INPUT
3
RED
2
5 BLACK
1
4 GREEN
SINGLE PHASE PUMP CONTROLLER
RED
1
TREATED WATER FLOATY
PUMP TIME
M/S INITIATIVE INI-SYS-MPV20NB-WD-406-01
All connections should be made with Tinned-Cu wires with Gray Insulatio,Appropriately Ferruled and lugged
R Y B N
R Y B
1 2 3 4 R Y B N
5 6 7 R Y B
8
9
10
11
TO PUMP CONTACTOR C NC
MPV POWER SUPPLY
12
13
AUX CONT. C
NC
Power Wiring: 1.5 sq. mm Control Wiring : 0.5 sq. mm
15
14 COM
NC
TO PUMP CONTRACTOR
13 OUTPUT 3 10 COM
NO
12 OUTPUT 1 COM 9
NO
11 OUTPUT 2 COM
TREATED WATER FLOATY
BRINE SWITCH
In set mode. password 84; programmable inputes (filter): 1. Inpute 1 (2-7) - raw water level / treated water level 2. Inpute 2 (3-7) - inpute pulse or treated water level 3. Inpute 4 - flow sensor (1-4-5) or pump time (4-5) Programmable output 1(9-12), 2(8-11) & output 3(10-13) can be configured in 9 modes as per requirement
8
NO
PUMP TIME 4-5
5
FLOW SENSOR
RED
THREE PHASE PUMP CONTROLLER
4 GREEN
RED
1
COM. FOR INPUTS
B
7
Y
GREEN
R
INPUT 3
B
BLACK
Y
BLACK
R
6
A2
COM. FOR INPUTES
14
5
T3
4
T2
INPUT 2
T1
3
13
INPUT 1
L3
2
L2
BLACK
L1
LCD MPV 20NB
A1
+12V
N
1
FLOW SENSOR 1-4-5 R-G-B
P
OR
STAND ALONE SOFTNER LCD MPV 20/25 NB - THREE PHASE CONTROLLER
PUMP TIME
M/S INITIATIVE INI-SYS-MPV20NB-WD-407-01
All connections should be made with Tinned-Cu wires with Gray Insulatio,Appropriately Ferruled and lugged
STAND ALONE SOFTNER LCD MPV 20/25 NB - SINGLE PHASE CONTROLLER
15
14 COM
NC
TO PUMP CONTRACTOR
13 OUTPUT 3 10 COM
NO
12 OUTPUT 1 COM 9
NO
11 OUTPUT 2 COM 8
7
INPUT 3
COM. FOR INPUTS
NO
PUMP TIME 4-5
OR
MCB 16A
A1
6
14
COM. FOR INPUTES
T3
5
T2
4
T1
INPUT 2
13
3
L3
INPUT 1
L2
2
L1
+12V
A2
LCD MPV 20NB
AUX SUPPLY FOR MPV
N
1
P
FLOW SENSOR 1-4-5 R-G-B
TYPICAL WIRING SCHEME
4
5
PUMP OUT
FLOW SENSOR
BRINE SWITCH
TREATED WATER FLOATY
In set mode. password 84; programmable inputes (filter): 1. Inpute 1 (3-5) - raw water level / treated water level 2. Inpute 2 (2-5) - inpute pulse or treated water level 3. Inpute 4 - flow sensor (1-4-5) or pump time (4-5) Programmable output 1(8-12) ,2(8-11) & 3(10-13) can be configured in 9 modes as per requirement PUMP TIME Power Wiring: 1.5 sq. mm Control Wiring : 0.5 sq. mm
GREEN
INPUT POWER
BLACK
1
BLACK
N
RED
P
BLACK
N
GREEN
P
M/S INITIATIVE INI-SYS-MPV20NB-WD-408-01
All connections should be made with Tinned-Cu wires with Gray Insulatio,Appropriately Ferruled and lugged
15
14 COM
NC
TO PUMP CONTRACTOR
13 OUTPUT 3 10 COM
NO
12 NO OUTPUT 1 COM 9
OUTPUT 2 COM 8
COM. FOR INPUTS 7
INPUT 3 6
4
5
COM. FOR INPUTES
NO
PUMP TIME 4-5 INPUT 2 3
INPUT 1
OR
FLOW SENSOR 1-4-5 R-G-B 2
B RUNNING WINDING
GREEN
5
BLACK
4 GREEN
1
BLACK
TO SUBMERSIBLE PUMP
RED
230 V AC
OUTPUT Y RUNNING WINDING
+12V
P PHASE
N NEUTRAL
R RUNNING WINDING
PUMP TIME
BLACK
INPUT
TO PUMP CONTACTOR
N
1
KHYATEE PANEL (KDP99)
P
LCD MPV 20NB
MPV POWER SUPPLY 230 VAC
11
STAND ALONE SOFTNER LCD MPV 20/25 NB - SUBMERSIBLE PUMP CONTROLLER
BRINE SWITCH FLOW SENSOR
TREATED WATER FLOATY
In set mode. password 84; programmable inputes (filter): 1. Inpute 1 (2-7) - raw water level / treated water level 2. Inpute 2 (3-7) - inpute pulse or treated water level 3. Inpute 4 - flow sensor (1-4-5) or pump time (4-5) Programmable output 1(9-12), 2(8-11) & output 3(10-13) can be configured in 9 modes as per requirement
Power Wiring: 1.5 sq. mm Control Wiring : 0.5 sq. mm
M/S INITIATIVE INI-SYS-MPV20NB-WD-410-01
All connections should be made with Tinned-Cu wires with Gray Insulatio,Appropriately Ferruled and lugged
CONNECTION TO CONTROL PANEL - SINGLE PHASE / THREE PHASE / SUBMERSIBLE PUMP / FREE WIRING SCHEME E
MPV1-SOFTNER
P
F
E
MPV2-FILTER
N
P
F
E
MPV3-FILTER
N
P
LCD MPV 20NB
LCD MPV 20NB
LCD MPV 20NB
1
+12V
1
+12V
+12V
INPUT 1
2
INPUT 1
FLOW SENSOR 1-4-5 R-G-B OR
1
2
FLOW SENSOR 1-4-5 R-G-B OR
2
INPUT 1
3
INPUT 2
PUMP TIME 4-5
3
INPUT 2
PUMP TIME 4-5
3
INPUT 2
4
F N
FLOW SENSOR 1-4-5 R-G-B OR PUMP TIME 4-5
A
4
4
B
5
COM. FOR INPUTES
5
COM. FOR INPUTES
5
COM. FOR INPUTES
6
INPUT 3
6
INPUT 3
6
INPUT 3
7
COM. FOR INPUTS
7
COM. FOR INPUTS
7
COM. FOR INPUTS
8
COM
OUTPUT 2
NO 11
8
COM
OUTPUT 2
NO
11
8
COM
OUTPUT 2
NO
11
9
COM
OUTPUT 1
NO 12
9
COM
OUTPUT 1
NO
12
9
COM
OUTPUT 1
NO
12
10 COM
OUTPUT 3
NO 13
10 COM
OUTPUT 3
NO
13
10 COM
OUTPUT 3
NO
13
14 COM
14 COM TO PUMP CONTRACTOR
15
14 COM TO PUMP CONTRACTOR
NC
15
TO PUMP CONTRACTOR
NC
15
NC INPUT 2(3-7), INPUT 3(6-7) OF EACH MPV can be configured for Raw Water Level, treated Water Level, Brine Switch ETC. OUTPUT 1(9-12), OUTPUT 3(10-13) Of EACH MPV can be configured for Mode 1 to Mode 9
MPV (SOFTNER) SELECT IN PASSWORD 84, FOR SENSOR: FLOSEN for Flow Sensor OR SENSOR: PMP TIM for Pump Time OUTPUT2: MODE 6
The most frequently cycled Unit is the first (lead) Unit. The Flow or Pump time should be connect and configured to the unit.
MPV2 (SAND FILTER)
MPV3 (SAND FILTER)
SELECT IN PASSWORD 84
SELECT IN PASSWORD 84
INPUT: PLUSE
INPUT: PLUSE
OUTPUT2 : MODE 6
AUX O/P: MODE 6
C
D
M/S INITIATIVE INI-SYS-MPV20NB-WD-411-01
20NB LCD TECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS : FOR FILTER / SOFTNER 1) Valve Connection with top opening vessel 2) Max Flow rate (valve + strainers + riser pipe) 3) Max.Operating pressure 4) Riser Pipe size 5) Inlet,Outlet,Drain Connections
: : : : :
2.5’’npsm (8 tpi). 2000 lph @ 0.5 kg/Cm2 5 kg/Cm2. 25mm PVC pipe. ¾’’BSPF Quick release coupling elbow ‘OR’ straight (adaptor for converting to ½’’ BSPF also available)
6) Riser pipe lenth with bottom strainer attached should be 9mm below vessel top. 7) 1/8’’ BSPF nozzles across inlet,outlet for pressure gauge/sample valve. ADDITIONAL FOR SOFTENER: 8) Regenerant suction tubing size : ¼’’ 9) Maximum resin quantity : 100 Lr. 10) Injector ratio : 1:2 11) Minimum pressure for uniform suction : 2 Kg/Cm2. Electrical Supply Voltage Frequency Power consumption Memory retention Display
80 to 280 Volts 50 Hzs 5VA 5 years 16 Character LCD
Relay outputs Aux I and Aux II
Both programmable in 6 Modes
Others Operating Temperature Humidity
0 - 50' 80% Max
80 to 280 Volts 50 Hzs 5VA 5 years 16 Character LCD
Both programmable in 6 Modes
0 - 50' 80% Max